ML20132F461

From kanterella
Jump to navigation Jump to search

Forwards List of Facility Change Requests Re Fire Protection Scheduled for Completion at End of Fifth Refueling Outage to Begin in Sept/Oct 1986.List Prioritized 25 Most Important to Nuclear Safety
ML20132F461
Person / Time
Site: Davis Besse 
Issue date: 09/26/1985
From: Williams J
TOLEDO EDISON CO.
To: Stolz J
Office of Nuclear Reactor Regulation
References
1186, TAC-52156, NUDOCS 8510010331
Download: ML20132F461 (2)


Text

,

s TOLEDO

%m EDISON Docket No. 50-346 JOE VVILUAMS. JR.

Senor Vce Presdent-Nuclear License No. NPF-3

$l$$$$

Serial No. 1186 i

September 26, 1985 Director of Nuclear Reactor Regulation Attention:

Mr. John F. Stolz Operating Reactor Branch No.-4 Division of Licensing United States Nuclear Regulatory Commission Washington, D. C.

20555

Dear Mr. Stolz:

On April 3, 1985 (Serial No. 1137), The Toledo Edison Company (TED) committed to submit a realistic implementation schedule for fire protec-tion modifications to be completed through the end of 1986. Attached to this letter is a list of the Facility Change Requests (FCR's) currently identified for completion at the end of the fifth refueling outage pre-sently scheduled to begin in September / October 1986.

As previously identified in our letters of September 6, 1984 and April 3, 1985 (Serial No's. 1076 and 1137), TED has completed the prioritization of the identified FCR's.

The attached list of 24 FCR's has been prioritized as the "most important to nuclear safety" modifications required to achieve full compliance with 10 CFR 50 Appendix R.

These FCR's will be implemented by the completion of the upcoming (fifth) refueling outage.

TED will accelerate our actions in order to achieve compliance with Appendix R prior to the end of the sixth refueling cycle as compared to our previous commitment of the seventh refueling cycle. We will promptly notify you in writing of any change to this commitment.

It should be noted that the attached list consists of FCR's in conceptual design, in detailed design and some which are being implemented.

Very truly yours, 8510010331 850926 ADOCK O5000346 JW:TJB:sm PDR

[00y PDR F

I Attachment e I cc: DB-1 NRC Resident Inspector, w/a THE TOLEDO EDISON COMPANY EDISON PLAZA - 300 MADISON AVENUE TOLEDO, OH;O 43652

p si Docket No. 50-346 License No.,NPF-3 Serial No. 1186 September 26,-1985 Attachment-I Fire Protection Modifications FCR No.

Description Status 81-0321 Barrier Mod. - 2 New Dampers In Field Working 83-0137 Barrier Mod.. Upgrade 1 Damper In Field Working 83-0148 Barrier Mod. - Modify 48 Damper Openings In Field Working

~

83-0149 Barrier Mod. - Relocate and Upgrade 1 Damper In Field Working 83-0150 Barrier Mod. - Relocate and Upgrade 1 Damper In Field Working 84-0007 Barrier Mod. - 2 New Dampers In Field Working 84-0008 Barrier Mod. - Remove Blades from 20 Dampers In Field Working 84-0041 Barrier Mod. - Upgrade Wall to 3 Hour Detailed Design 84-0044 Barrier Mod. - Upgrade Wall to 3 Hour, 2 New Dampers Detailed Design 84-0053-Barrier Hod. - Provide New 3 Hour Wall In Field Working 84-0072 Barrier Mod. - 1 New Damper

-_ Detailed Design 84-0091 Barrier Mod. - Upgrade Cont. Shield Wall to 3 Hour Detailed Design 0093 Barrier Mod. - Upgrade Walls Detailed Design 84-0094 Barrier Mod. - Upgrade Walls Detailed Design 84-0133 Barrier Mod. - 4_New 3 Hour Dampers Detailed Design 84-0175 Safe Shutdown Mod. - Reroute / Protect Cable'

. Conceptual Design 84-0177 Safe Shutdown Mod. - Electrical Isolation Conceptual Design.

84-0178 Safe Shutdown Mod. - Reroute / Protect Cable Conceptual Design 84-0179 Safe Shutdown Mod. --Reroute / Protect Cable Conceptual Design 84-0183-Safe Shutdown Mod. - Electrical Isolation-Conceptual Design.

84-0186 Safe Shutdown Mod. - Electrical Isolation Conceptual Design 84-0209 Barrier Mod. - Upgrade Wall Conceptual Design

-l 85-0001 Barrier Mod. - Upgrade Wall Conceptual Design I

85-0063 Ground Fault Protection for Electrical Isolation:

Conceptual Design 1 - Power feed to battery changes DBC2PN 2 - CCW Pump Room HVAC Exhaust Fan 1-1 3 - Power Feed to MCC EF12C I