Technical Basis Document No. 24-01-12-2888 R0 Dose Contribution from Insignificant Radionuclides in the Oyster Creek Site-Specific Suite of Radiological Nuclides Revision 1 Prepared by:
Westinghouse - Radiological Engineering Group 141 Longwater Drive Suite 113 Norwell, MA 02061
Technical Basis Document No. 24-01-12-2888 R0 Dose Contribution from Insignificant Radionuclides in the Oyster Creek Site-Specific Suite of Radiological Nuclides Page 2 Revision Record Revision Record 0
1/18/2024 1
Summary of Changes:
Rev 0 - Initial Issue Rev 1 - DCGL Value Updates 2/14/2024
Technical Basis Document No. 24-01-12-2888 R0 Dose Contribution from Insignificant Radionuclides in the Oyster Creek Site-Specific Suite of Radiological Nuclides Page 3 Author:
Martin C. Erickson Date Reviewer:
Joseph Bisson Date Reviewer:
William Parish Date Approved:
Christopher C. Messier Date
Technical Basis Document No. 24-01-12-2888 R0 Dose Contribution from Insignificant Radionuclides in the Oyster Creek Site-Specific Suite of Radiological Nuclides Page 4 CONTENTS EXECUTIVE
SUMMARY
..................................................................................................... 5
1.0 INTRODUCTION
....................................................................................................... 6 2.0 TECHNICAL BASES................................................................................................. 6 3.0 METHODOLOGY...................................................................................................... 6 4.0 CALCULATIONS....................................................................................................... 8
5.0 CONCLUSION
............................................................................................................ 8 6.0 RECOMMENDATIONS............................................................................................. 8 Table 2-1: MDC Values for HTD Radionuclides.......................................................................... 7 Table 4-1: Calculation of Aggregate HTD Dose........................................................................... 8 Attachment A: Off-Site Results.................................................................................................... 10
Technical Basis Document No. 24-01-12-2888 R0 Dose Contribution from Insignificant Radionuclides in the Oyster Creek Site-Specific Suite of Radiological Nuclides Page 5 EXECUTIVE
SUMMARY
The Oyster Creek Nuclear Generating Station (OCNGS) site-specific suite of radionuclides consists of 21 radionuclides of which 14 are hard-to-detect (HTD) beta-emitting and alpha-emitting radionuclides. Site characterization data have shown that the HTD nuclides are consistently below or slightly above the minimum detectable concentration (MDC) in laboratory results, which supports classifying them as insignificant nuclides. Dose assessment showing the HTD nuclides collectively contribute less than 10% of the dose criterion provides confirmation for the insignificant classification. Some gamma-emitting radionuclides were also identified as potentially insignificant based on analytical data; however, since they will all be analyzed for in every FSS sample, they are excluded in this technical basis document.
Five soil samples from the OCNGS Radiologically Controlled Area (RCA), the area where the residual plant radioactivity was greatest during the Phase 1 site characterization, were collected and sent off-site for analysis of HTD nuclides. Except for Sr-90, the analytical results showed that the concentrations of all other HTD nuclides were below their respective MDC values in all samples. Sr-90 was detected at a concentration greater than MDC for the analysis in only 1 of the 5 samples.
The HTD nuclide values were set at the maximum of the MDC values, except for Sr-90, which was set at the identified analysis value, and then compared to the OCNGS Industrial Use (IU)
DCGLs discussed in the OCNGS LTP Chapter 6.
The results of the assessment confirmed that the HTDs contribute less than 10% of the site closure dose criteria (i.e., 25 mrem/y) and can be deemed insignificant. The HTD radionuclides will not be required to undergo further assessment, however, the potential dose contribution of 0.075 mrem/y will be added to each survey unit total dose. Survey unit QC samples will still include an assessment of the HTDs to verify their insignificant status. Should the QC sample results indicate the presence of HTD Radionuclides the potential dose contribution will be evaluated and adjusted, as appropriate.
This effort resulted in the following four recommendations:
- QC sample analyses should include the analysis of insignificant radionuclides.
- A dose contribution of 0.075 mrem/y from soil should be added to the FSS survey unit total dose.
- If additional information regarding the presence of insignificant radionuclides become available during remediation activities or FSS, the potential dose contribution/analysis frequency will be reevaluated and adjusted, as appropriate.
- The approach used for determining the insignificant status of HTD nuclides in soil should be applied to other volumetric site media, such as concrete in basement remaining below grade and buried pipe.
Technical Basis Document No. 24-01-12-2888 R0 Dose Contribution from Insignificant Radionuclides in the Oyster Creek Site-Specific Suite of Radiological Nuclides Page 6
1.0 INTRODUCTION
Derivation of a site-specific suite of radionuclides present at Oyster Creek Nuclear Generating Station (OCNGS) is discussed in Chapter 6, Compliance with the Radiological Criteria for License Termination, of the OCNGS License Termination Plan (LTP). This suite of potential radionuclides contains a total of 21 radionuclides. This Technical Basis is centered on the hard-to-detect (HTD) radionuclides since all easy-to-detect radionuclides will be analyzed for in every Final Status Survey (FSS) sample.
OCNGS submitted 5 soil samples from the Radiologically Controlled Area (RCA) to an off-site laboratory for analysis of 14 HTD radionuclides. The analyses positively identified only 1 HTD radionuclide, Sr-90, in 1 sample at a concentration above the MDC.
2.0 TECHNICAL BASES The guidance contained in NUREG-1757, Vol. 2, Section 3.3, states:
it is reasonable to eliminate radionuclides or pathways that are insignificant contributors to dose from further detailed consideration.
The guidance further states, NRC staff considers radionuclides and exposure pathways that contribute no greater than 10 percent of the dose criteria, considering uncertainty, to be insignificant contributors to dose. Because the dose criteria are performance criteria, this 10 percent limit is an aggregate limitation only.
That is, the sum of the dose contributions from all radionuclides and pathways is necessary considered insignificant should be no more than 10 percent of the dose criteria. No limitation on either single radionuclides or individual pathways is necessary.
Once a licensee has demonstrated that radionuclides or exposure pathways are insignificant, then (1) the dose from the insignificant radionuclides and pathways must be accounted for in demonstrating compliance, but (2) the insignificant radionuclides and pathways may be eliminated from further detailed evaluations.
Therefore, it is necessary to calculate potential dose from HTD radionuclides and compare the aggregate potential dose to ensure that it does not exceed 10% of the dose limit (i.e.,
2.5 mrem/y TEDE).
3.0 METHODOLOGY Five sample locations were chosen based on a review of all the soil data collected during the Phase I Characterization effort. These locations were all within the RCA and represented the highest Co-60 and Cs-137 activity concentrations. Once identified, GPS was used to stake out the original sample location. An area representing approximately 1m2 around each location was scanned and a soil sample collected at the highest direct measurement location. Transfer of the sample to the off-site laboratory was controlled by chain of custody procedure and documented by a COC form. Detection sensitivities for
Technical Basis Document No. 24-01-12-2888 R0 Dose Contribution from Insignificant Radionuclides in the Oyster Creek Site-Specific Suite of Radiological Nuclides Page 7 analysis of the HTD radionuclides were established at the lowest levels achievable by the off-site laboratory to ensure detection of very low activity concentrations.
The OCNGS Phase 1 Characterization soil samples sent for HTD analysis consistently indicate the activities and subsequent dose, contribute, in aggregate, less than 10% of the of the 25 mrem/y release criteria for unrestricted use. Therefore, it is appropriate to deem these radionuclides as insignificant dose contributors. The potential dose contribution and pathways for these radionuclides must be determined and included in the final dose evaluation for site release.
Except for Sr-90, the estimated dose for HTDs is based on the maximum MDC values.
The estimated dose for Sr-90 was based on an activity concentration of 0.0697 pCi/g which corresponds to the activity concentration of the sample result (see soil sample RCS-SOIL-16-B in Table 3-1 below.) The MDC values for the HTD radionuclide are presented in in Table 4-1. The HTD nuclide values were set at the maximum of the MDC values, except for Sr-90, which was set at the identified analysis value, and then compared to the OCNGS Industrial Use (IU) DCGLs discussed in the OCNGS LTP Chapter 6. Industrial Use DCGLs include direct exposure, indirect ingestion of soil, inhalation, and ingestion of aquatic foods.
Table 3-1: MDC Values for HTD Radionuclides
- Sr-90 Positively identified in analysis Am-241 Pu-238 Sr-90 Tc-99 MDC Values MDC Values MDC Va lues MDC Values Sample ID (pCi/g)
Sample ID (pCi/g)
Sample ID (pCi/g)
Sample ID (pCi/g)
RCA-SOIL-04-B 0.0622 RCA-SOIL-04-B 0.0125 RCA-SOIL-04-B 0.0167 RCA-SOIL-04-B 1.46 RCA-SOIL-10-B 0.0298 RCA-SOIL-10-B 0.019 RCA-SOIL-10-B 0.0176 RCA-SOIL-10-B 1.08 RCA-SOIL-15-B 0.152 RCA-SOIL-15-B 0.0198 RCA-SOIL-15-B 0.0171 RCA-SOIL-15-B 0.921 RCA-SOIL-16-B 0.051 RCA-SOIL-16-B 0.0184 RCA-SOIL-16-B*
0.0697 RCA-SOIL-16-B 0.703 RCA-SOIL-19-B 0.104 RCA-SOIL-19-B 0.0192 RCA-SOIL-19-B 0.0176 RCA-SOIL-19-B 0.814 Maximum 0.152 Maximum 0.0198 Maximum 0.0697 Maximum 1.46 Cm-243/244 Pu-239/240 H-3 Fe-55 MDC Values MDC Values MDC Va lues MDC Va lues Sample ID (pCi/g)
Sample ID (pCi/g)
Sample ID (pCi/g)
Sample ID (pCi/g)
RCA-SOIL-04-B 0.0497 RCA-SOIL-04-B 0.0274 RCA-SOIL-04-B 4.51 RCA-SOIL-04-B 75.1 RCA-SOIL-10-B 0.0339 RCA-SOIL-10-B 0.0241 RCA-SOIL-10-B 4.54 RCA-SOIL-10-B 88.9 RCA-SOIL-15-B 0.253 RCA-SOIL-15-B 0.0347 RCA-SOIL-15-B 4.47 RCA-SOIL-15-B 90.6 RCA-SOIL-16-B 0.0411 RCA-SOIL-16-B 0.0184 RCA-SOIL-16-B 4.38 RCA-SOIL-16-B 87.5 RCA-SOIL-19-B 0.102 RCA-SOIL-19-B 0.0244 RCA-SOIL-19-B 4.55 RCA-SOIL-19-B 79.5 Maximum 0.253 Maximum 0.0347 Maximum 4.55 Maximum 90.6 Np-237 Pu-241 C-14 Ni-63 MDC Va lues MDC Values MDC Va lues MDC Va lues Sample ID (pCi/g)
Sample ID (pCi/g)
Sample ID (pCi/g)
Sample ID (pCi/g)
RCA-SOIL-04-B 0.0083 RCA-SOIL-04-B 7.49 RCA-SOIL-04-B 0.62 RCA-SOIL-04-B 5.51 RCA-SOIL-10-B 0.0066 RCA-SOIL-10-B 7.65 RCA-SOIL-10-B 0.618 RCA-SOIL-10-B 5.26 RCA-SOIL-15-B 0.0107 RCA-SOIL-15-B 6.97 RCA-SOIL-15-B 0.634 RCA-SOIL-15-B 5.03 RCA-SOIL-16-B 0.0118 RCA-SOIL-16-B 7.06 RCA-SOIL-16-B 0.626 RCA-SOIL-16-B 4.89 RCA-SOIL-19-B 0.0058 RCA-SOIL-19-B 6.77 RCA-SOIL-19-B 0.636 RCA-SOIL-19-B 4.51 Maximum 0.0118 Maximum 7.65 Maximum 0.636 Maximum 5.51
Technical Basis Document No. 24-01-12-2888 R0 Dose Contribution from Insignificant Radionuclides in the Oyster Creek Site-Specific Suite of Radiological Nuclides Page 8 4.0 CALCULATIONS Calculation of Potential Dose from Insignificant Nuclides The dose from the postulated insignificant radionuclides was calculated using the HTD maximum MDC radionuclide values provided in Table 4-1. The individual radionuclide doses were calculated by multiplying the ratio of the MDC to DCGL by the release criterion (25 mrem/y). The total potential dose from all HTD radionuclides is 7.50E-02 mrem/y using the maximum MDC values and following equation:
HTD mrem/y = ((MDC, pCi/g)/(DCGL, pCi/g))* 25 mrem/y The aggregate dose is the summation of the individual HTD doses.
Table 4-1: Calculation of Aggregate HTD Dose Soil DCGL Max MDC HTD Dose ROC (IU)
(pCi/g)
(mrem/y)
(pCi/g)
Am-241 7.30E+02 1.52E-01 5.21E-03 C-14 2.07E+03 6.36E-01 7.68E-03 Cm-243 1.81E+02 2.53E-01 3.49E-02 Cm-244 1.82E+03 2.53E-01 3.48E-03 Fe-55 8.39E+06 9.06E+01 2.70E-04 H-3 5.02E+04 4.55E+00 2.27E-03 Ni-63 7.75E+06 5.04E+00 1.63E-05 Np-237 5.75E+01 1.18E-02 5.13E-03 Pu-238 1.14E+03 1.98E-02 4.34E-04 Pu-239 2.37E+02 3.47E-02 3.66E-03 Pu-240 1.08E+03 3.47E-02 8.03E-04 Pu-241 2.50E+04 7.65E+00 7.65E-03 Sr-90 4.24E+03 6.97E-02 4.11E-04 Tc-99 1.37E+04 1.46E+00 2.66E-03 Aggregate dose 7.46E-02
5.0 CONCLUSION
As shown in Table 4-1, the total dose contribution of the OCNGS HTD radionuclides is less than 10% of the dose criteria and therefore it is appropriate to consider them as insignificant.
6.0 RECOMMENDATIONS Survey Unit QC offsite sample analyses should include analysis of the postulated
Technical Basis Document No. 24-01-12-2888 R0 Dose Contribution from Insignificant Radionuclides in the Oyster Creek Site-Specific Suite of Radiological Nuclides Page 9 insignificant radionuclides to address the potential for dose from the postulated insignificant radionuclides and exposure pathways.
A dose contribution of 0.075 mrem/y should be added to the FSS survey unit total dose whereby accounting for the potential dose contribution for postulated insignificant radionuclides.
If additional information regarding the presence of insignificant radionuclides become available during remediation activities or FSS, the potential dose contribution/analysis frequency will be reevaluated and adjusted, as appropriate.
The approach used for determining the insignificant status of HTD nuclides in soil should be applied to other volumetric site media, such as concrete in basement remaining below grade and buried pipe.
Technical Basis Document No. 24-01-12-2888 R0 Dose Contribution from Insignificant Radionuclides in the Oyster Creek Site-Specific Suite of Radiological Nuclides Page 10 Attachment A Off-Site Results
November 09, 2023 Chris Messier BHI Energy 97 Libbey Industrial Parkway 4th Floor Weymouth, Massachusetts 02189 Re: Oyster Creek Soil Analysis Work Order: 642226
Dear Chris Messier:
GEL Laboratories, LLC (GEL) appreciates the opportunity to provide the enclosed analytical results for the sample(s) we received on October 20, 2023. This original data report has been prepared and reviewed in accordance with GELs standard operating procedures.
The samples were delivered with proper chain of custody documentation and signatures. All sample containers arrived without any visible signs of tampering or breakage. There are no additional comments concerning sample receipt.
Test results for NELAP or ISO 17025 accredited tests are verified to meet the requirements of those standards, with any exceptions noted. The results reported relate only to the items tested and to the sample as received by the laboratory. These results may not be reproduced except as full reports without approval by the laboratory.
Copies of GELs accreditations and certifications can be found on our website at www.gel.com.
Our policy is to provide high quality, personalized analytical services to enable you to meet your analytical needs on time every time. We trust that you will find everything in order and to your satisfaction. If you have any questions, please do not hesitate to call me at (843) 556-8171, ext. 4504.
Sincerely, PM_SIGN_HERE Erin Trent Project Manager Purchase Order: ENG-P2023-98002888-01 Enclosures Page 1 of 30 SDG: 642226 Amanda Turner for m ~ II Laboratories LLC a member of The GEL Group INC
Reviewed by USER_SIGN_HERE GEL LABORATORIES LLC 2040 Savage Road Charleston SC 29407 - (843) 556-8171 - www.gel.com Certificate of Analysis Report HBHI001 Holtec BHI Client SDG: 642226 GEL Work Order: 642226 Where the analytical method has been performed under NELAP certification, the analysis has met all of the requirements of the NELAC standard unless qualified on the Certificate of Analysis.
The designation ND, if present, appears in the result column when the analyte concentration is not detected above the limit as defined in the 'U' qualifier above.
This data report has been prepared and reviewed in accordance with GEL Laboratories LLC standard operating procedures. Please direct any questions to your Project Manager, Erin Trent.
The Qualifiers in this report are defined as follows:
- A quality control analyte recovery is outside of specified acceptance criteria
- Analyte is a Tracer compound
for Page 2 of 30 SDG: 642226
Certificate of Analysis GEL LABORATORIES LLC 2040 Savage Road Charleston SC 29407 - (843) 556-8171 - www.gel.com Report Date: November 9, 2023 Parameter Result Units Qualifier Analyst Date Time DF Batch Method RL MDC PF Rad Alpha Spec Analysis Rad Gas Flow Proportional Counting Rad Liquid Scintillation Analysis 2513350 2513355 2513351 2513353 2512641 2512884 2512921 2512495 2512806 2512838 0837 1433 1045 1718 1833 2026 0931 2233 1012 0758 pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g 10/31/23 10/28/23 10/28/23 10/30/23 11/02/23 10/25/23 10/31/23 10/30/23 10/30/23 11/01/23 EJ1 EJ1 EJ1 EJ1 ST2 KXA1 KXA1 AG2 TXJ1 TXJ1 0.261 0.488 0.0110 0.219 0.281 8.83 0.0177 5.05 0.0284 0.157 516 7.24 Chris Messier
Contact:
BHI Energy Company :
97 Libbey Industrial Parkway Weymouth, Massachusetts 02189 Address :
Oyster Creek Soil Analysis Project:
642226001 Soil 12-OCT-23 10:59 20-OCT-23 RCA-SOIL-16-B HBHI00222 Project:
HBHI001 Client ID:
Client
+/-0.0291
+/-0.0139
+/-0.00516
+/-0.0133
+/-0.0170
+/-4.08
+/-0.0121
+/-2.54
+/-0.366
+/-0.412
+/-55.9
+/-2.89 Sample ID:
Receive Date:
4th Floor Client Sample ID:
Matrix:
Collect Date:
Collector:
0.0510 0.0411 0.0118 0.0184 0.0184 7.06 0.0161 4.38 0.626 0.703 87.5 4.89 1
2 3
4 5
6 7
8 9
10 U
U U
U U
U U
U U
U U
Americium-241 Curium-243/244 Neptunium-237 Plutonium-238 Plutonium-239/240 Plutonium-241 Strontium-90 Tritium Carbon-14 Technetium-99 Iron-55 Nickel-63 Alphaspec Am241, Cm, Solid "Dry Weight Corrected" Alphaspec Np, Solid "Dry Weight Corrected" Alphaspec Pu, Solid "Dry Weight Corrected" Liquid Scint Pu241, Solid "Dry Weight Corrected" GFPC, Sr90, Solid "Dry Weight Corrected" LSC, Tritium Dist, Solid "As Received" Liquid Scint C14, Solid "As Received" Liquid Scint Tc99, Solid "As Received" Liquid Scint Fe55, Solid "Dry Weight Corrected" Liquid Scint Ni63, Solid "Dry Weight Corrected" 0.0131
-0.00598
-0.00365 0.00676 0.0144 1.22 0.0697 1.29 0.131 0.0416
-24.9 2.00 The following Prep Methods were performed:
Dry Soil Prep Dry Soil Prep GL-RAD-A-021 10/23/23 2512302 1152 WGR Method Description Analyst Date Time Prep Batch Uncertainty Page 3 of 30 SDG: 642226
Certificate of Analysis GEL LABORATORIES LLC 2040 Savage Road Charleston SC 29407 - (843) 556-8171 - www.gel.com Report Date: November 9, 2023 Parameter Result Units Qualifier Analyst Date Time DF Batch Method RL MDC PF Chris Messier
Contact:
BHI Energy Company :
97 Libbey Industrial Parkway Weymouth, Massachusetts 02189 Address :
Oyster Creek Soil Analysis Project:
642226001 RCA-SOIL-16-B HBHI00222 Project:
HBHI001 Client ID:
Sample ID:
4th Floor Client Sample ID:
Surrogate/Tracer Recovery Recovery%
Test Acceptable Limits Americium-243 Tracer Americium-243 Tracer Plutonium-242 Tracer Plutonium-242 Tracer Strontium Carrier Technetium-99m Tracer Iron-59 Tracer Nickel Carrier Alphaspec Am241, Cm, Solid "Dry Weight Corrected" Alphaspec Np, Solid "Dry Weight Corrected" Alphaspec Pu, Solid "Dry Weight Corrected" Liquid Scint Pu241, Solid "Dry Weight Corrected" GFPC, Sr90, Solid "Dry Weight Corrected" Liquid Scint Tc99, Solid "As Received" Liquid Scint Fe55, Solid "Dry Weight Corrected" Liquid Scint Ni63, Solid "Dry Weight Corrected" 46.2 78.5 69.9 69.9 65.9 93.9 101 88.8 (15%-125%)
(15%-125%)
(15%-125%)
(15%-125%)
(25%-125%)
(15%-125%)
(15%-125%)
(25%-125%)
The following Analytical Methods were performed:
1 2
3 4
5 6
7 8
9 10 Method Description DOE EML HASL-300, Am-05-RC Modified ASTM C 1475-00 Modified DOE EML HASL-300, Pu-11-RC Modified DOE EML HASL-300, Pu-11-RC Modified EPA 905.0 Modified/DOE RP501 Rev. 1 Modified EPA 906.0 Modified EPA EERF C-01 Modified DOE EML HASL-300, Tc-02-RC Modified DOE RESL Fe-1, Modified DOE RESL Ni-1, Modified Analyst Comments Uncertainty Nominal 1.38E+06 Result 1.30E+06 CPM Notes:
Counting Uncertainty is calculated at the 95% confidence level (1.96-sigma).
Lc/LC: Critical Level PF: Prep Factor RL: Reporting Limit SQL: Sample Quantitation Limit Column headers are defined as follows:
DF: Dilution Factor DL: Detection Limit MDA: Minimum Detectable Activity MDC: Minimum Detectable Concentration Page 4 of 30 SDG: 642226
Certificate of Analysis GEL LABORATORIES LLC 2040 Savage Road Charleston SC 29407 - (843) 556-8171 - www.gel.com Report Date: November 9, 2023 Parameter Result Units Qualifier Analyst Date Time DF Batch Method RL MDC PF Rad Alpha Spec Analysis Rad Gas Flow Proportional Counting Rad Liquid Scintillation Analysis 2513350 2513355 2513351 2513353 2512641 2512884 2512921 2512495 2512806 2512838 1104 1433 1045 1734 1220 2103 1007 2336 1027 0815 pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g 10/28/23 10/28/23 10/28/23 10/30/23 11/01/23 10/25/23 10/31/23 10/30/23 10/30/23 11/01/23 EJ1 EJ1 EJ1 EJ1 ST2 KXA1 KXA1 AG2 TXJ1 TXJ1 0.261 0.488 0.0110 0.219 0.281 8.83 0.0177 5.05 0.0284 0.157 516 7.24 Chris Messier
Contact:
BHI Energy Company :
97 Libbey Industrial Parkway Weymouth, Massachusetts 02189 Address :
Oyster Creek Soil Analysis Project:
642226002 Soil 12-OCT-23 10:41 20-OCT-23 RCA-SOIL-19-B HBHI00222 Project:
HBHI001 Client ID:
Client
+/-0.0831
+/-0.0591
+/-0.00422
+/-0.00828
+/-0.0161
+/-3.88
+/-0.0115
+/-2.57
+/-0.372
+/-0.489
+/-51.0
+/-2.54 Sample ID:
Receive Date:
4th Floor Client Sample ID:
Matrix:
Collect Date:
Collector:
0.104 0.102 0.00583 0.0192 0.0244 6.77 0.0176 4.55 0.636 0.814 79.5 4.51 1
2 3
4 5
6 7
8 9
10 U
U U
U U
U U
U U
U U
U Americium-241 Curium-243/244 Neptunium-237 Plutonium-238 Plutonium-239/240 Plutonium-241 Strontium-90 Tritium Carbon-14 Technetium-99 Iron-55 Nickel-63 Alphaspec Am241, Cm, Solid "Dry Weight Corrected" Alphaspec Np, Solid "Dry Weight Corrected" Alphaspec Pu, Solid "Dry Weight Corrected" Liquid Scint Pu241, Solid "Dry Weight Corrected" GFPC, Sr90, Solid "Dry Weight Corrected" LSC, Tritium Dist, Solid "As Received" Liquid Scint C14, Solid "As Received" Liquid Scint Tc99, Solid "As Received" Liquid Scint Fe55, Solid "Dry Weight Corrected" Liquid Scint Ni63, Solid "Dry Weight Corrected" 0.0727 0.0215 0.00305
-0.000960 0.00911 0.543 0.0173 0.269 0.111 0.633
-13.1
-1.10 The following Prep Methods were performed:
Dry Soil Prep Dry Soil Prep GL-RAD-A-021 10/23/23 2512302 1152 WGR Method Description Analyst Date Time Prep Batch Uncertainty Page 5 of 30 SDG: 642226
Certificate of Analysis GEL LABORATORIES LLC 2040 Savage Road Charleston SC 29407 - (843) 556-8171 - www.gel.com Report Date: November 9, 2023 Parameter Result Units Qualifier Analyst Date Time DF Batch Method RL MDC PF Chris Messier
Contact:
BHI Energy Company :
97 Libbey Industrial Parkway Weymouth, Massachusetts 02189 Address :
Oyster Creek Soil Analysis Project:
642226002 RCA-SOIL-19-B HBHI00222 Project:
HBHI001 Client ID:
Sample ID:
4th Floor Client Sample ID:
Surrogate/Tracer Recovery Recovery%
Test Acceptable Limits Americium-243 Tracer Americium-243 Tracer Plutonium-242 Tracer Plutonium-242 Tracer Strontium Carrier Technetium-99m Tracer Iron-59 Tracer Nickel Carrier Alphaspec Am241, Cm, Solid "Dry Weight Corrected" Alphaspec Np, Solid "Dry Weight Corrected" Alphaspec Pu, Solid "Dry Weight Corrected" Liquid Scint Pu241, Solid "Dry Weight Corrected" GFPC, Sr90, Solid "Dry Weight Corrected" Liquid Scint Tc99, Solid "As Received" Liquid Scint Fe55, Solid "Dry Weight Corrected" Liquid Scint Ni63, Solid "Dry Weight Corrected" 21.3 73.4 74.4 74.4 72.7 90.8 100 95 (15%-125%)
(15%-125%)
(15%-125%)
(15%-125%)
(25%-125%)
(15%-125%)
(15%-125%)
(25%-125%)
The following Analytical Methods were performed:
1 2
3 4
5 6
7 8
9 10 Method Description DOE EML HASL-300, Am-05-RC Modified ASTM C 1475-00 Modified DOE EML HASL-300, Pu-11-RC Modified DOE EML HASL-300, Pu-11-RC Modified EPA 905.0 Modified/DOE RP501 Rev. 1 Modified EPA 906.0 Modified EPA EERF C-01 Modified DOE EML HASL-300, Tc-02-RC Modified DOE RESL Fe-1, Modified DOE RESL Ni-1, Modified Analyst Comments Uncertainty Nominal 1.38E+06 Result 1.26E+06 CPM Notes:
Counting Uncertainty is calculated at the 95% confidence level (1.96-sigma).
Lc/LC: Critical Level PF: Prep Factor RL: Reporting Limit SQL: Sample Quantitation Limit Column headers are defined as follows:
DF: Dilution Factor DL: Detection Limit MDA: Minimum Detectable Activity MDC: Minimum Detectable Concentration Page 6 of 30 SDG: 642226
Certificate of Analysis GEL LABORATORIES LLC 2040 Savage Road Charleston SC 29407 - (843) 556-8171 - www.gel.com Report Date: November 9, 2023 Parameter Result Units Qualifier Analyst Date Time DF Batch Method RL MDC PF Rad Alpha Spec Analysis Rad Gas Flow Proportional Counting Rad Liquid Scintillation Analysis 2513350 2513355 2513351 2513353 2512641 2512884 2512921 2512495 2512806 2512838 1104 1433 1050 1751 1717 2140 1042 0038 1043 0832 pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g 10/28/23 10/28/23 10/28/23 10/30/23 10/31/23 10/25/23 10/31/23 10/31/23 10/30/23 11/01/23 EJ1 EJ1 EJ1 EJ1 ST2 KXA1 KXA1 AG2 TXJ1 TXJ1 0.261 0.488 0.0110 0.219 0.281 8.83 0.0177 5.05 0.0284 0.157 516 7.24 Chris Messier
Contact:
BHI Energy Company :
97 Libbey Industrial Parkway Weymouth, Massachusetts 02189 Address :
Oyster Creek Soil Analysis Project:
642226003 Soil 12-OCT-23 10:58 20-OCT-23 RCA-SOIL-15-B HBHI00222 Project:
HBHI001 Client ID:
Client
+/-0.0653
+/-0.0981
+/-0.00729
+/-0.0118
+/-0.0130
+/-3.94
+/-0.0110
+/-2.63
+/-0.376
+/-0.549
+/-58.5
+/-2.91 Sample ID:
Receive Date:
4th Floor Client Sample ID:
Matrix:
Collect Date:
Collector:
0.152 0.253 0.0107 0.0198 0.0347 6.87 0.0171 4.47 0.634 0.921 90.6 5.03 1
2 3
4 5
6 7
8 9
10 U
U U
U U
U U
U U
U U
U Americium-241 Curium-243/244 Neptunium-237 Plutonium-238 Plutonium-239/240 Plutonium-241 Strontium-90 Tritium Carbon-14 Technetium-99 Iron-55 Nickel-63 Alphaspec Am241, Cm, Solid "Dry Weight Corrected" Alphaspec Np, Solid "Dry Weight Corrected" Alphaspec Pu, Solid "Dry Weight Corrected" Liquid Scint Pu241, Solid "Dry Weight Corrected" GFPC, Sr90, Solid "Dry Weight Corrected" LSC, Tritium Dist, Solid "As Received" Liquid Scint C14, Solid "As Received" Liquid Scint Tc99, Solid "As Received" Liquid Scint Fe55, Solid "Dry Weight Corrected" Liquid Scint Ni63, Solid "Dry Weight Corrected"
-0.00435
-0.0592 0.00819 0.00314
-0.00479 0.463 0.0160 1.92 0.287 0.538 4.01 0.629 The following Prep Methods were performed:
Dry Soil Prep Dry Soil Prep GL-RAD-A-021 10/23/23 2512302 1152 WGR Method Description Analyst Date Time Prep Batch Uncertainty Page 7 of 30 SDG: 642226
Certificate of Analysis GEL LABORATORIES LLC 2040 Savage Road Charleston SC 29407 - (843) 556-8171 - www.gel.com Report Date: November 9, 2023 Parameter Result Units Qualifier Analyst Date Time DF Batch Method RL MDC PF Chris Messier
Contact:
BHI Energy Company :
97 Libbey Industrial Parkway Weymouth, Massachusetts 02189 Address :
Oyster Creek Soil Analysis Project:
642226003 RCA-SOIL-15-B HBHI00222 Project:
HBHI001 Client ID:
Sample ID:
4th Floor Client Sample ID:
Surrogate/Tracer Recovery Recovery%
Test Acceptable Limits Americium-243 Tracer Americium-243 Tracer Plutonium-242 Tracer Plutonium-242 Tracer Strontium Carrier Technetium-99m Tracer Iron-59 Tracer Nickel Carrier Alphaspec Am241, Cm, Solid "Dry Weight Corrected" Alphaspec Np, Solid "Dry Weight Corrected" Alphaspec Pu, Solid "Dry Weight Corrected" Liquid Scint Pu241, Solid "Dry Weight Corrected" GFPC, Sr90, Solid "Dry Weight Corrected" Liquid Scint Tc99, Solid "As Received" Liquid Scint Fe55, Solid "Dry Weight Corrected" Liquid Scint Ni63, Solid "Dry Weight Corrected" 17.5 74 71.6 71.6 90.9 88.5 94 85.1 (15%-125%)
(15%-125%)
(15%-125%)
(15%-125%)
(25%-125%)
(15%-125%)
(15%-125%)
(25%-125%)
The following Analytical Methods were performed:
1 2
3 4
5 6
7 8
9 10 Method Description DOE EML HASL-300, Am-05-RC Modified ASTM C 1475-00 Modified DOE EML HASL-300, Pu-11-RC Modified DOE EML HASL-300, Pu-11-RC Modified EPA 905.0 Modified/DOE RP501 Rev. 1 Modified EPA 906.0 Modified EPA EERF C-01 Modified DOE EML HASL-300, Tc-02-RC Modified DOE RESL Fe-1, Modified DOE RESL Ni-1, Modified Analyst Comments Uncertainty Nominal 1.38E+06 Result 1.22E+06 CPM Notes:
Counting Uncertainty is calculated at the 95% confidence level (1.96-sigma).
Lc/LC: Critical Level PF: Prep Factor RL: Reporting Limit SQL: Sample Quantitation Limit Column headers are defined as follows:
DF: Dilution Factor DL: Detection Limit MDA: Minimum Detectable Activity MDC: Minimum Detectable Concentration Page 8 of 30 SDG: 642226
Certificate of Analysis GEL LABORATORIES LLC 2040 Savage Road Charleston SC 29407 - (843) 556-8171 - www.gel.com Report Date: November 9, 2023 Parameter Result Units Qualifier Analyst Date Time DF Batch Method RL MDC PF Rad Alpha Spec Analysis Rad Gas Flow Proportional Counting Rad Liquid Scintillation Analysis 2513350 2513355 2513351 2513353 2512641 2512884 2512921 2512495 2512806 2512838 1104 1433 1050 1807 1717 2217 1118 0141 1059 0848 pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g 10/28/23 10/28/23 10/28/23 10/30/23 10/31/23 10/25/23 10/31/23 10/31/23 10/30/23 11/01/23 EJ1 EJ1 EJ1 EJ1 ST2 KXA1 KXA1 AG2 TXJ1 TXJ1 0.261 0.488 0.0110 0.219 0.281 8.83 0.0177 5.05 0.0284 0.157 516 7.24 Chris Messier
Contact:
BHI Energy Company :
97 Libbey Industrial Parkway Weymouth, Massachusetts 02189 Address :
Oyster Creek Soil Analysis Project:
642226004 Soil 12-OCT-23 11:05 20-OCT-23 RCA-SOIL-10-B HBHI00222 Project:
HBHI001 Client ID:
Client
+/-0.0215
+/-0.0214
+/-0.00403
+/-0.00818
+/-0.00859
+/-4.34
+/-0.0102
+/-2.69
+/-0.365
+/-0.633
+/-56.6
+/-3.16 Sample ID:
Receive Date:
4th Floor Client Sample ID:
Matrix:
Collect Date:
Collector:
0.0298 0.0339 0.00656 0.0190 0.0241 7.65 0.0176 4.54 0.618 1.08 88.9 5.26 1
2 3
4 5
6 7
8 9
10 U
U U
U U
U U
U U
U U
U Americium-241 Curium-243/244 Neptunium-237 Plutonium-238 Plutonium-239/240 Plutonium-241 Strontium-90 Tritium Carbon-14 Technetium-99 Iron-55 Nickel-63 Alphaspec Am241, Cm, Solid "Dry Weight Corrected" Alphaspec Np, Solid "Dry Weight Corrected" Alphaspec Pu, Solid "Dry Weight Corrected" Liquid Scint Pu241, Solid "Dry Weight Corrected" GFPC, Sr90, Solid "Dry Weight Corrected" LSC, Tritium Dist, Solid "As Received" Liquid Scint C14, Solid "As Received" Liquid Scint Tc99, Solid "As Received" Liquid Scint Fe55, Solid "Dry Weight Corrected" Liquid Scint Ni63, Solid "Dry Weight Corrected" 0.0109 0.00931 0.00205
-0.000949
-0.00285
-0.255 0.00683 2.31 0.253 0.211
-28.7 3.57 The following Prep Methods were performed:
Dry Soil Prep Dry Soil Prep GL-RAD-A-021 10/23/23 2512302 1152 WGR Method Description Analyst Date Time Prep Batch Uncertainty Page 9 of 30 SDG: 642226
Certificate of Analysis GEL LABORATORIES LLC 2040 Savage Road Charleston SC 29407 - (843) 556-8171 - www.gel.com Report Date: November 9, 2023 Parameter Result Units Qualifier Analyst Date Time DF Batch Method RL MDC PF Chris Messier
Contact:
BHI Energy Company :
97 Libbey Industrial Parkway Weymouth, Massachusetts 02189 Address :
Oyster Creek Soil Analysis Project:
642226004 RCA-SOIL-10-B HBHI00222 Project:
HBHI001 Client ID:
Sample ID:
4th Floor Client Sample ID:
Surrogate/Tracer Recovery Recovery%
Test Acceptable Limits Americium-243 Tracer Americium-243 Tracer Plutonium-242 Tracer Plutonium-242 Tracer Strontium Carrier Technetium-99m Tracer Iron-59 Tracer Nickel Carrier Alphaspec Am241, Cm, Solid "Dry Weight Corrected" Alphaspec Np, Solid "Dry Weight Corrected" Alphaspec Pu, Solid "Dry Weight Corrected" Liquid Scint Pu241, Solid "Dry Weight Corrected" GFPC, Sr90, Solid "Dry Weight Corrected" Liquid Scint Tc99, Solid "As Received" Liquid Scint Fe55, Solid "Dry Weight Corrected" Liquid Scint Ni63, Solid "Dry Weight Corrected" 57.8 85.3 64.5 64.5 61.4 63.6 101 81.4 (15%-125%)
(15%-125%)
(15%-125%)
(15%-125%)
(25%-125%)
(15%-125%)
(15%-125%)
(25%-125%)
The following Analytical Methods were performed:
1 2
3 4
5 6
7 8
9 10 Method Description DOE EML HASL-300, Am-05-RC Modified ASTM C 1475-00 Modified DOE EML HASL-300, Pu-11-RC Modified DOE EML HASL-300, Pu-11-RC Modified EPA 905.0 Modified/DOE RP501 Rev. 1 Modified EPA 906.0 Modified EPA EERF C-01 Modified DOE EML HASL-300, Tc-02-RC Modified DOE RESL Fe-1, Modified DOE RESL Ni-1, Modified Analyst Comments Uncertainty Nominal 1.38E+06 Result 8.79E+05 CPM Notes:
Counting Uncertainty is calculated at the 95% confidence level (1.96-sigma).
Lc/LC: Critical Level PF: Prep Factor RL: Reporting Limit SQL: Sample Quantitation Limit Column headers are defined as follows:
DF: Dilution Factor DL: Detection Limit MDA: Minimum Detectable Activity MDC: Minimum Detectable Concentration Page 10 of 30 SDG: 642226
Certificate of Analysis GEL LABORATORIES LLC 2040 Savage Road Charleston SC 29407 - (843) 556-8171 - www.gel.com Report Date: November 9, 2023 Parameter Result Units Qualifier Analyst Date Time DF Batch Method RL MDC PF Rad Alpha Spec Analysis Rad Gas Flow Proportional Counting Rad Liquid Scintillation Analysis 2513350 2513355 2513351 2513353 2512641 2512884 2512921 2512495 2512806 2512838 0837 1433 1050 1823 1833 2254 1154 0647 1114 0905 pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g 10/31/23 10/28/23 10/28/23 10/30/23 11/02/23 10/25/23 10/31/23 10/31/23 10/30/23 11/01/23 EJ1 EJ1 EJ1 EJ1 ST2 KXA1 KXA1 AG2 TXJ1 TXJ1 0.261 0.488 0.0110 0.219 0.281 8.83 0.0177 5.05 0.0284 0.157 516 7.24 Chris Messier
Contact:
BHI Energy Company :
97 Libbey Industrial Parkway Weymouth, Massachusetts 02189 Address :
Oyster Creek Soil Analysis Project:
642226005 Soil 12-OCT-23 10:48 20-OCT-23 RCA-SOIL-04-B HBHI00222 Project:
HBHI001 Client ID:
Client
+/-0.0459
+/-0.0213
+/-0.00475
+/-0.0143
+/-0.0148
+/-4.23
+/-0.0115
+/-2.70
+/-0.367
+/-0.869
+/-50.5
+/-3.19 Sample ID:
Receive Date:
4th Floor Client Sample ID:
Matrix:
Collect Date:
Collector:
0.0622 0.0497 0.00828 0.0125 0.0274 7.49 0.0167 4.51 0.620 1.46 75.1 5.51 1
2 3
4 5
6 7
8 9
10 U
U U
U U
U U
U U
U U
Americium-241 Curium-243/244 Neptunium-237 Plutonium-238 Plutonium-239/240 Plutonium-241 Strontium-90 Tritium Carbon-14 Technetium-99 Iron-55 Nickel-63 Alphaspec Am241, Cm, Solid "Dry Weight Corrected" Alphaspec Np, Solid "Dry Weight Corrected" Alphaspec Pu, Solid "Dry Weight Corrected" Liquid Scint Pu241, Solid "Dry Weight Corrected" GFPC, Sr90, Solid "Dry Weight Corrected" LSC, Tritium Dist, Solid "As Received" Liquid Scint C14, Solid "As Received" Liquid Scint Tc99, Solid "As Received" Liquid Scint Fe55, Solid "Dry Weight Corrected" Liquid Scint Ni63, Solid "Dry Weight Corrected" 0.0474
-0.00142 0.00202 0.00832 0.00432
-0.724 0.0436 2.64 0.272 0.820 71.1 0.856 The following Prep Methods were performed:
Dry Soil Prep Dry Soil Prep GL-RAD-A-021 10/23/23 2512302 1152 WGR Method Description Analyst Date Time Prep Batch Uncertainty Page 11 of 30 SDG: 642226
Certificate of Analysis GEL LABORATORIES LLC 2040 Savage Road Charleston SC 29407 - (843) 556-8171 - www.gel.com Report Date: November 9, 2023 Parameter Result Units Qualifier Analyst Date Time DF Batch Method RL MDC PF Chris Messier
Contact:
BHI Energy Company :
97 Libbey Industrial Parkway Weymouth, Massachusetts 02189 Address :
Oyster Creek Soil Analysis Project:
642226005 RCA-SOIL-04-B HBHI00222 Project:
HBHI001 Client ID:
Sample ID:
4th Floor Client Sample ID:
Surrogate/Tracer Recovery Recovery%
Test Acceptable Limits Americium-243 Tracer Americium-243 Tracer Plutonium-242 Tracer Plutonium-242 Tracer Strontium Carrier Technetium-99m Tracer Iron-59 Tracer Nickel Carrier Alphaspec Am241, Cm, Solid "Dry Weight Corrected" Alphaspec Np, Solid "Dry Weight Corrected" Alphaspec Pu, Solid "Dry Weight Corrected" Liquid Scint Pu241, Solid "Dry Weight Corrected" GFPC, Sr90, Solid "Dry Weight Corrected" Liquid Scint Tc99, Solid "As Received" Liquid Scint Fe55, Solid "Dry Weight Corrected" Liquid Scint Ni63, Solid "Dry Weight Corrected" 40.7 84.5 64.9 64.9 59.1 53 91.8 78.9 (15%-125%)
(15%-125%)
(15%-125%)
(15%-125%)
(25%-125%)
(15%-125%)
(15%-125%)
(25%-125%)
The following Analytical Methods were performed:
1 2
3 4
5 6
7 8
9 10 Method Description DOE EML HASL-300, Am-05-RC Modified ASTM C 1475-00 Modified DOE EML HASL-300, Pu-11-RC Modified DOE EML HASL-300, Pu-11-RC Modified EPA 905.0 Modified/DOE RP501 Rev. 1 Modified EPA 906.0 Modified EPA EERF C-01 Modified DOE EML HASL-300, Tc-02-RC Modified DOE RESL Fe-1, Modified DOE RESL Ni-1, Modified Analyst Comments Uncertainty Nominal 1.38E+06 Result 7.33E+05 CPM Notes:
Counting Uncertainty is calculated at the 95% confidence level (1.96-sigma).
Lc/LC: Critical Level PF: Prep Factor RL: Reporting Limit SQL: Sample Quantitation Limit Column headers are defined as follows:
DF: Dilution Factor DL: Detection Limit MDA: Minimum Detectable Activity MDC: Minimum Detectable Concentration Page 12 of 30 SDG: 642226
QC Summary GEL LABORATORIES LLC 2040 Savage Road Charleston, SC 29407 - (843) 556-8171 - www.gel.com Rad Alpha Spec 2513350 2513351 Batch Batch Americium-241 Curium-243/244 Americium-241 Curium-243/244 Americium-241 Curium-243/244 Plutonium-238 Plutonium-239/240 Plutonium-238 Plutonium-239/240 Plutonium-238 Plutonium-239/240 Parmname Chris Messier
Contact:
BHI Energy 97 Libbey Industrial Parkway Weymouth, Massachusetts November 9, 2023 Report Date:
Units pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g Anlst Date Time EJ1 EJ1 10/28/23 11:04 10/28/23 11:04 10/28/23 11:04 10/28/23 10:50 10/28/23 10:50 10/28/23 10:50 QC 0.0227 0.00265 0.837 0.906
-0.00103
-0.00611 0.00748 0.00278 0.0145 0.975
-0.00429
-0.00429 NOM Sample 0.0131
-0.00598 0.00676 0.0144 Range N/A N/A (75%-125%)
(75%-125%)
N/A N/A (75%-125%)
Qual U
U U
U U
U U
U QC1205555385 642226001 QC1205555386 QC1205555384 QC1205555388 642226001 QC1205555389 QC1205555387 N/A N/A N/A N/A REC%
88.1 93.9 99.1 0.950 0.965 0.984 DUP LCS MB DUP LCS MB 642226 Workorder:
4th Floor U
U U
U RPD%
Page 1 of 5 Page 13 of 30 SDG: 642226
QC Summary GEL LABORATORIES LLC 2040 Savage Road Charleston, SC 29407 - (843) 556-8171 - www.gel.com Rad Alpha Spec Rad Gas Flow Rad Liquid Scintillation 2513353 2513355 2512641 2512495 Batch Batch Batch Batch Plutonium-241 Plutonium-241 Plutonium-241 Neptunium-237 Neptunium-237 Neptunium-237 Strontium-90 Strontium-90 Strontium-90 Technetium-99 Parmname Units pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g Anlst Date Time EJ1 EJ1 ST2 AG2 10/30/23 18:56 10/30/23 19:12 10/30/23 18:40 10/28/23 14:33 10/28/23 15:34 10/28/23 14:33 11/08/23 18:15 10/30/23 17:40 10/31/23 17:17 10/31/23 08:52 QC
-0.00766 64.9
-1.55
-0.00521 1.36 0.00106 0.0444 1.69 0.00695 0.417 NOM Sample 1.22
-0.00365 0.0697 0.0416 Range N/A (75%-125%)
N/A (75%-125%)
(0% - 100%)
(75%-125%)
N/A Qual U
U U
U U
U QC1205555391 642226001 QC1205555392 QC1205555390 QC1205555394 642226001 QC1205555395 QC1205555393 QC1205553829 642226001 QC1205553830 QC1205553828 QC1205553510 642226001 N/A N/A 44.3 N/A REC%
100 111 105 64.7 1.23 1.61 DUP LCS MB DUP LCS MB DUP LCS MB DUP 642226 Workorder:
U U
U RPD%
Page 2 of 5 Page 14 of 30 SDG: 642226
QC Summary GEL LABORATORIES LLC 2040 Savage Road Charleston, SC 29407 - (843) 556-8171 - www.gel.com Rad Liquid Scintillation 2512495 2512806 2512838 Batch Batch Batch Technetium-99m Tracer Technetium-99 Technetium-99m Tracer Technetium-99 Technetium-99m Tracer Iron-55 Iron-55 Iron-55 Nickel-63 Nickel-63 Nickel-63 Parmname Units CPM pCi/g CPM pCi/g CPM pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g Anlst Date Time AG2 TXJ1 TXJ1 10/31/23 08:52 10/31/23 10:00 10/31/23 07:49 10/30/23 11:46 10/30/23 12:01 10/30/23 11:30 11/01/23 09:39 11/01/23 09:56 11/01/23 09:22 QC 1.28E+06 15.0 1.30E+06
-0.0783 1.29E+06
-45.3 562 6.77 1.62 144
-0.270 NOM Sample 1.30E+06
-24.9 2.00 Range (15%-125%)
(75%-125%)
(15%-125%)
(15%-125%)
N/A (75%-125%)
N/A (75%-125%)
Qual U
U U
U U
QC1205553511 QC1205553509 QC1205554207 642226001 QC1205554208 QC1205554206 QC1205554285 642226001 QC1205554286 QC1205554284 N/A N/A REC%
92.5 93 94.3 93.3 94.3 106 1.38E+06 16.1 1.38E+06 1.38E+06 596 137 LCS MB DUP LCS MB DUP LCS MB 642226 Workorder:
U U
RPD%
Page 3 of 5 Page 15 of 30 SDG: 642226
QC Summary GEL LABORATORIES LLC 2040 Savage Road Charleston, SC 29407 - (843) 556-8171 - www.gel.com Rad Liquid Scintillation 2512884 2512921 Batch Batch Tritium Tritium Tritium Tritium Carbon-14 Carbon-14 Carbon-14 Carbon-14 Parmname Units pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g Anlst Date Time KXA1 KXA1 10/26/23 00:07 10/26/23 01:21 10/25/23 23:30 10/26/23 00:44 10/31/23 13:06 10/31/23 14:17 10/31/23 12:30 10/31/23 13:41 QC 1.30 43.9 0.442 118 0.184 22.5 0.168 65.7 NOM Sample 1.29 1.29 0.131 0.131 Range N/A (75%-125%)
(75%-125%)
N/A (75%-125%)
(75%-125%)
Qual U
U U
U QC1205554433 642226001 QC1205554435 QC1205554432 QC1205554434 642226001 QC1205554553 642226001 QC1205554555 QC1205554552 QC1205554554 642226001 The Qualifiers in this report are defined as follows:
N/A N/A REC%
92.2 85 93.7 95 47.7 139 24.0 69.1 DUP LCS MB MS DUP LCS MB MS 642226 Workorder:
U J
X H
UI Analyte was analyzed for, but not detected above the MDL, MDA, MDC or LOD.
Value is estimated Consult Case Narrative, Data Summary package, or Project Manager concerning this qualifier Analytical holding time was exceeded Result is less than value reported Result is greater than value reported Gamma Spectroscopy--Uncertain identification U
U U
U RPD%
Notes:
Page 4 of 5 Page 16 of 30 SDG: 642226
QC Summary GEL LABORATORIES LLC 2040 Savage Road Charleston, SC 29407 - (843) 556-8171 - www.gel.com Parmname Page 5 of 5 Units Anlst Date Time QC NOM Sample Range Qual REC%
642226 Workorder:
BD h
R
^
N/A ND M
NJ FA UJ Q
K UL L
N1 Y
M J
Results are either below the MDC or tracer recovery is low Preparation or preservation holding time was exceeded Sample results are rejected RPD of sample and duplicate evaluated using +/-RL. Concentrations are <5X the RL. Qualifier Not Applicable for Radiochemistry.
RPD or %Recovery limits do not apply.
Analyte concentration is not detected above the detection limit M if above MDC and less than LLD Consult Case Narrative, Data Summary package, or Project Manager concerning this qualifier Failed analysis.
Gamma Spectroscopy--Uncertain identification One or more quality control criteria have not been met. Refer to the applicable narrative or DER.
Analyte present. Reported value may be biased high. Actual value is expected to be lower.
Not considered detected. The associated number is the reported concentration, which may be inaccurate due to a low bias.
Analyte present. Reported value may be biased low. Actual value is expected to be higher.
See case narrative Other specific qualifiers were required to properly define the results. Consult case narrative.
Analyte is a Tracer compound REMP Result > MDC/CL and < RDL See case narrative for an explanation N/A indicates that spike recovery limits do not apply when sample concentration exceeds spike conc. by a factor of 4 or more or %RPD not applicable.
^ The Relative Percent Difference (RPD) obtained from the sample duplicate (DUP) is evaluated against the acceptance criteria when the sample is greater than five times (5X) the contract required detection limit (RL). In cases where either the sample or duplicate value is less than 5X the RL, a control limit of +/- the RL is used to evaluate the DUP result.
- Indicates that a Quality Control parameter was not within specifications.
For PS, PSD, and SDILT results, the values listed are the measured amounts, not final concentrations.
Where the analytical method has been performed under NELAP certification, the analysis has met all of the requirements of the NELAC standard unless qualified on the QC Summary.
RPD%
Page 17 of 30 SDG: 642226
Radiochemistry Technical Case Narrative Holtec BHI SDG #: 642226 Product: Alphaspec Am241, Cm, Solid Analytical Method: DOE EML HASL-300, Am-05-RC Modified Analytical Procedure: GL-RAD-A-011 REV# 28 Analytical Batch: 2513350 Preparation Method: Dry Soil Prep Preparation Procedure: GL-RAD-A-021 REV# 24 Preparation Batch: 2512302 The following samples were analyzed using the above methods and analytical procedure(s).
GEL Sample ID# Client Sample Identification 642226001 RCA-SOIL-16-B 642226002 RCA-SOIL-19-B 642226003 RCA-SOIL-15-B 642226004 RCA-SOIL-10-B 642226005 RCA-SOIL-04-B 1205555384 Method Blank (MB) 1205555385 642226001(RCA-SOIL-16-B) Sample Duplicate (DUP) 1205555386 Laboratory Control Sample (LCS)
The samples in this SDG were analyzed on a "dry weight" basis.
Data Summary:
All sample data provided in this report met the acceptance criteria specified in the analytical methods and procedures for initial calibration, continuing calibration, instrument controls and process controls where applicable, with the following exceptions.
Technical Information Recounts Sample 642226001 (RCA-SOIL-16-B) was recounted due to a peak shift. The recount is reported. Sample 642226005 (RCA-SOIL-04-B) was recounted due to a suspected false positive. The recount is reported.
Miscellaneous Information Additional Comments The tracer peak centroid for sample 642226001 (RCA-SOIL-16-B) is greater than 50 keV from the expected library energy value for the tracer; however, the tracer yield requirement was met and the tracer peak is within the tracer region of interest.
Page 18 of 30 SDG: 642226
Product: Alphaspec Pu, Solid Analytical Method: DOE EML HASL-300, Pu-11-RC Modified Analytical Procedure: GL-RAD-A-011 REV# 28 Analytical Batch: 2513351 Preparation Method: Dry Soil Prep Preparation Procedure: GL-RAD-A-021 REV# 24 Preparation Batch: 2512302 The following samples were analyzed using the above methods and analytical procedure(s).
GEL Sample ID# Client Sample Identification 642226001 RCA-SOIL-16-B 642226002 RCA-SOIL-19-B 642226003 RCA-SOIL-15-B 642226004 RCA-SOIL-10-B 642226005 RCA-SOIL-04-B 1205555387 Method Blank (MB) 1205555388 642226001(RCA-SOIL-16-B) Sample Duplicate (DUP) 1205555389 Laboratory Control Sample (LCS)
The samples in this SDG were analyzed on a "dry weight" basis.
Data Summary:
There are no exceptions, anomalies or deviations from the specified methods. All sample data provided in this report met the acceptance criteria specified in the analytical methods and procedures for initial calibration, continuing calibration, instrument controls and process controls where applicable.
Product: Alphaspec Np, Solid Analytical Method: ASTM C 1475-00 Modified Analytical Procedure: GL-RAD-A-069 REV# 1 Analytical Batch: 2513355 Preparation Method: Dry Soil Prep Preparation Procedure: GL-RAD-A-021 REV# 24 Preparation Batch: 2512302 The following samples were analyzed using the above methods and analytical procedure(s).
GEL Sample ID# Client Sample Identification 642226001 RCA-SOIL-16-B 642226002 RCA-SOIL-19-B 642226003 RCA-SOIL-15-B 642226004 RCA-SOIL-10-B 642226005 RCA-SOIL-04-B 1205555393 Method Blank (MB) 1205555394 642226001(RCA-SOIL-16-B) Sample Duplicate (DUP) 1205555395 Laboratory Control Sample (LCS)
The samples in this SDG were analyzed on a "dry weight" basis.
Page 19 of 30 SDG: 642226
Data Summary:
All sample data provided in this report met the acceptance criteria specified in the analytical methods and procedures for initial calibration, continuing calibration, instrument controls and process controls where applicable, with the following exceptions.
Quality Control (QC) Information RDL Met Samples did not meet the detection limits. The samples were counted the maximum count time in order to achieve the lowest possible MDAs.
Sample Analyte Value 1205555394 (RCA-SOIL-16-BDUP) Neptunium-237 Result -0.00521 < MDA 0.0114 > RDL 0.011 pCi/g 642226001 (RCA-SOIL-16-B)
Neptunium-237 Result -0.00365 < MDA 0.0118 > RDL 0.011 pCi/g Product: Dry Weight Preparation Method: Dry Soil Prep Preparation Procedure: GL-RAD-A-021 REV# 24 Preparation Batch: 2512302 The following samples were analyzed using the above methods and analytical procedure(s).
GEL Sample ID# Client Sample Identification 642226001 RCA-SOIL-16-B 642226002 RCA-SOIL-19-B 642226003 RCA-SOIL-15-B 642226004 RCA-SOIL-10-B 642226005 RCA-SOIL-04-B The samples in this SDG were analyzed on an "as received" basis.
Data Summary:
There are no exceptions, anomalies or deviations from the specified methods. All sample data provided in this report met the acceptance criteria specified in the analytical methods and procedures for initial calibration, continuing calibration, instrument controls and process controls where applicable.
Product: GFPC, Sr90, Solid Analytical Method: EPA 905.0 Modified/DOE RP501 Rev. 1 Modified Analytical Procedure: GL-RAD-A-004 REV# 22 Analytical Batch: 2512641 Preparation Method: Dry Soil Prep Page 20 of 30 SDG: 642226
Preparation Procedure: GL-RAD-A-021 REV# 24 Preparation Batch: 2512302 The following samples were analyzed using the above methods and analytical procedure(s).
GEL Sample ID# Client Sample Identification 642226001 RCA-SOIL-16-B 642226002 RCA-SOIL-19-B 642226003 RCA-SOIL-15-B 642226004 RCA-SOIL-10-B 642226005 RCA-SOIL-04-B 1205553828 Method Blank (MB) 1205553829 642226001(RCA-SOIL-16-B) Sample Duplicate (DUP) 1205553830 Laboratory Control Sample (LCS)
The samples in this SDG were analyzed on a "dry weight" basis.
Data Summary:
All sample data provided in this report met the acceptance criteria specified in the analytical methods and procedures for initial calibration, continuing calibration, instrument controls and process controls where applicable, with the following exceptions.
Technical Information Recounts Sample 1205553828 (MB) was recounted due to a suspected blank false positive. The recount is reported.
Samples 642226001 (RCA-SOIL-16-B) and 642226005 (RCA-SOIL-04-B) were taken through additional clean-up steps and recounted to confirm the results. The recounts are reported. Sample 1205553829 (RCA-SOIL-16-BDUP) was recounted due to high relative percent difference/relative error ratio. The recount is reported. Samples 642226002 (RCA-SOIL-19-B), 642226003 (RCA-SOIL-15-B) and 642226004 (RCA-SOIL-10-B) were recounted due to a suspected false positive. The recounts are reported.
Product: Liquid Scint Pu241, Solid Analytical Method: DOE EML HASL-300, Pu-11-RC Modified Analytical Procedure: GL-RAD-A-035 REV# 24 Analytical Batch: 2513353 Preparation Method: Dry Soil Prep Preparation Procedure: GL-RAD-A-021 REV# 24 Preparation Batch: 2512302 The following samples were analyzed using the above methods and analytical procedure(s).
GEL Sample ID# Client Sample Identification 642226001 RCA-SOIL-16-B 642226002 RCA-SOIL-19-B 642226003 RCA-SOIL-15-B 642226004 RCA-SOIL-10-B 642226005 RCA-SOIL-04-B 1205555390 Method Blank (MB)
Page 21 of 30 SDG: 642226
1205555391 642226001(RCA-SOIL-16-B) Sample Duplicate (DUP) 1205555392 Laboratory Control Sample (LCS)
The samples in this SDG were analyzed on a "dry weight" basis.
Data Summary:
There are no exceptions, anomalies or deviations from the specified methods. All sample data provided in this report met the acceptance criteria specified in the analytical methods and procedures for initial calibration, continuing calibration, instrument controls and process controls where applicable.
Product: Liquid Scint Tc99, Solid Analytical Method: DOE EML HASL-300, Tc-02-RC Modified Analytical Procedure: GL-RAD-A-059 REV# 5 Analytical Batch: 2512495 The following samples were analyzed using the above methods and analytical procedure(s).
GEL Sample ID# Client Sample Identification 642226001 RCA-SOIL-16-B 642226002 RCA-SOIL-19-B 642226003 RCA-SOIL-15-B 642226004 RCA-SOIL-10-B 642226005 RCA-SOIL-04-B 1205553509 Method Blank (MB) 1205553510 642226001(RCA-SOIL-16-B) Sample Duplicate (DUP) 1205553511 Laboratory Control Sample (LCS)
The samples in this SDG were analyzed on an "as received" basis.
Data Summary:
All sample data provided in this report met the acceptance criteria specified in the analytical methods and procedures for initial calibration, continuing calibration, instrument controls and process controls where applicable, with the following exceptions.
Quality Control (QC) Information RDL Met Samples (See Below) did not meet the detection limits. Samples were counted the maximum count time in order to achieve the lowest MDAs possible.
Sample Analyte Value 1205553509 (MB)
Technetium-99 Result -0.0783 < MDA 0.62 > RDL 0.157 pCi/g 1205553510 (RCA-SOIL-16-BDUP) Technetium-99 Result 0.417 < MDA 0.676 > RDL 0.157 pCi/g 642226001 (RCA-SOIL-16-B)
Technetium-99 Result 0.0416 < MDA 0.703 > RDL 0.157 pCi/g 642226002 (RCA-SOIL-19-B)
Technetium-99 Result 0.633 < MDA 0.814 > RDL 0.157 pCi/g 642226003 (RCA-SOIL-15-B)
Technetium-99 Result 0.538 < MDA 0.921 > RDL 0.157 pCi/g 642226004 (RCA-SOIL-10-B)
Technetium-99 Result 0.211 < MDA 1.08 > RDL 0.157 pCi/g Page 22 of 30 SDG: 642226
642226005 (RCA-SOIL-04-B)
Technetium-99 Result 0.82 < MDA 1.46 > RDL 0.157 pCi/g Product: Liquid Scint Fe55, Solid Analytical Method: DOE RESL Fe-1, Modified Analytical Procedure: GL-RAD-A-064 REV# 1 Analytical Batch: 2512806 Preparation Method: Dry Soil Prep Preparation Procedure: GL-RAD-A-021 REV# 24 Preparation Batch: 2512302 The following samples were analyzed using the above methods and analytical procedure(s).
GEL Sample ID# Client Sample Identification 642226001 RCA-SOIL-16-B 642226002 RCA-SOIL-19-B 642226003 RCA-SOIL-15-B 642226004 RCA-SOIL-10-B 642226005 RCA-SOIL-04-B 1205554206 Method Blank (MB) 1205554207 642226001(RCA-SOIL-16-B) Sample Duplicate (DUP) 1205554208 Laboratory Control Sample (LCS)
The samples in this SDG were analyzed on a "dry weight" basis.
Data Summary:
There are no exceptions, anomalies or deviations from the specified methods. All sample data provided in this report met the acceptance criteria specified in the analytical methods and procedures for initial calibration, continuing calibration, instrument controls and process controls where applicable.
Product: Liquid Scint Ni63, Solid Analytical Method: DOE RESL Ni-1, Modified Analytical Procedure: GL-RAD-A-022 REV# 19 Analytical Batch: 2512838 Preparation Method: Dry Soil Prep Preparation Procedure: GL-RAD-A-021 REV# 24 Preparation Batch: 2512302 The following samples were analyzed using the above methods and analytical procedure(s).
GEL Sample ID# Client Sample Identification 642226001 RCA-SOIL-16-B Page 23 of 30 SDG: 642226
642226002 RCA-SOIL-19-B 642226003 RCA-SOIL-15-B 642226004 RCA-SOIL-10-B 642226005 RCA-SOIL-04-B 1205554284 Method Blank (MB) 1205554285 642226001(RCA-SOIL-16-B) Sample Duplicate (DUP) 1205554286 Laboratory Control Sample (LCS)
The samples in this SDG were analyzed on a "dry weight" basis.
Data Summary:
There are no exceptions, anomalies or deviations from the specified methods. All sample data provided in this report met the acceptance criteria specified in the analytical methods and procedures for initial calibration, continuing calibration, instrument controls and process controls where applicable.
Product: LSC, Tritium Dist, Solid Analytical Method: EPA 906.0 Modified Analytical Procedure: GL-RAD-A-002 REV# 24 Analytical Batch: 2512884 The following samples were analyzed using the above methods and analytical procedure(s).
GEL Sample ID# Client Sample Identification 642226001 RCA-SOIL-16-B 642226002 RCA-SOIL-19-B 642226003 RCA-SOIL-15-B 642226004 RCA-SOIL-10-B 642226005 RCA-SOIL-04-B 1205554432 Method Blank (MB) 1205554433 642226001(RCA-SOIL-16-B) Sample Duplicate (DUP) 1205554434 642226001(RCA-SOIL-16-B) Matrix Spike (MS) 1205554435 Laboratory Control Sample (LCS)
The samples in this SDG were analyzed on an "as received" basis.
Data Summary:
All sample data provided in this report met the acceptance criteria specified in the analytical methods and procedures for initial calibration, continuing calibration, instrument controls and process controls where applicable, with the following exceptions.
Miscellaneous Information Additional Comments The matrix spike, 1205554434 (RCA-SOIL-16-BMS), aliquot was reduced to conserve sample volume.
Product: Liquid Scint C14, Solid Page 24 of 30 SDG: 642226
Analytical Method: EPA EERF C-01 Modified Analytical Procedure: GL-RAD-A-003 REV# 17 Analytical Batch: 2512921 The following samples were analyzed using the above methods and analytical procedure(s).
GEL Sample ID# Client Sample Identification 642226001 RCA-SOIL-16-B 642226002 RCA-SOIL-19-B 642226003 RCA-SOIL-15-B 642226004 RCA-SOIL-10-B 642226005 RCA-SOIL-04-B 1205554552 Method Blank (MB) 1205554553 642226001(RCA-SOIL-16-B) Sample Duplicate (DUP) 1205554554 642226001(RCA-SOIL-16-B) Matrix Spike (MS) 1205554555 Laboratory Control Sample (LCS)
The samples in this SDG were analyzed on an "as received" basis.
Data Summary:
All sample data provided in this report met the acceptance criteria specified in the analytical methods and procedures for initial calibration, continuing calibration, instrument controls and process controls where applicable, with the following exceptions.
Quality Control (QC) Information RDL Met Samples (See Below) did not meet the detection limits due to the small sample aliquots used. The aliquots were reduced due to the matrix of the samples.
Sample Analyte Value 1205554552 (MB)
Carbon-14 Result 0.168 < MDA 0.617 > RDL 0.0284 pCi/g 1205554553 (RCA-SOIL-16-BDUP) Carbon-14 Result 0.184 < MDA 0.635 > RDL 0.0284 pCi/g 642226001 (RCA-SOIL-16-B)
Carbon-14 Result 0.131 < MDA 0.626 > RDL 0.0284 pCi/g 642226002 (RCA-SOIL-19-B)
Carbon-14 Result 0.111 < MDA 0.636 > RDL 0.0284 pCi/g 642226003 (RCA-SOIL-15-B)
Carbon-14 Result 0.287 < MDA 0.634 > RDL 0.0284 pCi/g 642226004 (RCA-SOIL-10-B)
Carbon-14 Result 0.253 < MDA 0.618 > RDL 0.0284 pCi/g 642226005 (RCA-SOIL-04-B)
Carbon-14 Result 0.272 < MDA 0.62 > RDL 0.0284 pCi/g Miscellaneous Information Additional Comments The matrix spike, 1205554554 (RCA-SOIL-16-BMS), aliquot was reduced to conserve sample volume.
Certification Statement Page 25 of 30 SDG: 642226
Where the analytical method has been performed under NELAP certification, the analysis has met all of the requirements of the NELAC standard unless otherwise noted in the analytical case narrative.
Page 26 of 30 SDG: 642226
Page 27 of 30 SDG: 642226 Page: ___ I of 2
[ij :ti I ~§.£~~~!g~ YRa8l
~y I Specrti~ d--?--(o GEL Laboratories, LLC Project#
2040 Savage Road GEL Quote#;
Charleston, SC 29407 COC Number '
11:
Chain of Custodv and Analvtical Reauest Phone: (843) 556-8171 PO Number:
GEL Work Order Number:
GEL Project Manager:
Fax: (843) 766-1178 Client Name: BHI Energy, Inc.
Phone # : 339-440- 1043 Sample Analysis Requested <5l (Fill in the number of containers for each test)
Project/Site Name: Oyster Creek I
Fax#
Should this
<- Preservative Type (6) sample be
£ Address: 741 Rouie 9, South, Forked River, NJ 0873 1 considered:
.e s
~
~
0 UJ N
+
Comments e
UJ 0
UJ UJ N
~
Collected By: Pa ul Leavitt Send Results To: C hris M essier
~ "'
co
+
UJ UJ UJ c.g:
~
co UJ CJ)
C")
Note: extra sam p le is
<D
~
co cw a~
~ =
li V
CX)
-<i V
N CX)
Q N
CC!
N
~
I'-:
~
req uired for sample
~ ime
-~ ~ :s.
e
~
i,-i st' r--:
~
~
- Date Collected Collected
~ -
=
V N
V V
00
~
Sample JD
.i a. a
".!!. N st' N
N i,-i C")
C")
V 0
c'ri s pecilic QC (M ilitary)
QC Field Swi,ple l2 :a " E E E
'9 N
N "l'
CJ)
CJ) 11 lf ~
~
- 6.
u
- For comrxmtes - 111d1cote.iart and stoo dote,t,me Codtn, Filtered I.II Mmrix <*>
~ :s 0
(.)
z
- l c'Ji (mon-dd-yy)
(hbmm) a:
C.
<(
(J (J
z (l_
(l_
I-RCA-SOIL-16-B I 0/1 212023 10:59 N
X X
X X
X X
X X
X X
Please count 10 RCA-SOlL-19-B I
1011212023 10:41 N
X
)(
X X
X X
X X
X X
values given above RCA-SOIL-15-B 1011212023 10 58 N
)(
X X
)(
X X
X X
X X
and lo the left representing RCA-SOLL-I 0-B I
10/12/2023 11:05 N
X
)(
)(
X X
X X
)(
)(
)(
1%DCGLLLD.
RCA-SOIL-04-B I
10/1212023 10:48 N
X
)(
)(
X X
)(
X X
X X
I I
I C~ain of Custody Signatures TAT Requested:
Normal: -- Rush: -:x __ Specify:
(Suhjecl to Surch:irgc)
Relinquished By (Signed)
Dale Timb Received by (signed)
Da1e Time Fax Results: r ] Yes rx l No A
I ~~,/
lo/Jq/:}3 10710 1 J-.L/1, J
/J -
/1) - /Cj. _:;i:Z, 1.'t/0 Select Deliverable: [XI C of A [ l QC Summary [ l level I
[ ] Level 2 I I Level 3
[ l Level 4 2 ( -I h J,; ll~.,IJ,,. -
le ~,~-:)~ 12--v<
2 C' \..
J I
A I ?\L, J,,.
Addirio11a/ Remarks:
3
(
3 ll~ etr1~~
I'-'/ /' 93, For Lab Recei11i11g Use Only: Custody Seal Intact? [ ] Yes
[ ]No Cooler Temp:
oc
> For sample sMppi11g am/ delfrery details, see S4mp/e Receipt & Review form (SRR.)
Sample Co/lectio11 Time Zo11e ; [ ] Eastern
[ J Pacific
( ] Central
[ ] Mountain
[ ] Other:
I ) Cham of Custody Number
- Client Dctcnmned 2 ) QC Codes N
- Nonna! Sample. TB
- Trip Blank, FD - Field Duplicaie, Ell
- Equipment Blank. MS* Matrix Spike Sample. MSD
- Mamx Spike Duplicate Snmplc. G
- Grnb. C - Composite 3 ) field Filtered For liquid matnces. md1C3lC with a - V - for yes 1he sample was field filtered or - N - for sample W3S not field filtered 4 ) M;:Hnx Codes OWc Onnkmg Water, C\V* Groundwaicr, S '*Surface Water, \V\V-Wostc Water. \V* Water. M L* Misc Liquid. SO==Soil. SD=-Sedimcnt, S1..- Sludye. SS=Soild Waste, 0 1110 11. F'- F1hcr. p;;c\Vipe. U* Urinc. F'* Fccal, N.aNnsal 5 ) Sample,lnalysis Reques1ed Analytical mc1hod requcSled (1.e 8260B. 60101l/7HOA) :md number of contamers prondcd for each (1
- 81608 - 3. 60/08 7./70A - I)
- 6) Preservative Type HA - Hydrochloric Acid, NI
- N11ric Ac ct. SI-I
- Sulfuric Acid, AA
- Ascorbic Acid, HX
- Hexane.ST
- Sodium Thiosulfatc, lfno prcserva11ve is added
- leave field blank 7 l KNOWN OR POSSIBLE HAZARDS Characteristic Hazards I Listed Waste Other Please provide a11y additio11al details FL = Flammable/Ign itable LW= Listed Waste OT= Other I Unknown below regarding lta11dlillg a111Jlor disposal RCRA Metals I
CO = Corrosive (F.K.P and U-listed wastes.)
(i.e.: Higlt/10111 pl-I. asbestos, beryffium. irritants. other concems. (i.e.: Origin of sample(s), type As= Arsenic Hg= Mercury RE = Reactive Waste code(s):
misc. health ha=ards. etc.)
of site collected from. odd matrices. ere.)
==
Description:==
Cd = Cadmium Ag= Silver TSC A Rci:utatcd C r = Chromium MR= Misc. RCRA melals PC B = Polychlorinated Pb = Lead biphenyls I
I
Page 28 of 30 SDG: 642226 Page:
2 of 2
', l m~11 GEL Laboratories, LLC
~
Laboratories LLc Project#
2040 Savage Road GEL Quote#:
gal com Chemistry I Radiochemistry I Rad1ob1oassay I Spec,alty AoalyUcs Charleston, SC 29407 COC N umber <1>:
Chain of Custodv and Analvtical Reauest Phone: (843) 556-8171 PO Number:
GEL Work Order Number:
GEL Project A1a11ager:
Fax: (843) 766-1178 Client Name: BH I Energy, Inc.
Phone# : 339-440- 1043 Sample Analysis Requested <
5> (Fill in the number of containers for each test)
Project/Site Name: Oyster Creek I
Fax#
Should this
<- Preservative Type (6)
Address: 741 Route 9, South, Forked River, NJ 08f 31 sample be considered:
c w
N w
Comments Collected By: Paul Leavitt Send R esults To: Chris Messier a2:-
~
+
0 UJ
~
Note: extra sample is Q,
lo]
0 ex:>
co
+
CJ i-;
~
~
UJ
- Time
~.s
,0 N
l{')
N required for sample
~ ! :s
~
6i 0
0
~ -
II)
- For comnosites ~,~fil~,a~nd stop daiJ/ime
'Date Collected Collected
.i 0..a_
0
~
C
(")
ti'i
"<I' specific QC (Militnry)
QC Field Sample C
.Q N
l{')
<"i N
~ t ~
(l)
Code"' Filteredm Matrix<-'>
- -a ci
+/-.
(mm-dd-yy)
(hhmm) a:: >, * -
~ C.
f-a..
LL a..
RCA-SOIL-I6-B I
1011212023 10:59 N
X X
X X
Please count lo I
RCA-SOlL-I9-B
]011212023 10:41 N
X X
X X
values given above RCA-SOIL-I 5-B I 011212023 10:58 N
X X
X X
and to the left representing I
RCA-SOIL-I0-B 10/1212023 11 :05 N
X X
X X
1% DCGL LLD.
RCA-SOIL-04-B 10/1212023 10:48 N
X X
X X
I I
I I
C~ain of Custody Signatures TAT Requested:
Normal:
Rush:
X Specify:
(Subj cl*t to Surcharge)
Relinquished By (Signed)
Date Time Received by (si1aied)
Date Time Fax Results: [ l Yes
[X] No I
.1.
.~~
I0/1'1/) 3 10710 I ~ju
, M j}
Ju - 1q - :25 11/6 I
Select Deliverable: [X 1 C of A [ 1 QC Summary
[ ] level I f l Level 2 f ] Level 3 r 1 Level 4
-+h1u ;_:, ~~
J/) -Jej_;:i~ /Z'I<... \
.t.o-1 n~.hM~ JfJ)o/25 2
~ *-
Additional Remarks:
'(
I
\,
'-1~~
3 3
For Lub Receiving Use Only: Custody Seal Intact? [ ] Yes
[ ]No Cooler Temp:
oc l
Sample Col/ectio11 Time Zo11e : [ ] Eastern
[ ] Pacific [ J Central
[ J Mountain [ J Other:
> For sample shipping and delivery details, see Sample Receipt & Review form (SRR.)
I ) Chain of Custody Number= Client Determined J
2 ) QC Codes: N = Nom,al Sample, TB = Tnp Blank. FD
- Fi Id Duplicate. EB = Equipmen1 Blank. MS= Matrix Spike Sample, MSD = Matrix Spike Duplicate Sample, G = Grab, C = Composite 3 ) Field Filtered, For liquid matrices, indicate with a - Y - for J s 1hc sample was field filtered or - N - for sample was not field filtered.
4.) Ma1nx Codes. D\V=Drmkmg Water. G\V=Groundwater. S\: ll=Surface Water. \VW=Waste Water, \\\\'=Water. ML=Misc Liquid. SO=Soil, SD=Sediment. SL,.Sludge. SS=Solid Waste. O=Oil, F= Filter, P=Wipe. U""'Urine. F=Fecal, N=Nasal
- 5) Sample Analysis Requested: Analytical method requested (i.~. 82608. 60I0B/7470A) and number of containers provided for each (i.e. 8 1 60B
- 3, 60/0B 74 70A - I)
- 6) Preservative Type: HA = Hydrochlonc Acid. NI = Nitric Acib, SH = Sodium Hydroxide, SA = Sulfuric Acid. AA = Ascorbic Acid. HX = Hexane. ST =- Sodium Thiosulfate, Ifno preservative is added = leave field blank 7.) KNOWN OR POSSIBLE HAZARDS Characteristic Hazards I Listed Waste I
I Other I
Please provide auy additional details FL= Flammable/Ignitable LW= Listed Waste OT= Other I Unknown below regarding J,a11dli11g a11dlor disposal RCRA Metals I
CO = Corrosive (F. K, P and U-listed wastes.)
(i.e.: High/low pH. asbestos, be1ylli11m, irritants, other concems. (i.e.: Origin ofsample(s), type As= Arsenic H g= Mercury RE = Reactive Waste code(s):
misc. heollh ha=ards, etc.)
of site collectedfi-0111, odd ma/rices. etc.)
Ba = Barium Se= Selenium Descriptio11:
Cd =Cadmium Ag= Silver TSCA Re!!ulatcd Cr = Chromium MR= Misc. RCRA metals PCB = Polychlorinated Pb = Lead biphenyls I
Page 29 of 30 SDG: 642226 lml!I J Laboratories LLC Client:
Date Received: 0 Circle Applkoble:
FedEx Ground UPS Field Services Courier Other Carrier and Tracking Number Suspected Hamrd Information
- ! l *If Net Counts> IOOcpm on s11mp]es not marked "radioactive", contact lhe Radiation Safety Group for further investigntion.
A)Shl ed as a DOT Hazardous?
B) Did the client designate the: samples are to be received as radioactive?
C) Did the RSO dassify lhe sam~es 11&
radioactive?
D) Old the client desi ate sam Jes are haznnlous?
E) Did the RSO identif ossible hazards?
Snmple Receipt C:ritedn Shipping containers received intact and sooled?
2 Chain of custody documents included with shipment?
3 Samples requiring cold preservation within (0 < 6 de. C)?*
4 Daily check pe1formed and passed on IR temperature gun?
5 Sample containers intact and sealed?
6 Samples requiring chemical preservation at proper pH?
7 Do any samples require Volatile Analysis?
8 Samples received within holding time?
9 Sample ID's on COC match ID's on bottles?
12 Arc sample containers identifiable as GEL rovided b use ofGELlabels? L 13 COC form is properly signed in
__________ -~ rclinquishe.d/n::ceived.scctions'1-----. -
Comments (Use Continuation Forni if needed):
Haz.ard Class Shipped:
UN#:
IfUN2910, Is the Radioactive Shipment Survey Compliant? YeL-No_
RCRA Asbestos Beryllhun Other:
CmnmenWQunliOcl's (Required for Non-Conforming Items)
Cil'cle Applicnblc:
Senls broken Damaged comainer Leaking container Olhcl' (desci*ibc)
Circle Applicable:
Clicm contacted am! pl'Ovidcd COC COC created upon receipt Preservation Method: Wet lee Ice Packs Dry ice on Olher:
- all temperatures are recorded in Celsius Temperature Device Scrla1 #:cl0R,c*'e'~----
Scco11daryTempemturc Device Serial# (If Applicable):
Circle Applicable:
Seals broken Damaged confllincr Leaking container Other (descl'ilie)
Sample 10'3 and Container.< Affected:
If Prcsciw!lon added, Lotil:
TEMP:;~--"'---
fYes, are Encores or Soil Kits present for solids? Yes_ No_ NA __ (Ifyes, take to VOA Freezer)
Do liquid VOA vials conlai11 acid presc1vation? Yes_ No_ NA_(Ifunknown, select No)
Arc liquid VOA vials f1ee ofheadspoce? Yes_ No_ NA __
ID's and tests affected:
!D's and containers affected:
Circle Applicable: No dates on containers No limes on conlainern COC missing info Other (describe)
Circle Applicable: No container count on COC Other (describe)
Gl-CHL-SA-001 Rev 7
State Certification Alabama Alaska Alaska Drinking Water Arkansas CLIA California Colorado Connecticut DoD ELAP/ ISO17025 A2LA Florida NELAP Foreign Soils Permit Georgia Georgia SDWA Hawaii Idaho Illinois NELAP Indiana Kansas NELAP Kentucky SDWA Kentucky Wastewater Louisiana Drinking Water Louisiana NELAP Maine Maryland Massachusetts Massachusetts PFAS Approv Michigan Mississippi Nebraska Nevada New Hampshire NELAP New Jersey NELAP New Mexico New York NELAP North Carolina North Carolina SDWA North Dakota Oklahoma Pennsylvania NELAP Puerto Rico S. Carolina Radiochem Sanitation Districts of L South Carolina Chemistry Tennessee Texas NELAP Utah NELAP Vermont Virginia NELAP Washington 42200 17-018 SC00012 88-00651 42D0904046 2940 SC00012 PH-0169 2567.01 E87156 P330-15-00283, P330-15-00253 SC00012 967 SC00012 SC00012 200029 C-SC-01 E-10332 KY90129 KY90129 LA024 03046 (AI33904) 2023019 270 M-SC012 Letter 9976 SC00012 NE-OS-26-13 SC000122024-04 2054 SC002 SC00012 11501 233 45709 R-158 2023-152 68-00485 SC00012 10120002 9255651 10120001 TN 02934 T104704235-23-21 SC000122023-38 VT87156 460202 C780 List of current GEL Certifications as of 09 November 2023 Page 30 of 30 SDG: 642226