RS-12-171, MPR-3801, Seismic Walkdown Report in Response to the 50.54(f) Information Request Regarding Fukushima Near-Term Task Force Recommendation 2.3: Seismic, Revision 1, Part 12 of 13

From kanterella
(Redirected from RS-12-171)
Jump to navigation Jump to search
MPR-3801, Seismic Walkdown Report in Response to the 50.54(f) Information Request Regarding Fukushima Near-Term Task Force Recommendation 2.3: Seismic, Revision 1, Part 12 of 13
ML12342A131
Person / Time
Site: Limerick 
Issue date: 11/06/2012
From: Schlaseman C
Exelon Generation Co, MPR Associates
To:
Office of Nuclear Reactor Regulation
References
RS-12-171 MPR-3801, Rev 1
Download: ML12342A131 (41)


Text

Table C-2. Unit 0 Seismic Walkdown Checklists (SWCs)

Anchorage Awc-UO-Component ID Description Configuration xx Confirmed?

0OB132 Control Enclosure Safeguard 440V MCC Y

1 00B519 Spray Pond 440V AC Power MCC Y

2*

DIV I Spray Pond Pump Structure 120V AC 2*

01X566 Instrument Panel XFMR Control Panel Spray Pond Pump Structure N

2*

0AC564 Air Supply Fan OAK112 Control Structure Chiller N

8 0AP162 Control Room HVAC Chilled Water Pump N/A 8*

0AP506 RHR Service Water Pump Y

2 0AP548 Emergency Service Water Pump Y

2*

0BV543 B' Spray Pond PP. Structure Air Supply Fan Y

5 0CC667 ESW Division III Control Panel N

AWC-U2-19 HD-078-027A Control Room Intake Damper N/A 6

HD-081-041A Spray Pond Intake Fan Damper N/A 7

HV-078-021 B Outside Air to MCR Isolation Valve N/A 3

HV-1 2-032A Spray Nozzles A Inlet N/A 4

PSH-12-004A RHR Service Water Pump 0A506 Loop A N/A 9

Limerick Generating Station Unit 2 MPR-3801, Revision 1 Correspondence No.: RS-12-171 C-416

Sheet 1 of 2 Status:@ N U Seismic Walkdown Checklist (SWC)

Equipment ID No. 0OB132 Equip. Class" (01) Motor Control Centers / Low & Medium Voltage Switchgears Equipment Description Control Enclosure Safeguard 440VMCC Location: Bldg. Control Floor El. 304 Room, Area Room 619E Structure Manufacturer, Model, Etc. (optional but recommended)

Instructions for Completing Checklist This checklist may be used to document the results of the Seismic Walkdown of an item of equipment on the SWEL. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.

Anchorage

1. Is the anchorage configuration verification required (i.e., is the item one of the 50% of SWEL items requiring such verification)?
2. Is the anchorage free of bent, broken, missing or loose hardware?
3. Is the anchorage free of corrosion that is more than mild surface oxidation?
4. Is the anchorage free of visible cracks in the concrete near the anchors?

qYl~NE I

NDI UD-N/AD 14 NEI UD] N/AL]

A NE UD N/Arn

5. Is the anchorage configuration consistent with plant documentation?

YJZ NiD UD" N/AD (Note: This question only applies if the item is one of the 50% for t\\V which an anchorage configuration verification is tequired.)

" '4t1 0evd 4

01 tg4-ýb

"'wee po,10/

af 44vt IS bpie/ ^-. e~e

!fV to' ?c4

6. Based on the 'toveanchorage evaluations, isme anchorage ree of Y9 UDN na Ud]

Do

).00 potentially adverse seismic conditions?

Sedo 4 j

01.

V.

12 Enter the equipment class name from Appendix B: Classes of Equipment.

Limerick Generating Station Unit 2 MPR-3801, Revision 1 r.nrrPqnnndnP-nr. Nn *R.- 19-171 C-417

Sheet 2 of 2 Equipment ID No. 00B132 Equip. Class12 (01) Motor Control Centers / Low & Medium Voltage Switchgears Equipment Description Control Enclosure Safeguard 440VMCC Interaction Effects

7. Are soft targets free from impact by nearby equipment or structures?
8. Are overhead equipment, distribution systems, ceiling tiles and lighting, and masonry block walls not likely to collapse onto the equipment?
9. Do attached lines have adequate flexibility to avoid damage?
10. Based on the above seismic interaction evaluations, is equipment free ofpotentially adverse seismic interaction effects?

Y)ANO XNEI UD N/AD Ur N/AD UD N/AD YMNO UO Other Adverse Conditions

11. Have you looked for and found no other seismic conditions that could Y,< NE UD adversely affect the safety functions of the equipment?

Comments (Additional pages may be added as necessary)

Evaluated by:

Date:

Il-

< C-4 >

Limerick Generating Station Unit 2 MPR-3801, Revision 1

.nrrP.qnnnHAnr.A Nn

-RR-19-171 C-418

Equipment ID: 00B132 Limerick Generating Station Unit 2 MPR-3801, Revision 1 r*nrrPqnnndPnr.p Nn

  • RR-19-171 C-419

Equipment ID: 00B132 Limerick Generating Station Unit 2 MPR-3801, Revision 1 r.nrrP-nnndPnr*P Nn-RR-19-171 C-420

Equipment ID: 00B132 I

Limerick Generating Station Unit 2 C-421 MPR-3801, Revision 1 f.nrrp~nnndfnrA Nn-R.R-19-171

Sheet 1 of 2 Status: (D N U Seismic Walkdown Checklist (SWC)

Equipment ID No. 00B519 Equip. Class 12 (01) Motor Control Centers / Low & Medium Voltage Switchgears Equipment Description S&ray Pond 440VAC Power MCC Location: Bldg. Spray Pond Floor El. 268 Room, Area 'Room 1000 Building Manufacturer, Model, Etc. (optional but recommended)

Instructions for Completing Checklist This checklist may be used to document the results of the Seismic Walkdown of an item of equipment on the SWEL. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.

Anchorage

1. Is the anchorage configuration verification required (i.e., is the item one Y1<1ND of the 50% of SWEL items requiring such verification)?
2. Is the anchorage free of bent, broken, missing or loose hardware?

UE. N/AD A 6.,

at b~'tfV'tx%

heiy 4

t-A to bef 1 y ebe Ag (ZVMS

+1% Itebi roo E-It/. AaU pl,D.&J kAvet

,v,

~'

CAI,-Ade, A f, p

- AL 1,dWA11., 7vetY7 14,11

,'.i' v, Ce'OA.-

fftOP&A.q*.

V.40*,,

V"V P#

f,,-f

-t t,.

A,.tet.Ot (?ý.e.

3. Is the anchorage free of corrosion that is more than mild surface Yt2_JNU UD N/AD oxidation?

C.rI4AA

-j fawe art.

4. Is the anchorage free of visible cracks in the concrete near the anchors?

YdND-UD N/AD

5. Is'the anchorage configuration consistent with plant documentation?

V 1"-I UD N/AD (Note: This question only applies if the item is one of the 50% for which an anchorage configuration verification is required.)

/

  • y Pei A pa.kD,,, D+.

5.esP

-L 4..

tfi t*3

~4'A1,eW Mij r&

6. Based on the above anchorage+valuations, is tl~e anchorage free of,

$4N

,UD potentially adverse seismic conditions?

iA0,4t,4,ty, 4a.j;Ks ftq6.-.

C#

(46111 tdXi*

4vj to ýVe.

Se v.,.*--x~t#,* J+d.

t, 12 Etrthe equipment class name from Appendix B: Classes of Equipment.

"k,- 5# IP xw Vi imerick Generating Station Unit 2 C-422 MPR-3801, Revision 1 (flnrr~~nnnd~nr* Nn "RR-17-171

Sheet 2 of 2 Equipment ID No. 00B519 Equip. Class12 (01) Motor Control Centers / Low & Medium Voltage Switchgears Equipment Description Spray Pond 440VAC Power MCC Interaction Effects

7. Are soft targets free from impact by nearby equipment or structures?

-1UE]

NI/AE 104f1et

, o kr. -4v "AL 01 1'A f IfA& 4-2A rX I

ýA &1*g1 8.~ Are ovre q

1i Ib

8. A0hei*he p*me t, distribution systems, ceiling tiles and 1irghtin*, -Y*.rN UQ NIADJ and masonry block walls not likely to collapse onto the equipment?

1511 afJv

9. Do attached lines have adequate flexibility to avoid damage?
10. Based on the above seismic interaction evaluations, is equipment free of potentially adverse seismic interaction effects?

YXNEI UDi N/AE-2!NEI UEJ Other Adverse Conditions

11. Have you looked for and found no other seismic conditions that could Yi"NEI U3 adversely affect the safety functions of the equipment?

Comments (Additional pages may be added as necessary)

A!e~ta-e,-

r -e 6CA~j,6 47 4L,,

  • -4fe, 6A e~i

!4 A,,

0ic~

Y6 0.5 CA

&'f~

4 ~

.~A e~'~

ý 4 / e'-.V j~~-it el bl A

,t U(4~

(~e4 ~

d~V~trk.

'~?

~

4te,4iLI1~s3

+~4' S 4s")

-.1 I l Date:

Evaluated bv:

Y t h ( 4ý-

<C-4 >

Limerick Generating Station Unit 2 MPR-3801, Revision 1 r.nrrP,,nnndhpnnP Nn - RR-19-171 C-423

-p

(.)PKG.

NO.2~ SECTI~ON ts IE~v 4 Iauc aaw vamc ow TXom a"#"f orsa

1)

I.

Plant

~m:

1 to& 17& ~a so KW MOR

___OP,___________%Z S'C 2M

'2I SEC TI Oý7 e.

II.

Va~tImp

  • 'ev "Co O~O

~Nru

2. =958 c m

£

3. 4ft.

W Mape 5.0 If pwtu Ibms KOaO a-N-k L-zm care pimi.

f~~

le MRe dEvi Sz"d Ed____________

2.~~

1Ac4mA.N 4~bw 1NM 2

orrA 6.ty Rwsioul Dm.zt, in C.~~~~~~

rA~t 600 LP.i~~$~A

3. Znout mi adupt.

N/~A' PoTJ

?urtiE t~.

i.

P4~

3. it1 obw Comm= ~rits a 1tb.......

wPI adma.

26

-r%~~

~

CA-E b!

  1. (TmsrLYJ-i a,

O FLOOnmn

~PAUL"set

b. vs talo 2~~.0" VV 9 40" 1~4~~

20 Nf..

rGl ~ii~oAN A

60 Las VSIL Seno 7.~

~~

Todn dMISA ODMWF SR DE~-8,4 P-6 C-42O LinriE Geeatn

-aio ni MPR380 Rvison.1

-~.

E Cnrmnnnrpflr Nn 5~-1-on

Equipment ID: 00B519 I

Limerick Generating Station Unit 2 MPR-3801, Revision 1 r.nrrmnnndrnr.P Nn* RR-19-171 C-425

Equipment ID: 00B519 I

I Limerick Generating Station Unit 2 MPR-3801, Revision 1 rnrrP.nnnt*~nrP. Nn - RR-19-171 C-426

Sheet 1 of 2 Status:O N U Seismic Walkdown Checklist (SWC)

Equipment ID No. 101X566 Equip. Class1 2 (02) Transformers Equipment Description DIVI Spray Pond Pump Structure 120VAC Instrument Panel XFMR Location: Bldg. S&ray Pond Floor El. 268 Room, Area Room 1000 Building Manufacturer, Model, Etc. (optional but recommended)

Instructions for Completing Checklist This checklist may be used to document the results of the Seismic Walkdown of an item of equipment on the SWEL. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.

Anchora2e

1. Is the anchorage configuration verification required (i.e., is the item one YJZ Ni]

of the 50% of SWEL items requiring such verification)?

mi9-

2. Is the anchorage free of bent, broken, missing or loose hardware?
3. Is the anchorage free of cZrrosion that is more than mild surface oxidation?

~NEI UO

'NOJ UD N/AD

4. Is the anchorage free of visible cracks in the concrete near the anchors?

9

[

UI-N/AD COW114"14y It, efý CAPOCtiV V1 V'14 "7t re4Aws

~

5. Is the anchorage configuration consistent with plant documentation?

Y* ND UD N/AD (Note: This question only applies if the item is one of the 50% for which an anchorage configuration verification is required.)

C-632-,

04^

5.

kev., (0 M-9/7/12-

/

6. Based on the above anchorage evaluations, is the anchorage free of Y

.N& UD potentially adverse seismic conditions?

1 2 Enter the equipment class name from Appendix B: Classes of Equipment.

ý<C-3 >

Limerick Generating Station Unit 2 MPR-3801, Revision 1 CnrrP~nnndHnr. Nn - RR-19-171 C-427

Sheet 2 of 2 Equipment ID No. 01X566 Equip. Class12 (02) Transformers Equipment Description DIV I Spray Pond Pump Structure 120VAC Instrument Panel XFMR Interaction Effects

7. Are soft targets free from impact b nrby! eq*iPmet or structures?

At actb4ea YfN'NE! U-1 N/AD

8. Are overhead equipment, distribution systems, ceiling tiles and lighting, Y#]*NI" and masonry block walls not likely to collapse onto the equipment?

P fat(.

.f kV1)d -hto-l e(,e UD N/AD

9. Do attached lines have adequate flexibility to avoid damage?
10. Based on the above seismic interaction evaluations, is equipment free of potentially adverse seismic.interaction effects?

YE I-'I UE-N/AD YN-1 U-Other Adverse Conditions 1 1. Have you looked for and found no other seismic conditions that could Y" NEI U[-]

adversely affect the safety functions of the equipment?

Comments (Additional pages may be added as necessary)

Date:

4 7

c Limerick Generating Station Unit 2 MPR-3801, Revision 1 r.nrrP.nnndPnr.p Nn* RR-19'-171 C-428

Equipment ID: 01X566 Limerick Generating Station Unit 2 MPR-3801, Revision 1 rlnrrA~nnnrlPnrP Nn

  • R.-1*-171 C-429

She t1of2 Status:

N U Seismic Walkdown Checklist (SWC)

Equipment ID No. 0AC564 Equip. Class12 (18) Control Panels & Cabinets Equipment Description Control Panel Spray Pond Pump Structure Air Supply Fan Location: Bldg. Spray Pond Floor El. 268 Room, Area Room 1000 Location: Bldg. Spray PodFloor El. 268....

Room, Area Room 1000 Building Manufacturer, Model, Etc. (optional but recommended)

Instructions for Completing Checklist This checklist may be used to document the results of the Seismic Walkdown of an item of equipment on the SWEL. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.

Anchoraze

1. Is the anchorage configuration verification required (i.e., is the item one of the 50% of SWEL items requiring such verification)?
2. Is the anchorage free of bent, broken, missing or loose hardware?
3. Is the anchorage free of corrosion that is more than mild surface oxidation?
4. Is the anchorage free of visible cracks in the concrete near the anchors?
5. Is the anchorage configuration consistent with plant documentation?

(Note: This question only applies if the item is one of the 50% for which an anchorage configuration verification is required.)

YN YQ(NE1 UE' N/A-YIWNEJ-UQ-N/A' YW NEI U" N/AC-1 YrI NEI U-' N/At

6. Based on the above anchorage evaluations, is the anchorage free of

"@-NE" UE-potentially adverse seismic conditions?

Al

"&1V'(r' O

12 Enter the equipment class name from Appendix B: Classes of Equipment.

is 7"4

<C-3 Limerick Generating Station Unit 2 MPR-3801, Revision 1 rnrrp.nnndpnr-.p Nn ' PS-19-171 41---

C-430

Sheet 2 of 2 Equipment ID No. 0AC564 Equip. Class12 (18) Control Panels & Cabinets Equipment Description Control Panel Spray Pond Pump Structure Air Supply Fan Interaction Effects

7. Are soft targets free from impact by nearby equipment or structures?

Y

"-IN UD N/AD

8. Are overhead equipment, distribution systems, ceiling tiles and lighting, Y

ND UD N/AD and masonry block walls not likely to collapse onto the equipment?

9. Do attached lines have adequate flexibility to avoid damage?

YZ2ND UD N/AD

10. Based on the above seismic interaction evaluations, is equipment free ND UrI of potentially adverse seismic interaction effects?

Other Adverse Conditions

11. Have you looked for and found no other seismic conditions that could NEIN-UD adversely affect the safety functions of the equipment?

Comments (Additional pages may be added as necessary)

P op o atb'oe-f

'j 6f -el WAY 4 e C e'o fe, Evaluated by:

Date:

41ý3ý I

fo--,. //_..

X/-ýgZj 2-I

/ -

6 7

.v Limerick Generating Station Unit 2 MPR-3801, Revision 1 rnrrP nnndPnr.PNn' RR-19-171 C-431

Equipment ID: 0AC564 t

Limerick Generating Station Unit 2 MPR-3801, Revision 1 rnrrFnnndPnrA Nn

  • RR-12-171 C-432

Equipment ID: 0AC564 Limerick Generating Station Unit 2 MPR-3801, Revision 1 Cnrrpnnndprnc.p. Nn

  • RR-19-171 C-433

Sheet 1 of 2 Status:( t N U Seismic Walkdown Checklist (SWC)

Equipment ID No. OAK1 12 Equip. Class 12 (09) Chillers Equipment Description Control Structure Chiller Location: Bldg. Control Floor El. 200 Room, Area Room 258 Structure Manufacturer, Model, Etc. (optional but recommended)

Instructions for Completing Checklist This checklist may be used to document the results of the Seismic Walkdown of an item of equipment on the SWEL. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.

Anchorane

1. Is the anchorage configuration verification required (i.e., is the item one of the 50% of SWEL items requiring such verification)?
2. Is the anchorage free of bent, broken, missing or loose hardware?
3. Is the anchorage fleeof corrosion that is more than mild surface oxidation? Qy 1

E:

A Of 14 At ^td fv 'i

4. Is the anchbrage free of visible cracks in the concrete near the anchors?

U5. Is the anchorage configuration consistent with plant documentation?

(Note: This question only applies if the item is one of the 50% for which an anchorage configuration verification is required.)

6. Based on the above anchorage evaluations, is the anchorage free of potentially adverse seismic conditions?

YOEJo NO UO N/AO X

NEI Y

No U-N/Af UE-N/An Y)*NO Un-1 Enter the equipment class name from Appendix B: Classes of Equipment.

<C-3 >,

Limerick Generating Station Unit 2 MPR-3801, Revision 1 (TnrrPrnnndPnr'P Nn - RR-12-171 C-434

Sheet 2 of 2 Equipment ID No. OAK1 12 Equip. Class"2 (09) Chillers Equipment Description Control Structure Chiller Interaction Effects

7. Are soft targets free from impact by nearby equipment or structures?

YAND

8. Are overhead equipment, distribution systems, ceiling tiles and lighting, YOND an masonry block walls not likely to collapse o t the equipment?
6rb, p-5Q UD N/AD uJr N/AD UDj N/AD
9. Do attached lines have adequate flexibility to avoid damage?
10. Based on the above seismic interaction evaluations, is equipment free of potentially adverse seismic interaction effects?

YND Y~NU Other Adverse Conditions

11. Have you looked for and found no other seismic conditions that could YŽNND UD adversely affect the safety functions of the equipment?

Comments (Additional pages may be added as necessary)

Date:

/ Is /

Limerick Generating Station Unit 2 MPR-3801, Revision 1 rlnrrP.qnnndf, nr.P Nn ' RR-19-171 C-435

Equipment ID: OAK112 Limerick Generating Station Unit 2 C-436 MPR-3801, Revision 1 flnrrm.qnnndrnr.p. Nn - RR-17-171

Equipment ID: OAK112 Limerick Generating Station Unit 2 MPR-3801, Revision 1 rnrrP~nnndfnr. Nn -RR-1

-171 C-437

Sheet 1 of 2 Status:&

N U Seismic Walkdown Checklist (SWC)

Equipment ID No. OAP 162 Equip. Class' (03) Horizontal Pumps Equipment Description Control Room HVAC Chilled Water Pump Location: Bldg. Control Floor El. 200 Room, Area Room 258 Structure Manufacturer, Model, Etc. (optional but recommended)

Instructions for Completing Checklist This checklist may be used to document the results of the Seismic Walkdown of an item of equipment on the SWEL. The space below each of the following questions may be used to record the results ofjudgments and findings. Additional space is provided at the end of this checklist for documenting other comments.

Anchorage

1. Is the anchorage configuration verification required (i.e., is the item one YI"IN]

of the 50% of SWEL items requiring such verification)?

2. Is the anchorage free of bent broken, missing or loose hardware?
3. Is the anchoraee free of corrosion that is more than mild"i-urface oxidain/*14_-

0o V */

_, t5

/

4. Is the anchorage free of visible cracks in the concrete near the anchors?
5. Is the anchorage configuration consistent with plant documentation?

(Note: This question only applies if the item is one of the 50% for which an anchorage configuration verification is required.)

6. Based on the above anchorage evaluations, is the anchorage free of potentially adverse seismic conditions?

154NO

/[-]

)XNO Aý 90 YO" NEl UD-N/Aý 541 12 Enter the equipment class name from Appendix B: Classes of Equipment.

< C-3 >

Limerick Generating Station Unit 2 MPR-3801, Revision 1 rnrnrP.nnndrnr.

Nn " RR-17-171 C-438

Sheet 2 of 2 Equipment ID No. 0AP162 Equip. Class12 (03) Horizontal Pumps Equipment Description Control Room HVAC Chilled Water Pump Interaction Effects

7. Are soft targets free from impact by nearby equipment or structures?
8. Are overhead equipment, distribution systems, ceiling tiles and lighting, and masonry block walls not likely to collapse onto the equipment?
9. Do attached lines have adequate flexibility to avoid damage?
10. Based on the above seismic interaction evaluations, is equipment free of potentially adverse seismic interaction effects?

YI(NF YAND UD-N/AD UD N/AD UE-N/AD

  • D1 UD Other Adverse Conditions
11. Have you looked for and found no other seismic conditions that could Y04 1 UI adversely affect the safety functions of the equipment?

Comments (Additional pages may be added as necessary)

Date:

ZC1 1:2 J

v Limerick Generating Station Unit 2 MPR-3801, Revision 1 rnrroqnnntlPnr.p Nn P R9-19-171 C-439

Equipment ID: 0AP162 I

Limerick Generating Station Unit 2 MPR-3801, Revision 1 rlnrrP.nnnrl~nrA. Nn - R5'-1-1-71 C-440

Equipment ID: 0AP162 Limerick Generating Station Unit 2 C-441 MPR-3801, Revision 1 rnrrPnnnrl-nrA Nn " P.R-12-171

Sheet 1 of 2 Status: *N U Seismic Walkdown Checklist (SWC)

Equipment ID No. 0AP506 Equip. Class12 (04) Vertical Pumps Equipment Description RHR Service Water Pump Location: Bldg. Spray Pond Floor El. 268 Room, Area Room 1000 Location: Bldg. SprayPn Floor El. 268

,'Room, Area 'Room 1000 Building Manufacturer, Model, Etc. (optional but recommended)

Instructions for Completing Checklist This checklist may be used to document the results of the Seismic Walkdown of an item of equipment on the SWEL. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.

Anchora*e

1. Is the anchorage configuration verification required (i.e., is the item one of the 50% of SWEL items requiring such verification)?
2. Is the anchorage free of bent, broken, missing or loose hardware?
3. Is the anchorage free of corrosionhat is more than mild surfaceN oxidation? -1

.4 41T Ce, c

/*/o G4 VK6%,,

4,1-twt

(

7Vbt,,.-.

jfZ.

t~l-C/Ie

4. Is the anchorage free of visible cracks in the corbrete near the anchors?
5. Is the anchorage configuration consistent with plant documentation?

(Note: This question only applies if the item is one of the 50% for which an anchorage configuration verification is required.)

Y0NEI 39 NDI UI N/AD

)ZINO UD N/AD VN' U"

N/AD Y& NDI Ul N/AD

6. Based on the above anchorage evaluations, is the anchorage free of Y&N' U"

potentially adverse seismic conditions?

12 Enter the equipment class name from Appendix B: Classes of Equipment.

Limerick Generating Station Unit 2 MPR-3801, Revision 1 r.nrrPqnnnr1Pnr.P Nn - RR-19-171 C-442

Sheet 2 of 2 Equipment ID No. 0AP506 Equip. Class' 2 (04) Vertical Pumps Equipment Description RHR Service Water Pump Interaction Effects

7. Are soft targetsfree from impact by nearb eqment or structures?
8. Are overhead equipment, distribution systems, ceiling tiles and lighting, and masonry block walls not likely to collapse onto e e nt?

AqjýfP 8 -t:,,~.4(dt P,

t0 V

9. Do attached lines have adequate flexibility to atoid damage?
10. Based on the above seismic interaction evaluations, is equipment free of potentially adverse seismic interaction effects?

YA NEI UE1 N/AEI 4V1 nul3 Other Adverse Conditions

11. Have you looked for and found no other seismic conditions that could Y

NU] U"I adversely affect the safety functions of the equipment?

Comments (Additional pages may be added as necessary)

Evaluated by:

f t A-*v-. d* e Date:

k i#o(IL

< C-4 >)

Limerick Generating Station Unit 2 MPR-3801, Revision 1 r.nrrPznondpner'. No

  • RR-19-171 C-443

Equipment ID: 0AP506 I

Limerick Generating Station Unit 2 MPR-3801, Revision 1 rlnrrPnnndPnr.P Nn

  • R-19-171 C-444

Equipment ID: 0AP506 Limerick Generating Station Unit 2 MPR-3801, Revision 1 f.nrrPmnnndpnc.P Nn

  • RR-12-171 C-445

Shert 1 of 2 Status:

N U Seismic Walkdown Checklist (SWC)

Equipment ID No. OAP548 Equip. Class12 (04) Vertical Pumps Equipment Description Emtergencv Service Water Pump Location: Bldg. Spray Pond Floor El. 268 Room, Area Room 1000 Building Manufacturer, Model, Etc. (optional but recommended)

Instructions for Completing Checklist This checklist may be used to document the results of the Seismic Walkdown of an item of equipment on the SWEL. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.

Anchoraze

1. Is the anchorage configuration verification required (i.e., is the item one of the 50% of SWEL items requiring such verification)?
2. Is the anchorage free of bent, broken, missing or loose hardware?
3. Is the anchorage free of corrosion that is more than mild surface oxidation?

1i/t [QC6 c.&O,47.O acc e.

4. Is the anchorage free of visible cracks in the concrete near the anchors?
5. Is the anchorage configuration consistent with plant documentation?

(Note: This question only applies if the item is one of the 50% for which an anchorage configuration verification is required.)

6. Based on the above anchorage evaluations, is the anchorage free of potentially adverse seismic conditions?

4NO YP*N[] U" N/Af" Y4-N[" UI" N/A-YAMNEI UE" N/AO-Y(N'-I UUE" N/AE-

  • 934l-' UE 12Enter the equipment class name from Appendix B: Classes of Equipment.

<C-3 >

Limerick Generating Station Unit 2 MPR-3801, Revision 1 r.nrrmqnnndpnr.p Nn - RR-19-171 C-446

Sheet 2 of 2 Equipment ID No. 0AP548 Equip. Class12 (04) Vertical Pumps Equipment Description Emergency Service Water Pump Interaction Effects

7. AIe soft targets free from impact by nearby equipment or structures?

/V IoKk4rW YoNE U0 N/AC

8. Are overhead equipment, distribution systems, ceiling tiles and lighting, Yf I-'I UL N/AC and masonry block walls not likely to collapse onto the equipment?

I Ov Il-Ad '( t l

[C e

a L"t' ( y P vvri 4t vj

'(

9. Do attached lines have adequate flexibility to avoid damage?
10. Based on the above seismic interaction evaluations, is equipment free of potentially adverse seismic interaction effects?

Y0;NQ UC N/AC Y

klD UC Other Adverse Conditions

11. Have you looked for and found no other seismic conditions that could

)e4DC UC adversely affect the safety functions of the equipment?

Comments (Additional pages may be added as necessary)

Date:

54/1Z Z-

< C-4 >

Limerick Generating Station Unit 2 MPR-3801, Revision 1 rlnrrPqnnndP.nrP Nn - PS-19-171 C-447

Equipment ID: 0AP548 Limerick Generating Station Unit 2 MPR-3801, Revision 1 f.nrrP~nnndPlnrP Nn* RR-19-171 C-448

Sheet 1 of 2 Status: (2) N U Seismic Walkdown Checklist (SWC)

Equipment ID No. 0BV543 Equip. Class 12 (08) Fans & Air Handlers Equipment Description B' Spray Pond PP. Structure Air Supply Fan Location: Bldg. Spray Pond Floor El. 268 Room, Xrea Room 1005 Building Manufacturer, Model, Etc. (optional but recommended)

Instructions for Completing Checklist This checklist may be used to document the results of the Seismic Walkdown of an item of equipment on the SWEL. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.

Anchorage

1. Is the anchorage configuration verification required (i.e., is the item one of the 50% of SWEL items requiring such verification)?
2. Is the anchorage free of bent, broken, missing or loose hardware?
3. Is the anchorage free of corrosion that is more than mild surface oxidation?
4. Is the anchorage free of visible Vacks in the concrete near the anchors?

~~4,~

litI-

5. Is the anchorage configuration consistent with plant documentation?

(Note: This question only applies if the item is one of the 50% for which an anchorage configuration verification is required.)

6. Based on the above anchorage evaluations, is the anchorage free of potentially adverse seismic conditions?

YrANEI Yo NEI U-] N/AC YZNI-U-] N/A[

YgN[-' UC-N/ACl YJ;J NEI UD N/AD

)ONE]

CUC 12 Enter the equipment class name from Appendix B: Classes of Equipment.

< C-3 >

Limerick Generating Station Unit 2 MPR-3801, Revision 1 rnrrPqnnndr.nrP Nn RR-19-171 C-449

Sheet 2 of 2 Equipment ID No. OBV543 Equip. Class' 2 (08) Fans & Air Handlers Equimen Desripion

',pray Pond PP. Structure Air Sup ly Fan Interaction Effects

7. Are soft targets tree from impact by arb equipment or structures?
8. Are overhead equipment, distribution systems, ceiling tiles and lighting, and masonry block walls not likely to collapse onto the equipment?
9. Do attached lines have adequate flexibility to avoid damage?
10. Based on the above seismic interaction evaluations, is equipment free of potentially adverse seismic interaction effects?

YJKl-I Ul-1 N/AEI YCNI-UL-N/AO N-NEI UO N/Afl Y6 NO UI-I Other Adverse Conditions

11. Have you looked for and found no other seismic conditions that could YKVE-U-'

adversely affect the safety functions of the equipment?

Comments (Additional pages may be added as necessary)

.1'01

/

Evaluated by:

Date:

6);//

91 t 1V)I

< C-4 >,

Limerick Generating Station Unit 2 MPR-3801, Revision 1 rnrrsnnndPnrA. Nn RRA-19-171 C-450

Equipment ID: 0BV543 Limerick Generating Station Unit 2 MPR-3801, Revision 1 Snrrqnnndlnr-PNn*

RP-19-171 C-451

Sheet 1 of 2 Status: (D N U Seismic Walkdown Checklist (SWC)

Equipment ID No. 0CC667 Equip. Class12 (18) Control Panels & Cabinets Equipment Description ESW Division III Control Panel Location: Bldg. Control Floor El. 269 Room, Area Room 533 C *,2 e (

Structure Manufacturer, Model, Etc. (optional but recommended)

Instructions for Completing Checklist This checklist may be used to document the results of the Seismic Walkdown of an item of equipment on the SWEL. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.

Anchoraze

1. Is the anchorage configuration verification required (i.e., is the item one YEI NX of the 50% of SWEL items requiring such verification)?
2. Is the anchorage free of bent, broken, missing or loose hardware?

YjNI"].UE] N/All

-C vgeo17;*

ike/

4-9

  • 5).t o,.M A.f.
3. Is the anchorage free of corrosion that is more than mild surface X4,NE] UE] N/AE]

oxidation?

4. Is the anchorage free of visible cracks in the concrete near the anchors?

Y -- lJ UE] N/AE]

5. Is the anchorage configuration consistent with plant documentation?

YE] NEI UE] N/AX (Note: This question only applies if the item is one of the 50% for which an anqhorage configuration verification is required)

, I I.-

V.{~e C~-t.

4-hO4.

s4Cj(

o~t W

3 10fybats em 4 C le

-6* f,4~ aid '

CVIci i

fo71,04-r'.6 (i ft oft A."o

6. Based on the aboV anchorage evaluations,*s the anchorage free of Y

NEI UE]

potentially adverse seismic conditions?

0o*&,,1(,

Ck*

  • t,(A i S" ' V 1-3,,, t

.0

  • 149V~e, A

OP 4ý 10A/ e4""' Do Ndte A

C7 10 G;-4t'14e P"lIwCC-,.

12 Enter the equipment class name from Appendix B: Classes of Equipment.

<C-3 >

Limerick Generating Station Unit 2 C-452 MPR-3801, Revision 1 r.nrrP..nnndPnr.P Nn" RR-19-171

Sheet 2 of 2 Equipment ID No. 0CC667 Equip. Class"2 (18) Control Panels & Cabinets Equipment Description ESWDivision III Control Panel Interaction Effects

7. Are soft targets free from impact by nearby equipment or structures?

Y NEI U[] N/At]

MuP fj'+

11r-t A, fr-

ý I1 oi'r-eý

8. Are overhead equipment, distribution systems, ceiling tiles and lighting, and masonry block walls not likely to collapse onto the equipment?

V V4 C)

9. Do attached lines have adequate flexibility to avoid damage?
10. Based on the above seismic interaction evaluations, is equipment free of potentially adverse seismic interaction effects?

YId(Nt1 Ut] N/At]

YaNt] Ut] N/At]

YXTINED Ut]

Other Adverse Conditions

11. Have you looked for and found no other seismic conditions that could Y*-NDI Ut]

adversely affect the safety functions of the equipment?

Comments (Additional pages may be added as necessary)

Evaluated by:

Date: _Y/3 2-C4ZI/

Limerick Generating Station Unit 2 MPR-3801, Revision 1 r.nrrP~nnndPnr.P Nn RR-12-171 C-453

Occ-o ),

t o

'1 1.4.5 Termination Cabinets The frames and enclosures of Limerick termination cabinets are the same size and structurally identical to the tested termination cabinet (Reference 4).

The only difference between the Limerick cabinets and the tested termination cabinet is the quantity and location of termination modules.

This will not affect the structural capability of the cabinets.

The TRS envelops the RRS as shown in the Appendix, Fugure 4.2.

These cabinets are located in the Control Room, elevation 269'.

The SQRT forms for the Class IE Termination Cabinets (P700 series) are contained in Section 3.

1.4.6 Floor Mounting 1.4.6.1 Auxiliary Equipment Room, 289' Elevation Panels located in the Auxiliary Equipment Room are mounted on PGCC floor sections.

As shown in Ref. 5, sections similar to those at Limerick were tested to determine if there were any amplifications of accelerations to the panels.

Panel accelerometer readings show that the floor sections actually reduce the transmissibility on the tested panels by as much as 10 percent.

This is due to structural damping.

The results presented in this report conservatively assume that the floor sections are rigid, and no credit is taken for the reduced transmissibility.

1.4.6.2 Control Room, 269' Elevation Panels located in the control room (and C61-POOI) are bolted to a 4" base which is welded to the floor.

This base was on the tested Limerick H12-P601, P603, and P661 panels.

Examination of test data in panels without this base shows no appreciable difference in transmissibilities.

The base is therefore assumed rigid.

1-8 i)

Limerick Generating Station Unit 2 C-454 MPR-3801, Revision 1 r*nrrPqnnndpnrP Nn R5-19-171 I

Equipment ID: 0CC667 I

Limerick Generating Station Unit 2 MPR-3801, Revision 1 rnrrP.annndlPnr*p Nn* RR-12-171 C-455

Equipment ID: 0CC667 Limerick Generating Station Unit 2 MPR-3801, Revision 1 rnrrpnnnri-nrý- Nn R,-19-171 C-456