Letter Sequence Response to RAI |
---|
CAC:MF7290, Use of TS 3.10.1 for SCRAM Time Testing Activities (Approved, Closed) |
|
MONTHYEARRS-16-015, License Amendment Request to Revise Technical Specification Section 5.5.13, Primary Containment Leakage Rate Testing Program, for Permanent Extension of Type a and Type C Leak Rate Test Frequencies2016-01-25025 January 2016 License Amendment Request to Revise Technical Specification Section 5.5.13, Primary Containment Leakage Rate Testing Program, for Permanent Extension of Type a and Type C Leak Rate Test Frequencies Project stage: Request ML16076A1202016-03-17017 March 2016 Supplemental Information Needed for Acceptance of Requested Licensing Action Concerning Extension of Leak Rate Testing (CAC No. MF7290)(RS-16-015) Project stage: Acceptance Review RS-16-075, Supplemental Information Regarding License Amendment Request to Revise Technical Specification Section 5.5.13, Primary Containment Leakage Rate Testing Program, for Permanent Extension of Type a and Type C Leak Rate Test.2016-03-31031 March 2016 Supplemental Information Regarding License Amendment Request to Revise Technical Specification Section 5.5.13, Primary Containment Leakage Rate Testing Program, for Permanent Extension of Type a and Type C Leak Rate Test. Project stage: Supplement ML16095A2852016-04-0404 April 2016 License Amendment Request for Adoption of Technical Specification Task Force Traveler TSTF-484, Revision 0, Use of TS 3.10.1 for Scram Time Testing Activities. Project stage: Request ML16104A0552016-04-25025 April 2016 Acceptance Review Concerning Permanent Extension of Type a and Type C Leak Rate Test Frequencies (CAC No. MF7290) (RS-16-015) Project stage: Acceptance Review ML16238A2502016-10-0303 October 2016 Acknowledgement of Suspension Request for Licensing Actions Project stage: Other RS-16-208, Response to NRC Acknowledgement of Suspension Request for Licensing Actions2016-11-0101 November 2016 Response to NRC Acknowledgement of Suspension Request for Licensing Actions Project stage: Request RS-17-020, Response to RAI Concerning License Amendment Request to Revise Technical Specification Section 5.5.13, Primary Containment Leakage Rate Testing Program, for Permanent Extension of Type a and Type C Leak Rate Test Frequencies2017-03-0202 March 2017 Response to RAI Concerning License Amendment Request to Revise Technical Specification Section 5.5.13, Primary Containment Leakage Rate Testing Program, for Permanent Extension of Type a and Type C Leak Rate Test Frequencies Project stage: Response to RAI ML17125A3212017-05-0202 May 2017 NRR E-mail Capture - Clinton Power Station, Unit 1 - Request for Additional Information Regarding the Permanent Extension of Leak Rate Testing Project stage: RAI RS-17-079, Response to Request for Additional Information Regarding the Permanent Extension of Leak Rate Testing2017-06-0101 June 2017 Response to Request for Additional Information Regarding the Permanent Extension of Leak Rate Testing Project stage: Response to RAI ML17237A0102017-09-26026 September 2017 Issuance of Amendment Regarding Permanent Extension of Type a and Type C Leak Rate Test Frequencies Project stage: Approval 2016-04-25
[Table View] |
|
---|
Category:Letter type:RS
MONTHYEARRS-23-097, Constellation Energy Generation, LLC, Advisement of Leadership Changes and Submittal of Updated Standard Practice Procedures Plans2023-10-12012 October 2023 Constellation Energy Generation, LLC, Advisement of Leadership Changes and Submittal of Updated Standard Practice Procedures Plans RS-23-090, Annual Report of Emergency Core Cooling System Evaluation Model Changes and Errors for Clinton Power Station2023-09-0707 September 2023 Annual Report of Emergency Core Cooling System Evaluation Model Changes and Errors for Clinton Power Station RS-23-080, Constellation Energy Generation, LLC, Application to Revise Technical Specifications to Adopt TSTF-264-A, Revision 0, 3.3.9 and 3.3.10 - Delete Flux Monitors Specific Overlap Requirement SRs2023-08-30030 August 2023 Constellation Energy Generation, LLC, Application to Revise Technical Specifications to Adopt TSTF-264-A, Revision 0, 3.3.9 and 3.3.10 - Delete Flux Monitors Specific Overlap Requirement SRs RS-23-081, Request for License Amendment to Revise Technical Specifications Related to Reactor Water Cleanup Isolation Instrumentation2023-08-21021 August 2023 Request for License Amendment to Revise Technical Specifications Related to Reactor Water Cleanup Isolation Instrumentation RS-23-085, Supplemental Information Related to Request for Partial Site Release2023-08-0303 August 2023 Supplemental Information Related to Request for Partial Site Release RS-23-077, Response to NRC Regulatory Issue Summary 2023-01, Preparation and Scheduling of Operator Licensing Examinations2023-06-16016 June 2023 Response to NRC Regulatory Issue Summary 2023-01, Preparation and Scheduling of Operator Licensing Examinations RS-23-073, Request for Partial Site Release2023-06-0707 June 2023 Request for Partial Site Release RS-23-042, Application to Revise Technical Specifications to Adopt TSTF-580, Provide Exception from Entering Mode 4 with No Operable RHR Shutdown Cooling2023-05-25025 May 2023 Application to Revise Technical Specifications to Adopt TSTF-580, Provide Exception from Entering Mode 4 with No Operable RHR Shutdown Cooling RS-23-049, Constellation Energy Generation, LLC, Report on Status of Decommissioning Funding for Reactors and Independent Spent Fuel Storage Installations2023-03-23023 March 2023 Constellation Energy Generation, LLC, Report on Status of Decommissioning Funding for Reactors and Independent Spent Fuel Storage Installations RS-23-039, Request for License Amendment to Revise Technical Specifications Section 3.8.3, Diesel Fuel Oil, Lube Oil, and Starting Air2023-03-0101 March 2023 Request for License Amendment to Revise Technical Specifications Section 3.8.3, Diesel Fuel Oil, Lube Oil, and Starting Air RS-23-045, Constellation Energy Generation, LLC Submittal of Fitness for Duty Performance Data Reports for 2022 Per 10 CFR 26.717(c) & 10 CFR 26.2032023-02-28028 February 2023 Constellation Energy Generation, LLC Submittal of Fitness for Duty Performance Data Reports for 2022 Per 10 CFR 26.717(c) & 10 CFR 26.203 RS-23-003, Constellation Energy Generation, LLC, Summary of Changes to Quality Assurance Topical Report, NO-AA-10, and Decommissioning Quality Assurance Program, NO-DC-102023-01-31031 January 2023 Constellation Energy Generation, LLC, Summary of Changes to Quality Assurance Topical Report, NO-AA-10, and Decommissioning Quality Assurance Program, NO-DC-10 RS-23-002, Application to Adopt TSTF-332, ECCS Response Time Testing2023-01-13013 January 2023 Application to Adopt TSTF-332, ECCS Response Time Testing RS-22-126, Constellation Energy Generation, LLC - Request to Use Provisions of a Later Edition of the ASME Boiler and Pressure Vessel Code, Section XI2022-11-30030 November 2022 Constellation Energy Generation, LLC - Request to Use Provisions of a Later Edition of the ASME Boiler and Pressure Vessel Code, Section XI RS-22-121, Notice of Intent to Pursue Subsequent License Renewal Applications2022-11-0909 November 2022 Notice of Intent to Pursue Subsequent License Renewal Applications RS-22-092, Nine and Quad Cities - Application to Revise Primary Containment Isolation Instrumentation Technical Specifications in Accordance with TSTF-306, Revision 2, Add Action to LCO 3.3.6.1 to Give Option to Isolate the Penetration2022-10-0303 October 2022 Nine and Quad Cities - Application to Revise Primary Containment Isolation Instrumentation Technical Specifications in Accordance with TSTF-306, Revision 2, Add Action to LCO 3.3.6.1 to Give Option to Isolate the Penetration RS-22-107, Annual Report of Emergency Core Cooling System Evaluation Model Changes and Errors for Clinton Power Station2022-09-29029 September 2022 Annual Report of Emergency Core Cooling System Evaluation Model Changes and Errors for Clinton Power Station RS-22-093, Advisement of Leadership Changes for Constellation Energy Generation, LLC and Submittal of Updated Standard Practice Procedures Plans2022-08-18018 August 2022 Advisement of Leadership Changes for Constellation Energy Generation, LLC and Submittal of Updated Standard Practice Procedures Plans RS-22-089, Additional Information Supporting Request for License Amendment to Revise the Secondary Containment Design Basis to Credit the Fuel Building Railroad Airlock2022-07-25025 July 2022 Additional Information Supporting Request for License Amendment to Revise the Secondary Containment Design Basis to Credit the Fuel Building Railroad Airlock RS-22-061, Request for License Amendment to Adopt TSTF-269, Revision 2, Allow Administrative Means of Position Verification for Locked or Sealed Valves2022-05-24024 May 2022 Request for License Amendment to Adopt TSTF-269, Revision 2, Allow Administrative Means of Position Verification for Locked or Sealed Valves RS-22-060, Request for License Amendment to Adopt TSTF-230, Revision 1, Add New Condition B to LCO 3.6.2.3, RHR Suppression Pool Cooling2022-05-24024 May 2022 Request for License Amendment to Adopt TSTF-230, Revision 1, Add New Condition B to LCO 3.6.2.3, RHR Suppression Pool Cooling RS-22-068, Constellation Radiological Emergency Plan Addendum Revision2022-05-19019 May 2022 Constellation Radiological Emergency Plan Addendum Revision RS-22-055, Submittal of Preliminary Decommissioning Cost Estimate and Spent Fuel Management Plan2022-04-18018 April 2022 Submittal of Preliminary Decommissioning Cost Estimate and Spent Fuel Management Plan RS-22-051, Constellation Energy Generation, LLC - Update to Correspondence Addressees and Service Lists2022-04-12012 April 2022 Constellation Energy Generation, LLC - Update to Correspondence Addressees and Service Lists RS-22-020, Request for License Amendment to Revise the Secondary Containment Design Basis to Credit the Fuel Building Railroad Airlock2022-04-0707 April 2022 Request for License Amendment to Revise the Secondary Containment Design Basis to Credit the Fuel Building Railroad Airlock RS-22-049, Constellation Energy Generation, LLC, Supplemental Information to Correct Typographical Errors in Constellation'S Application to Revise Technical Specifications to Adopt TSTF-541 Revision 2, Add Exceptions to Surveillance Requirements for2022-04-0404 April 2022 Constellation Energy Generation, LLC, Supplemental Information to Correct Typographical Errors in Constellation'S Application to Revise Technical Specifications to Adopt TSTF-541 Revision 2, Add Exceptions to Surveillance Requirements for V RS-22-045, Constellation Energy Generation, LLC, Response to NRC Regulatory Issue Summary 2022-01, Preparation and Scheduling of Operator Licensing Examinations2022-03-25025 March 2022 Constellation Energy Generation, LLC, Response to NRC Regulatory Issue Summary 2022-01, Preparation and Scheduling of Operator Licensing Examinations RS-22-023, Constellation Energy Generation, LLC, Executed Trust Fund Agreement Amendment and Subordinate Trust Agreement2022-02-23023 February 2022 Constellation Energy Generation, LLC, Executed Trust Fund Agreement Amendment and Subordinate Trust Agreement RS-22-027, Constellation, Response to Request for Additional Information Regarding Application to Revise Technical Specifications to Adopt TSTF-541 Revision 2, Add Exceptions to Surveillance Requirements for Valves and Dampers Locked in the Actuated2022-02-23023 February 2022 Constellation, Response to Request for Additional Information Regarding Application to Revise Technical Specifications to Adopt TSTF-541 Revision 2, Add Exceptions to Surveillance Requirements for Valves and Dampers Locked in the Actuated P RS-22-019, Constellation Energy Generation, LLC - Update to Correspondence Addressees and Service Lists2022-02-16016 February 2022 Constellation Energy Generation, LLC - Update to Correspondence Addressees and Service Lists RS-22-015, Notification of Completion of License Transfer and Request to Continue Processing Pending NRC Actions Previously Requested by Exelon Generation Company, LLC2022-02-0101 February 2022 Notification of Completion of License Transfer and Request to Continue Processing Pending NRC Actions Previously Requested by Exelon Generation Company, LLC RS-22-004, Supplement to Application to Adopt TSTF-554, Revision 1, Revise Reactor Coolant Leakage Requirements2022-01-0404 January 2022 Supplement to Application to Adopt TSTF-554, Revision 1, Revise Reactor Coolant Leakage Requirements RS-21-121, Proposed Changes to Decommissioning Trust Agreements and Master Terms2021-12-15015 December 2021 Proposed Changes to Decommissioning Trust Agreements and Master Terms RS-21-102, Annual Report of Emergency Core Cooling System Evaluation Model Changes and Errors2021-09-29029 September 2021 Annual Report of Emergency Core Cooling System Evaluation Model Changes and Errors RS-21-091, Implementation of Insider Threat Program Requirements Associated with the Voluntary Security Clearance Program and Advisement of Leadership Changes2021-09-13013 September 2021 Implementation of Insider Threat Program Requirements Associated with the Voluntary Security Clearance Program and Advisement of Leadership Changes RS-21-087, Additional Information Supporting Request for License Amendment to Revise Degraded Voltage Relay Allowable Values2021-08-31031 August 2021 Additional Information Supporting Request for License Amendment to Revise Degraded Voltage Relay Allowable Values RS-21-078, Response to Request for Additional Information for Application to Revise Technical Specification to Adopt TSTF-582, Reactor Pressure Vessel Water Inventory Control (RPV WIC) Enhancements, and TSTF-583-T, TSTF-582 Diesel2021-08-19019 August 2021 Response to Request for Additional Information for Application to Revise Technical Specification to Adopt TSTF-582, Reactor Pressure Vessel Water Inventory Control (RPV WIC) Enhancements, and TSTF-583-T, TSTF-582 Diesel RS-21-076, Application to Adopt TSTF-273, Safety Function Determination Program Clarifications2021-07-30030 July 2021 Application to Adopt TSTF-273, Safety Function Determination Program Clarifications RS-21-063, Application to Adopt TSTF-554, Revision 1, Revise Reactor Coolant Leakage Requirements2021-06-30030 June 2021 Application to Adopt TSTF-554, Revision 1, Revise Reactor Coolant Leakage Requirements RS-21-070, Proposed Alternative to Utilize Code Case N-8932021-06-30030 June 2021 Proposed Alternative to Utilize Code Case N-893 RS-21-069, Third Inservice Inspection Interval Relief Request I3R-182021-06-28028 June 2021 Third Inservice Inspection Interval Relief Request I3R-18 RS-21-054, Response to NRC Regulatory Issue Summary 2021-01, Preparation and Scheduling of Operator Licensing Examinations2021-04-29029 April 2021 Response to NRC Regulatory Issue Summary 2021-01, Preparation and Scheduling of Operator Licensing Examinations RS-21-039, Supplemental Information Regarding Application for Order Approving Transfers and Proposed Conforming License Amendments2021-03-25025 March 2021 Supplemental Information Regarding Application for Order Approving Transfers and Proposed Conforming License Amendments RS-21-037, Response to Request for Additional Information Regarding License Amendment Request to Adopt TSTF-505, Revision 22021-03-23023 March 2021 Response to Request for Additional Information Regarding License Amendment Request to Adopt TSTF-505, Revision 2 RS-21-028, Fitness for Duty Performance Data Reports - Annual 20202021-02-26026 February 2021 Fitness for Duty Performance Data Reports - Annual 2020 RS-21-032, Amended Decommissioning Trust Agreements2021-02-25025 February 2021 Amended Decommissioning Trust Agreements RS-21-030, Report on Status of Decommissioning Funding for Reactors and Independent Spent Fuel Storage Installations2021-02-24024 February 2021 Report on Status of Decommissioning Funding for Reactors and Independent Spent Fuel Storage Installations RS-21-014, License Amendment Request for One-Time Extension of the Containment Type a Integrated Leakage Rate Test Frequency2021-02-24024 February 2021 License Amendment Request for One-Time Extension of the Containment Type a Integrated Leakage Rate Test Frequency RS-21-005, Request for License Amendment to Revise Degraded Voltage Relay Allowable Values2021-01-20020 January 2021 Request for License Amendment to Revise Degraded Voltage Relay Allowable Values RS-21-002, Company - Update to Correspondence Addressees and Service Lists2021-01-0404 January 2021 Company - Update to Correspondence Addressees and Service Lists 2023-09-07
[Table view] Category:Response to Request for Additional Information (RAI)
MONTHYEARRS-22-089, Additional Information Supporting Request for License Amendment to Revise the Secondary Containment Design Basis to Credit the Fuel Building Railroad Airlock2022-07-25025 July 2022 Additional Information Supporting Request for License Amendment to Revise the Secondary Containment Design Basis to Credit the Fuel Building Railroad Airlock CNL-22-064, Response to Request for Additional Information Regarding Tennessee Valley Authority License Amendment Request to Revise Emergency Plan Implementing Procedure Regarding Seismic Event Emergency Action Level Change2022-06-0909 June 2022 Response to Request for Additional Information Regarding Tennessee Valley Authority License Amendment Request to Revise Emergency Plan Implementing Procedure Regarding Seismic Event Emergency Action Level Change RS-22-027, Constellation, Response to Request for Additional Information Regarding Application to Revise Technical Specifications to Adopt TSTF-541 Revision 2, Add Exceptions to Surveillance Requirements for Valves and Dampers Locked in the Actuated2022-02-23023 February 2022 Constellation, Response to Request for Additional Information Regarding Application to Revise Technical Specifications to Adopt TSTF-541 Revision 2, Add Exceptions to Surveillance Requirements for Valves and Dampers Locked in the Actuated P NMP1L3447, Constellation Energy Generation, LLC - Response to Request for Additional Information - Proposed Relief Request Associated with Reactor Pressure Vessel Water Level Instrumentation Partial Penetration Nozzle Repairs2022-02-0202 February 2022 Constellation Energy Generation, LLC - Response to Request for Additional Information - Proposed Relief Request Associated with Reactor Pressure Vessel Water Level Instrumentation Partial Penetration Nozzle Repairs JAFP-21-0087, Response to Request for Additional Information Regarding Request for Approval of Transfer of Licenses and Conforming Amendments2021-09-16016 September 2021 Response to Request for Additional Information Regarding Request for Approval of Transfer of Licenses and Conforming Amendments RS-21-087, Additional Information Supporting Request for License Amendment to Revise Degraded Voltage Relay Allowable Values2021-08-31031 August 2021 Additional Information Supporting Request for License Amendment to Revise Degraded Voltage Relay Allowable Values RS-21-078, Response to Request for Additional Information for Application to Revise Technical Specification to Adopt TSTF-582, Reactor Pressure Vessel Water Inventory Control (RPV WIC) Enhancements, and TSTF-583-T, TSTF-582 Diesel2021-08-19019 August 2021 Response to Request for Additional Information for Application to Revise Technical Specification to Adopt TSTF-582, Reactor Pressure Vessel Water Inventory Control (RPV WIC) Enhancements, and TSTF-583-T, TSTF-582 Diesel NMP2L2773, Company - Response to Request for Additional Information2021-06-30030 June 2021 Company - Response to Request for Additional Information JAFP-21-0044, Response to Request for Additional Information Regarding Request for Approval of Transfer of Licenses and Conforming Amendments2021-06-11011 June 2021 Response to Request for Additional Information Regarding Request for Approval of Transfer of Licenses and Conforming Amendments JAFP-21-0032, Response to Request for Additional Information - Proposed Alternative Concerning ASME Section XI Repair/Replacement Documentation for Replacement of Pressure Retaining Bolting2021-04-20020 April 2021 Response to Request for Additional Information - Proposed Alternative Concerning ASME Section XI Repair/Replacement Documentation for Replacement of Pressure Retaining Bolting ML21111A0042021-04-20020 April 2021 Response to Request to Request Clinton, Unit 1, COVID-19 Related Request for Exemption from Part 26 Work Hours Requirements RS-21-037, Response to Request for Additional Information Regarding License Amendment Request to Adopt TSTF-505, Revision 22021-03-23023 March 2021 Response to Request for Additional Information Regarding License Amendment Request to Adopt TSTF-505, Revision 2 RS-20-139, Response to Request for Additional Information Regarding License Amendment Requests to Adopt TSTF-505, Revision 2, and 10 CFR 50.692020-11-24024 November 2020 Response to Request for Additional Information Regarding License Amendment Requests to Adopt TSTF-505, Revision 2, and 10 CFR 50.69 RS-20-096, Response to Request for Additional Information Related to Relief Request I4R-07 for the Fourth Inservice Inspection Interval2020-08-13013 August 2020 Response to Request for Additional Information Related to Relief Request I4R-07 for the Fourth Inservice Inspection Interval RS-20-095, Response to Request for Additional Information Related to Relief Request I4R-06 for the Fourth Inservice Inspection Interval2020-08-13013 August 2020 Response to Request for Additional Information Related to Relief Request I4R-06 for the Fourth Inservice Inspection Interval ML20188A2642020-07-0606 July 2020 Clinton Power Station, R.E. Ginna Station, Limerick Station, Nine Mile Point Station & Peach Bottom Station - Proposed Alternative to Utilize Code Case OMN-26 - Response to Request for Additional Information RS-20-069, Additional Information Supporting Request for License Amendment Regarding Automatic Operation of Transformer Load Tap Changer2020-06-29029 June 2020 Additional Information Supporting Request for License Amendment Regarding Automatic Operation of Transformer Load Tap Changer RS-20-067, Response to Request for Additional Information Related to Relief Request I4R-01 for the Fourth Inservice Inspection Interval2020-05-13013 May 2020 Response to Request for Additional Information Related to Relief Request I4R-01 for the Fourth Inservice Inspection Interval RS-20-045, Response to Request for Additional Information Related to Relief Request 14R.05 for the Fourth Inservice Inspection Interval2020-04-0101 April 2020 Response to Request for Additional Information Related to Relief Request 14R.05 for the Fourth Inservice Inspection Interval RS-19-112, Response to Request for Additional Information Regarding License Amendment Request to Revise Technical Specifications Following Adoption of TSTF-542, Reactor Pressure Vessel Water Inventory Control2019-12-0505 December 2019 Response to Request for Additional Information Regarding License Amendment Request to Revise Technical Specifications Following Adoption of TSTF-542, Reactor Pressure Vessel Water Inventory Control NMP2L2711, Byron Station; Calvert Cliffs; Clinton Power Station; LaSalle County Station; Limerick Generating Station; and Nine Mile Point Nuclear Station - Proposed Alternative to Utilize Code Case N-8792019-10-16016 October 2019 Byron Station; Calvert Cliffs; Clinton Power Station; LaSalle County Station; Limerick Generating Station; and Nine Mile Point Nuclear Station - Proposed Alternative to Utilize Code Case N-879 JAFP-19-0057, Response to Request for Additional Information - Proposed Alternative to Utilize Code Cases N-878 and N-8802019-06-0404 June 2019 Response to Request for Additional Information - Proposed Alternative to Utilize Code Cases N-878 and N-880 NMP1L3279, Response to Request for Additional Information - Proposed Alternatives to Utilize Code Cases N-878 and N-880 for Plants2019-05-0101 May 2019 Response to Request for Additional Information - Proposed Alternatives to Utilize Code Cases N-878 and N-880 for Plants JAFP-19-0006, Response to Request for Additional Information - Proposed Alternative to Utilize Code Cases N-878 and N-8802019-01-0808 January 2019 Response to Request for Additional Information - Proposed Alternative to Utilize Code Cases N-878 and N-880 RS-18-150, Transmittal of Supplemental Information for Exelon Evaluation of Preliminary White Finding2018-12-20020 December 2018 Transmittal of Supplemental Information for Exelon Evaluation of Preliminary White Finding RS-18-143, Supplemental Information Supporting License Amendment Requests for Approval of Changes to Emergency Plan Staffing Requirements2018-11-29029 November 2018 Supplemental Information Supporting License Amendment Requests for Approval of Changes to Emergency Plan Staffing Requirements RS-18-103, Response to Request for Additional Information Concerning License Amendment Request to Revise Alternate Source Term Dose Calculation2018-08-29029 August 2018 Response to Request for Additional Information Concerning License Amendment Request to Revise Alternate Source Term Dose Calculation RS-18-097, Response to Request for Additional Information and Supplemental Information-License Amendment.2018-07-27027 July 2018 Response to Request for Additional Information and Supplemental Information-License Amendment. RS-18-067, Response to Request for Additional Information Regarding Generic Letter 2016-012018-05-29029 May 2018 Response to Request for Additional Information Regarding Generic Letter 2016-01 RS-18-061, Response to Request for Additional Information Regarding Decommissioning Funding Plans for Independent Spent Fuel Storage Installations (Isfsis)2018-05-0202 May 2018 Response to Request for Additional Information Regarding Decommissioning Funding Plans for Independent Spent Fuel Storage Installations (Isfsis) ML18025A7992018-01-25025 January 2018 Response to Request for Additional Information Regarding Generic Letter 2016-01 RS-17-145, Supplement to Application to Revise Technical Specifications to Adopt TSTF-542, Reactor Pressure Vessel Water Inventory Control2017-11-15015 November 2017 Supplement to Application to Revise Technical Specifications to Adopt TSTF-542, Reactor Pressure Vessel Water Inventory Control RS-17-079, Response to Request for Additional Information Regarding the Permanent Extension of Leak Rate Testing2017-06-0101 June 2017 Response to Request for Additional Information Regarding the Permanent Extension of Leak Rate Testing RS-17-044, Response to Request for Additional Information Regarding Proposed Alternative for the Use of Encoded Phased Array Ultrasonic Examination Techniques in Lieu of Radiography2017-03-13013 March 2017 Response to Request for Additional Information Regarding Proposed Alternative for the Use of Encoded Phased Array Ultrasonic Examination Techniques in Lieu of Radiography RS-17-020, Response to RAI Concerning License Amendment Request to Revise Technical Specification Section 5.5.13, Primary Containment Leakage Rate Testing Program, for Permanent Extension of Type a and Type C Leak Rate Test Frequencies2017-03-0202 March 2017 Response to RAI Concerning License Amendment Request to Revise Technical Specification Section 5.5.13, Primary Containment Leakage Rate Testing Program, for Permanent Extension of Type a and Type C Leak Rate Test Frequencies RS-16-121, Response to Request for Additional Information Concerning License Amendment Request to Incorporate Revised Alternative Source Term Dose Calculation in USAR2016-06-0202 June 2016 Response to Request for Additional Information Concerning License Amendment Request to Incorporate Revised Alternative Source Term Dose Calculation in USAR RA-16-049, Response to Request for Additional Information Regarding Requests to Withhold Emergency Preparedness Documents from Public Disclosure2016-05-26026 May 2016 Response to Request for Additional Information Regarding Requests to Withhold Emergency Preparedness Documents from Public Disclosure RS-16-077, Response to Request for Additional Information Regarding Request for License Amendment to Reduce the Reactor Steam Dome Pressure Specified in the Technical Specification 2.1.1, Reactor Core Sls.2016-04-14014 April 2016 Response to Request for Additional Information Regarding Request for License Amendment to Reduce the Reactor Steam Dome Pressure Specified in the Technical Specification 2.1.1, Reactor Core Sls. RS-15-278, Supplement to Request for Additional Information Regarding License Amendment Request for a One-Time Extension of the Shutdown Service Water Division 2 Subsystem Completion Time2015-10-20020 October 2015 Supplement to Request for Additional Information Regarding License Amendment Request for a One-Time Extension of the Shutdown Service Water Division 2 Subsystem Completion Time RS-15-260, Response to Request for Additional Information Regarding License Amendment Request for a One-Time Extension of the Shutdown Service Water Division 2 Subsystem Completion Time2015-09-30030 September 2015 Response to Request for Additional Information Regarding License Amendment Request for a One-Time Extension of the Shutdown Service Water Division 2 Subsystem Completion Time RS-15-141, Response to Request for Additional Information Regarding License Amendment Request to Revise Technical Specification 5.5.2, Primary Coolant Sources Outside Containment.2015-06-24024 June 2015 Response to Request for Additional Information Regarding License Amendment Request to Revise Technical Specification 5.5.2, Primary Coolant Sources Outside Containment. 2022-07-25
[Table view] |
Text
4300 Winfield Road A-Warrenville, IL 60555 14111111innow .
Amwr Exelon Generation G30 657 2000 Office RS-17-079 10 CFR 50.90 June 1, 2017 U.S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, DC 20555-0001 Clinton Power Station, Unit 1 Facility Operating License No. NPF-62 NRC Docket Nos. 50-461
Subject:
Response to Request for Additional Information Regarding the Permanent Extension of Leak Rate Testing Clinton Power Station, Unit 1
References:
- 1. Letter from Patrick R. Simpson (Exelon Generation Company, LLC) to U.S.
NRC, "License Amendment Request to Revise Technical Specification Section 5.5.13, 'Primary Containment Leakage Rate Testing Program,' for Permanent Extension of Type A and Type C Leak Rate Test Frequencies,"
dated January 25, 2016 (ML16025A182)
- 2. Letter from Patrick R. Simpson (Exelon Generation Company, LLC) to U.S.
NRC, "Response to Request for Additional Information Concerning License Amendment Request to Revise Technical Specification Section 5.5.13,
'Primary Containment Leakage Rate Testing Program,' for Permanent Extension of Type A and Type C Leak Rate Test Frequencies," dated March 2, 2017 (ML17062A584)
- 3. Email from Jennie Rankin (U.S. NRC) to John L. Schrage (Exelon Generation Company, LLC), "Clinton Power Station, Unit 1 - Request for Additional Information Regarding the Permanent Extension of Leak Rate Testing (CAC No. MF7290)," dated May 2, 2017 (ML17125A321)
- 4. Teleconference Between U.S. NRC (J. Rankin, et al) and Exelon Generation Company, LLC (J. Schrage, et al) on May 2, 2017 In Reference 1, Exelon Generation Company, LLC (EGC) requested an amendment to Facility Operating License (FOL) No. NPF-62 for Clinton Power Station (CPS), Unit 1. The proposed amendment would revise FOL Appendix A, Technical Specification (TS) 5.5.13, "Primary Containment Leakage Rate Testing Program" to allow for the permanent extension of the Type A Integrated Leak Rate Testing (ILRT) and Type C Leak Rate Testing frequencies.
June 1, 2017 U.S. Nuclear Regulatory Commission Page 2 EGC transmitted a response to 13 requests for additional information (RAls) related to the proposed license amendment in Reference 2.
In Reference 3, the NRC transmitted one additional RAI, and provided clarification to EGC during the Reference 4 teleconference.
The Enclosure to this letter provides the information requested in Reference 3.
There are no regulatory commitments contained within this letter.
If you have any questions concerning this letter, please contact Mr. John L. Schrage at (630) 657-2821.
1 declare under penalty of perjury that the foregoing is true and correct. Executed on the 1" day of June 2017.
Respectfully, Patrick R. Simpson Manager Licensing Exelon Generation Company, LLC
Enclosure:
RAI Response for ILRT LAR for Clinton Power Station, RM Documentation No.
CL-LAR-09, Revision 0 cc: NRC Regional Administrator, Region III NRC Senior Resident Inspector Clinton Power Station Illinois Emergency Management Agency Division of Nuclear Safety
Enclosure RAI Response for ILRT LAR for Clinton Power Station RM Documentation No. CL-LAR-09, Revision 0
1~ Exelon Ri~`. lAanagamment Team RM DOCUMENTATION NO. CL-LAR-09 REV: 0 PAGE NO. I STATION: Clinton Power Station UNIT(s) AFFECTED: 1 TITLE: Round 2 RAI Response for ILRT LAR for Clinton Power Station
SUMMARY
The purpose of this document is to provide Exelon Generation's responses to Requests for Additional Information (RAls) associated with Clinton ILRT License Amendment Request, This is a Category I RM Document IAW ER-AA-600-1012, which requires independent review and approval.
Review required after periodic Update X ] Internal RM Documentation External RM Documentation Electronic Calculation Data Files: N/A Method of Review: [X ] Detailed ] Alternate Review of External Document This RM documentation supersedes: N/A Prepared by: Garrett Snedeker 5/30/17 Print Sign Date Reviewed by: John E. Steinmetz 1 1 5/30/17 Print Sign Date Reviewed by: Tony Hable 1 5/30/17 Print in Date Approved by: Eugene M. Kelly 5/30/17 Print Sin Date Rev. 0
CL-LAR-08 RESPONSE TO RAls ASSOCIATED WITH ILRT LAR FOR CLINTON POWER STATION RAI 2-1 ni iPOinn Facts & Observation (F&O) 6-8 identified that the probabilistic risk assessment (PRA) takes credit for opening doors to ensure cooling for the Emergency Core Cooling System (ECCS) pump rooms, but no formal engineering analyses was provided. In RAI 2.b, the NRC staff requested justification for the resolution of this F&O. As indicated in the F&O resolution and in the response to RAI 2.b, a computational fluid dynamics (CFD) simulation has been performed for Residual Heat Removal (RHR)-B to support the credit for opening doors. The licensee stated in the RAI response that the RHR-A pump room is judged as having similar behavior to RHR-B because the rooms are generally symmetrical in terms of dimensions. The licensee also stated that other ECCS pump rooms are comparable and provided information on the volume and heat loads for those rooms.
Based on this information some of the ECCS rooms (RHR-C, High Pressure Core Spray, and Low Pressure Core Spray) do not appear to be similar to RHR-B. These rooms have higher heat loads as well as higher heat load per unit volume than the RHR-B room. Therefore, the CFD calculation performed for RHR-13 pump room cannot be considered applicable or bounding for these rooms. The RAI response also stated that a "phenomenological failure term" is included in the PRA model to represent the possibility that the rooms are dissimilar, however the assigned failure probability is not justified. As a result, the justification sought by the staff in RAI 2.b has not been provided for all ECCS rooms and F&O 6-8 appears to remain unresolved.
Justify the credit for opening doors for the remaining ECCS rooms (e.g., CFD analyses) or alternatively, provide the results of a quantitative sensitivity analysis that assesses the impact of removing the credit for opening doors of the ECCS rooms on the current application.
Response to RAI 2-1 Since no formal engineering analysis is currently available to further justify credit for opening doors for ECCS rooms RHR C, High Pressure Core Spray (HPCS), and Low Pressure Core Spray (LPCS), a quantitative sensitivity analysis was performed to eliminate credit in the PRA model. The following table provides the results with no credit for opening of the doors for failure of room cooling in the RHR C, HPCS and LPCS rooms.
Rev. 0 2
CL-LAR-08 BASE CDF1" NEW CDF``'
CDF 2.23E-6/yr 2.49E-6/yr LERF 1. 1 6E-7/vr 1.34E-7/vr Notes to Table:
Base CDF and LERF from the original ILRT LAR analysis.
CDF and LERF based on removing credit for opening the doors for loss of room cooling for RHR C, HPCS, and LPCS rooms, The new results were used to re-create Tables 5.6-1, 5.7-1, 5.7-2, 5.7-3, and 5.7-4 from the ILRT LAR analysis.
TABLE 5.6-1 CPS ILRT/DWBT CASES:
BASE, 3 TO 10, AND 3 TO 15 YR EXTENSIONS (INCLUDING AGE ADJUSTED STEEL CORROSION LIKELIHOOD BASE CASE EXTEND TO EXTEND TO 3 IN 10 YEARS 1 IN 10 YEARS 1 IN 15 YEARS DOSE CDF PERSON- CDF PERSON- CDF PERSON-EPRICLASS PER-REM (1/YR) REMIYR (11YR) REMNR (1/YR) REMIYR 1 2.71 E+03 9.18E-07 2.49E-03 8.81 E-07 2.39E-03 8.54E-07 2.32E-03 2 5.48E+05 3.32E-07 1.82E-01 3.32E-07 1.82E-01 3.32E-07 1.82E-01 3a 2.71 E+04 1.35E-08 3.65E-04 4.48E-08 1.22E-03 6.73E-08 1.83E-03 3b 2.71 E+05 2.74E-09 7.43E-04 9.14E-09 2.48E-03 1.38E-08 3.74E-03 7LERF 5.48E+05 1.33E-07 7.28E-02 1.33E-07 7.28E-02 1,33E-07 7.28E-02_
7 non-LERF 3.37E+05 1.09E-06 3.71 E-01 1.09E-06 3.71 E-01 1.09E-06 3.71 E-01 8 5.48E+05 1.55E-09 8.49E-04 1.55E-09 8.49E-04 1.55E-09 8.49E-04 Total 2.49E-06 0.631 2.49E-06 0.633 2.49E-06 0.635 I LRT Dose Rate 1.11 E-03 3.70E-03 5.57E-03 from 3a and 3b Delta From 3 yr --- 2.48E-03 4.28E-03 Total Dose Rate From 10 yr --- 1.80E-03 3b Frequency (LERF) 2.74E-09 9.14E-09 1.38E-08 From 3 yr --- 6.41 E-09 1.10E-08 Delta 3b LERF --- ---
From 10 yr 4.64E-09 CCFP % 62.64% 62.90% 63.09%
From 3 yr --- 0.26% 0.44%
Delta CCFP % ---
From 10 yr 0.19%
Rev. 0 3
CL-LAR-08 TABLE 5.7-1 OTHER HAZARD GROUP CONTRIBUTOR
SUMMARY
OTHER HAZARD INITIATOR GROUP CDF (1/YR)
Seismic 9 1.7E-05 Internal Fire [81 6.0E-06" High Winds/Tornadoes Screened External Floods Screened Transportation and Nearby Facility Accidents Screened Total (for initiators with CDF available) 2.3E-05 Internal Events CDF 2.23E-06121 External Events Multiplier 10.3112.)
Note to Table 5.7-1:
The Clinton Fire PRA does not credit opening the doors for ECCS room cooling, therefore, there is no change in Fire CDF.
(2)
The External events multiplier was conservatively left the same as the original ILRT submittal. Using the updated CDF would results in an external events multiplier of 9.24.
TABLE 5.7-2 CPS 3B (LERF) AS A FUNCTION OF ILRT/DWBT FREQUENCY FOR INTERNAL AND EXTERNAL EVENTS (INCLUDING AGE ADJUSTED STEEL CORROSION LIKELIHOOD) 313 313 313 FREQUENCY FREQUENCY FREQUENCY (3-PER-10 (1-PER-10 (1-PER-15 YEAR YEAR YEAR LERF ILRT/DWBT ILRT/DWBT) ILRT/DWBT) INCREASE(') -
Internal Events 2.74E-09 9.14E-09 1.38E-08 1.10E-08 Contribution Other Hazard Group Contribution (Internal 2.82E-08 9.43E-08 1.42E-07 1.14E-07 Events CDF x 10.31 Combined 3.10E-08 1.03E-07 1.56E-07 1.25E-07 Note to Table 5.7-2:
Associated with the change from the baseline 3-per-10 year frequency to the proposed 1-per-15 year frequency.
Rev. 0 4
CL-LAR-08 TABLE 5.7-3 COMPARISON TO ACCEPTANCE CRITERIA INCLUDING OTHER HAZARD GROUPS CONTRIBUTION FOR CPS CONTRIBUTOR j ALERF PERSON-REM/YRt'~ \CCFP(2)
CPS Internal Events 1.10E-8/ r 4.28E-03/ r 0.68% 0.44%
CPS Other Hazard 1.14E-7/yr 4.42E-02/yr (0.68%) I 0.44%
Groups CPS Total 1.25E-7! r 4.85E-02/ r 0.68% 0.44%
<1.0 person-rem/yr Acceptance Criteria j <1.0E-6/yr o <_1.5%
or <1.0/0 Notes to Table 5.7-3:
77 The EPRI Class (1, 2, 7, 8) release Person-Rem/yr are assumed to be the same percentage relative to base risk (0.73%) for internal and external events.
(2)
The Probability of DW and WW leakage due to the ILRT/DWBT extension is assumed the same for both Internal and External Events, therefore the percentage change for CCFP remains constant (0.44%).
TABLE 5.7-4 IMPACT OF 15-YR ILRT EXTENSION ON LERF (313) FOR CPS Internal Events LERF 1.34E-07/yr Internal Fire LERF 9.21 E-07/yr i Other Hazard Group LERF 8.84E-07/yr (Internal Events LERF x 7.62)
Internal Events LERF due to ILRT 1.38E-08/yr Class 3b at 15 ears 0)
Other Hazard group LERF due to ILRT at 15 years 1.42E-07/ r Total 2.09E-061 r Note to Table 5.7-4:
Including age adjusted steel corrosion likelihood.
As can be seen, the impacts from the sensitivity are as follows:
- 1. Change in LERF = 1.25E-7/yr, which is slightly above the 1.0E-7/yr upper boundary for the "very small" risk increase as defined in RG 1.174, but at the bottom of the band for "small" risk increase.
- 2. Change in population dose rate is 4.85E-2 person-rem/yr (0.68%), which is less than 1.0 person-rem/year or 1 % of the total population dose.
- 3. Change in CCFP is 0.44%, which is less than 1.5%.
Rev. 0
Similar to the original IRT LAR submittal the 1.25E-07/yr increase in LERF due to the combined hazard events from extending the CPS I'-RT/DWBT frequency from 3-per-10 years to 1-per-15 years falls within Region ll between 'I E-7 to 1E-6 per reactor year
("Small Change" in risk) of the RG 1.174 acceptance guidelines. Per RG 1.174, when t,ie calculated increase in LER due to the proposed plant change is in the "Small Change" range, the risk assessment must also reasonably show that the total LERF is ess than 1E-5/yr. S:mclar bounding assumptions ~egarding the external event contributions that were made above are used for the total LERF estimate. As can be seen in Table 5.7-4 above, tie estimated LERF 1"or CPS using the Fire LERF and CDF based multiplier approach for seismic is 2.09E-06/yr, which is less than the RG 1.174 required value of 1 E-5/yr.
.rev. 0