JAMES A. FITZPATRICK NUCLEAR POWER PLANT OPERATING DATA REPORT DOCKET NO. 50-333 UNIT NAME FITZPATRICK DATE NOVEMBER 1985 COMPLETED BY JOHN COOK TELEPHONE (315)342-3840 OPERATING STATUS 1

I

1. UNIT NAME: FITZPATRICK
2. REPORTING PERIOD: 851001 - 851031
3. LICENSED THERMAL POWER (MWT): 2436
4. NAMEPLATE RATING (GROSS puE): 883 i S. DESIGN ELECTRICAL RATING (NET MWE): 821
6. MAXIMUM DEPENDABLE CAPACITY (GROSS MWE): 830
7. MAXIMUM DEPENDABLE CAPACITY (NET MWE): 810 4
8. IF CHANGES OCCUR IN CAPACITY RATINGS (ITEMS 3 - 7) SINCE LAST REPORT, GIVE REASONS:

NONE

, 9. POWER LEVEL TO WHICH RESTRICTED, IF ANY (NET MWE): NONE

10. REASONS FOR RESTRICTIONS, IF ANY:

l THIS MONTH YR-TO-DATE CUMULATIVE

11. HOURS IN REPORTING PERIOD: 745 7296 89977 i 12. NUMBER OF HOURS REACTOR WAS CRITICAL: 730.4 4381 63997
13. REACTOR RESERVE SHUTDOWN HOURS: 0 0 0
14. HOURS GENERATOR ON-LINE: 730.4 4186.1 62133.4
15. UNIT RESERVE SHUTDOWN HOURS: 0 0 0

! 16. GROSS THERMAL ENERGY GENERATED (MWH): 1,760,664 9575856 132511810

, 17. GROSS ELECTRICAL ENERGY GENERATED (MWH): 598910 3223920 45504200

18. NET ELECTRICAL ENERGY GENERATED (MWH): 578860 3115605 43513610
19. UNIT SERVICE FACTOR: 98.0% 57.4% 69.1%

! 20. UNIT AVAILABILITY FACTOR: 98.0% 57.4% 69.1%

21. UNIT CAPACITY FACTOR (USING MDC NET): 95.9% 52.7% 62.6%
22. UNIT CAPACITY FACTOR (USING DER NET): 94.6% 52.0% 58.9%
23. UNIT FORCED OUTAGE RATE: 1.9% 11.9% 13.4%
24. SHUTDOWNS SCHEDULED OVER NEXT 6 MONTHS (TYPE, DATE AND DURATION OF EACH):

Planned maintenance outage March 10, 1986, to last approximately 2 weeks.

25. IF SHUT DOWN AT END OF REPORT PERIOD, ESTIMATED DATE OF STARTUP: November 1, 1985
26. UNITS IN TEST STATUS (PRIOR TO COMMERCIAL OPERATION): FORECAST ACHIEVED
INITIAL CRITICALITY INITIAL ELECTRICITY COMMERCIAL OPERATION 8511200297 85 g h l
" "c"
  • m Y q y-ms 9 - 9 m -.,-e- ,- --

9y r --ee-wr

-e -

NEW YORK POWER AUTHORITY JAMES A. FITZPATRICK NUCLEAR POWER PLANT AVERAGE DAILY POWER LEVEL DOCKET NO. 50-333 UNIT FITZPATRICK DATE NOVEMBER 1985 COMPLETED BY JOHN COOK TELEPHONE (315)342-3840 MONTH- OCTOBER 1985 I

DAY AVERAGE DAILY POWER LEVEL DAY AVERAGE DAILY POWER LEVEL 1 797 17 800 2 796 18 797 3 797 19 797

'4 795 20 798 5 797 21 799 6 799 22 803 7 800 23 803 8 796 24 801 9 799 25 798 10 798 26 788 11 801 27 831 12 664 28 801 13 749 29 802 14 797 30 803

'15 798 31 314 16 799

SUMMARY

The FitzPatrick plant operated at near full thermal power for the first' thirty days of the reporting period.

l f

i

JAMES A. FITZPATRICK NUCLEAR POWER PLANT UNIT SHUTDOWNS AND POWER REDUCTIONS i DOCKET NO. 50-333 l UNIT NAME FITZPATRICK I

DATE NOV. 1985 REPORT MONTH OCTOBER 1985 COMPLETED BY JOHN COOK TELEPHONE (315)342-3840 D C UH R METHOD S O RO E OF YC MC CAUSE AND CORRECTIVE ACTION AU A SHUTTING LICENSEE S0 PO TO l

NO. DATE TYPE TR S DOWN EVENT TD 0D PREVENT RECURRENCE I IS 0 THE REPORT EE NE O N REACTOR H E N N l T I 13 851031 F 14.6 H 3 FK N/A Reactor Scram on load reject due to equipment failure at the EDIC substation.

At the time of the trip the plant was feeding one of two transmission lines. The second line was out of service for maintenance. No corrective action is required.

I i

1 2 3 4 F FORCED REASON: METHOD: EXHI67T G.- INSTRUCTIONS S: SCHEDULED A. EQUIPMENT FAILURE (EXPLAIN) 1-MANUAL FOR PREPARATION OF DATA B. MAINTENANCE OF TEST 2-MANUAL SCRAM ENTRY SHEETS FOR LICENSEE C. REFUELING 3-AUTOMATIC SCRAM EVENT REPORT (LER) FILE D. REGULATORY RESTRICTION 4-0THER (EXPLAIN) (NUREG-0161)

E. OPERATOR TRAINING AND LICENSE EXAMINATION l F. ADMINISTRATIVE G. OPERATIONAL ERROR (EXPLAIN)

H. OTHER (EXPLAIN)

L_ _ _

L NARRATIVE

SUMMARY

OF OPERATING EXPERIENCE OCTOBER 1985 The FitzPatrick plant operated at near full thermal power for the first thirty days of the reporting period.

On October 31 the plant was operating near full thermal power with one of two transmission lines out of service for scheduled maintenance. An

. electrical disturbance following operation of a motor operated disconnect

!at an off-site substation led to a load reject situation when protective relaying tripped the. breaker on the remaining line.

At the end of the reporting period the plant was in the process of-starting up following the load reject of October 31.

I

\

4.

]

I'

__s

NEW YORK POWER AUTHORITY JAMES A. FITZPATRICK NUCLEAR POWER PLANT .

MAINTENANCE

SUMMARY

OCTOBER 1985 ACTION TAKEN REPAIR WORK REQUEST NO. HOW CAUSE OF RESULTS OF TO PRECLUDE TIME DATE SYSTEM COMPONENT NO. DETECTED MALFUNCTION MALFUNCTION RECURRENCE HOURS 851021 05 038701 I&C WIRED WRONG FROM CAL STAT. LIGHT CORRECTED WIRING 8 MTU-255A FACTORY DIDN'T COME ON PROBLEM 851021 05 038703 I&C WIRE FROM E25 NOT CAL STAT. LIGHT TERMINATED TO E53 PER 4 MTU-255B TERMINATED DIDN'T COME ON SCHEMATIC 851010 07 031489 OPS UNKNOWN READS HICH WITH TESTED, UPSCALE, 4 LPRM-28-13C RX IN COLD S/D WROTE WR FOR REP 851007 07 034592 OPS N/A FAILED UPSCALE NONE NEEDED-PERFORMED 1 LPRM-12-21 LPRM CALIBRATION 851017 07 034957 I&C BAD CONNECTOR DRIFTED UPSCALE REPLACED CABLE 6 LPRM-20-13B CAUSING ALARM CONNECTOR 850925 07 037406 OPS N/A DRIFTED UP THEN NO DRIFT FOUND - 6 LPRM-12-37 DOWN PERFORMED CAL.

851001 07 039145 OPS DRIFT IN COUNT WON'T INOP W/0 RESET COUNT CIRC. 2 A APRM CIRCUIT 10 LPRMS UNBYP. TO INOP @ll 850930 07 039477 OPS UNKNOWN READING HIGH WITH PER0RMED LPRM 3 LPRM-12-13 REACTOR S/D CALIBRATION I I Page . _ _ _ _ _ _ _ _ _ _

NEW YORK POWER AUTHORITY JAMES A. FITZPATRICK NUCLEAR POWER PLANT .

MAINTENANCE

SUMMARY

OCTOBER 1985 ACTION TAKEN REPAIR WORK REQUEST NO. HOW CAUSE OF RESULTS OF TO PRECLUDE TIME DATE SYSTEM COMPONENT NO. DETECTED MALFUNCTION MALFUNCTION RECURRENCE HOURS 851002 07 039484 OPS LOOSE WIRE AT READING 0 IN FIXED WIRE, PERF. 8 LPRM-36-05 POWER CONNECTOR OPERATE LPRM CARD CAL.

851009 07 041476 OPS DEFECTIVE LPRM FAILED WROTE WR 07/32804 FOR 8 LPRM-20-13C DETECTOR UPSCALE REPLACEMENT 851015 10 038962 OPS FOUND GAIN OUT OF ALARM WILL NOT ADJUSTED GAIN 10 LS-104 ADJUSTMENT CLEAR 851021 11 037603 OPS BAD LAMP ASSEMBLY LOST SQUIB REPLACED LAMP 7 RELAY 67B CONTINUITY ASSEMBLY ALARM (B) 851025 16 039018 OPS INSTRUMENT OUT TRACKS 4 PTS ADJUSTED TIMING, 22 DPR-200 0F ADJUSTMENT INSTEAD OF 2 REPLACED ASSEMBLY 851021 17 032785 I&C N/A VENT MONITORS CALIBRATED PER 17 RM-50A,B NEED CALIBRATION IMP-17.1, REPLACED CABLE CONNECTOR 851021 17 038727 I&C N/A PERFORMED FUNCT. TESTED, REPAIRED 64 RM-350,351 TEST FOR TECH. SOLDER ADJUSTED SPECS SET 851015 27 038733 I6C LOW FLOW SWITCH STOPS FLOW, GIVES ADJUSTED LOW FLOW 10 PCX-101B OUT OF ADJUSTMNT LO PRESS ALARM Page (_ __

NEW YORK POWER AUTHORITi JAMES A. FITZPATRICK NUCLEAR POWER PLANT ,

MAINTENANCE

SUMMARY

OCTOBER 1985 ACTION TAKEN REPAIR WORK REQUEST NO. HOW CAUSE OF RESULTS OF TO PRECLUDE TIME DATE SYSTEM COMPONENT NO. DETECTED MALFUNCTION MALFUNCTION RECURRENCE HOURS 851017 27 039050 OPS UNKNOWN READS TOO HIGH CALIBRATED PER 80 PCX-101B ISP-30-1 l 850927 27 040812 OPS AGE / WEAR RECORDER STICKS REPLACED BULL GEAR 16 RR-104A AT END OF SCALE 851022 68 039582 OPS DESIGN OF FAILS TO RECORD SENT FOR REPAIRS 10 TR-102 RECORDER DATA l 851011 76 037533 OPS UNKNOWN ALARM IS IN NONE-TESTED PROPERLY 2 ZONE 4 ON FIRE PANEL l

I l 851021 76 037605 OPS BURNED POWER WILL NOT TEST- REPLACED POWER SUPPLY ,

8 CP-132 SUPPLY, BLOWN COMM. ALARM IN FUSE FUSE 851023 76 037608 OPS UNKNOWN BENT PIN STRAIGHTENED PIN - 6 74A RELAY NO REPLACEMENT 851016 76 038961 OPS FAULTY ALARM BELL ALARMS DID NOT REPLACED BELL, 8 ALARM BELL IN SYSTEM - OPERATE TESTED ALARMS l 850927 93 039136 OPS LOOSE ALLENS, DOESN'T MATCH TIGHTENED BOTH, 10 l

LI-101A-6A LOOSE NUT DIPSTICK LEVEL PERFORMED IMP-93.5 l

l Page l

l R

I S -

AER 4 PMU 6 -

EIO 1 RTH e g

a P

S N N EE E KDE LE AUC LP TLN AA CE T NER D ORR ED IPU NE T C ET COE TS ATR HU GJ I D TA N L FO HE OI CV T TE SC AL T TN M N LU K A UF TC L SL I P EA 'N T RM SS R EP E CI YW DD TO IPY R R ORA HAf TEM ULL 5 N ACS 8 O ,

U 9 FI S RNE 1 OT N E C C EST WKN R EN LDN OCA E SU LEE PIN B UF AEM RE O AL NT KTT T CA E S RAN C M SEU OPI O OPJ YZA OAD TM LTA WI EF N .

A D E

S T E WC S M OE P A HT O J E D

O .

N O N

T B S T 6 E N 7 -

U E 3 B Q N 1 1 E O 9 0 R P 3 1 M 0 -

K O I R C L O

W M

E T

S 3 Y 9 S

3 E 0 T 0 A 1 D 5 8

t

IEW W)HK PGER AlHERITY i --

JAMES A. FlTZPA'IRIm ECEAR PGER PIANT '-

SAFEIY REIA'IED Fm'IRICAL & MCHANICAL MAINIPNANCE SIMinRY L, OCIDBER 1985 nrrAIR: m.

ERK RBQWST f . -TDE IMIE SYSTEM CMP 0 DENT HOW IEIECIED CAUSE OF MAIRNCTION ACTION TAKEN 'IO PpwmW RECURRENCE HOURS 10/10 66 - 29554 OPS Dirty Y Strainers Cleaned Y strainers. 74 UC-22 A then K

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ ___________---______________________ ----________________________-___--___________________x 10/9 27 37578 OPS Bamet Gaaket Tak Replaced bonnet gasket. 8 FCV-122B

__ -- _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ - - - _________________________________________ e 10/8- 13 39022- -OPS Cracked Overload Relay Replaced overload relay'and case. 8 EN-1A Case

________--__--____________________--________________________________________________c 10/7 71 -37529 OPS Circuit Board Failure Replaced A-Z circuit board. 84 INV-3A

________--_________________________________________c 10/22 01-125 37574 OPS Worn Drive Belts Replaced drive belts 18-FN-1B 10/22 93 37595 OPS Failed Contactor Coil Replaced contactor coil.. 5 l

m-3A

____________________________________________________________________--__________________________c 10/22 :71 30710 OPS Failed Reversing ' Replaced reversing starter contactor. 2 C-153-OFI Starter Contactor

___________ _ _ _ _______________ _ ____________ _ ---______-- _________________--________________________________c l 10/28 23 41497 OPS Failed Position Replaced switch. 4 HOV-2 Indicating Switch

_________ ___________ _ _ _ ______________________________-----____________---__ --_____________________________________c 10/28 13 37638 OPS Torque Switch Failure Replaced torque switch and motor. 16 M N-131

_______-- ___________________________--_______________ ________ -________________________________________________c 10/28 71 39140 OPS Broken Fbse Holder Replaced fuse holder. 1 BKR-10650

_________________________________________________________________________________________________________________e

PEF M POWER AUIMRITY ...'

, JAMES A. FITZPATRIG NUC AR POWER PIANT *<

SAFE 1Y REULIED EWCIRICAL & MECHANICAL MAINITNANCE SlDNARY -

OCI0BER 1985' wrAIR-l ~~ M REQUEST-# TIME DATE SYSIDI CWFWENT -IN DEIECIED CAUSE OF MAIR]NCTIN ACTION TAKEN TO PRFrTI1nE RECURRENCE H0lRS L* 10/30 13- 37612 . OPS Wom Valve Packing Replaced packing. 10

.RCIC-698A l  !

10/31 .13 38001 . PMs- Bent Declutch Imver Replaced lever shaft.- _2 .

N N-132 Shaft

... - --------- --- __ =----------==== _------------------== -------------------------------------------

10/31- 38429 OPS Ioose Incking Screw Replaced SMB-1 Limitorque with 46 MN-16 Causing Torque Setting with SB-1 Style Limitorque, to' Change & T imitorque Motor Failure

-- __ _-- ---------------==__---- =------------------ __===----------------------------------------------------

T e

' , . - e sy- -

-y y v ==

r"-

James A. Fit:Pitrick Nrlear Power P! ant PO. Ebu 41 Lycoming. New York 13093 315 342 3840 Radford J. Converse

  1. > NewYorkPbwer 4# Authority Novembver 7, 1985 JAFP 85-0895 Director, Office of Inspection and Enforcement U.S. Nuclear Regulatory Commission Washington, D.C. 20555 ATTENTION: DOCUMENT CONTROL DESK

REFERENCE:

DOCKET NO. 50-333

Dear Sir:

Enclosed please find the J. A. FitzPatrick Operating Status Report for the month of October, 1985. Refueling information remains the same as previously submitted.

If there are aay questions concerning this report, please contact John Cook at (315) 342-3840, Ext. 439.

L.

M RADFOLD J. CONVERSE RJC:JPC:mac Enclosures cc: Distribution l