Attachment 1 Response to Request for Additional Information (Non-Confidential Information)

Non-Confidential Information Submitted Under 10 CFR 2.390 Response to Request for Additional Information Page 1 Request for Additional Information (RAI) #1:

Background

Section 5 of the November 16, 2020, application states, in part:

the typical applications in which the subject proprietary fittings will be used are generally limited to instrumentation, sampling, and cooling water piping lines. They exclude Class 1 systems and any systems containing boric acid. Design temperatures may be up to 650°F

[degrees Fahrenheit]. Design pressures could be as high as 2000 psi [pounds per square inch]

but will generally be less than 200 psi. The environmental conditions are anything in the nuclear power plant environment, including air, water, or steam systems, and possibly lube oil or fuel systems. They could be inside or outside containment. Prior operating experience for these fittings in these environments have shown successful performance, with no leaks or structural failures, as long as they are installed in accordance with the manufacturers instructions. They have been successfully used in pipe schedules from 40 to 160, subject to the manufacturer's recommendations and limitations.

The application states that prior operating experience demonstrated successful performance of fittings from the material listed in Code Case N-893. However, the application does not provide specific details of the operating experience, such as fitting size, corrosion performance and failure rates, as it related to the environmental conditions.

Request Provide details related to prior operating experience in nuclear and non-nuclear applications.

Include corrosion performance and failure rates for these fittings, up to nominal pipe size 4, in the environments which they will be used or similar environments.

Response

The following is a listing of the application of the fittings with the material requested by Code Case N-893. No known nuclear applications are in use for the LTCS-333 material, which is the subject material of Code Case N-893.

Non-Confidential Information Submitted Under 10 CFR 2.390 Response to Request for Additional Information Page 2 Lokring LTCS-333 Installations.

Type of Size & Pipe Max.

Company facility Date Schedule Spec. Service Press Temp. CA*

Wood Group / Offshore Jan-10 1 1/2" Sch A333 Flare Gas 232 PSI 60ºC T[alisman 160 #150 Piper (North Sea)

Murco Refinery Jan-10 3/4" A106 Gr LPG, Butane, 387 PSI 52ºC 2.5 Petroleum B Propane (S.Wales UK) mm BP Alaska - Production Feb-10 2" A333 Drain #600 <80 F 1/

Crude Line Liberty 8" PXP (West Offshore Feb-10 3/4" Sch 40 A53B / Sealed Drain 285 PSI 200ºF Coast API5LB Flare System California) 1/8" Conoco Phillips Refinery Feb-10 2" Sch 80 & A106 Open Drain #150 750ºF 1/8 Ferndale 3/4" Sch 160 "

ConocoPhillips Production Mar-10 1" A333 Drain #600 <80ºF 1/8" Alaska - crude line Kuparuk Chevron Offshore Mar-10 3/4" Sch A333 Hydrocarbon 12 Bar 100ºC 3 mm Captain (North 160 Sea)

Preem /BIS Refinery Mar-10 2" Sch 80 A335 Gr Waste Line to 1 Bar 50ºC Bilfinger A Flame (Sweden)

Maersk (North FPSO Mar-10 2" Sch 80 A333 Fuel Gas vent 25.8 90ºC 3 mm Sea) to Flare Barg Maersk (North FPSO Apr-10 2" Closed Drain Sea)

PXP (West Offshore Apr-10 1" Sch 80 A106 Natural Gas 250 PSI 70ºF 1/16" Coast California)

Talisman Offshore Apr-10 2" Sch 80 A333 Crude Oil Atmos Ambient 3 mm Fulmar (North Open Drain Sea)

Talisman Offshore May- 1" Sch 40 A333 Crude Oil Atmos Ambient 3 mm Fulmar (North 10 Open Drain Sea)

ConocoPhillips Production May- 2" A333 Drain #600 <80 F 1/8" Alaska - crude 10 line Kuparuk Exxon Mobil PetroChe May- 2" Sch 160 A333 Propylene 80 PSI 40ºC Fawley mical 10 Blow Down Line CNR Ninnian Offshore May- 1" A333 Condensate 3 mm North (North 10 Sea)

Talisman Offshore May- 2" Sch 80 A333 Metering Skid 7 Bar 100ºC 3 mm Buchan (North 10 Drain Line Sea)

ConocoPhillips Production May- 2" A333 Drain #600 <80 F 1/8" Alaska - crude 10 line Kuparuk BP Alaska - Production Jun-10 1" A333 Drain #600 <80 F 1/8" crude line Liberty

Non-Confidential Information Submitted Under 10 CFR 2.390 Response to Request for Additional Information Page 3 Lokring LTCS-333 Installations.

Type of Size & Pipe Max.

Company facility Date Schedule Spec. Service Press Temp. CA*

Talisman Offshore Jun-10 1 1/2" Sch A333 Metering Skid 7 Bar 100ºC 3 Buchan (North 80 Drain Line Sea) mm Talisman Offshore Jun-10 2" Sch 80 A333 Gas Plant 1 Bar 60ºC 3 mm Montrose (North Sour Drains Sea)

Talisman Offshore Jul-10 1/2" Sch 80 A333 Metering Skid 7 Bar 100ºC 3 mm Buchan (North Drain Line Sea)

ConocoPhillips Production Jul-10 1" & 1 1/2" A333 Drain #600 <80 F 1/8" Alaska - Crude line Alpine Talisman Offshore Aug-10 1" & 2" Sch A333 Diesel Fuel 20 Bar 38ºC 3 mm Claymore 80 (North Sea)

CNR (North Offshore Aug-10 3" A333 Sea)

Maersk Oil Offshore Aug-10 1" Sch 160 A333 LP Fuel Gas 5.5 Bar 60ºC 3 mm North Sea Producer (North Sea)

Wood Group / Offshore Sep-10 1 1/2" Sch A106 Diesel 6.5 Bar Ambient 1 mm Talisman 80 Buchan (North Sea)

Maersk Oil Offshore Sep-10 1" Sch 160 A333 LP Fuel Gas 19.6 Bar 190ºC 3 mm North Sea #150 Producer (North Sea)

Ineos LAO PetroChe Oct-10 2" A333 Butene Plant Alberta mical Apache Energy Offshore Oct-10 Process Gas 350 110ºc (Perth) - STAG KPa Platform Talisman Tartan Offshore Oct-10 2" Sch 40 A106 Closed Drains 50 PSI 93ºC 1.5 mm (North Sea)

Talisman Offshore Oct-10 3/4" Sch 80 A106 Hydrocarbon/ 20 Bar 100ºC 3 mm Buchan (North Water Sea)

Talisman Offshore Nov-10 1 1/2" Sch A106 Diesel Oil 2 Bar 50ºC 3 mm Buchan (North 80 Sea)

Talisman Offshore Nov-10 3" Sch 40 A333 Diesel Oil 1 Bar Ambient 1 mm Fulmar (North Sea)

Fairfield Energy Offshore Nov-10 2" A333 Dunlinn Alpha (North Sea)

Talisman Offshore Dec-10 3/4" Sch 80 A106 Hydrocarbon/ 20 Bar 100ºC 1.5 mm Buchan (North Water Sea)

Chevron Alba Offshore Dec-10 3/4" Sch A333 Flat Crude 1.5 Bar ¨-6 to 3 mm (North Sea) 160 50ºC

Non-Confidential Information Submitted Under 10 CFR 2.390 Response to Request for Additional Information Page 4 Lokring LTCS-333 Installations.

Type of Size & Pipe Max.

Company facility Date Schedule Spec. Service Press Temp. CA*

Conoco Phillips Offshore Dec-10 2" A333 Viking (Southern North Sea)

Tatweer Onshore Dec-10 2" Sch 80 API 5L Gas Lift Line 2175 Petroleum Production Gr B PSI (Bapco/

Occidental)

Apache Energy Offshore Jan-11 2" Sch 80 A106 Fuel Gas / 1960 50ºC 3 mm (Perth) - STAG Instrument Air kPa Platform Total E & P (St Gas Plant Jan-11 1 1/2" Sch API 5L Gas to Flare #150 Ambient 1.5 mm Fergus) 40 Perenco UK Offshore Jan-11 2" Sch 80 A333 Gr Condensate 43.5 38ºC 1/8" (Southern North 6 PSI Max Sea) #150 Talisman Tartan Offshore Feb-11 1 1/2" A106 Gr Diesel 100 psi 120ºC 1.5 mm (North Sea) B / A333 Petronas LNG Plant Feb-11 2" Sch 80 API 5L Closed Drain 116 PSI (Bintulu Line Integrated Facility)

QENOS PetroChe Feb-11 3/4" Sch 80 A106 DEA Polymer 125 PSI 180ºC (Melbourne) mical Chevron Alba Offshore Feb-11 3/4" A333 Gr Prover Inlet 3.2 mm FSU (North 6 Valve Sea) Pipework Chevron Alba Offshore Feb-11 3/4" A333 Gr Prover Outlet 3.2 mm FSU (North 6 Plug Valve Sea) Vent Chevron Alba Offshore Feb-11 3/4" A333 Gr Closed Drains 3.2 mm FSU (North 6 Sea)

Centrica Offshore Mar-11 1-1/2" & 2" A333 Gr Plant Air 6 Bar Ambient 1.6 mm Kittiwake (North 6 Distribution Sea)

Talisman Offshore Mar-11 1 1/2" A106 Gr Hydrocarbon 30 PSI 30ºC 3.2 mm Buchan (North B / A333 Closed Drain #150 Sea)

INEOS PetroChe Apr-11 2" Butene /

Oligomers mical Hexane Joffre LAO Plant BG Group Offshore Apr-11 2" A333 Gr6 Hydrocarbons 13.5 Bar 3.2 mm Everest (North / A106 Sea) Grb Apache Forties Offshore Apr-11 4" A333 Gr Fuel Gas tie 12 PSI 30ºC 3.2 mm Alpha (North 6 ins Sea)

Talisman Offshore Apr-11 1 1/2" A333 Gr Diesel Oil 70 PSI 30ºC 1.6 mm Montrose (North 6 Sea)

Talisman Offshore Apr-11 2" A333 Gr Closed Drain 17.1 Bar 38ºC 3 mm Montrose (North 6 (Mostly Crude Sea) Oil)

Non-Confidential Information Submitted Under 10 CFR 2.390 Response to Request for Additional Information Page 5 Lokring LTCS-333 Installations.

Type of Size & Pipe Max.

Company facility Date Schedule Spec. Service Press Temp. CA*

Chevron Refinery Apr-11 2" A106 Gr Naphtha/LPG 125 PSI 121ºC 0.062" Pembroke (Now B Valero)

Chevron Alba Offshore Apr-11 2" A333 Gr Offload 3.2 mm FSU (North 6 Metering Sea) Pipework Chevron Refinery May- 2" A106 Gr Water - Light 125 PSI 0.062" Pembroke (Now 11 B Hydrocarbons Valero)

Talisman Saltire Offshore May- 2" A333 Gr Atmospheric 5 PSI 85ºC & 1.6 mm (North Sea) 11 6 Vent 180ºC British Gas Gas May- 1-1/2" Sch A333 Gr Closed Drain- 97.5Bar 55*C 3 mm Rivers Terminal Receiving 11 160 6 Amine Terminal British Gas Gas May- 2" Sch 160 A333 Gr Closed Drain- 97.5Bar 65*C 3 mm Rivers Terminal Receiving 11 6 Amine Terminal Condensate/

Oily Water British Gas Gas May- 1-1/2" Sch A333 Gr Closed Drain- 97.5Bar 55*C Rivers Terminal Receiving 11 160 6 Amine Terminal 3 mm Taqa Bratani Offshore May- 3" A333 Gr Oil / Water 16 Bar 75ºC 1.6 mm Cormorant 11 6 (Produced)

North (North Sea)

Taqa Bratani Offshore May- 3" A333 Gr Oil / Water 21 Bar 75ºC 1.6 mm Cormorant 11 6 (Produced)

North (North Sea)

Apache Forties Offshore May- 2" A333 Gr Test Manifold 19.6 Bar 80ºC 3 mm Alpha (North 11 6 Closed Drain Sea) Line Talisman Offshore May- 1 1/2" A333 Gr Closed Drains 190 PSI 30ºC 1.5 mm Buchan (North 11 6 Sea)

Apache Forties Offshore Jun-11 1 1/2" A333 Gr Oil Recycle 260 PSI 77ºC 3.2 mm (North Sea) 6 Enquest Thistle Offshore Jun-11 2" & 3" A333 Gr Instrument Air 11.2 Bar Ambient 1.6 mm Alpha (North 6 / A106 tie in Sea) Gr b Talisman Offshore Jun-11 1-1/2" A333 Gr Nitrogen 10 Bar 40ºC 3 mm Saltire (North 6 Sea)

Talisman Offshore Jun-11 2" A333 Gr Atmospheric Atmos 180ºC 3 mm Saltire (North 6 Vent #300 Sea)

Talisman Offshore Jun-11 2" A333 Gr Atmospheric Atmos 85ºC 3 mm Saltire (North 6 Vent #150 Sea)

Talisman Auk Offshore Jun-11 1" A333 Gr Diesel Oil 3 Bar Ambient 3 mm (North Sea) 6 Talisman Offshore Jun-11 1-1/2" A333 Gr Oil Recycle 17.92 77ºC 3.2 mm Claymore 6 Bar (North Sea) #300

Non-Confidential Information Submitted Under 10 CFR 2.390 Response to Request for Additional Information Page 6 Lokring LTCS-333 Installations.

Type of Size & Pipe Max.

Company facility Date Schedule Spec. Service Press Temp. CA*

Talisman Offshore Jul-11 2" A333 Gr Fuel Gas 6.55 Bar 200ºC 3 mm Arbroath (North 6 Sea)

Talisman offshore Jul-11 3/4" A333 Gr Hydrocarbon 5.9 Bar 100ºC 3 mm Buchan (North 6 #150 Sea)

ConocoPhillips Offshore Jul-11 2" A333 / LP Vent Atmos 38ºC 3.2 mm Viking A106 (Southern North Sea)

ConocoPhillips Offshore Jul-11 2" A333 Pipe Bridge 12 Bar Ambient 3.2 mm Loggs Fuel Oil Line (Southern North Sea)

ConocoPhillips Offshore Jul-11 2" A106 Open Drains #150 3.2 mm Loggs (Southern North Sea)

ConocoPhillips Offshore Jul-11 1-1/2" A333 Purge Gas #300 3.2 mm Loggs (Southern North Sea)

ConocoPhillips Offshore Jul-11 1-1/2" A333 HP Fuel Gas #300 3.2 mm Viking to Vent (Southern North Sea)

ConocoPhillips Offshore Jul-11 1-1/2" A333 Purge Gas to #300 3.2 mm Loggs Vent (Southern North Sea)

ConocoPhillips Offshore Jul-11 2" A333 Closed Drains 241 Bar 60ºC 3.2 mm Vulcan (North Isolation Des Sea) #1500 ConocoPhillips Offshore Jul-11 2" A333 Diesel Oil #150 3.2 mm Viking (Southern North Sea)

ConocoPhillips Offshore Jul-11 2" A333 Methanol #300 3.2 mm Viking Lines (Southern North Sea)

Apache Forties Offshore Jul-11 4" A333 LP Flare 3.5 Bar 100ºC 1.6 mm Alpha (North Sea)

Centrica Offshore Jul-11 1" & 2" A106 Plant Air 1.6 mm Kittiwake (North Distribution Sea)

Talisman Offshore Aug-11 2" A333 Gr Closed 30 Bar 94ºC 3 mm Tartan (North 6 Hydrocarbon Sea) Drains Talisman Offshore Aug-11 1" & 2" A333 Gr Condensate 49 Bar 68ºC 3 mm Tartan (North 6 Recovery Sea)

Talisman Offshore Aug-11 4" A333 Gr Water 5.16 Bar 100ºC 3 mm Tartan (North 6 Skimmer Sea) Hydrocyclone

Non-Confidential Information Submitted Under 10 CFR 2.390 Response to Request for Additional Information Page 7 Lokring LTCS-333 Installations.

Type of Size & Pipe Max.

Company facility Date Schedule Spec. Service Press Temp. CA*

Nexen Scott Offshore Aug-11 1" A333 Gr Chemical Inj Atmos 23ºC 3 mm (North Sea) 6 (Corrosion &

Scale Inhibitor)

Talisman Offshore Aug-11 2" A333 Gr Closed 29.4 Bar 70ºC 3 mm Tartan (North 6 Hydrocarbon Sea) Drains Talisman Offshore Aug-11 1-1/2" & 2" A333 Gr Process 50 Bar 68ºC 3 mm Tartan (North 6 Water Sea)

BP Exploration Production Aug-11 1" A333 Fuel Gas 100 PSI 60ºF 1/8" Alaska Ineos Finnart Offshore Aug-11 1-1/4" A333 Gr Crude Oil 10 Bar 55ºC 3 mm Ocean Terminal 6 Import ConocoPhillips Offshore Aug-11 2" A333 Gr Process Drain Atmos Ambient 3.2 mm Viking 6 Sump (Southern North Sea)

ConocoPhillips Gas Plant Aug-11 2" A333 Natural Gas 3.8 Bar (-46 to 3.2 mm TGT +30ºC)

ConocoPhillips Gas Plant Aug-11 2" A333 Fuel Gas 3.8 Bar (-46 to 3.2 mm TGT Reroute +30ºC)

ConocoPhillips Gas Plant Aug-11 3" A333 Diesel Oil #150 3.2 mm TGT Chevron Alba Offshore Aug-11 2" A333 Offload 3.2 mm FSU (North Metering Sea) Pipework Enquest Thistle Offshore Aug-11 2" & 3" A333 Diesel Oil 10 Bar (-7 to 3.2 mm Alpha (North +50ºC)

Sea)

Enquest Thistle Offshore Aug-11 2" A333 Instrument Air 11.2 Bar (-7 to 1.6 mm Alpha (North +50ºC)

Sea)

ConocoPhillips Offshore Aug-11 1-1/2" A333 Process #150 3.2 mm Judy (North Isolation Sea)

Talisman Bleo Offshore Sep-11 2" A333 Gr Crude Oil 4 Bar 100ºC 3 mm Holm (North 6 Handling to Sea) Closed Drains Total (St Offshore Sep-11 2" A333 LP Nitrogen 11 Bar (-20 to 1.6 mm Fergus) +25ºC)

Shell MLNG Onshore Oct-11 2" A333 Pilot Fuel Gas 5 Bar (-15 to 3.2 mm Malaysia 10ºC)

ConocoPhillips Gas Plant Oct-11 1" A333 Active Fire 3.2 mm TGT Protection Pipework Shell (Sakhalin Offshore Oct-11 1-1/2" & 2" A333 Gr Fuel Gas 27.3 Bar (-46 to 1.6 mm Energy) & 3" 6 +70ºC)

BP Andrew Offshore Oct-11 1" & 2" A333 Gr Flare Stack 3 mm (North Sea) 6 Refit Petrofac - Offshore Oct-11 1" A333 Produced Atmos (-10 to 1.6 mm G.Yarmouth Water +38ºC)

(Southern North Sea)

Non-Confidential Information Submitted Under 10 CFR 2.390 Response to Request for Additional Information Page 8 Lokring LTCS-333 Installations.

Type of Size & Pipe Max.

Company facility Date Schedule Spec. Service Press Temp. CA*

ConocoPhillips Offshore Oct-11 2" A333 Gr Foamer 1.5 Bar (-5 to 3 mm Vulcan (North 6 Chemicals +40ºC)

Sea)

Shell - Bacton Gas Oct-11 2" A333 Propane #150 (-20 to 3.2 mm Terminal Discharge +150ºC)

Sable Platform Offshore Nov-11 2" A333 Gr6 Hydrocarbon 2414 Ambient -

Closed Drain kPag 30ºC Syngenta Agri- Nov-11 3" Sch 40 API 5L DiMethyl 6 Bar Ambient 1.6 mm chemicals Formamide Chevron Alba Offshore Nov-11 2" A106 Gr Open Drain 19.6 Bar 38ºC 3 mm North (North B Sea)

Talisman Clyde Offshore Nov-11 2" A106 Gr Instrument Air 10 Bar Ambient 1.5 mm (North Sea) B System ConocoPhillips Offshore Nov-11 1" & 2" A333 Gr Diesel 4 Bar 35ºC 3 mm Caister (North 6 Pipework Sea)

Georgia Gulf Petroche Nov-11 1 1/2" Sch PT Mix 300 100ºF Corporation mical 160 (Propane & PSIG Propylene Centrica Offshore Dec-11 4" Sch 40 A333 Water Glycol 3.4 Bar 71-110*C 3.2 mm Storage-Rough grade 6 Heating Bravo Gas Medium Platform Flint Hills - Refinery Dec-11 1 1/2" Sch A106 Merox 40 PSI 100ºF 1/8" Corpus Christi 160 Caustic TX BP Magnus Offshore Dec-11 4" A333 Gr Vent Line on 3 mm (North Sea) 6 Seal Oil Tank Talisman Offshore Dec-11 3" A106 Gr Diesel Fuel 15.9 Bar 150ºC 3 mm Montrose (North B System Sea)

ConocoPhillips Offshore Dec-11 2" A333 Gr Bridge Plant 10.5 Bar (-10 to 3 mm Loggs (North 6 Air Pipework +50ºC)

Sea)

Talisman Bleo FPSO Dec-11 4" A333 Gr Natural Gas 35 Bar 135ºC 1.5 mm Holm (North 6 Sea)

Talisman Bleo FPSO Dec-11 3/4" & 1" & A106 Gr Steam 10 Bar 185ºC 1.5 mm Holm (North 2" B / A333 Condensate Sea) Gr 6 BG Group Offshore Dec-11 2" A106 Gr Grey & Black #150 (-6 to 3 mm Everest (North B Water Vents +80ºC)

Sea)

BG Group Offshore Dec-11 2" A106 Gr Hydrocarbon 6.9 Bar 70ºC 3 mm Everest (North B Drain from Sea) TEG contactor BG Group Offshore Dec-11 2" A106 Gr Glycol Closed 6.9 Bar 90ºC 3 mm Everest (North B Drain Sea)

BG Group Offshore Dec-11 2" A333 Gr Chem. 6.9 Bar 30ºC 3 mm Everest (North 6 Injection Sea) Drain (film forming Amine)

Non-Confidential Information Submitted Under 10 CFR 2.390 Response to Request for Additional Information Page 9 Lokring LTCS-333 Installations.

Type of Size & Pipe Max.

Company facility Date Schedule Spec. Service Press Temp. CA*

Centrica Gas Dec-11 1" Sch 80 A333 Gr Methanol/ 17 Bar Ambient 3 Storage - Receiving 6 Natural Gas/ #150 to-LT on Easington Terminal Vent Blowdow n .2 mm BP Amethyst - Offshore Jan-12 3/4" & 2" A333 Condensate 1 Bar Ambient 3.2 mm Gas platform Sch 80 Grade 6 Drain to-LT on Blowdow n

Centrica Offshore Jan-12 1" Sch 80 A333 Drain Lines 1 Bar Ambient 3.2 mm Storage-Rough Grade 6 to-LT on Bravo Gas Blowdow Platform n Syngenta Agri- Jan-12 1" & 2" A333 Gr Sodium 9 bar 30ºC 3.2 mm Grangemouth chemicals 6 Methoxide Hibernia Offshore Jan-12 1" & 3/4" Nitrogen &

Platform Instrument air Talisman Bleo FPSO Jan-12 2" A333 Gr Flare Gas 3.5 Bar 120ºC 3 mm Holm (North 6 Sea)

Talisman Tartan Offshore Jan-12 1" A333 Gr Closed Drains 1.4 Bar 200ºC 3 mm (North Sea) 6 #150 BG Group Offshore Jan-12 2" A333 Gr Closed Drain 6.9 bar 30ºC 3.2 mm Lomond (North 6 (from Chem. 150 Sea) Inj package)

Talisman Offshore Jan-12 1" A333 Gr Produced Atmos 21ºC 3 mm Fulmar (North 6 Water Vent Sea)

Talisman Tartan Offshore Jan-12 2"& 4" A333 Gr Closed Drains 1.4 Bar 200ºC 3 mm (North Sea) 6 #150 Talisman Offshore Jan-12 3" A333 Gr Drains Atmos Ambient 3 mm Fulmar (North 6 #150 Sea)

Talisman Tartan Offshore Jan-12 2" A333 Gr Closed Drain 1.4 Bar 200ºC 3 mm (North Sea) 6 CNR Ninnian Offshore Jan-12 2" A333 Gr Air System 9 Bar Ambient 1.6 mm North (North 6 Overhaul Sea)

Talisman Flotta Oil & Jan-12 4" A106 Gr Hydrocarbon 6.9 Bar 38ºC 1.6 mm Terminal Propane B Vapour Flare #150 Orkney Terminal ConocoPhillips Offshore Jan-12 1-1/2" A333 Gr Hydrocarbon 83.5 Bar (-19 to + 3 mm Loggs 6 Condensate 50ºC)

(Southern North Sea)

ConocoPhillips Offshore Feb-12 1/2" A333 Gr Gas Metering 130.4 (-46 to 3 mm Loggs 6 Pipework Bar +200ºC)

(Southern North #1500 Sea)

ConocoPhillips Offshore Feb-12 2" A333 Gr Anti Foamer 19.6 Bar (-46 to 3 mm Viking 6 Bund Drain +38ºC)

(Southern North Sea)

BP Kinneil stabilisatio Feb-12 1/2" A333 Gr Refrigerated Grangemouth n& 6 LPG separation plant

Non-Confidential Information Submitted Under 10 CFR 2.390 Response to Request for Additional Information Page 10 Lokring LTCS-333 Installations.

Type of Size & Pipe Max.

Company facility Date Schedule Spec. Service Press Temp. CA*

Perenco - Offshore Mar-12 3" A106 Gr Condensate 43.5 38ºC 1/8" (Southern North B / A333 PSI (# Max Sea) Gr 6 600 Flange)

Conoco Phillips Offshore Mar-12 2" Sch 80 Compressed #150 3.2 mm Norway Lube Oil Tank Drain ExxonMobil - Petroche Mar-12 2" & 4" A106 Gr Nonene - 50 PSI Ambient 1.6 mm Fawley mical B Offilent (#150 Feedstock Flange)

Talisman FPSO Mar-12 4" A106 Gr Hydrocarbon 1.5 Bar 100ºC 3.2 mm Buchan (North B / A333 Atmospheric Sea) Gr 6 Vent Talisman Bleo FPSO Mar-12 2" A106 Gr Steam 10 Bar 180ºC 1.5 mm Holm (North B / A333 Condensate Sea) Gr 6 Talisman Bleo Offshore Mar-12 4" A333 Gr Flare Gas 10 Bar (-45 to 3 mm Holm (North 6 +120ºC)

Sea)

Talisman Tartan Offshore Mar-12 2" A333 Gr Texatherm 16 Bar 300ºC 1.5 mm (North Sea) 6 HT22 (Heating Medium)

BP Bruce Offshore Mar-12 1-1/2" A333 Gr Fuel Gas 5.25 Bar 65ºC (North Sea) 6 Vent to Atmosphere ConocoPhillips Offshore Mar-12 2" A333 Gr SNS Isolation 51.1 Bar (-46 to 3 mm Viking 6 +38ºC)

(Southern North Sea)

Talisman Auk Offshore Mar-12 1" & 2" API 5L Diesel Fuel 19.6 Bar 55ºC 1 mm South (North Sea)

BP Refinery - Refinery Apr-12 2" Sch 80 A106 Sour Water 15 PSI 110ºF 1/8" Texas City Talisman Clyde Offshore Apr-12 1" A106 Gr Export (North Sea) B Metering Upgrade Talisman Saltire Offshore Apr-12 4" API 5L / Open Drains Atmos Ambient 2.54 mm (North Sea) A333 Gr 6

Talisman Offshore Apr-12 1/2" & 3/4" API 5L Process Gas 13.8 Bar 98ºC 2.54 mm Montrose & 1" & 2" Condensate (North Sea)

Talisman Saltire Offshore Apr-12 2" API Vent to LP 3.5 Bar (-7 to 3 mm (North Sea) 5L/A333 Flare #150 +100ºC)

Gr 6 Talisman Piper Offshore Apr-12 3" API 5L / Vent to 0.35 Bar (-7 to 3 mm (North Sea) A333 Gr atmosphere #150 +85ºC) 6 Talisman Flotta Oil & Apr-12 3" A106 Gr Instrument Air 7.6 Bar 16ºC 1.6 mm Terminal Propane B System Orkney Terminal BP Magnus Offshore Apr-12 1" A106 Gr Instrument Air 19.6 Bar (-46 to 1.6 mm (North Sea) B System +120ºC)

Non-Confidential Information Submitted Under 10 CFR 2.390 Response to Request for Additional Information Page 11 Lokring LTCS-333 Installations.

Type of Size & Pipe Max.

Company facility Date Schedule Spec. Service Press Temp. CA*

ConocoPhillips Offshore Apr-12 1" A333 Gr Utility Air 3 mm Viking 6 Pipework (Southern North Sea)

ConocoPhillips Offshore Apr-12 1" & 2" A333 Gr Emergency 153.1 (-46 to 3 mm Viking 6 Generator Bar +38ºC)

(Southern North Diesel Supply Sea)

Georgia Gulf Petroche May- 3" Sch 160 Propane 500 100ºF Corporation mical 12 PSIG Total (West Offshore May- 2" A333 Gr Open 5 Bar (-6 to 3 mm Franklin EPCI 4 12 6 Hazardous +55ºC) project) (North Drain Sea)

Total (West Offshore May- 2" A333 Gr Closed Drain 15 Bar (-46 to 3 mm Franklin EPCI 4 12 6 +140ºC) project) (North Sea)

Total Alwyn Offshore May- 1" & 2" & 3" A333 Gr Firewater 3 North (North 12 6 Pumps Sea) Replacement mm BP Magnus Offshore May- 1" A333 Gr Plant Air to 12 Bar (-46 to 1.6 mm (North Sea) 12 6 Crane +120ºC)

Talisman Clyde Offshore May- 1"& 1-1/2" A106 Gr Hydrocarbon 20 Bar 85ºC 3 mm (North Sea) 12 B Closed Drains #300 Talisman AUK Offshore May- 2" A106 Gr Hazardous 3.5 Bar 100ºC 3 mm (North Sea) 12 B Closed Drains Chevron Offshore May- 1" A333 Gr Diesel 11 Bar Ambient 3 mm Captain (North 12 6 Sea)

BP Magnus Offshore May- 1" A106 Gr Plant air to 12 Bar 120ºC 1.6 mm (North Sea) 12 B / A333 Crane Gr 6 ConocoPhillips Offshore May- 2" A333 Gr Diesel 51.1 Bar (-46 to 3 mm Victor (North 12 6 Storage Tank +38ºC)

Sea) Fill Line BG Group Offshore May- 2" A106 Gr Hydrocarbon 15 Bar 70ºC 3 mm Everest (North 12 B / A333 #300 Sea) Gr 6 Apache VI Offshore May- 2" A106 Diesel #150 #150 3mm Power 12 Generation Upgrade WA Total West Offshore May- 2" A333 Gr Plant Air 10.5 Bar (-10 to 3 mm Franklin (North 12 6 +60ºC)

Sea)

QLD Gas / BG Gas Plant May- 3" A106 Gr Produced #150 (-6 to 3 mm Group 12 B Water Piping +55ºC)

BP Exploration Production May- 2" A333 Fuel Gas 100 PSI (-50ºF to 1/8" Alaska 12 Ambient)

BP Magnus Offshore May- 1" A333 Gr Instrument / 19.6 Bar (-46 to 1.6 mm (North Sea) 12 6/A106 Plant Air to +120)

Gr b HPU Conoco Phillips Production May- 1" A333 Drain Line 100 PSI (-50ºF to 1/8" Alaska 12 Ambient)

Non-Confidential Information Submitted Under 10 CFR 2.390 Response to Request for Additional Information Page 12 Lokring LTCS-333 Installations.

Type of Size & Pipe Max.

Company facility Date Schedule Spec. Service Press Temp. CA*

BP Bruce Offshore May- 4" A333 Gr Oily Water Atmos (-10 to 3.2 (North Sea) 12 6 Drain +60) Mm BP Exploration Production May- 1-1/2" & 3" A333 Fuel Gas 150 PSI 60ºF Alaska 12 Shell MLNG Onshore May- 3" Sch 80 A333 Gas 8.6 Bar (-47 to 3.2 mm Malaysia 12 Discharge +85ºC)

ExxonMobil Gas Plant May- 1 1/2" A333 Gr Process 3.47 Bar (-2 to 1.6 mm Mossmorran 12 B Hydrocarbon 3ºC)

Drain line Arcelor Mittal - Steel May- 1-1/2" SCH A106 Hydraulic Oil 2500 Ambient 1/16" Burns Harbour Production 12 160 PSI Arcelor Mittal - Steel Jun-12 2" Sch 160 A106 Hydraulic Oil 2500 Ambient 1/16" Burns Harbour Production Total West Offshore Jun-12 2" A333 Gr Open Drain 3 mm Franklin (North 6 Sea)

Total St Fergus Gas Plant Jun-12 1" & 1-1/2" A106 Gr Hydraulic Oil 172 bar Ambient b #1500 BG Group Offshore Jun-12 2" & 3" A333 Gr Hydrocarbon 73 Bar ) (-45 to 3 mm Lomond (North 6 Gas (Treated #600 +195ºC)

Sea)

BP Exploration Production Jun-12 2" A333 Fuel Gas 50 PSI 60ºF 1/8" Alaska Conoco Phillips Production Jun-12 2" A333 Fuel Gas 50 PSI 60ºF 1/8" Alaska Talisman Offshore Jun-12 2" A333 Gr Heating 4.82 Bar 93ºC 3.2 mm Montrose (North 6 Medium Sea)

Talisman Offshore Jun-12 2" A333 Gr Accommodati 14.5 Bar Ambient 1.6 mm Montrose 6/A106 on Flushing (North Sea) Gr b Water Talisman Offshore Jun-12 2" A333 Gr MEG (Mono 4.82 Bar 93ºC 3 mm Montrose (North 6/A106 Ethylene Sea) Gr b Glycol)

Total North Offshore Jun-12 1/2" & 3/4" A333 Gr 209 Bar 3 mm Alwyn B (North & 1-1/2" 6 Sea)

Total North Offshore Jun-12 3" A333 Gr 19.6 Bar (-46 to 3 mm Alwyn B (North 6 +200ºC)

Sea)

Total North Offshore Jun-12 1" A333 Gr 35 Bar (-46 to 3 mm Alwyn B (North 6 +130ºC)

Sea)

Total Elgin Offshore Jun-12 2" A333 Gr Hazardous 5 Bar (-6 to 3 mm (North Sea) 6/A106 Open Drain 55ºC)

Gr b

  • Corrosion Allowance

Non-Confidential Information Submitted Under 10 CFR 2.390 Response to Request for Additional Information Page 13 Field failures of the Lokring LTCS-333 material are at a rate of [0.045%]. The LTCS-333 product was introduced in the late 1990s in partnership with BP and ConocoPhillips for upstream oil and gas applications. In approximately 2010, the product line was further developed into a wider range of product configurations and sizes (up to NPS 4). To date, it is estimated that 40,000 LTCS-333 products are installed and in service. And to date, the total combined return rate for product field performance related issues is [18], which is a return rate = [18/40,000 = 0.045%]. The following are details on the return date, product affected, quantity, effect and root cause determined from an evaluation of the returned product Quantity Return Year Product Affected Effect Root cause

[

]

Non-Confidential Information Submitted Under 10 CFR 2.390 Response to Request for Additional Information Page 14 The following is a detailed summary of the effect, quantity, and percentage of failure rate (%):

Total Lokring fittings 40,000

[

]

With regards to corrosion, Attachment 5 contains an Executive Summary - Crevice Corrosion Test of Lokring LTSC-333 and Socket weld Fittings (Confidential Information).

RAI #2:

Background

Section 5 of the November 16, 2020, application states, in part:

Rather, the margins are based on the ratio between burst pressure and the design pressure of the coupled piping. The rated pressure is downrated from the burst pressure, based on elevated-temperature tensile testing, in the same manner as was used to rate the fittings made from the material in Code Case N-879.

The proprietary fittings that Exelon desires to use are designed in accordance with ASME Section Ill, NC/ND-3671.7, Sleeve-Coupled and Other Patented Joints, using the option of prototype testing. All fittings sizes will be tested prior to installation.

The fittings Exelon desires to use have been extensively tested to demonstrate that the fittings will not fail before the pipe on which they are installed. The fittings have been tested by tensile (pull-out) testing, pressurization to burst, fatigue testing, and torsion testing. Fatigue analysis is not required for the requested applications but is performed for the purpose of establishing a stress intensification factor (SIF), for use by the piping system designer.

While the licensees application states that all fitting sizes will be tested prior to installation, prototype testing is not specified in paragraphs NC/ND-3671.7 of the ASME BPV Code, Section III.

Specifically, paragraphs NC/ND-3671.7 state, Coupling-type, mechanical gland type, and other patented joints may be used where experience or tests have demonstrated to the satisfaction of the designer that the joint is safe for the Design Loadings and when adequate provision is made to prevent separation of the joint. The application also indicates that tensile testing, pressurization testing to burst, fatigue testing, and torsion testing have been performed, and this testing is provided as a basis for the acceptability of fabricating fittings from the material listed in Code Case

Non-Confidential Information Submitted Under 10 CFR 2.390 Response to Request for Additional Information Page 15 N-893. This testing appears similar to the prototype testing required by paragraph NB-3671.7 of the ASME BPV Code, Section III. However, paragraphs NC/ND-3671.7 do not require prototype testing and do not provide guidance on what types of testing should be performed.

Request Provide a summary of the qualification testing (with applicable testing specifications) that has been or will be performed for all Class 2 and 3 Lokring fittings made using Code Case N-893 material. Clarify if the specific sizes of all fittings used for repairs will be subject to tensile (pull-out) testing, pressurization to burst, fatigue testing, and torsion testing. If not, provide a technical basis for not performing tensile (pull-out) testing, pressurization to burst, fatigue testing, and torsion testing on all fitting sizes.

Response

Test Summary Matrix for LTCS-333 product made with Code Case N-893 material. Tests performed per NC/ND 3671.7 Tensile - Vibration -

Burst - Test to Test per EPRI Pipe Pipe Test per max. Torsion - Test High Cycle Size Spec, ANSI Flex- Test per load to max. load Fatigue Product NPS Grade B16.9 ASME B31J capacity capacity method LTCS-333-CPL-P08 1/2 (1) (1) (1)

LTCS-333-CPL-P12 3/4 A106 LTCS-333-CPL-P16 1 Grade B, (1) (1) (1)

A53 LTCS-333-CPL-P24 1 1/2 (1) (1)

Grade B, LTCS-333-CPL-P32 2 API 5L Grade B LTCS-333-CPL-P48 3 (1)

LTCS-333-CPL-P64 4 Notes:

1. The results of tested size may be extrapolated between one half and 1.5 times the NPS size of the tested specimen (NC/ND-3671.7).
2. Qualification testing of LTCS-333 on ASTM A335 Grades P11 and P22 is underway. Qualification testing estimated completion in 2021.

Attachment 2 Executive Summary - Crevice Corrosion Test of Lokring LTSC-333 and Socket weld Fittings (Non-Confidential Information)

Non-Confidential Information Submitted Under 10 CFR 2.390 LOKRING TECHN NOLOGY, LLC C 383766 APOLLO PAR RKWAY WILL LOUGHBY OHIO 44094-7724 TEL.: (440) 942-0880 FAX: (440)-942-1186 wwww.lokring.co om DDate: March 8, 2013 EExecutive Sum mmary - Creviice Corrosion Test of Lokring LTCS-333 and Socket w weld Fittings

((Ref: Element Report No. 12 2040601)

[

LLokring Techno ology (Elastic Strain Preload d) Fittings havee been installedd on pipe and tuube in a wide rrange of appliccations for mmore than 20 years. The Lok kring products have h been quallified per the A ASME B31 pipping codes and are an accepteed alternative to o thhe more widely y used socket welded w connecction method. It I can be proveen that Lokringg fittings are inntrinsically a beetter pperforming pipe and tube con nnection (reliabbility, consistenncy and repeataability) than a socket weld.

LLokring frequently meets with h customers th hat are hesitant to use either soocket welds orr Lokring fittinngs in system coonditions that ccan create creviice corrosion. The Lokring fitting f design has h a hairline gaap between thee pipe and fittinng body of which creates a

""wetted" cavity y. There are no o known issuess with the Lokrring fitting thatt have been cauused by crevicee corrosion. Addditionally LLokring has perrformed variou us corrosion tessts (ASTM B117, NACE TM M0-177), but haas not done tests specifically focused on ccorrosion due to the affects off the small cavity created betw ween the pipe and fitting boddy.

EElement Materiials Technolog gy, Sheffield, England E were asked a to develoop an appropriaate test methodd to determine tthe impact of thhe small cavity y, or crevice, in n the Lokring fitting f design which w resulted in using "ASTM M G78 Standard Guide for C Crevice CCorrosion Testting of Iron-Basse and Nickel-B Base Stainless Alloys in Seaw water and Otheer Chloride-Coontaining Aqueeous EEnvironments" as a basis for an a accelerated 30 day test. Th he intent was too evaluate the crevice specifiic to the Lokrinng and to a ssocket weld dessign, therefore requiring mod difications to bee made to aspeects of the test set up. They hhowever maintained the test ssolution and ex xposure conditiions as outlined d in ASTM G7 78 TTest Solution A:A 5.0 wt% sodium chloride an nd 0.5 wt% glaacial acetic acidd dissolved in distilled or deiionised water (e.g., 50.0 g of NNaCl and 5.0g of CH3COOH dissolved in 945 9 g of distilleed or de-ionisedd water).

IIn this test for the t affects of corrosion were investigated with w several connditions that coould potentiallyy have an effecct on the rresults, relating g to the conditioons of the pipee & installation n. There were ttwo Lokring (L LTCS-333-CPL L-P16) fittingss installed on AASTM A333 Grade G 6, 1" NPSS Schedule 80 pipe, with the following connditions:

Fittingg #1 o End "a"- Pip pe end cut at 10 degrees. Th his is not recommmended practiice, but could ooccur in the fieeld.

o End "b"-Pip pe outside diammeter and Lokrring fitting boddy inside diameeter coated withh Belzona 1111 liquid metal coating. Th his is an option n offered to cusstomers, whichh when fully cuured fills the gaap between thee pipe and Lokring fittting body.

Fittingg #2 o End "c"- Pip pe is scored longitudinally to o extend the gap ap, or crevice, ppast the inboard seal on the fiitting body.

o End "d"- Th his is a standarrd fitting installlation as done pper Lokring Innstallation Proccedure LP-105.

TThere is one so ocket welded fitting in this tesst, which is a sttandard ASTM M A105 fitting socket welded to ASTM A3333 Grade 6, 1" NNPS Schedule 80 pipe. (2 x Weld W referenced d W1 & W2).

]

CCopyright 2013 3 Lokring Tech hnology, All rig ghts reserved wwww.lokring.com m TR12-006 E Exec Summ 0308113

Non-Confidential Information Submitted Under 10 CFR 2.390 LOKRING TECHN NOLOGY, LLC C 383766 APOLLO PAR RKWAY WILL LOUGHBY OHIO 44094-7724 TEL.: (440) 942-0880 FAX: (440)-942-1186 wwww.lokring.co om TTest Results:

TTesting of the Lokring L fitting and Socket weeld fitting test specimen resullted in finding crevice corrossion, general coorrosion and

[ ppitting corrosioon in the gap, or o crevice, of th he standard soccket welds. Wiith the Lokringg fitting, there w was general coorrosion and sstaining found in the gap, or crevice, c but theere was no crev vice corrosion or pitting corroosion found annywhere withinn the fitting.

TThe results of o the testing g of the Lokrring LTCS-3 333 fitting annd Socket weeld fitting arre as followss:

Fitting Lokring g Coupling insttalled on pipe Socket weld coupling installed on pipe End E # 1a 1b 2c 2d W1 W2 Fitting Maaterial AISI 4130 Q Q&T ASTMM A105 Pipe ASTM M A333 Gradee 6 Sched 80 ASTM A3333 Grade 6 Sched 80 Saample pipe end d cut Belzona 1111 1 applied** pipe scored standard standard installaation to ASME at 100 longitudinally installation B311.3 Cond dition degreees Obsservations for Cut face ofo the Generall and General G General and General and General and General and smalll small amount small pitting. pitting.

Creevice, General pipe end amoun nt of of pitting. amount or Pitting pittin ng. of pitting.

corrosion Internal Fitting Generral Clean C General General General and General and (staininng) (staining) (staining) pitting. pitting.

body inclu uding seals Pipe OD Generral Clean C General General General and General and (staininng) (staining) (staining) pitting. pitting.

Exteernal- Generral Clean C General General NA NA (staininng) (staining) (staining) outboard d seal Sum mmary No Crevicce No Crev vice No Crevice No Crevice Crevice Crevice Corrosio on Corrosionn or Pitting. Corrosion or Corrosion or Corrosion, Corrosion, or Pittin ng The Belzoona shows Pitting Pitting General and General and Pitting Pitting slight improvement corrosion was corrosion of the corrrosion found. was found resistance..

]

CCopyright 2013 3 Lokring Tech hnology, All rig ghts reserved ww ww.lokring.com m TR12-006 EExec Summ 0308113

Non-Confidential Information Submitted Under 10 CFR 2.390 LOKRING TECHN NOLOGY, LLC C 383766 APOLLO PAR RKWAY WILL LOUGHBY OHIO 44094-7724 TEL.: (440) 942-0880 FAX: (440)-942-1186 wwww.lokring.co om DDiscussion:

A[ further evaaluation wass performed to determinee causes for crevice corrrosion to occcur in the soccket weld ttest specimen n and not in the Lokring g fitting test specimen.

s S Several variaables can haave an effect on crevice aand pitting corrosion. Th hey are prim marily related d to the geom metry and maaterial type aand hardness exposed to o tthe corrosivee media as well w as the ch hemicals and d the environnmental condditions invollved.

TThe socket weld w specimeen were foun nd to have material m hardnness values below Rc 200 within the crevice, wwhich is a haardness levell considered d not to have an effect onn pitting and crevice corrrosion for thhis type of mmaterial. Th he test specim men materiall types (all are a low carboon steel) andd test chemiccals and condditions are tthe same.

WWe concludee the cause for f the sockeet weld speciimen and to crevice corrrode and the Lokring fittings not to ccrevice corro ode may be due d the diffeerence in the geometries exposed to tthe test meddia. The geom metries that ccreate the gaap in a socket weld produ uce a larger volume v betw ween the pipe and fittingg for the corrrosive mediaa tto accumulatte versus thee Lokring fittting. The so ocket weld fiitting by the nature of itss design and method to mmanufacture (forged finished shape) will have a more loose fit on pipe ccompared wiith the tight ttolerances ffound in a Lo okring fitting g that is preccision machiined to fit tigght with the pipe and reqquires a gagee (multi-ppurpose gagee) to inspect the pipe diaameter and fiit prior to insstallation. T The size of thhe gap existiing in the ssocket weld may m create the t condition ns for the corrrosive mediia to work effectively inn limiting oxygen rreplenishmen nt to the areaa thus reduciing cathodicc reactions reesulting in piitting and coorrosion.

LLokring are theerefore pleased d to endorse Lo okring LTCS-333 Fittings forr applications thhat may result in Crevice Corrrosion. We wwould howeverr suggest that you y work closeely with your Lokring L represeentative to ensuure all parties aare comfortablee with the ooverall system conditions & parameters.

p

      • If Belzona 1111 1 is to be ap pplied please foollow Lokring Work Instructtion WI-INST--001.

LLokring havee also previo ously conduccted acceleraated Salt Sprray testing too ASTM B117 that incluuded CCorrosion an nalysis & Bu urst tests. Tesst report, Im mages & Certtification avaailable.

WWhen selecting g Lokring fittin ngs for use in an ny application, total system ddesign must bee considered to ensure safe, trrouble free pperformance. Material M compaatibility, system m pressure andd temperature rratings, adequaate corrosion coontrol or allow wances, control oof fluid velocitiies, fluid chemmical treatment,, proper installaation, operationn and maintenaance are the reesponsibility off the system ddesigner, owner and operator..

]

CCopyright 2013 3 Lokring Tech hnology, All rigghts reserved ww ww.lokring.com m TR12-006 EExec Summ 0308113