ML23291A419
| ML23291A419 | |
| Person / Time | |
|---|---|
| Site: | Susquehanna |
| Issue date: | 10/12/2023 |
| From: | Susquehanna |
| To: | Office of Nuclear Reactor Regulation |
| Shared Package | |
| ML23291A105 | List:
|
| References | |
| PLA-8081 | |
| Download: ML23291A419 (1) | |
Text
SSES-FSAR Text Rev. 64 FSAR Rev. 70 7.5-1 7.5 SAFETY-RELATED DISPLAY INSTRUMENTATION (SRDI)
Safety-Related Display Instrumentation (SRDI) required for safe functioning of the plant during normal operating and accident conditions is incorporated in a control room complex named the Advanced Control Room (ACR). It is necessary to consider the ACR as a whole to verify conformance to the requirements.
The ACR is a complex of major components, provided with the NSSS, for monitoring and controlling two units and providing safety functions. The entire complex consists of the Power Generation Control Complex (PGCC) in the upper relay room at the 754/ft. 0/in. level and the lower relay room at the 698/ft. 0/in. level, the Plant Integrated Computer System at the 698/ft. 0/in. level and the plant-operator interface at the 729/ft. 0/in. level.
a)
PGCC The PGCC provides support and interconnections to the systems panels of the upper and lower relay rooms and the computer room of the ACR complex. The plant-operator interface noted below is not mounted on PGCC, however, all other principles of the PGCC concept, e.g., separation, are used.
b)
Plant-Operator Interface Major components are in the main control room arranged as shown on Dwg. A-105, Sh. 1 and described on Figure 7.7-13A and include the following:
Unit Operating Benchboard Panel (C651/H12-P680) - houses controls, hardwired displays, the control rod position display and process displays which are computer generated from the Plant Integrated Computer System described briefly below and more completely in Section 7.7. The combination of displays on this panel and panel (C652/H12-P678),
Standby Information Panel, are arranged by system and are used for start up, normal operation, and shut down.
See Section 7.7 for a description of the Plant Integrated Computer System, in regard to the displays on all control room panels.
Standby Information Panel (C652/H12-P678) - houses hardwired indicators and recorders required to start up, run, and shut down the plant. It is a hardwired backup to the Plant Integrated Computer System.
Reactor Core Cooling System Benchboard (C601/H12-P601) - houses hardwired indicators, recorders, manual controls, and annunciators for ESF systems including containment atmosphere systems.
Unit Services Benchboard (C668/H12-P870) - houses hardwired indicators, recorders, annunciators and controls for unit BOP system's functions which do not require the operator's immediate attention during normal operation of the power plant. Functions on this panel have been determined to be long time response functions.
SSES-FSAR Text Rev. 64 FSAR Rev. 70 7.5-2 Plant Operating (Common Plant) Benchboard (C653/H12-P853) - houses hardwired indicators, recorders, controls and annunciators for systems common to both units. Manual controls for the diesel generators are located here. It also houses two displays connected to the Plant Integrated Computer System.
Unit Monitoring Console (C684/C92-P628) - provides the unit operator with sit down surveillance of the unit operating benchboard and access to the Plant Integrated Computer System.
Safety Parameter Display System/Plant Monitoring Console (C667) - provides sit down surveillance of both units and access to Plant Computer System displays and Plant Computer Functions as well as SPDS displays.
Panels which support the primary plant-operator interface are mounted in back rows of the main control room and on PGCC floor modules on floors above and below the main control room.
The annunciator system is a hardwired system which provides the operator with the alarm information required for unit operation, startup, and shutdown. This system is independent of the Plant Integrated Computer System, is not part of the SRDI, and is not Class 1E.
c)
Plant Integrated Computer System The Plant Integrated Computer System is primarily used for monitoring unit operation by generating graphic displays to display optimized information for operator surveillance. In addition, it is capable of generating other displays, making NSSS and BOP calculations, recording historical data, logging data, and performing off-line functions.
In addition to the NSSS calculational capabilities, a Reactor Data Analysis System (RDAS) is available to monitor core conditions. The RDAS will receive data from the Plant Integrated Computer System and will be capable of providing information to be displayed in the ACR. The Plant Integrated Computer System and RDAS are not part of the SRDI and are not Class 1E.
The Plant Integrated Computer System makes use of redundant computers for critical applications to maximize availability. As stated above, the information important to safety displayed by the Plant Integrated Computer System, is also displayed on hardwired indicators, recorders and alarm annunciators. Alarms in Plant Integrated Computer System displays are redundant to those provided by the hardwire annunciator system. While the operator makes primary use of the computer generated displays during normal operation, he is not dependent on computers or annunciators to operate the plant safely during startup, steady-state operation, or any design basis events.
Plant Integrated Computer System displays are designed to be used on the ACR benchboard panels, and are organized by system and plant mode of operation. The operator can select displays on most benchboard displays, appropriate to each benchboard area and plant mode of operation, with one select operation from a control position on each benchboard associated with that display. The operator can individually call up any available display on any display for the Plant Integrated Computer System.
SSES-FSAR Text Rev. 64 FSAR Rev. 70 7.5-3 7.5.1a Description This section describes the hardwired displays noted above in the ACR description. It does not describe computer generated displays. SRDI is described on the basis of NSSS and non-NSSS responsibility by system. NSSS and non-NSSS share panels and use the same types of instruments which were provided with the NSSS. (Some of the instrumentation described below may be non-SRDI, and is provided to give a more complete picture of the totality of information available to the Operator in the ACR. Reference should be made to Tables 7.5-1 through 7.5-7a to determine which instrumentation is part of the SRDI.)
Therefore, control room panels and instruments, unless otherwise noted, use NSSS qualification and separation techniques.
As noted in Section 7.1, sections with an "a" describe NSSS and "b" denote non-NSSS.
7.5.1a.1 General Description of NSSS Safety-Related Display Instrumentation This section describes the instrumentation which provides information to the operator to enable him to perform required safety functions.
The Safety-Related Display Instrumentation is listed in Table 7.5-1. It tabulates SRDI equipment which may be illustrated on the various system figures located in Sections 7.2, 7.3, 7.4, and 7.6.
The instrumentation and ranges shown in Tables 7.5-1 through 7.5-7a are selected on the basis of giving the reactor operator information to perform manual safety functions and yet the capability to track process variables pertinent to safety during expected operational perturbations.
Separation of redundant display instrumentation and electrical isolation of redundant sensors and channels is illustrated in the Elementary Diagrams, Electrical Schematics and the Loop Diagrams associated with the individual circuits. Additional information on the redundancy of monitored variables and component sensors and channels can be found in Design Specifications, P&ID and Design Basis Documents.
7.5.1a.2 Normal Operation The information channel ranges and hardwired indicators and recorders were selected on the basis of giving the reactor operator the necessary information to perform all the normal plant startup, steady-state maneuvers, with the required precision and to be able to track all the process variables pertinent to safety during expected operational perturbations.
7.5.1a.3 Abnormal Transient Occurrences The ranges of indicators and recorders provide adequate information for all abnormal transient events.
7.5.1a.4 Accident Conditions The DBA-LOCA is the most extreme postulated operational action event. Adequate instrumentation is provided from the standpoint of operator action, information, and event tracking requirements, in order to cover all other design-basis events or incident requirements.
SSES-FSAR Text Rev. 64 FSAR Rev. 70 7.5-4 7.5.1a.4.1 Initial Accident Event The design basis of all ESF to mitigate the accident event condition takes into consideration that no operator action or assistance is assumed for the first twenty minutes of the event with one exception. The only operator action assumed in the Section 6.3 ECCS analysis is that a RHR heat exchanger is placed in service within 20 minutes into the accident. This requirement, therefore, makes it mandatory that all protective action necessary in the first twenty minutes be "automatic.
Therefore, although continuous tracking of process variables is available, no operator action based on them is required.
7.5.1a.4.2 Post-Accident Tracking No operator action (and, therefore, post-accident information) is required for at least twenty minutes following an accident although the various monitoring devices are continuously tracking and indicating important parameter information and displaying it to the operator as well as recording appropriate data.
The DBA-LOCA serves as the envelope accident sequence event to provide and demonstrate the plant's post-accident tracking capabilities. All other accidents have less severe and limiting tracking requirements. Refer to Chapter 15 "Accident Analysis."
The following process instrumentation provides information to the operator after a DBA-LOCA to monitor reactor parameters.
7.5.1a.4.2.1 Reactor Water Level (1)
Two independent wide range water level signals are transmitted to and recorded on two separate recorders. The differential pressure transmitters have one side connected to a condensing chamber reference leg and the other side connected directly to a vessel nozzle for the variable leg. The water level system is uncompensated for variation in reactor water density and is calibrated to be most accurate at operational pressure and temperature conditions at which it is used. The range of the recorded level is from the top of the feedwater control range (just above the high level turbine trip point) down to a point near the top of the active fuel. The power sources for the two channels are separate, divisionalized Class 1E buses.
(2)
Two fuel zone water level signals are transmitted from two independent differential pressure transmitters. One signal goes to a fuel zone water level indicator and the other water level signal goes to a fuel zone water level recorder. The differential pressure transmitters have one side connected to a condensing chamber reference leg and the other side connected directly to the bottom tap of a calibrated jet pump for the variable leg. The fuel zone water level system is uncompensated for variation in reactor water density and is calibrated to be most accurate at saturated atmospheric conditions at which it is used. The level range is from over the top of the active fuel to near the bottom of the active fuel. The ranges of the wide range level and the fuel zone level will overlap. Power sources are as stated in the previous paragraph.
(3)
Two extended range water level signals are transmitted from two independent differential pressure transmitters. Each level transmitter is connected to a dual indicator which displays both wide and extended range. The differential transmitter reference leg is tubed to a condensing chamber and the variable leg to vessel nozzle. The water level system is
SSES-FSAR Text Rev. 64 FSAR Rev. 70 7.5-5 uncompensated for variation in reactor water density and is calibrated to be most accurate at operational pressure and temperature conditions at which it is used. The level range is from over the top of the steam lines to near the top of the active fuel. The range of the extended level will overlap the wide range level. Power sources are as stated in the first paragraph.
(4)
Non-condensible gases may exist in the reference legs of the nuclear boiler instrumentation system. During a rapid or normal depressurization of the reactor, these gases may come out of solution displacing water from the reference legs and leading to false high level indications. The non-condensible gases are believed to be H2 and O2 generated by the dissociation of H2O from neutron flux. (Reference NRC Generic Letter 92-04 and Information Notice 93-27.) All three of the following conditions must exist in order for these level indication errors to occur:
- 1.
An elevated level of non-condensible gases in the condensing chamber,
- 2.
A migration of the gases into the reference leg, and
- 3.
A Reactor Pressure Vessel depressurization (below 450 psig).
Non-condensible gases will exist in the condensing chamber during normal operations. Vessel depressurizations will inevitably occur during the life of the plant and migration of gases may be undetectable. To prevent level indication errors from occurring, the concentration of non-condensibles in the reference legs must be kept below 150 ppmv. This value has been determined to be acceptable by Boiling Water Reactor Owner's Group (BWROG) testing.
Vent lines from condensing chambers XY-B21-1/2D004A and XY-B21-1/2D004B to the variable leg piping from vessel nozzles N11A and N11B and from condensing chambers XY-B21-1/2D002 and XY-1/24202 to the RPV head vent line are installed to prevent non-condensible gas build-up in the reference leg by providing a path to sweep away any gases which may build-up in the chamber. This eliminates condition 1 above, by assuming that the non-condensible gases never build-up in the steam space of the condensing chamber.
7.5.1a.4.2.2 Reactor Pressure Three independent reactor pressure signals (ranged 0 to 1500 psig) are transmitted and indicated on control room panels. Two signals are recorded on two separate recorders. Power sources are as stated in Subsection 7.5.1a.4.2.1.
7.5.1a.4.2.3 Reactor Shutdown, Isolation, and Core Cooling Indication 7.5.1a.4.2.3.1 Reactor Operator Information and Observations The information furnished to the main control room operator permits him to assess reactor shutdown, isolation, and availability of emergency core cooling following the postulated accident.
Some of the information listed below is provided by non-SRDI equipment.
(1)
Operator verification that reactor shutdown has occurred may be made by observing the following indications:
SSES-FSAR Text Rev. 64 FSAR Rev. 70 7.5-6
- a.
Control rod status lamps indicating each rod fully inserted. The power source is one of the instrument AC buses.
- b.
Control rod scram pilot valve indicating lamps which are illuminated when the control rod scram pilot valves are energized. The power source is an RPS MG Set.
- c.
Neutron monitoring power range channels and recorders downscale. The power sources are RPS MG sets.
- d.
Annunciators for reactor protection system variables and trip logic in the tripped state. The power source is dc from a plant battery.
(2)
The reactor operator may verify reactor isolation by observing the following indications:
- a.
Isolation valve position lamps indicating valve closure. The power source is the same as for the associated valve motor-operator.
- b.
Main steamline flow indication downscale. The power source is instrument AC.
- c.
Annunciators for the containment and reactor vessel isolation system variables and trip logic in the tripped state. The power source is DC from one or more plant batteries.
(3)
Operation of the emergency core cooling and the RCIC system following the accident may be verified by observing the following indications:
- a.
Annunciators for HPCI, CS, RHR, ADS, RCIC sensor initiation logic trips. The power source is DC from a plant battery.
- b.
Flow and pressure indications for each emergency core cooling system. The power sources are independent and from the same standby buses as the driven equipment.
- c.
RCIC isolation valve position lights indicating to open valves. The power source is from the same bus as the valve motive power.
- d.
Injection valve position lights indicating either open or closed valves. The power source is the same as the valve motor.
- e.
Relief valve initiation circuit status by open or closed indicator lamps. The power source is the same as for the pilot solenoid.
- f.
Relief valve position may be inferred from reactor pressure indications. The power source is instrument AC from the standby AC systems.
- g.
Relief valve discharge pipe temperature monitors. The power source is instrument AC.
- h.
Relief valve position is indicated by acoustic monitors (see Subsection 18.1.24.3).
SSES-FSAR Text Rev. 64 FSAR Rev. 70 7.5-7 7.5.1a.4.2.3.2 System Operation Information-Display Equipment (1)
RCIC Two meters, one displaying RCIC discharge flow rate and one displaying RCIC pump discharge pressure, are located in the main control room.
(2)
HPCI Three meters, one displaying HPCI discharge flow rate and one displaying HPCI pump discharge pressure, and one displaying HPCI turbine steam pressure, are located in the main control room.
(3)
CS System Two meters displaying CS flow rate are located in the main control room.
(4)
RHR One meter displaying RHR flow rate for each of the two RHR loops, and one meter displaying RHR service water flow rate for each of the two service water loops are located in the main control room.
(5)
Miscellaneous In addition to the above displays, the following also provide information to enable the reactor operator in the main control room to perform post-accident safety functions:
- a.
Control rod status lamps
- b.
Scram pilot valve status lamps
- c.
Neutron flux level meters.
7.5.1a.4.2.3.3 System Operation Information-Display Equipment Qualification Environmental Qualification of Safety-Related Display Instrumentation is addressed in the Susquehanna SES Environmental Qualification Program for Class 1E Equipment. Additionally, some of the safety-related display instrumentation help to satisfy our commitment to Regulatory Guide 1.97, Rev. 2, and meet the additional requirements as committed to for that regulatory guide.
7.5.1a.4.2.4 Containment Indications Refer to Table 7.5-3.
7.5.1b Description of non-NSSS Safety-Related Displays Non-NSSS safety-related displays provide the operator with information to monitor certain containment conditions, non-NSSS ESF systems, and auxiliary support systems.
Description is provided in the form of Tables 7.5-2 through 7.5-7, which list details of the displays by ESF systems as previously listed.
SSES-FSAR Text Rev. 64 FSAR Rev. 70 7.5-8 7.5.1b.1 Containment Isolation Refer to Table 6.2-12 for list of isolation valves. All containment isolation valves have status indication lights on control room panels (C651/H12-P680) or (C601/H12-P601).
7.5.1b.2 Combustible Gas Control Refer to Table 7.5-3 for list of displays for containment atmosphere monitoring.
7.5.1b.3 Primary Containment Vacuum Relief Status indication only is provided for test operation described in Subsection 7.3.1.1b.3.
Containment pressures are noted in Table 7.5-3.
7.5.1b.4 Standby Gas Treatment, RX Building Recirculation and Isolation System These systems are listed in Table 7.5-4.
7.5.1b.5 Habitability Systems These systems are listed in Table 7.5-2.
7.5.1b.6 Auxiliary Support Systems Emergency service water system displays are listed in Table 7.5-5. RHR service water system displays are listed in Table 7.5-6. Containment instrument gas system displays are listed in Table 7.5-7.
7.5.1b.7 Bypass Indication System This system is established and used during normal reactor operations to control planned actions whose manual initiation would effectively disable any safety function.
The design complies with Regulatory Guide 1.47 (May 1973).
7.5.1b.7.1 System Description The primary control method is administrative control which is exercised by the unit control room operator; however, these administrative controls are supplemented by an automated Bypass Indication System (BIS). Restricted access to various in-plant areas is also used to supplement the administrative control.
The BIS indicators annunciate on the Reactor Core Cooling System benchboard in the control room, automatically, at the system level, indicates the bypass or deliberately induced inoperability of a safety-related system.
The BIS is provided with the capability for manual initiation of each system-level indicator. This manual-entry method is used to cover system components that have not been provided with automatic BIS input capability.
SSES-FSAR Text Rev. 64 FSAR Rev. 70 7.5-9 The Bypass Indication System for non-NSSS Systems consists of the following:
a)
Two indicator lamp boxes each consisting of 4x6 array of lights and located in the control room on the Reactor Core Cooling System benchboard. Each window, provided with dual lamps and an integral pushbutton for lamp test, will indicate a system-level bypass.
b)
Two annunciator windows, located above the lamp box assemblies will alert the operator that a system-level bypass has occurred.
c)
The indication of the bypass status of components, systems, channels, and/or divisions is provided on a backrow panel in the main control room. This panel contains the hardware logic required to translate the combination of component bypasses that constitute system bypasses.
A manual control switch for each safety system enables the operator to indicate a system's inoperability whenever a component which is not included in the automatic indication system is deliberately bypassed.
The BIS and its logic can be tested by depressing test pushbuttons.
The following systems provide inputs to the Bypass Indication System:
Emergency Service Water System Diesel Generator Control System Diesel Generator Output System Diesel Generator Auxiliary System Control Room Habitability System Standby Gas Treatment System Battery Room Exhaust System RHR Service Water System Remote Shutdown Panel Containment Instrument Gas System Containment Isolation System Drywell Ventilation System Reactor Building Emergency Switchgear And Motor Control Center Cooling Control Structure HVAC Alternate Operation System Table 7.5-8 identifies the system and components of the automatic Bypass Indication System.
7.5.1b.8 Post-Accident Neutron Flux Monitoring System The post-accident neutron flux monitoring function is performed by the Average Power Range Monitoring System (APRM). This system is discussed in Section 7.6.1a.5.6.
The use of the conventional Nuclear Monitoring System (NMS), in particular the APRMs, to perform the post-accident monitoring function was evaluated from an Emergency Procedure Guideline (EPG) standpoint in NEDO-31558A. The results from the BWROG analysis show a
SSES-FSAR Text Rev. 64 FSAR Rev. 70 7.5-10 separate accident monitoring system (e.g., the ex-core system) is not required for accident conditions, since the conventional NMS would provide adequate indication. The analysis also showed that, since operators could use other plant parameters to determine neutron flux, even a failure of the conventional NMS would not compromise plant safety.
The NRC Office of Nuclear Reactor Regulation found the BWROG report (NEDO-31558) acceptable and concluded that "Category 1 neutron flux monitoring instrumentation is not needed for existing BWRs to cope with LOCA, ATWAS, or other accidents that do not result in severe core damage conditions. Instrumentation to monitor the progression of core melt accidents would be best addressed by the current severe accident management program."
The ex-core neutron flux monitoring system was originally installed at SSES to meet the requirements of Regulatory Guide 1.97, Revision 2. Based on the results of the BWROG report, the NRC position on this issue, and SSES specific reviews, the post-accident neutron flux monitoring function was changed to be performed by the Average Power Range Monitoring System (APRM). The excore neutron flux monitoring system has been removed from service.
7.5.1b.8.1 (This Subsection Has Been Deleted) 7.5.2a Analysis of NSSS Safety-Related Displays 7.5.2a.1 General The safety-related display instrumentation provides adequate information to allow the reactor operator to perform the necessary manual safety function.
All protective actions required under accident conditions for the NSSS equipment are automatic, redundant, and decisive such that immediate reactor operator information or intervention is unnecessary.
The ACR design improves the availability of the plant by providing the operator with more readily accessible information and control of the various plant operational parameters. This is accomplished by the logical organization of functional plant system indicators, displays, controls and a computer display system.
A complete description and analysis of design criteria applicable to the hardwired indicators, displays and controls for the various safety-related systems are described elsewhere in Chapter 7 with the systems they serve. Redundancy and independence or diversity are provided in all of those information systems which are used as a basis for operator-controlled safeguards action.
A complete failure of the Plant Integrated Computer System which serves as an active part of the operator/plant interface does not degrade the quantity or quality of necessary information presented by hardwired devices needed to determine the status or action of plant safety systems.
7.5.2a.1.1 DESIGN CRITERIA 7.5.2a.1.1.1 Power Generation Control Complex Criteria The applicable design criteria for the PGCC aspects of the ACR design are provided in General Electric Licensing Topical Report, NEDO-10466-A.
SSES-FSAR Text Rev. 64 FSAR Rev. 70 7.5-11 7.5.2a.1.1.2 Advance Control Room Design and Operational Criteria 7.5.2a.1.1.2.1 Design Criteria (1)
The implementation of the ACR design does not affect the ability of any system to meet the requirements of its design specification.
(2)
In the implementation of the ACR design, instruments for the reactor protection system and the engineered safety features meet the system design requirements of the systems they serve. They are located at easily visible and accessible positions.
(3)
The design employs modular techniques to implement distinct circuits so that separation and redundancy requirements are satisfied.
The interfacing circuitry between the Class 1E safety systems and the non-Class 1E non-safety Display Control System utilizes both digital and analog safety signals. Isolation devices have not been provided between certain Class 1E systems and the non-safety Display Control System.
As an alternative to providing isolation devices, analyses of the Class 1E safety systems from which the non-Class 1E non-safety Display Control System derive their signals was performed. The analyses evaluated the effects of an open or short circuit in the non-safety system component and a fault voltage of 250 VDC (288 VDC max.) on the cabling connecting the non-safety system component to the Class 1E system. The analyses determined that the design of the interfacing circuitry between the Class 1E safety systems and the non-Class 1E non-safety Display Control System was acceptable by demonstrating that the Class 1E safety systems are not degraded below an acceptable level when postulating faults in the non-safety Display Control System that derive their signals from Class 1E circuits. This acceptance is documented in a letter dated November 5, 1997 from the USNRC entitled, Single Failure Analysis of Class 1E/Non Class 1E Interface Circuits in the GE Scope of Supply, Susquehanna Steam Electric Station, Units 1 and 2 (TAC NOS.
M90541 and M90542).
(4)
All reactor protection system components incorporated by the ACR design are of at least comparable quality to the components that are integral to the design of related systems and have demonstrated operational reliability.
(5)
The implementation of the ACR makes use of modular control and indication components.
Plug-connected cables are used to facilitate removal of the modules. Cables and connectors are easily accessible and identified. Connector separation requires deliberate action.
(6)
Cabling is identified at each connection point, in the panels, wireways and termination cabinets so that visual verification of separation can be easily made. Connectors and cabling at connection points are clearly marked with system and reference designations.
(7)
All plant system controls remain hardwired. They are external to, and not dependent upon, the computer systems.
(8)
Simplification of controls is restricted to manual functions operating independently from, but compatible with, the automatic protective functions.
SSES-FSAR Text Rev. 64 FSAR Rev. 70 7.5-12 (9)
All safety system functions, either automatic protective or interlocking, including controls, displays and alarms remain hardwired. These system functions can be changed only by physically modifying the wiring or equipment. They are independent from the computer systems.
7.5.2a.1.1.2.2 Operating Criteria The implementation of the ACR design provides for planned operations or normal plant operation under planned conditions in the absence of significant abnormalities. Operations subsequent to an incident (transient, accident or special event) are not considered planned operations until the procedures being followed or equipment being used are identical to those used during any one of the defined planned operations. The established planned operations can be considered as a chronological sequence from refueling outage to refueling outage. The following planned operations are identified:
- a.
Refueling Outage
- b.
Achieving Criticality
- c.
Heatup
- d.
Reactor Power Operation
- e.
Achieving Shutdown
- f.
Cooldown 7.5.2a.2 Normal Operation Subsection 7.5.1a.2 describes the basis for selecting ranges for instrumentation. Since abnormal, transient, or accident condition monitoring requirements exceed those for normal operation, the normal ranges are covered adequately. The accuracy of safety-related display instrumentation is included in the Technical Specifications.
7.5.2a.3 Abnormal Transient Occurrences These occurrences are not limiting from the point of view of instrument ranges and functional capability. (See Subsection 7.5.2a.4.)
The variety of indications which may be utilized to verify that shutdown and isolation safety actions have been accomplished as required (see Subsection 7.5.1a.4.2.3) meets the requirements of IEEE 279-1971.
7.5.2a.4 Accident Conditions The DBA-LOCA is the most extreme operational event. Information readouts are designed to accommodate this event from the standpoint of operator actions, information, and event tracking requirements, and therefore, will cover all other design basis events or incident requirements.
Refer to Chapter 15 "Accident Analysis.
7.5.2a.4.1 Initial Accident Event The design basis of all engineered safety features to mitigate accident event condition takes into consideration that "no operator action or assistance is required or recommended for the first
SSES-FSAR Text Rev. 64 FSAR Rev. 70 7.5-13 twenty (20) minutes of the event with one exception." The only operator action assumed in the Section 6.3 ECCS analysis is that a RHR heat exchanger is placed in service within 20 minutes into the accident. This requirement therefore makes it mandatory that all protective action necessary in the first twenty minutes be "automatic, excluding the exception above. Therefore, although continuous tracking of variables is available, no operator action based on them is intended.
7.5.2a.4.2 Post-Accident Tracking The operator has many options which are procedures controlled based on the following information:
(1)
Reactor Water Level and Pressure Vessel water level and pressure instrumentation is redundant and electrically independent.
Power is from independent divisionalized Class 1E buses. This instrumentation complies with the independence and redundancy requirements of IEEE 279-1971 and provides recorded outputs. All equipment except the recorders and indicators will perform their required functions during a seismic event.
The reactor water level and pressure sensors are mounted on independent local panels.
The sensors and recorders are designed to operate during normal operation and post-accident environmental conditions. The design criteria that the instruments must meet are discussed in Subsection 7.1.2a.1.31.
Refer to Table 7.5-1 during the following discussion.
A combination of three different level instrument ranges, with two independent channels each, monitor Reactor Vessel Level:
- 1.
The extended range instrumentation measure from over the top of the steam lines to near the top of the active fuel and outputs to three control room level indicators per channel.
- 2.
The wide range instrumentation measures from the top of the feedwater control range (just above the high level turbine trip point) down to a point near the top of the active fuel and outputs to one control room recorder and three control room indicators per channel.
- 3.
The fuel zone range instrumentation measures from over the top of the active fuel to near the bottom of the active fuel and outputs to a control recorder (one channel) and a control room indicator (one channel).
These three ranges of instruments combine to provide level indication from the bottom of the Core to above the main steam line.
Two independent channels of reactor vessel pressure (ranged 0 to 1500 psig) are transmitted to and recorded on two separate recorders.
The recorders are located in the control room on the Reactor Core Cooling System benchboard. In the case of the wide range level, one recorder is with the Division 1
SSES-FSAR Text Rev. 64 FSAR Rev. 70 7.5-14 systems and the other recorder is with the Division 2 systems. The design, considering the accuracy, range and quality of the instrumentation, is adequate to provide the operator with accurate reactor water level and reactor pressure information during normal operation, abnormal, transient, and accident conditions.
(2)
ECCS Performance of ECCS following an accident may be verified by observing redundant and independent indications as described in Subsection 7.5.1a.4.2.3(3) and fully satisfies the need for operator verification of operation of the system.
(3)
Continued Shutdown Tracking The various indications described in Subsection 7.5.1a.4.2 provide adequate information regarding status of the reactor vessel level and pressure to allow reactor operators to make proper decisions regarding core and containment cooling operations, and fully satisfies the need for post-accident surveillance of these variables.
7.5.2a.4.3 Safe Shutdown Display The safe shutdown display instrumentation in Subsection 7.5.1a includes the control rod status lamps, scram pilot valve status lamps, and neutron monitoring instrumentation. These displays are expected to remain operable for a long enough time following an accident to indicate the occurrence of safe and orderly shutdown.
The displays provide redundancy by being in three separate systems and the rod position and neutron monitoring outputs are recorded (the former by the process computer). The systems cited are either manually or automatically connectable to the standby AC power.
7.5.2a.4.4 Engineered Safety Feature Operation Display The other operating instruments covered in Subsection 7.5.1a provide indication of operation of various safety systems but, except for the isolation valve status, do not constitute post-accident surveillance or safe shutdown display. Isolation valve status indication is designed to perform as stated in Subsection 7.5.2a.4.
7.5.2a.5 Compliance with Regulatory/Industry Standards 7.5.2a.5.1 Conformance to IEEE-279-1971 7.5.2a.5.1.1 General The rod status and scram pilot valve status circuits do not individually meet the requirements of IEEE-279. Jointly, however, they do meet the requirements applicable to display instrumentation except for seismic qualification.
Safety-related portions of the neutron monitoring system are designed to meet all the requirements of IEEE 279 as a part of the RPS. However, its RPS function is a "fail-safe" function while safe shutdown display is not. Further, its RPS function terminates with the generation and maintenance of a shutdown signal. In this regard, post DBA environment conditions may cause malfunction but not until the RPS function of scram generation is concluded. This makes it impossible to claim
SSES-FSAR Text Rev. 64 FSAR Rev. 70 7.5-15 continuous indicating capability for safe shutdown display by the neutron monitoring system.
Redundancy, power switching capabilities, RPS capabilities, and expected time to failure under DBA environment conditions allow the neutron monitoring system to meet the functional requirements of IEEE-279 as applicable to display instrumentation.
7.5.2a.5.1.2 Automatic Initiation of Protective Action (IEEE-279, Paragraph 4.1)
This requirement is not applicable to the safe shutdown display instrumentation.
7.5.2a.5.1.3 Single Failure Criterion (IEEE 279, Paragraph 4.2)
Indications associated with redundant channels meet the single failure criterion.
7.5.2a.5.1.4 Quality of Indicators (IEEE 279, Paragraph 4.3)
The quality of the indicators will be in accordance with their importance to safety.
7.5.2a.5.1.5 Equipment Qualification (IEEE 279, Paragraph 4.4)
All safety-related equipment except indicators and recorders will be qualified to assure performance of their safety-related functions including post-seismic performance.
7.5.2a.5.1.6 Channel Integrity (IEEE 279, Paragraph 4.5)
The failure of any indicator will not adversely affect channel integrity.
7.5.2a.5.1.7 Channel Independence (IEEE 279, Paragraph 4.6)
The failure of any indicator will not adversely affect channel independence.
7.5.2a.5.1.8 Control and Protection System Interaction (IEEE 279, Paragraph 4.7)
This design requirement is not applicable to the safe shutdown display instrumentation.
7.5.2a.5.1.9 Deviation of System Inputs (IEEE 279, Paragraph 4.8)
This is not applicable to display instrumentation.
7.5.2a.5.1.10 Capability for Sensor Checks (IEEE 279, Paragraph 4.9)
This is not applicable to safe shutdown display instrumentation.
7.5.2a.5.1.11 Capability for Test and Calibration (IEEE 279, Paragraph 4.10)
This is not applicable.
7.5.2a.5.1.12 Channel Bypass (IEEE 279, Paragraph 4.11)
This is not applicable.
SSES-FSAR Text Rev. 64 FSAR Rev. 70 7.5-16 7.5.2a.5.1.13 Operating Bypasses (IEEE 279, Paragraph 4.12)
This is not applicable.
7.5.2a.5.1.14 Indication of Bypass (IEEE 279, Paragraph 4.13)
This is not applicable.
7.5.2a.5.1.15 Access to Means for Bypassing (IEEE 279, Paragraph 4.14)
Bypassing is not applicable.
7.5.2a.5.1.16 Multiple Setpoints (IEEE 279, Paragraph 4.15)
This design requirement is not applicable to shutdown instrumentation.
7.5.2a.5.1.17 Completion of Protective Action Once it is Initiated (IEEE 279, Paragraph 4.16)
This is not applicable.
7.5.2a.5.1.18 Manual Actuation (IEEE 279, Paragraph 4.17)
Manual actuation is not applicable to display instrumentation.
7.5.2a.5.1.19 Access to Setpoints (IEEE 279, Paragraph 4.18)
This design requirement is not applicable to display instrumentation.
7.5.2a.5.1.20 Identification of Protective Action (IEEE 279, Paragraph 4.19)
Indicators will indicate protective actions to the channel level.
7.5.2a.5.1.21 Information Read Out (IEEE 279, Paragraph 4.20)
Indicators will provide required information.
7.5.2a.5.1.22 System Repair (IEEE 279, Paragraph 4.21)
This design requirement is not applicable, except for the role played by the indicators in providing diagnostic information.
7.5.2a.5.1.23 Identification (IEEE 279, Paragraph 4.22)
Indicators will be identified.
7.5.2a.5.2 Conformance with IEEE 323 See Subsection 3.11.2.1.
SSES-FSAR Text Rev. 64 FSAR Rev. 70 7.5-17 7.5.2a.5.3 Conformance with IEEE 344 See Section 3.10a.2.1.
7.5.2a.5.4 Regulatory Guide 1.47 The Safety-Related Display Instrumentation (SRDI) is designed to operate continuously, and there is no requirement for bypass provisions. Removal of instrumentations for servicing during plant operation is administratively controlled.
7.5.2a.5.5 Regulatory Guide 1.97 Safety-related display instrumentation will be in accordance with PP&L's commitment to Regulatory Guide 1.97, Rev. 2. The systems are discussed in the referenced sections:
Post-Accident ARMS, see Subsection 12.3.4 Suppression Pool/Drywell Spray Flow, see Subsection 5.4.7.1 Standby Liquid Control System, see Subsection 9.3.5.2 Instrument Gas Bottles Pressure Indication, see Subsection 7.3.1.1b.8.3.
RPV Water Level/Pressure, see Subsection 7.5.1a.4.2 RHR Heat Exchanger Outlet Temperature, see Subsection 7.4.2.3.1 All other items required for commitments to Regulatory Guide 1.97, Revision 2, appear in the appropriate subsections and tables in Section 7.5.
7.5.2a.5.6 10CFR50, Appendix B Safety-related display instrumentation environmental qualification is addressed in PP&L's commitment to Regulatory Guide 1.97, Rev. 2.
7.5.2b Analysis of non-NSSS Safety-Related Display Instrumentation 7.5.2b.1 Identification, Redundancy, Accuracy SRDI which is provided under non-NSSS responsibility is summarized in Subsection 7.5.1b and in Tables 7.5-2 through 7.5-7a. The safety-related displays are for ESF systems and for auxiliary support systems. These tables illustrate the redundancy applied to the displays and location of the panel on which the instrument is mounted, within the plant-operator interface.
7.5.2b.2 Isolation, Separation Table 1.7-1 lists elementary diagrams which show electrical isolation of divisions. It should be noted that these divisions are routed through separate divisionalized panels and use the divisional separation and identification provisions of the PGCC. Outside PGCC, refer to Section 3.12.
SSES-FSAR Text Rev. 64 FSAR Rev. 70 7.5-18 7.5.2b.3 Qualification of Components Primary containment isolation, primary containment vacuum relief, containment atmosphere, ESW, RHRSW and containment instrument gas rely on NSSS qualifications in Section 3.10a.
Standby gas treatment, reactor building recirculation, habitability systems use qualification described in Section 3.10b. Post-accident monitoring instruments in panel C693, C690A&B, and Bypass Indication are also qualified as described in Section 3.10b.
7.5.2b.4 Capability for Checking Under normal conditions periodic cross checking between indicators of two divisions, and checking against previous records will provide notification of malfunction. Under any conditions, normal or abnormal, if there is disagreement of readings, it is necessary to check to determine which indication is correct. The suspect indication is checked against a third indictor or checked against an alternate indicator from which the correct indication may be inferred.
7.5.2b.5 Analysis of the Bypass Indication System The Bypass Indication System (BIS) indicates on panel (C601/H12-P601) that any non-NSSS ESF or ESF supporting system is inoperable. That is indication of inoperability at a system level.
Indication of component inoperability within the non-NSSS ESF systems is provided on Panel C694. Both panels are located in the operator interface ring of panels.
Table 7.5-8 lists the systems and components included in the system.
Manual capability for testing operability of each indication is provided. The system design maintains the divisionalized structure of the ESF and signals to the BIS are mechanically and electrically isolated from the associated ESF system.
Regulatory Guide 1.47 and Branch Technical Position E1CSB 21 are complied with in the design of BIS.
7.5.2b.6 This Section Has Been Deleted
SSES-FSAR Table Rev. 57 FSAR Rev. 63 Page 1 of 1 TABLE 7.5-1 SAFETY RELATED DISPLAY INSTRUMENTATION Design Criteria Type Readout Panel Number Number of Channels Rated Range Location PAM Reactor Vessel Pressure Recorder UR14201A/B 1C601 2
0-1500 PSIG CR X
Indicator PI14202A/B PI14204A/B PI14202A1/B1 PI14262 1C601 1C601 1C651 1C201 2
2 2
1 0-1500 PSIG 0-1500 PSIG 0-1500 PSIG 0-1500 PSIG CR CR CR RSP X
X X
X Recorder UR14201A/B 1C601 2
-150"/0/+60" (wide)
CR X
Reactor Vessel Water Level Recorder UR14201a 1C601 1
-310"/TAF/-110" (fuel zone)
CR X
Indicator LI14201A/B 1C601 2
-150"/0/+180" (extended)
-150"/0/+60" (wide)
CR X
Indicator LI14203A 1C601 2
-150"/0/+180" (extended)
-150"/0/+60" (wide)
CR X
Indicator Ll14201A1/B1 1C651 2
-150"/0/+180" (extended)
-150"/0/+60" (wide)
CR X
Indicator UR14201B LI14262 1C601 1C201 1
1
-310"/TAF/-110" (fuel zone)
-150"/0/+60" (wide)
CR RSP X
RCIC Flow Indicator FIE511R600-1 1C601 1
0-700 GPM CR X
RCIC Discharge Pressure Indicator PIE511R601 1C601 1
0-1500 PSIG CR HPCI Flow Indicator FIE411R600-1 1C601 1
0-6000 GPM CR X
HPCI Discharge Pressure Indicator PIE411R601 1C601 1
0-1800 PSIG CR HPCI Turbine Steam Pressure Indicator PIE411R602 1C601 0-1500 PSIG CR CS Flow Indicator FIE211R601A 1C601 2
0-10,000 GPM CR X
RHR Flow (LPCI and Shutdown Cooling)
Indicator FIE111R603A 1C601 2
0-30,000 GPM CR RHR Service Water Flow Indicator FIE111R602A 1C601 2
0-12,000 GPM CR RHR Heat Exchanger Outlet Temperature Indicator TI15127A 1C601 2
40-340°F CR X
Primary Containment Area Radiation Recorder RR15755A 1C693 2
10-10E6 CPM CR X
The indicator/recorder numbers and panel numbers shown are for Unit 1. The Unit 2 numbers are the same except that a 2 appears before the sequence number instead of a 1.
SSES-FSAR TABLE 7.5-2 SAFETY RELATED DISPLAY INSTRUMENTATION HABITABILITY (EMERGENCY OUTSIDE AIR SYSTEM/CONTROL STRUCTURE HVAC)
Parameter No. of Type of Panel Power IE Measured Channels Range Accuracy Readout Location No.
Bus RPS ESF AS PPD Remarks CS NORMOA SUPPLY DMP 2
LT CR 0C681 Yes X
HDD7802A CREOASSA,B INLET DMP 2
LT CR 0C681 Yes X.
HDD7814A CREOASSA,B DSCH 2
LT
.CR 0C681 Yes X
OMP HDD7811A EOASS RET AIR 2
LT CR 0C681 Yes X
LT CR 0C681 Yes X
OMP HDO7833A CREOASS AIRFLOW NB 2
0-10,000 cfm
+/-2%
Ind/Ctr CR 0C681 Yes X
FIC07816A BATTERY RMS EXH SYS DMP 4
LT CR OC681 Yes X
HDD787182 Note:
PAM = Post Accident Monitoring; RSP = Remote Shutdown Panel; RPS = Reactor Protection System:
ESF = Engineered Safety Feature; AS = Auxiliary Support; PPD = Plant Process Display Rev. 54, 10/99 Page 1 of 1
SSES-FSAR Table Rev. 56 Rev. 66 Page 1 of 2 TABLE 7.5-3 SAFETY-RELATED DISPLAY INSTRUMENTATION CONTAINMENT AND SUPPRESSION POOL INSTRUMENTATION Parameter Measured No. of Channels Range Accuracy Type of Readout Location Panel No.
Power IE Bus RPS ESF AS PAM PPD Remarks Containment Hydrogen 2
0-10%
0-30%
+2%
Ind CR C690 Yes X
X X
Containment Oxygen 2
0-10%
0-25%
+2%
Ind CR C690 Yes X
X X
0-25% Range is not calibrated Containment O2/H2 2
02:0-10%
0-25%
H2:0-10%
0-30%
+2%
Rec CR C601 Yes X
X X
Operating History 0-25% Range is not calibrated Drywell Temperature 2
50-350F
+2%
Ind-Rec CR C693 No X
X Operating History Containment Temperature 2
40-440F
+2%
Rec CR C601 Yes X
Containment Temperature 1
0-350F
+2%
Ind RSP C201 Yes X
Suppression Pool Water Temperature 2
30-230F
+2%
Ind-Rec CR C690 Yes X
X X
Suppression Pool Water Temperature 2
30-230F
+2%
Ind RSP C201 Yes X
Suppression Pool Water Temperature 2
30-230F
+2%
Ind CR C601 Yes Suppression Chamber Atmos Temperature 2
0-400F
+5%
Ind-Rec CR C693 No X
Suppression Pool Air Temperature 1
0-350F
+2%
Ind RSP C201 Yes X
Drywell Hi Accident Range Pressure 2
0-250 psig
+2%
Rec CR C601 Yes X
X Operating History I
I I
I I
I I
I I
I I
I
SSES-FSAR Table Rev. 56 Rev. 66 Page 2 of 2 Parameter Measured No. of Channels Range Accuracy Type of Readout Location Panel No.
Power IE Bus RPS ESF AS PAM PPD Remarks Drywell LOCA Range Pressure 2
-14.7 to 65 psig
+2%
Rec CR C601 Yes X
X Operating History Drywell Normal Range Pressure 1
-3 to +3 psig
+2%
Ind CR C601 No X
Normal Operation Drywell Normal Range Pressure 1
-3 to +3 psig
+2%
Ind RSP C201 Yes X
Normal Operation Suppression Chamber LOCA Range Pressure 2
-14.7 to +65 psig
+2%
Rec CR C601 Yes X
Operating History Suppression Chamber Normal Range Pressure 1
-3 to +3 psig
+2%
Ind CR C601 No X
Normal Operation Suppression Pool Level (wide range) 2 5-49 feet
+5%
Rec CR C601 Yes X
X Suppression Pool Level (narrow range) 2 18-26.5 feet
+5%
Rec CR C601 Yes X
X Operating History Suppression Pool Level (narrow range) 2 18-26.5 feet
+2%
Ind CR C601 Yes X
X Suppression Pool Level (wide range) 4.5-49 feet
+2%
Ind RSP C201 Yes X
Remote Shutdown Containment & Suppression Chamber Gas Sample Vlvs Inboard/Outboard Isolation Status 2
LT CR C601 Yes X
X X
Containment & Suppression Chamber Nitrogen Purge Inboard/Outboard Isolation Vlv Status 2
LT CR C601 Yes X
X X
Suppression Chamber Spray Flow 2
0-750 GPM
+1%
Ind CR C601 Yes Drywell Spray Flow 2
0-12000
+1%
Ind CR C601 Yes NOTE:
PAM = Post Accident Monitoring RSP = Remote Shutdown Panel RPS = Reactor Protection System ESF = Engineered Safety Feature AS = Auxiliary Support PPD = Plant Process Display I
I I
I I
I I
I I
I I
SSES-FSAR TABLE 7.5-4 SAFETY RELATED DISPLAY INSTRUMENTATION STANDBY GAS TREATMENT SYSTEM, RX BLDG RECIRCULATION AND ISOLATION SYSTEM
!]
1l[~iiiji!i~liii ]~! ~~wr il~i!i m:ii~g,;:
""
- i![idiJ: I1iZij~zf i:.jf ~i~i::: l ~:t~: I;i~:,c ;~gii ;:~~:,, it~b::' ;:~i~ii RB Zone 1 Outdoor 2
0.2-1
+/-2%
Ind CR 0C681 Ye*s X
(Pressure Diff.)
in wg RB Zone 2 Outdoor I
2 I 0.2-1 I
+/-2%
I Ind I
CR I 0C681 I Yes I I X (Pressure Diff.)
in wg RB Zone 3 Outdoor I
2 I 0.2-1 I
+/-2%
I Ind I
CR I 0C681 I Yes I I X (Pressure Diff.}
in wg RB Zones Outdoor I
2 I 0.2-1 I
+/-2%
I lnd/Ctlr I CR I 0C681 I Yes I I X (Lowest Pressure Qiff.L in wg SGTSUnit1Drywell& I 1
I I
I LT I
CR I 1C681 I Yes I IX Wetwell Damper A SGTS Unit 1 Drywell & I 1
I I
I LT I
CR I 1C681 I Yes I I X Wetwell Damper B SGTS Unit 2 Drywell & I 1
I I
I LT I
CR I 2C681 I Yes I I X Wetwell Damper A SGTS Unit 2 Drywell & I 1
I I
I LT I
CR I 2C681 I Yes I I X Wetwell Damper B SGTS Flow I
2 I 0-15,000 I
+/-2%
I lnd/Ctlr I CR I 0C681 I Yes I
I X cfm RB Recirc System to I
2 I
I I
LT I
CR I 1C681 I Yes I
I X Zone 1 Sueely A,B I
RB Recirc System to 2
r LT I
CR I 1C681 I Yes I I X Zone 1 Exhaust A,B RB Recirc System to I
2 T- -~
I I
LT I
CR I 1C681 I Yes I
I X Zone 1 Equip.
Com_E)_artment Exh. A,B Rev. 54, 10/99 Page 1 of 3
SSES-FSAR TABLE 7.5-4 SAFETY RELATED DISPLAY INSTRUMENTATION STANDBY GAS TREATMENT SYSTEM, RX BLDG RECIRCULATION AND ISOLATION SYSTEM
,,:iI~J~1/4]lii~~:i~j:1: ~~wr tJ1i:: 1::~:~~ii:, i!]j~~~~'.! :ri:~~i :~J~f l~i:: ::~~~~Iti i'~:;32i,:~;~; ::;t~ :
U!i,~, i':: ::i~~:IAf ~::
Recirc Pump A,B Motor 2
LT 1C681 Yes X
Cooler Inlet Outboard lsol. Valve SGTS Outdoor/Zone 1 I:
2 I 0.2-1 I
+/-2%
I Ind I
CR
- I 0C681 I Yes I I. X Pressure Oiff. A,B
___ jrl wg_
SGTS Outdoor/Zone 2 I. 2 I 0.2-1 I
+/-2%
I Ind I
CR I 0C681 I Yes I I X Pressure Diff. A1B
_ _in w_g_
SGTS Outdoor/Zone 3 j 2
I 0.2-1 I
+/-2%
I Ind I
CR I 0C681 I Yes I
I X Pressure Diff. A1B in wg SGTS Outdoor/Zones I 2
I 0.2-1 I
+/-2%
I lnd/Ctlr I CR I 0C681 I Yes I
I X Pressure Diff. A1 B in wg SGTS Unit 1 Orywell & I 1
I I
I LT I
CR I 1C681 I Yes I I X Wetwell Oamj)_er A SGTSUnit 1 Orywell& I 1
I I
I LT I
CR I 1C681 I Yes I
I X Wetwell Damper B SGTS Unit 2 Drywell & I 1
I I
I LT I
CR I 2C681 I Yes I
I X Wetwell Dam_E>_er A SGTS Unit2 Drywell & I 1
I I
I LT I
CR I 2C681 I Yes I I X Wetwell Dam_E>_er B SGTS Flow I
2 I 0-15,000 I
+/-2%
I lnd/Ctlr I CR I 0C681 I Yes I I X RB Recirc System to Zone 1 Supply A,B RB Recirc System to Zone 1 Exhaust A,B Rev. 54, 10/99 2
2 cfm LT LT CR 1C681 Yes X
CR 1C681 Yes X
Page 2 of 3 r
SSES*FSAR TABLE 7.5-4 SAFETY RELATED DISPLAY INSTRUMENTATION STANDBY GAS TREATMENT SYSTEM, RX BLDG RECIRCULATION AND ISOLATION SYSTEM
- ,
- :~*i;[Wi~((~~fu~:: :~ili\i :::;,~~i~
1 iil~Q~~~! t:~f 11m: ilf t~~Ii~~11 t!~,~~,;::i ::~~iji ii~l: i~~~::r~1! 1
- 'i~6I111ili~iw,.1 RBRecircSystemto 2
LT CR 1C681 Yes X
Zone 1 Equip.
Compartment Exh. A1B Recirc Pump A,B Motor I 2
I I
I LT I
I 1C681 I Yes I
l X.
Cooler Inlet Outboard Isa!. Valve Recirc Pump A,B Motor I 2
I I
I LT I
I 1C681 I Yes I I X Cooler Outlet Outboard
. lsol. Valve Recirc Loop A,B I
2 I
I I
LT I
I 1C681 I Yes I I X Incoming Line Outboard lsol. Valve Recirc Loop A,B I
2 I
I I
LT I
I 1C681 I Yes -I I X Outgoing Line Outboard lsol. Valve Note: PAM = Post Accident Monitoring; RSP = Remote Shutdown Panel; RPS = Reactor Protection System; ESF = Engineered Safety Feature; AS = Auxiliary Support; PPD ;;; Plant process Display Rev_ 54, 10/99 Page 3 of 3
No.
of Parameter Measured Channels ESW Flow Loop NB 2
ESW Pump AC/BO 2
Discharge Pressure ESW Pump AC/BO 2
Discharge Temperature ESW Diesel Cooler 4
Outlet Temperature ESW and RHRSW 2
Total Flow A/8 ESWPump 4
ABCD Status ESW Diesel Cooler 8
Inlet/Outlet Valve Status Diesel Generator 4
Room Flooded ESW Structure 2
NB Flooded ESW Loop NB 2
in Service SSES-FSAR TABLE 7.5-5 SAFETY RELATED DISPLAY INSTRUMENTATION EMERGENCY SERVICE WATER SYSTEM Type of Panel Power Range Accuracy Readout. Location No.
IE Bus 0-12,000
+/-2%
fnd/Rec CR C653 Yes GPM 0-200 psig
+/-2%
Ind CR C653 Yes 0-200° F
+/-2%
Ind CR C653 Yes 50r150° F
+/-2%
Ind CR C653 No 0-30,000
+/-0.5%
Rec CR C653 No GPM LT CR C653 Yes LT CR C653 Yes LT CR C653 Yes Annun CR C653 Yes LT CR C653 Yes RPS ESF Note: PAM = Post Accident Monitoring; RSP = Remote Shutdown Panel; RPS = Reactor Protection System; ESF = Engineered Safety Feature: AS = Auxiliary Support; PPD = Plant Process Display Rev. 54, 10/99 AS
- PAM. PPO Remarks X
X X
X X
X X
X X
X X
X Page 1 of 1
SSES-FSAR TABLE 7.5*6 SAFETY RELATED DISPLAY INSTRUMENTATION RHR SERVICE WATER SYSTEM AND SPRAY POND Parameter Measured No. of Range Accuracy Type of location Panel#
Power RPS ESF AS PAM PPD Rernarks Channols Readout IF Bus RHRSW HX A Inlet Flow 1
0-12,000 GPM
+/-2%
Ind CR C601 yes X
0-12,000 GPM
+/-2%
Ind CR C601 VOS X
RHRSW HX A Lnlet Flow (Unit 2 onlyl 1
0-12,000 GPM
+/-2%
Ind ESP C201 yes X
Remote Shutdown RHRSW HX B Inlet Flow (Unit 1 only) 1 0-1 2,000 GPM
+/-2%
Ind ESP C201 yes X
Remote Shutuown RHRSW Pump A,B Status 2
LT CR CGOl yes X
RHRSW HX A/B Inlet Temperature 2
0-100°F
.1.2%
Ind CA C601 no X
AHRSW HX AIB Inlet Viv Position 2
0-100%
.1.2%
Ind CA C601 no X
Stntus on PSP AHASW HX AIB Dish Viv Status 2
LT CR C601 ye-;
X Status on PSP RHRSW loop A/8 Flow to Spray Pond 2
0-20,000 GPM
+/-.5%
Roe CR C653 no RHRSW Pump AIB Disch Pressure 2
0-200 PSIG
+/-2%
Ind CR CGOI no X
RHRSW Crosstia A/8 to AHA Viv Status 4
LT CR CGOI ves X
X ESS Spray Pond Inlet Viv Loop A/8 Status 2
LT CR C653 yes X
ESS Spray Pond 8ypa~s Viv Loop A/B Status 2
LT CR C653 yes X
ESS Spray Pond Temperature 4
25-125°F
+/-2%
Ind CR CG53 no X
SeIec1i,e Channel~
NoIes:PAM
- Post AcciderH Monitoring; RSP ~ Remote Shutdown Panel; RPS = Engineered Safety Feature; AS
~ Auxiliarv Support; PPD = Plant Process Display Rev. 54, 10/99 Page 1 of 1
No.
Parameter
,i of Measured
. <::hannels Instrument Gas 1
Pressure to Main Steam Relief Valve Instrument Gas 1
Supply Pressure Instrument Gas Bottle 2
Pressure Indication (Unit 2 only)
Instrument Gas 2
Bottles lsol Viv Status Instrument Gas 2
Suction IB/0B lsol Viv Status Instrument Gas 9
Containment IB/08 lsol Viv Status SSES-FSAR TABLE 7.5-7 SAFETY RELATED DISPLAY INSTRUMENTATION CONTAINMENT INSTRUMENT GAS SYSTEM Type of Panel. Power Range Accuracy Readout Location No.
IE Bus 0-200 psig
+/-2%
Ind CR C601 No 0-100 psig
+/-2%
Ind CR C601 No 0-3000 psig
+/-2%
Ind CR C601 Yes LT CR C601 Yes LT CR C601 Yes LT CR C601 Yes RPS ESF AS X
X X
X X
X Note: PAM = Post Accident Monitoring; RSP = Remote Shutdown Panel; RPS = Reactor Protection System; ESF = Engineered Safety Feature; AS = Auxiliary Support; PPD = Plant Process Display Rev. 54, 10/99 PAM
-PPD Remarks X
Computer Input
")
")
.)
Page 1 of 1
No. of P*r-ter Measured Channels Range SLCS Flow 1
0-5000 Tank Level Gal R.-v. ~. 07/88 SSES-FSAR TABLE 7.5-7a SAFETY-RELATID DISPLAY tNSTRUfo£NtATlON STAMDBY Ll(JJID CONTROL SYSTEM Type of Panel P~r Accuracy Readout Location No.
IE llu11
- U%
Indlcator 14806 CR C601 Yea
- f:2%
Indicator 14806 CR C601 Yes RPS ESF AS PAM PP:>
Reurlt9 X
X
SSES-FSAR Table Rev. 56 FSAR Rev. 70 Page 1 of 3 TABLE 7.5-8 BYPASS INDICATION FOR NON-NSSS SYSTEMS Bypassed System Indication Bypassed Component Indication ESW, Loop A ESW Pump 0P-504A Power Loss Out-of-Service ESW Pump 0P-504C Power Loss ESW Pump Cooling Fans A/C Disabled ESW, Loop B ESW Pump 0P-504B Power Loss Out-of-Service ESW Pump 0P-504D Power Loss ESW Pump Cooling Fans B/D Disabled Diesel-Gen. A(B,C,D)
DG A(B,C,D) DC Control Power Loss Control System DG A(B,C,D) Field Flash and Excitation Control Power Loss Out-of-Service DG A(B,C,D) Auto Control Unavailable DG A(B,C,D) Cooling Fans Disabled 4 Kv Bus 1AXFMR101CRT Breaker Disabled Diesel-Gen. A(B,C,D)
DG A(B,C,D) Breaker Racked Out Output System DG A(B,C,D) Control Power Loss Out-of-Service 4 Kv Bus 1A XFMR 201CRT Breaker Disabled Diesel-Gen. A(B,C,D)
DG A(B,C,D) Aux. Supply/Control Power Loss Aux. System DG A(B,C,D) Aux. System Not in Auto Out-of-Service Oil Pump 0P-514A(B,C,D) Disabled Control Room Fan 0V-101A Disabled Habitability Fan 0V-103A Disabled System Div. I Fan 0V-115A Disabled Out-of-Service Fan 0V-117A Disabled Chilled Water Disabled NOTE: Whenever Diesel Generator 'E' is aligned for Diesel Generator A, B, C, or D, the Diesel Generator 'E' Bypass Indications are transferred into the Bypass Indication System in place of the substituted diesel generator.
Control Room Fan 0V-101B Disabled Habitability System Div. II Fan 0V-103B Disabled Out-of-Service Fan 0V-115B Disabled Fan 0V-117B Disabled Chilled Water Disabled Standby Gas Treatment Fan 0V-109A Disabled System Div. I Fan 0V-118A Disabled Out-of-Service Fan 0V-144A Disabled Fan 0V-201A Disabled
SSES-FSAR Table Rev. 56 FSAR Rev. 70 Page 2 of 3 TABLE 7.5-8 BYPASS INDICATION FOR NON-NSSS SYSTEMS Bypassed System Indication Bypassed Component Indication Standby Gas Treatment Fan 0V-109B Disabled System Div. II Fan 0V-118B Disabled Out-of-Service Fan 0V-144B Disabled Fan 0V-201B Disabled Battery Room Exhaust Div. I Out-of-Service Fan 0V-116A Disabled Battery Room Exhaust, Div. II Out-of-Service Fan 0V-116B Disabled RHR Service Water Pump 1P-506A Power Loss Loop A Heat Exchanger Valve Control Power Loss Out-of-Service Fan 1V-506A Disabled Control Power Loss for Spray Pond Network Valves Spray Pond Drain Valves Power Loss / Not In Auto RHR Service Water Pump 1P-506B Power Loss Loop B Heat Exchanger Valve Control Power Loss Out-of-Service Fan 1V-506B Disabled Control Power Loss for Spray Pond Network Valves Spray Pond Drain Valves Power Loss / Not In Auto Remote Shutdown Panel Remote Shutdown Panel Div. I Div. I Switches in Switches in Emergency Position Emergency Position Remote Shutdown Panel Remote Shutdown Panel Div. II Div. II Switches in Switches in Emergency Position Emergency Position Containment Instrument Gas Nitrogen Supply HV-12648 Open System Div. II Nitrogen Supply HV-12643 Open Out-of-Service Containment Isolation System Div. I Out-of-Service Loss of Control Power for Motorized Valves (Div. I)
Containment Atmos Purge ISO Bypass Containment Isolation System Div. II Out-of-Service Loss of Control Power for Motorized Valves (Div. II)
Containment Atmos Purge ISO Bypass
SSES-FSAR Table Rev. 56 FSAR Rev. 70 Page 3 of 3 TABLE 7.5-8 BYPASS INDICATION FOR NON-NSSS SYSTEMS Bypassed System Indication Bypassed Component Indication Unit 1 Unit 2 Drywell Ventilation System Div. I Out-of-Service Fan 1V-414A / 2V414A Disabled Fan 1V-418A / 2V415A Disabled Fan 1V-416A / 2V416A Disabled Drywell Ventilation System Div. II Out-of-Service Fan 1V-414B / 2V414B Disabled Fan 1V-418B / 2V415B Disabled Fan 1V-416B / 2V416B Disabled Reactor Building Emerg.
Switchgear and LCC Cooling Div. I Out-of-Service Fan 1V-222A Disabled Reactor Building Emerg.
Switchgear and LCC Cooling Div. II Out-of-Service Fan 1V-222B Disabled Control Structure HVAC Train 'A' Alternate Control Switches in Emergency Position CSHVAC Alternate Control Panel Switches in Emergency Position
AutoCAD: Figure Fsar 7_5_3.dwg FSAR REV.65 FIGURE 7.5-3, Rev 49 NEUTRON FLUX AT PRIMARY FIELD SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 FINAL SAFETY ANALYSIS REPORT 1-- SUSQUBUANNA SIS 1 2'1d-f-'T"'T"l'fflffl'--r-'""'"rm-rnTfflll'-,-rmmr-TTT'l"ffll'l'-'T"'n"mrm-T"T'T'fflffl-'T"'TTnilffl""""'i 10-'
10--4 10-i 10-*
10-*
Neutron Energy (mev)