- ey MEMORATOUM FOR:
J. tielson Grace, IE n
SGA OL Thomas T. Martin, R-I d'
QC-01 William J. Olmstead, ELDe*.;h DRM FILE. I John A. 01shinski, R-II R. Lee Spessard, R-ll!
Thomas V. Wambach, DL FROM :
Richard H. Vollmer, Chairman t Fire Protection Steering Cor.mittee The enclosed is for your information relative to Steering Committee work.
JV'.-/
(
ichard H. Vollmer, Chairm n-Fire Protection Steering Committee i
cc:
'F.
Rosa i
l
\\
N 5P.
w a
)
N H0V 3 0W 8808160137 000705' PDR FOIA 3
JONESB8-92 PDR
l
. A / *i v i.) (,0!.'..*.M. i I
,I.
['
"r REGION il e
,g f
a 101 MARitTT A STREE T.N.W.
- J,A f
/ 7
\\*****/
Ip 90V15 at MEMORANDUM FOR: Victor Stello, Jr., Deputy Executive Director for Regional Operations and Generic Requirements FROM:
James P. O'Reilly, Regional Administrator
SUBJECT:
RECOMMENDED FIRE PROTECTION POLICY AND PROGRAM ACTIONS As requested by memorandum of November 2,1984, from William J. Dircks, the NRC Fire Protection Policy Steering Comittee's "Recommended Fire Protection Policy And Program Actions" of October 26, 1984, have been reviewed.
The enclosed coments should be considered for improvements prior to promulgating the Comittee's recomendations.
Of more import, however, are issues that were not addressed by the Comittee.
For example, at one Region Il facility, over two hundred people will work fulltime for the next one and one-half years to implement Appendix R requirements at an estimated cost of about 30 million dollars. At another Region II facility, a six-month delay in licensing, along with additional modification costs, have resulted because of recent Appendix R inspection findings.
The issues are whether the staff interpretations exceed what the Comission intended when it approved Appendix R and if we should provide unusually clear and additional
(
definitive guidance to licensees to assure that the extensive work being done is performed efficiently and effectively.
Before we progress any further with Appendix R inspections or enforcement, I believe the issues should, in our view, be extensively discussed with the Commission.
My staff is available to discuss these coments if you have further que:tions.
b c/mth_
mes P. O'Reilly
Enclosure:
Region 11 Coments on Fire Protection cc w/ encl:
R. DeYoung, IE:HQ T. Murley, RI J. Keppler, R!ll R. Martin, RIV J. Martin, RV R. Fraley, ACRS R. Vollmer DE F. Rosa, NRR CONTACT:
'A S
$E
{ ' ' ' kt I
bpi
}
l l
ENCLOSURE REGION II COMMENTS ON FIRE PROTECTION STEERING COMMITTEE'S OCTOBER 26, 1984 RECOMMENDED FIRE PROTECTION POLICY AND PROGRAM ACTIONS Steering Committee Recommendations 1.a.
Concur 1.b.
Concur.
However, if adequate resources are available, the Region should conduct an Appendix R inspection of all Regional facilities during 1985.
1.c.
Concur 1.d.
Concur 1.e.
Concur.
However, the "Appendix R Questions and Answers" (Enclosure 6) should be closely reviewed and revised to comply with the new "Interpreta-tion of Appendix R" (Enclosure 3), to use standard fire protection termi-nology and to provide a consistent application of positions for both OR
(
and NT0L plants.
Refer. to comments on "Appendix R Questions and Answers"
\\
listed below.
2.a.
Concur 2.b.
Concur 2.c.
Concur 2.d.
We agree with this concept to achieve resolution of NRC/ Licensee Fire Protection issues. However, the section should identify the referee as a Fire Protection Issue Review Board in lieu of a "Referee" to resolve the differences between the inspection teams and the licensees.
3.a.
Concur.
However, refer to the below listed connents on "Fire Protection License Condition".
3.b.
A time schedule should be established for the completion of the evaluation of existing fire protection guidance for consistency with the Steering Comittee's recomendations.
3.c.
Concur 3.d.
Do not concur.
Region 11 recommends that the entire NRC fire protection program be under the management and control of a single organization in NRR.
Refer to Question 8.15 under "Appendix R Questions and Answers" for further comments.
i Enclosure 2
4.
Concur Generic letter on Fire Protection Do not concur. A new rule or c Comission approved guidance document appears to be necessary.
Interpretations of Appendix R Concur; but before these interpretation are released, the "Appendix R Questions and Answers" document should be closely reviewed and revised to comply with the new interpretations.
Guidance for Enforcement Actions Concerning Fire Protection Requirements Concur.
The fire protection enforcement policy should be included in the NRC enforcement policy of 10 CFR 2 Appendix C.
Fire Protection License Condition Concur, except item 1.
Lines 2 and 3 should be revised to read as follows:
... described in the Final Safety Analysis Report or Fire Hazards Analysis for the facility...".
This change is necessary to cover those facilities in which
(
the fire protection program is,, described in a document separate f rom the FSAR.
Appendix R Questions and Answers Coments and recommended changes are offered on the response to the following questions.
3.1 The response to the question was "Yes".
A history of the develop-ment of the definition was given in the response based on:
1.
BTP f.PCSB 9.5-1 2.
NRC supplementary guidance 3.
Appendix A to BTP 9.5-1 However, all of the above stated "definitions" are r.ot in agree-mant with the new "NRC Interpretation of Appendix RD) tems 4 and 6.
These definitions (i.e., fire area and fire zone are the subject of the original Fire Protection Differing Professional Opinion written within NRC. Therefore, the new guidance proposed in items 4 and 6 of Interpretations of Appendix R should be added to the response of Question 3.1; and the "Yes" answer qualified to i
reflect the new interpretations.
In this way, clear and useful guidance based on NRC historical experience will be provided to the industry.
(For editing purposes it is recomended that the order or presentation of historical definitions be chronological; namely, BTP 9.5 Appendix R, guidance (add BTP CHEB 9.5-1 as given in 3.1.2) and new Interpretations of Appendix R.)
Enclosure 3
3.1.2 The definition of fire barrier presented should be that as stated in BTP APCSB 9.5-1, which was in use during the period of a 1977 fire hazards analysis.
BTP CMEB 9.5-1 was not issued until 1981; namely, Rev. 3. BTP CMEB 9.5-1 (NUREG 0800). Reference should be made not only to Item 4 of the "Interpretations of Appendix R",
but also response to Item 6 and response to Quel, tion 3.1.1.
This will aid in fully understanding the relationship of the fire areas and the associated fire barriers.
3.1.4 The response should add references to Items 3, 4, and 6 of the Interpretations of Appendix R. Enclosure 3.
This will provide an overall understanding of the relationship of (1) "free from fire damage" vs. resulting damage; (2) largest credible fire vs. design basis fire; and (3) fire areas vs. fire rones. It seems that the technical tenninology used in this response should be clearly defined in a definition section and agree with that in the previous responses and interpretations.
The response should be revised to present consistent use of technical tenns, as noted above, and a consistent philosophy of analysis as presented in the previous question responses and interpretations.
3.1.5 The requirements of Section III.G.3, as stated, are not complete.
The following requirement of III.G.3 should be added to the last paragraph on page 11:
"For those configurations that do not
\\
satisfy the requirements of III.G.2, fire detection and fixed fire suppression system shall be installed in the area, room, or zone under consideration."
Additionally, the new interpretations, Item 5, Automatic Detectian and Suppression, and Item 6. Alternative or Dedicated Shutdown, have not been referenced in this respor.se.
These should be r:ferenced in the next to last and last paragraph of the response.
3.4.2 The response should include a statement that further clarification related to partial coverage is provided in Item 5 of Interpreta-tions of Appendix R.
3.4.3 The response should reference Item 5 of Interpretations of Appendix R.
3.4.6 The response should reference Item 5 of Interpretations of Appendix R (Enclosure 3) of this document.
3.5.2 The response should also reference item 4 of Interpretations of Appendix R which states that "...all unsealed openings should be identified and evaluated."
3.8.2 The response must be expanded to clarify use of the term "design basis fire".
The response states that neither industry nor the staff has been able to develop criteria establishing design basis fire...; however, this tern, is used in the NRC response to a previous question, 3.1.1.
A similar term "... largest credible r
l fire" is used in the response to question 3.1.4 "design basis i -
-a w--c.
nr.----=we
e-m v.,
y
---et---,++m,.--*,-----
---,+-%--
--,-e---,-
ry
.1-
Enclosure 4
fires" are defined in BTP APCSB 9.5-1 Section C, which is quoted in the NRC response to Question 3.1.1.
The NRC response should be revised to provide clear and consistent technical infomation.
5.3.1 The answer given to question 5.3.1 is not clear and does not provide any clear information. This response should be revised in its entirety.
5.3.2 There should be a definition given for "Hot Short".
A high impedence short conducts very little current. Once current flow is increased it will burn open or trip a circuit protection device. The postulation that the fire would eventually clear the "hot short" is secondary. The hot short would clear whether there was a f. ire or not.
5.3.4 The response should also refer Item 2 of Interpretations of Appendix R (Enclosure 3) for clarification of "free of fire damage".
5.3.11 Reference should be made to Item 6 of Interpretations of Appendix R (Enclosure 3).
7.1 The requirements for seismic design of hydrogen lines as delineat-(
ed in BTP CMEB 9.5-1 C.3.d.(5) are not included in BTP APCSB 9.5-1 or AppenTix A to which most early Operating Reactors (ors) are comitted. Only NTOL plants have had a formal NRR review to BTP CMEB 9.5-1 requirements. This response, as stated, may have direct impact on early ors of the older PWR type.
Early OR hydrogen system designs may need to be modified, requiring exten-sive backfitting.
7.2 It should be noted that the stated CEMB 9.5-1 requirement may not necessarily apply to those ors reviewed by NRR under BTP APCSB 9.5-1 and Appendix A.
8.8 The response should reference Section 3 of this enclosure and item 4 of Interpretations of Appendix R.
B.10 The term "design basis fire" should not be used in this text.
8.11 The Region 11 staff does not agree that BTP CMEB 9.5-1 includes the requirements of Appenr11x R and previous guidance documents incorporated into the Branch Technical Position.
Refer to memo-randum from Tom E. Conlon to Faust Rosa dated November 7,1984, and the statement on page 5 of the October 26, 1984 memorandum from the Fire Protection Policy Steering Committee to William J. Dircks.
8.15 The response provided clearly indicates the need for a mechanism within the agency to assure and maintain a high level of consis-ter.cy for fire protection pclicy to the industry. To accomplish
Enclosure 5
this, it is recommended that the total fire protection responsi-bilities/ reviews presently assigned to three divisions within NRC and one in IE be reassigned to one division such that the entire NRC fire protection prograrn will be under the management and control of a single organization at the headquarters level.
(
\\