.c-,L ADMINISTRATIVE CONTROLS The reports shall also include the following:
a summary description of the radiological environmental monitoring program including a map of all sampling locations keyed to a table giving distances and directions from the reactor; and the results of licensee participation in the Intercomparison Program required by Specification 3.12.3, and discussion of all analyses in which the LLD required by Table 4.12-1 was not achievable, b.
Semiannual Effluent Release Report.
(1) Within 60 days after January 1 and July 1 of each year, a report shall be submitted covering the radioactive content of effluents released to unrestricted areas during the previous six months of operation.
(2) The radioactive effluent release reports shall include a summary of the quantities of radioactive liquid and gaseous effluents and solid waste released from the unit as outlined in Regulatory Guide 1.21, Revision 1, June 1974, " Measuring, Evaluating and Reporting Radioactivity in Solid Wastes and Releases of Radioactive Materials in Liquid and Gaseous Effluents from Light-Water-Cooled Nuclear Power Plants," with data summarized on a quarterly basis following the format of Appendix B thereof.
In addition the Radioactive Effluent Release Report to be submitted 60 days after January 1 of each year shall also include an annual summary
- of hourly meteorological data collected over the previous year. This annual summary may be either in the form of an hour-by-hour listing on magnetic tape of wind speed, wind direction, atmospheric stability and precipitation (if measured), or in the form of joint frequency distributions of wind speed, wind direction and atmospheric stability.**
This same report shall include an assessment of the radiation doses
- due to the radioactive liquid and gaseous effluents released from the unit during the previous calendar year.
(The semiannual effluent release report submitted within 60 days of July 1 each year need not contain any dose estimates from the previous 6 months' effluent releases.) This report shall also include an assessment of the radiation doses from radioactive effluents to MEMBER (S) OF THE PUBLIC due to the allowed recreational activities inside the SITE BOUNDARY (Figures 5.1-3 and 5.1-4) during the previous calendar year. All assumptions used in making these assessments (e.g., specific activity, exposure time and In lieu of including in the radioactive effluent release report required to be submitted within 60 days af ter January 1 additional information that covers the summary of annual meteorological data and assessment of radiation doses, a supplemental report is permitted to 1-submitted within'150 days after January 1 containing this information.
In lieu of submission with the first half year radioactive effluent release report, the licensee has the options of retaining this summary of required meteorological data in a file that shall be provided to the NRC upon request.
YANKEE-ROWE 6-20 Amendment No. Jdf.)>6 8601100151 860106 PDR ADOCM 05000029 P