Letter Sequence Meeting |
---|
|
|
MONTHYEARML23278A0262023-10-0505 October 2023 Presubmittal Teleconference with Wolf Creek Nuclear Operating Corporation Regarding a Planned License Amendment Request for Wolf Creek Generating Station, Unit 1 Project stage: Meeting ML23275A1712023-10-16016 October 2023 October 16, 2023, Licensee Pre-submittal Meeting Slides - License Amendment Request to Revise Technical Specifications to Adopt Risk-Informed Completion Times TSTF-505-A, Revision 2 for Wolf Creek Generating Station Project stage: Meeting ML23303A2182023-11-0606 November 2023 Summary of October 16, 2023, Pre-Submittal Teleconference with Wolf Creek Nuclear Operating Corporation Regarding a License Amendment Request to Adopt TSTF-505 for Wolf Creek Generating Station, Unit 1 Project stage: Meeting 2023-10-05
[Table View] |
|
---|
Category:Meeting Summary
MONTHYEARML23303A2182023-11-0606 November 2023 Summary of October 16, 2023, Pre-Submittal Teleconference with Wolf Creek Nuclear Operating Corporation Regarding a License Amendment Request to Adopt TSTF-505 for Wolf Creek Generating Station, Unit 1 ML22147A0932022-06-0606 June 2022 2021 Annual Assessment Public Meeting Summary ML22011A0862022-01-11011 January 2022 Summary of January 10, 2022, Pre-Submittal Teleconference with Wolf Creek Nuclear Operating Corporation Regarding a License Amendment Request to Use Portable Lighting for Wolf Creek Generating Station, Unit 1 ML21333A1312021-12-0707 December 2021 Summary of Meeting with Wolf Creek Nuclear Operating Corporation Diesel Generator Completion Time License Amendment Request for Wolf Creek Generating Station ML21200A1102021-07-21021 July 2021 Summary of July 13, 2021, Pre-Submittal Teleconference with Wolf Creek Nuclear Operating Corporation Regarding a Temporary Emergency Preparedness Exercise Exemption Request ML21140A3892021-05-24024 May 2021 Riv Column 1 EOC 2020 Public Meeting Summary ML21127A1322021-05-11011 May 2021 Summary of April 16, 2021, Conference Call with Representatives of Wolf Creek Generating Station Regarding the Spring 2021 Steam Generator Tube Inspections ML20332A0422020-12-0101 December 2020 Summary of November 19, 2020, Pre-Submittal Teleconference with Wolf Creek Nuclear Operating Corporation an Emergency Response Organization Staffing License Amendment Request ML20332A0462020-11-30030 November 2020 Summary of November 18, 2020, Pre-Submittal Teleconference with Wolf Creek Nuclear Operating Corporation a Risk-Informed Generic Safety Issue (GSI)-191 License Amendment Request ML20189A2832020-07-0707 July 2020 Summary of Region IV Annual Assessment Public Meeting ML19143A4182019-05-21021 May 2019 Summary of Public Meeting with Wolf Creek Nuclear Operation Corporation ML19140A4742019-05-20020 May 2019 Closed Meeting with Wolf Creek Nuclear Operating Corporation to Conduct a Mediation Session Regarding Falsification of Documentation Associated with Licensee Maintenance Activities ML18313A2542018-11-16016 November 2018 Summary of Public Meeting with Wolf Creek Nuclear Operating Corporation Regarding License Amendment Request for Transition to Westinghouse Core Design and Safety Analyses for Wolf Creek Generating Station ML17276B4892017-10-23023 October 2017 9/25/17 Summary of Public Meeting with Wolf Creek Nuclear Operating Corporation Regarding the Proposed LAR for Change in Emergency Plan Staff Augmentation Response Times for Wolf Creek Generating Station (CAC No. MG0174; EPID L-2017-LRM-001 ML16271A4822016-09-27027 September 2016 Summary of Regulatory Conference to Discuss Safety Significance of Wolf Creek Generating Station Emergency Generator Excitation Diode Apparent Violation ML16250A1652016-09-0909 September 2016 8/25/16 Summary of Preapplication Meeting with Wolf Creek Nuclear Operating Corporation to Discuss Amendment Request to Transition to Westinghouse Analyses Methodologies and Alternate Source Term at Wolf Creek Generating Station ML16243A5132016-09-0101 September 2016 Summary of August 25, 2016, Public Meeting with Wolf Creek Nuclear Operating Corporation and Amerenue Regarding a Proposed Application for a New Technical Specification for the Class 1E Electrical Equipment Air Conditioning System (MF8118 a ML16106A1742016-04-22022 April 2016 Summary of Meeting with Wolf Creek Nuclear Operating Company to Discuss the Generic Safety Issue (GSI)-191 Testing Plan/Fiber Penetration and Head Loss Testing Approach for Wolf Creek Generating Station ML15182A0952015-06-30030 June 2015 Summary of Annual Assessment Meeting with Wolf Creek Nuclear Operating Corporation (WCNOC) Regarding Wolf Creek Generating Station 2014 Performance ML14188C4812014-07-0707 July 2014 Summary of Annual Assessment Meeting with Wolf Creek Generating Station ML14134A1842014-05-14014 May 2014 Summary of Public Meeting to Discuss an Apparent Violation Identified at Wolf Creek Generating Station ML14038A3852014-02-0606 February 2014 1/22/2014 - Summary of Public Meeting to Discuss Corrective Actions Implemented to Address the Chilling Effect Letter ML13221A2132013-08-12012 August 2013 8/7/2013 - Summary of Preapplication Meeting with Wolf Creek Nuclear Operating Corporation to Discuss Long-Term Corrective Actions for Water Hammer Events in the Essential Service Water System at Wolf Creek ML13221A2152013-08-12012 August 2013 7/30/2013 - Summary of Preapplication Meeting with Wolf Creek Nuclear Operating Company to Discuss Proposed Transition to Westinghouse Methodologies for Core Design and Non-LOCA Safety Analyses at Wolf Creek Generating Station ML13121A4892013-05-0101 May 2013 End of Cycle Meeting Summary 4-18-13 ML13077A0732013-04-0101 April 2013 Summary of 2/28/13 and 3/11/13 Conference Calls with Licensee and Its Contractors Ongoing Steam Generator Tube Inspection Activities During Refueling Outage 19 ML12355A6922012-12-20020 December 2012 Summary of Public Meeting with Wolf Creek Nuclear Operating Corp Re Improved Station Performance ML12276A2652012-11-0101 November 2012 Meeting Summary with Wolf Creek Nuclear Operating Corporation to Discuss Transition from Current to NRC-Approved Westinghouse Methodologies for Performing the Core Design and Non-LOCA Safety Analysis at Wolf Creek ML12191A1742012-07-0909 July 2012 6/25/2012 Summary of Public Meeting with Wolf Creek Nuclear Operating Corporation ML12191A1462012-07-0606 July 2012 6/26/2012 - Summary of Public Meeting to Discuss Performance of Wolf Creek Nuclear Operating Corporation ML13246A3802012-05-0808 May 2012 Email from M. King, NRR on Ioeb Clearinghouse Screening Summary for Tuesday, May 8, 2012 ML1207601012012-03-16016 March 2012 Summary of Public Meeting with Wolf Creek Nuclear Operating Corporation ML13246A3782012-02-16016 February 2012 Email from M. King, NRR on Ioeb Clearinghouse Screening Summary for Thursday, February 16, 2012 ML13246A3772012-01-31031 January 2012 Email from M. King, NRR on Ioeb Clearinghouse Screening Summary for Tuesday, January 31, 2012 ML13246A3762012-01-23023 January 2012 Email from M. King, NRR on Ioeb Clearinghouse Screening Summary for Monday, January 23, 2012 ML12011A1012012-01-19019 January 2012 Summary of Meeting with NEI and to Address Di&C Issues ML13246A3742012-01-17017 January 2012 Email from M. King, NRR on Ioeb Clearinghouse Screening Summary for Tuesday, January 17, 2012 ML1110104292011-04-11011 April 2011 Summary of Annual Performance Assessment Meeting with Wolf Creek Nuclear Operating Corporation to Discuss Wolf Creek Generating Station Performance for the NRC Inspection Period Ending December 31, 2010 ML1024506282010-09-0202 September 2010 Summary of Public Meeting with Wolf Creek Nuclear Operating Corporation ML1013404892010-05-14014 May 2010 Summary of Annual Performance Assessment Meeting with Wolf Creek Nuclear Operating Corporation to Discuss the Wolf Creek Generating Station Performance for the NRC Inspection Period from January 1 Through December 31, 2009 ML0933805662009-12-17017 December 2009 Summary of Meeting with Union Electric Company and Wolf Creek Nuclear Operating Company to Discuss NRC Requests for Additional Information on Generic Letter 2004-02 Sent 7/31/2009 and 8/27/2009, Respectively ML0933702032009-12-0303 December 2009 Summary of Public Meeting for Wolf Creek Generating Station ML0924607142009-09-28028 September 2009 Summary of Meeting with Union Electric Co., and Wolf Creek, to Discuss Draft Requests for Additional Information on GL 2004-02 for Callaway, Unit 1, and Wolf Creek ML0911205282009-04-21021 April 2009 Summary of Annual Performance Assessment Meeting for Wolf Creek Generating Station ML0902102062009-01-23023 January 2009 Summary of Meeting with Wolf Creek Nuclear Operating Corporation to Discuss Changes to Post Fire Shutdown Unresolved Items Analysis Methods Pre-Application for Wolf Creek Generating Station ML0829607972008-10-22022 October 2008 Summary of Meeting with Wolf Creek, Discussing Several Initiatives Being Implemented to Improve Plant Performance ML0817706682008-06-25025 June 2008 Summary of Meeting with Wolf Creek Nuclear Operating Corporation to Discuss Several Initiatives That Were Being Implemented to Improve Plant Performance at Wolf Creek ML0813606472008-06-10010 June 2008 05/01/2008-Summary of Public Meeting on Safety Evaluation Report with Open Items Regarding the Wolf Creek Generating Station License Renewal Review ML0812803052008-05-0808 May 2008 Summary of Conference Call with Wolf Creek Nuclear Operating Corporation Spring 2008 Steam Generator Tube Inspections During Refueling Outage 16 at Wolf Creek Generating Station ML0807904692008-04-10010 April 2008 Summary of Teleconference with Wolf Creek Nuclear Operating Corporation, Ameren Union Electric Company for Callaway Plant, and Performance Contracting, Inc. Containment Sump Head Loss Testing 2023-11-06
[Table view]Some use of "" in your query was not closed by a matching "". |
Text
November 6, 2023 LICENSEE: Wolf Creek Nuclear Operating Corporation FACILITY: Wolf Creek Generating Station, Unit 1
SUBJECT:
SUMMARY
OF OCTOBER 16, 2023, PRE-SUBMITTAL TELECONFERENCE WITH WOLF CREEK NUCLEAR OPERATING CORPORATION REGARDING A LICENSE AMENDMENT REQUEST TO ADOPT TSTF-505 FOR WOLF CREEK GENERATING STATION, UNIT 1 (EPID L-2023-LRM-0076)
On October 16, 2023, an Observation public teleconference was held between the U.S. Nuclear Regulatory Commission (NRC) and representatives of the Wolf Creek Nuclear Operating Corporation (the licensee). The purpose of the pre-submittal teleconference was to discuss preliminary information regarding the licensees planned submission of a license amendment request (LAR) for Wolf Creek Generating Station, Unit 1 (Wolf Creek), to adopt Technical Specifications Task Force (TSTF) Traveler TSTF-505, Revision 2, Provide Risk-Informed Extended Completion Times - RITSTF [Risk-Informed TSTF] Initiative 4b (Agencywide Documents Access and Management System (ADAMS) Accession No. ML18183A493). The NRC issued a model safety evaluation (SE) approving TSTF-505, Revision 2, on November 21, 2018 (ML18269A041). The licensees presentation slides are available in ADAMS at Accession No. ML23275A171. The meeting notice and agenda dated October 5, 2023, are available in ADAMS at Accession No. ML23278A026. A list of attendees is enclosed.
During the meeting, the licensee indicated that the proposed risk-informed completion time (RICT) methodology would be based on Nuclear Energy Institute (NEI) 06-09, Risk-Informed Technical Specifications Initiative 4b, Risk-Managed Technical Specifications (RMTS)
Guidelines. The NRC staff issued a model SE approving NEI 06-09 on May 17, 2007 (ML071200238). The licensee indicated that the proposed RICT would apply to 50 Wolf Creek technical specification (TS) required actions. The RICT would not apply to shutdown conditions because the licensee has not developed a shutdown probabilistic risk assessment (PRA) model for Wolf Creek. The proposed LAR would also include adoption of TSTF-439, Revision 2, Eliminate Second Completion Times Limiting Time From Discovery of Failure to Meet an LCO
[Limiting Condition for Operation]. The NRC issued a model SE approving TSTF-439, Revision 2, on January 11, 2006 (ML060120272). The licensee indicated that TSTF-439 affected 10 Wolf Creek TS required actions.
The licensee has assessed its PRA model against the American Society of Mechanical Engineers (ASME)/American Nuclear Society (ANS) PRA Standard RA-Sa-2009 and Regulatory Guide 1.200, Revision 2, An Approach for Determining the Technical Adequacy of Probabilistic Risk Assessment Results for Risk-Informed Activities, dated March 2009 (ML090410014). The licensee indicated that its seismic-induced fire PRA was under peer review and would be addressed in the LAR. The licensees goal would be no open facts and observations (F&O) and any remaining F&Os would be dispositioned in the LAR.
The NRC staff discussed the importance of lessons learned from past precedence, for example, resolving the issue of joint human error probability. The NRC staff also discussed the purpose of the NRC staffs regulatory audit. The NRC staff noted that the Wolf Creek TSFT-505 audit would be late compared with a typical review schedule, because the licensee could support the audit after the completion of the spring 2024 outage. The NRC staff commented that the licensee should consider supplementing its LAR after the audit instead of waiting for the NRC staffs request for additional information, thus saving time in the review process.
The licensee indicated that it planned to submit the TSTF-505 LAR in November 2023.
No regulatory decisions were made at the meeting.
Please direct any inquiries to me at 301-415-3168 or by email at Samson.Lee@nrc.gov.
/RA/
Samson S. Lee, Project Manager Plant Licensing Branch IV Division of Operating Reactor Licensing Office of Nuclear Reactor Regulation Docket No. 50-482
Enclosure:
List of Attendees cc: Listserv
LIST OF ATTENDEES OCTOBER 16, 2023, PRE-SUBMITTAL TELECONFERENCE REGARDING TSTF-505, REVISION 2, PROVIDE RISK-INFORMED EXTENDED COMPLETIONS TIMES -
RITSTF [RISK-INFORMED TSTF] INITIATIVE 4b LICENSE AMENDMENT REQUEST WOLF CREEK NUCLEAR OPERATING CORPORATION WOLF CREEK GENERATING STATION, UNIT 1 U.S. Nuclear Regulatory Commission, Office of Nuclear Reactor Regulation Gurjendra Bedi -DEX,1 Mechanical Engineering and Inservice Testing Branch Edmund Kleeh - DEX, Electrical Engineering Branch Hang Vu - DEX, Instrumentation and Controls Branch Samson Lee - Division of Operating Reactor Licensing, Plant Licensing Branch IV Robert Pascarelli - Branch Chief, DRA,2 APLA3 Adrienne Brown - DRA, APLA Malcolm Patterson - DRA, APLA Naeem Iqbal - DRA, APLB4 Charles Moulton - DRA, APLB Steven Alferink - DRA, PRA Licensing Branch C Brian Wittick - Branch Chief, DSS,5 SCPB6 David Nold - DSS, SCPB Noushin Amini - DSS, SNSB7 Santosh Bhatt - DSS, SNSB Andrea Russell - DSS, STSB8 Khadijah West - DSS, STSB 1
Division of Engineering and External Hazards 2
Division of Risk Assessment 3
Probabilistic Risk Assessment (PRA) Licensing Branch A 4
PRA Licensing Branch B 5
Division of Safety Systems 6
Containment and Plant Systems Branch 7
Nuclear Systems Performance Branch 8
Technical Specifications Branch Enclosure
Wolf Creek Nuclear Operating Corporation Jaime McCoy - Site Vice President Mike Boyce - Vice President of Engineering Dustin Hamman - Director Nuclear and Regulatory Affairs Frank Galati - Senior Manager Nuclear Engineering Jeff Suter - Engineering Manager (Presenter)
David Vu - Lead Engineer Nuclear Engineering/PRA Lu Huang - Lead Engineer Nuclear Engineering/PRA Paul Nguyen - Nuclear Engineer Colby Thordsen - Licensing Engineer Jason Knust - Lead Engineer Licensing Nathan Lee - Lead Engineer Licensing/Acting Manager of Licensing Contractors to Wolf Creek Nuclear Operating Corporation Steve Wideman - Consultant to Wolf Creek Bruce Morgen - EPM Risk Services Casey Weiser - EPM Risk Services Carroll Trull - EPM Risk Services Travis Weber - EPM Risk Services Bill Victor - Excel Services
ML23303A215 (Package)
ML23278A026 (Meeting Notice)
ML23275A171 (Meeting Slides)
ML23303A218 (Meeting Summary) *concurrence by email NRC-001 OFFICE NRR/DORL/LPL4/PM NRR/DORL/LPL4/LA* NRR/DORL/LPL4/BC* NRR/DORL/LPL4/PM*
NAME SLee PBlechman JDixon-Herrity SLee DATE 10/30/2023 10/31/2023 11/6/2023 11/6/2023