ML20107E737

From kanterella
Jump to navigation Jump to search
Forwards Preliminary AO Rept 50-219/74/1
ML20107E737
Person / Time
Site: Oyster Creek
Issue date: 01/07/1974
From: Carroll J
JERSEY CENTRAL POWER & LIGHT CO.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
Shared Package
ML18039A986 List: ... further results
References
FOIA-95-258 NUDOCS 9604220063
Download: ML20107E737 (1)


Text

-

o To:

James P. O'Reilly Directorate of Regulatory Operations Region !

631 Park Avenue King of Prussia, Pennsylvania 19406 J

\\

l Prom:

Jersey Central Power.4 Light Company Oyster Creek Nuclear Generating Station Docket #50-219 Forked River, New Jersey 08731

), I normal.0ccurrence Report No. 50-219/74/1 Subj ect:.

I The following is a preliminary report being submitted in compliance with the Technical Specifications paragraph 6.6.2.

Preliminary Approval:

t b

4

/ 7/ 74 V

h. T. Carroll, Jr.

Date,,,,/

cc:. Nr. A. Ginsbusso W

9604220063 960213 PDR FOIA DEKOK95-258 PDR

Report Datot 1/7/ 74 Oc'aurrenc3:

1105 O

OYSTER CREEK NUCLEAR GENERATING STATION FORKED RIVER,.NEW JERSEY 08731 Abnormal occurrence Report No. 50-219/74/ 1 IDENTIFICATION Violation of the Technical Specifications, paragraph 2.3.7,

0F OCCURRENCE:

low Pressure Main Steam Line Pressure Switch (RE23C) was found to trip at a pressure less than 850 psig.

s

n pN e

4 His event is considered to be en abnormal occurrence as de-1 fined in the Tednical Specifications, paragraph 1.15 A '__ _ _.

1 CCDIDITIONS PRIOR TO OCCL7RENCE:

X _Ste.dy State Power Routine Shutdown Hot Standby Operation Cold Shutdown.

Load Changes During Refueling Shutdown Routine Power Operation Routine Startup Other (Specify)

Operation he major plant parameters at the time of the event were as follows:

Power - Core, 1830 W t

~

Elec., 642 We' (g Flow '..Recirc., 60.2 X10l 6/hr Peed.,

6.77 X10' # hr l

Stack Gas - 24,000' WC1/Sec i

DESCRIPTION On Fridy, January 4,1974 at 11,05, while performing surveil-l OP OCCURRENG:

l lance testing on the four Main Steam Line Low Pressure Switdes, j

RB23A, B, C, and D, RE23C was found to trip at 841 psig which is 9 psig below the minimum required setpoint of 850 psig. De other pressure switches were found to trip at the following

,j values:

{l RE23A - 850 psig

_ RE238 - 851 psig -

RB23D - 851 psig-M 4b W

~

w

~ Repsrt No. 50-219/74/1 Pige 2 O

APPAREE CAUSE Design Procedure OP OCCURRENCE:

~ Manufacture Unusual Service Condition Installation /

Inc. Environmental Construction Component Failure Operator 0ther (Specify)

At this time, the cause of this event, whid has occurred in the past, has yet to be determined.

In the past, the manu-facturer had been contacted and had informed plant personnel j

that the problem of setpoint drift has been recognized with this type of instrument.

An investigative program'has been initiated by the manufacturer, but no formal report on the results issued as of yet.

W l

ANALYSIS OF As indicated in the bases of the Technical Shcifications, "The OCCURRENCE:

low pressure isolation of the Main Steam Lines at 850 psig was provided to give protection against fast reactor depressuriza-i tion and the resulting rapid cooldown of the vessel. Advant-l age was taken of the scram feature which occurs when the Main i

Steam Line Isolation Valves are closed to provide for reactor l

shutdown so that high power operation at low reactor pressure f.

does not occur, thus providing protection for the fuel cladding 1

integrity safety limit."

i With regards to power operation below 850 psig and the atten-dant effects on the fuel cladding integrity safety limit, power l

a level must be limited when pressure is less than 600 psig or l

1

I Report Ho[ 50019 74[^3

~'

" ^ ~

~

~

~

- ~

~ ~ ~ ~ ~

Page 3 b

~

)

i flow is less than 10% to 354 Nft or approximately 18.3% of rat ed.

As stated in the Technical Specifications, "The value is applicable to ambient pressure and no flow conditions.

For any greater pressure or flow conditions there is increased margin." no fuel cladding integrity safety limit curve has been developed and is applicable for pressure in excess bf 600 psig.

Derefore, whether a reactor scram occurs at 850 psig or 841 psig has little safety significance since no severe restrictions on critical heat. flux are imposed until pressure is less than 600 psig.

In addition, the remaining three (3) sensors were operable and would have performed the protective action, if required and at the proper setpoint of I

>850 psig.

CORRECTIVE 1he pressure switch (RB23C), upon discovery of this condition, ACTION:

was reset to 850 psig to conform with the Technical Specifi-cations.

Recommendations to correct the abnormal occurrence and pre-f l

vent repetition of the occurrence and of similar occurrences will be provided after review by the Plant Operations Review Comaittse, i

FA1WRB DATA:

Manufacturer data pertinent to these switches are as follows:

I 4

4

~.

. Abnormal Occurrcne'>

keport No. 50-219/74/J Page 4 Heletron Corp. (subsidiary of Barksdale)

IAs Angeles, Californi6 Pressure Actuated Switch Nodel 372 Catalog #372-6SS49A-293 Range 850 G Dec.

Proof Psi. 1750 G h

Date:

/ ////

Prepared by:

s m3[

,.+- --

=l f/

o

_m.

e

=.

~

a P Q[

lersey Centra' Pc{her & Light Company MADISON AVENUE AT PUNCH BOVA. ROAD

  • MORRISTOWN, N.Jio7960 e 201539-6111 utnue or tus P,,'.[j"] Public Utilities Corporation General

.rme January 7, 1974 Mr. A. Giambusso Deputy Director for Reactor Projects Directorate of Licensing United States Atomic Energy Commission Washington, D. C. 20545

Dear Mr. Giambusso:

l

Subject:

Oyster Creek Station Docket No. 50-2I9 Reset' Problem with Test Spool Valve for Main Steam Isolation Valve NSO4A

]

This letter serves to report the failure of the test spool valve for NSO4A to properly reset after, a 5'5 closure test. The faulty operation of the test valve resulted in a condition which may have caused the main steam isolation valve (MSIV) to close slower than normal should an isolation signal have occurred during the test interval.

This event is considered to be an abnormal occurrence as defined in the Technical Specifications, paragraph 1.15D.

Notification of this event, as required by the Technical Specifications, paragraph 6.6.2.a, was made to AEC Region I, Directorate of Regulatory Oper-ations by telephone and 'telecopier on Thursday, December 20, 1973.

During the daily 5'5 closure exercises conducted on MSIV NSO4A on

}

December 18 and 19, pressure transients of 6 psig and 10 psig, respectively, were observed due to apparent valve overtravel.

An analysis of the prob 1cm indicated that possibly the overtri il was caused by the test spool valve not resetting properly.

On December 19, the reactor power was reduced to 853 MNt 4

(<40*. of rated power) to facilitate further examination of the test spool valve as_semb ly.

A 5's valvo closure test was performed with an instrument technician observing the valve.

The sticking condition had apparently worsened, allowing the MSIV t'o go approximately 50% closed before reopening in a normal manner.

'Duiing the test interval (approximately 2-3 minutes), if a situation existed whereby. had-MSIV NSO4A roccived a signal to isolate, it is unlikely that the valve would have met. the required closure time of <10 seconds since the exhaust air from the underside of the valve operator piston must pass through the test valve ~ assembly.

Because of the malpositioned valve assembly, the exhaust. air from the operator would have been restricted, thereby increasing bg5 g

e4puwg 4wi

i_ - -

},.

~

i Mr. Giambusso -

January 7, 1974 l6 s

the Valvo clos 0re time. The consequences of this event are minimized since

.NSO4A would eventually close and the redundant valve, NS03A, would have provided isolation and closed in the required time, in the event of a reactor isolation.

Furthermore, the " slow closuio condition" was only present for the length of time the St closure test was in progress (2-3 minutes).

The test spool valvo assembly for NS04A was replaced.. A 5% closure test and also a full closure timing test (6.7 seconds) were satisfactorily completed.

Upon removal and disassembly of the test spool valve, foreign material resembling red powder was found on and between the spool and sleeve assembly.

It has not been conclusively dete' mined that this material was the cause of the r

valve sticking.

The spool assembly is being sent to a testing lab for further

+

examination.

Until the laboratory analysis on the defective test spool assembly is completed and a cause for the valve sticking is conclusively determined, the operation of the test valves on all four MSIVs will be closely observed for further evidence of this problem.

'It is recognized that sticking is not a new probicm.with the 4-way air-and-spring operated valves (Numatics) used in the control circuits of the MSIVs at Oyster Creek, and work is in progress to formulate a modification to provide final resolution of this situation. The General Electric Company has recommended a modification to the MSIVs in which the present "Numatic" valves would be replaced with " Automatic" valves and manifold assemblics.

This modi-fication is currently being reviewed by appropriate groups within Jersey Central Power G Light Com'pany's Generating Department and, if adopted, an attempt till be made to have the installation work completed during the next refueling out-age presently scheduled for April 1974.

Enclosed are forty copics of this report.

'Very truly yours, 59lAt W.L ~

Donald A. Ra'ss Manager, Nucicar Generating Stations Cs cc: Mr. J. P. O'Reilly, Director Directorate of Regulatory Operations, Region I l

i

p l

. +..,

c

~l.

V.Qfls ersey Cent'ral pow (ier & Light Conipany 1y 8

MADISON AVENUE AT PUNCH DOWL ROAD + MORRISTOWN,N.J.07960

  • 201539-6111

.... u on g',.,'.yJ,

Pubhc Utihties Corporation cenerai

,rm.

January 3,1974 0 11 lp 40 A

Mtu6 q W4 Ftr. A. Giambusso N

Deputy Directvr for Reactor Projects 3

53. y',$3 Directorate of' Licensing nio *1 4

n United States Atomic Energy Commission f

W 5"#

9 Washington, D. C. 20545 tj7 g

Dear Mr. Gianbusso,

S

Subject:

Oyster Creek Station Docket No. 50-219 Spill of Chromated Water On December 20, 1973 at 7:00 a.m., a spill of approximately 3400 gal-lons of lightly contaminated radioactive chromated water occurred at the Oystcr Creek Nuclear Generating Station.

Ftr. Caphton of the Region I Regulatory Ope.r-ations Office was notified at 9:00 a.m. on December 20, 1973 of this incident and requested that a letter of explanation be forwarded for their review.

The spill occurred as 'a result of a. drain line from a temporary storage tank containing the water freezing and subsequently cracking during the severe cold weather oyer the past several days.

Warm weather on December 20 thawed the drain line and allowed a portion of the water stored in the tank to drain onto the ground inside the plant security area.

Upon discovery by oper-ating personnel during a routine plant tour, the Icak was stopped and the water contained in a relatively small area (40' x 150') adjacent to the radwaste building.

Innacdiate efforts to cican up the spill were made by pumping the water laying on the surface of the ground into containers.

A total of approxi-mately 1300 gallons was recovered in this manner.

The remaining water in the storage tank was pumped into containers.

A total of approximately 1300 gallons was recovered from the tank.

The amount of water that 1 caked into the soil amounted to approximately 2100 gallons, containing a total of 1.7 pounds of Cr03 This water also contained approximately 5.17x10-4 pCi/cc or a total of 0.004 Ci of activity.

Shallow wells are being drilled to permit subterranean water analyses, core sampics taken, and puddle water analyzed to determine the extent of the contamination and establish the best means of completing the cican up offorts.

On December 22, four new shallow wells ucre drilled in the area of the spill.

Sampics from these wells and an existing well in the nearby vicinity f were analyzed for chromate.

The well sampics. indicated that chron. ate 'was not y

present..

1,..,.!

((

s.

p

-WOS&hY@ 2PP

s 0

J Mr. Giambusso January 3,1974 On December 20, representatives of the USAEC, State of New Jersey, Department of Environmental Protection and. the Federal EPA were advised of this event.

The following day, a news release was mailed to area newspapers, copy of which is attached.

Mr. David Longstreet of the New Jersey Department of Environmental Protection came to the site on December 20, 1973 and obtained sampics of the water in the Icaking tank, the water underneath the tank, the soil underneath the tank and background soil and water samples some distance from the area of concern.

Mr. Fisher of the New Jersey Bureau of Radiation Protection also came 9

to the site and took a sampic of water from the tank and'a sampic of the soil p

underneath the tank.

Analysis results from those samples have not been made availabic as of this time, y'

Plans are being made to install some temporary heating in the remain-ing eleven tanks until a rubber liner can be properly set up which will eventually be capabic of containing the water presently stored in temporary tanks.

Because of unanticipated difficultics in developing an acceptabic chromate disposal method, we intend to proceed with an alternate storage method to replace the temporary tanks. This will consist of a 50,000-gallon rubber bag placed in a t rench.

This trench will be lined to prevent uater seeping into the ground in the unlikely event of a Icak developing in the rubber bag.

Our original approach was to use a precipitation method for the ultimate disposal of this chromate.

This method has not been able to mcqt the State of New Jnyscy, Departent of Environmental Protection's requirement of 0:05 mg/l concentration prior to dis-charge.

The Jersey Central Power 6 Light Company's Generation Engineering Department l~s presently investigating the feasibility 7f an activated charcoal absorption method to meet the State's dischar.ge requirements.

Enclosed are forty copics of this report.

Very truly yours, MfdY

'/ S-t;fd -

Donald A. Ross Manager, Nuclear Generating Stations es Attachment cc:

Mr. J. P. O'Reilly, Director Directorate of Regulatory Operations, Region I 4

/-

,,e rosa L;'-

C3

~ l cw~

ersey 'Gentral' Poser & Light Company y

v>

MADISON AVENUE AT PUNCH BOYA. ROAD

  • MORRISTOWN,N.J. 079G0
  • 201539-6111

..=, or ras g fi'.**' Public Utilities Corporation

),

-cenerat ann.

January 4, 1974

, 25%

'g/)5

4..jf tf %

Mr. A. Giambusso g fD 9,

Deputy Director for Reactor Projects ff

u, e

J M', !NQ Directorate of Licensing 7

United States Atomic Energy Commission Washington, D. C. 20545 f t1[F'[m OS p.,.f6

Dear Mr. Giambusso:

Subject:

Oyster Creck' Station

' /jf}

Docket No. S0-219 Drift in Set Point of Isolation Condenser High Flow Sensors This letur serves to report the failure oi four isolation condencer high flow sensors to trip on AP values that conform to those stated in Tech-nical Specification Table 3.3.1.11 (120 psid - steam,127. inches AP H O -

2 condensate).

This event is considered to be an abnormal occurrence as defined in i

the Technical Specifications, paragraph 1.15A.

Notification of this event, as I

required by the Technical Specifications, paragraph 6.6.2.a, wa ber 21, 1973, and by telecopier on Wednesday, December 26, 1973.

j On Friday, December 21, 1973, while performing surveillance testing i

on the isolation condenser high flow sensors (two each per condensate and l

steam lino per condenser), four of the sensors were found to trip at set points in excess of their respective limits. Specifically, the sensors of concern and l

their corresponding "as found" set points were as follows:

Condensate "A" Condenser IB11A1 - 29" of water i

IB11A2 - 31" of water 181182 - 29" of water Steam f

"B" Condenser IB05B1 - 22 psid The reason for the drift in set points is yet to be determined.

27.1 nn.

m ~7yfyv 9 p TLW

~. _

-, _. _ ~

J

.y January 4,1974 p;

~

. Mr. Giambusso~

~4 Upon discovery of the condition, the instrument technician performing the surveillance test reset the affected differential pressure (d/p). sensors to their required values (<27 inches 110 on condensato and <20 psid on the steam).

e 2

The safety implication of this' cvent is minimal, since the sensors were operabic and would have performed their function.

Past data has shown that upon initiating the condensers, the condensate line senses d/p ir excess of 60 inches of water; therefore, although the set point had drifted, the new value was well within the range-of the expected signal and the sensor was capabic of performing its protective action.

A review of the surveillance procedures will be made to insure that the test and calibration methods' and instruments are consistent with the capability of the instruments under surveillance.

J In addition, an investigation will be made into the _ feasibility of submitting a Technical Specification change to include tolerances on instrument

,, trip set points to account for instrumentation design accuracies where applicable.

}

Enclosed are forty copies of this report.

Very truly yours, (hi&b;L.

l W

Donald A. Ross Manager, Nucleae Generating Stations

~

cs Enclosures cc:

Mr. J. P. O'Rc'111y, Director Directorate of Regulatory Operations, Region I i

l l

-1 f

l

\\

._ _ i

' '~

v-n ;;

. jersey Central Pher & Light Company MADISON AVENUE AT PUNCH BOWL ROAD + MORRISTOWN, N.J. 07960

  • 201-539-6111

.., =

g,.g*

Public Utilities Corporation cenerat ama 7 53 '

January 7,1974

& J@ ~ 3 m Mr. A. Giambusso h

4. n: ::..[,,

Deputy Director for Reactor Projects

,;/,

[

';f "

Directorate of Licensing

'y U [.3

,/

t United States Atomic Energy Commission

',97 %. gN '

N Washington, D. C. 20545

/kl iu

Dear Mr. Giambusso:

Subject:

Oyster Creek Station Docket No. 50-219 Reset Problem with Test Spool Valve for Main Steam Isolation Valve NSO4A This Ictter serves to re for NSO4A to properly reset after' port the failure of the test spool valve j

a 5% closure test.

The faulty operation.of the test valve resulted in a condition which may have caused the main steam isolation valve (MSIV) to close slower than normal should an isolation signal have occurred during the test interval.

This event is considered to be an abnormal occurrence as defined in the Technical Specifications, paragraph 1.15D.

Notification of this event, as required by the Technical Specifications, paragraph 6.6.2.a, was made to AEC Region I, Directorate of Regulatory Oper-ations by telephone and telecopier on Thursday, December 20, 1973.

During the daily 5% closure exercises conducted on MSIV NS04A on

' December 18 and 19, pressure transients of 6 psig and 10 psig, respectively, i

were observed due to apparent valve overtravel. An analysis of the problem indicated that possibly the overtravel was caused by the test spool valve not resetting properly.

On December 19, the reactor power was reduced to 853 NWt

(<40% of rated power) to facilitate further examination of the test spool valve assembly.

A 5% valve closure test was performed with an instrument technician observing the valve. The sticking condition had apparently worsened, allowing the MSIV to go approximately 50% closed before reopening in a normal manner.

During the tiest interval (approximately 2-3 minutes), if a situation existed whereby had MSIV NSO4A received a signal to isolace, it is unlikely that the valve' would have met 'the. required closure time of <10 seconds since the exhaust air from the underside of the valve operator piston must pass through the test valve assembly.

Because of the malpositioned valve assembly, the exhaust air from the operator would have been restricted, thereby increasing 9

pasc u co 4

,* A 9

\\

e

)

~

3

,Mr. Giambusso January 7,1974 s

the valve closure time. The consequences of this event are minimized since NSO4A would eventually close and the redundant valve, NS03A, would have provided isolation and closed in the required time, in the event of a reactor isolation.

Furthermore, the " slow closure condition" was only present for the 1ength of time the St closure test was in progress (2-3 minu'es).

The test spool valve assembly for NS04A was replaced.

A 5'. closure test and also a full closure timing test (6.7 seconds) were satisfactorily 1

completed.

Upon removal and disassembly of the test spool valve, foreign material resembling red powder was found on and between the spool and sleeve assembly.

It has not been conclusively determined that this material was the cause of the valve sticking.

The spool assembly is being sent to a testing lab for further examination.

l Until the laboratory analysis on the defective test spool assembly is completed and a cause for the valve sticking is conclusively determined, the operation of the test valves on all four MSIVs will be closely observed for further evidence of this problem.

It is recognized that sticking is not a new' problem with the 4-way air-and-spring operated valves (Numatics) used in the control circuits of the MSIVs at Oyster Creek, and work is in progress to formulate a modification to provide final resolution of this situation.

The General Electric Company has recommended a modification to the MSIVs in which the present "Numatic" valves would be replaced with " Automatic" valves and manifold assemblies. This modi-fication is currently being reviewed by appropriate groups within Jersey Central a

Power 6 Light Company's Generating Department and, if adopted, an attempt will be made to have the installation work completed during the next refueling out-age presently scheduled for April 1974.

Enclosed are forty copies of this report.

Very truly yours, yh.

J.4d -

Donald A. Ross Manager, Nuc1 car Generating Stations es cc:

Mr. J. P. O'Reilly, Director Directorate of Regulatory Operations, Region 1 g

O O

o

w 4

r.

p.4 YRil v-a us

.crsey Central Power & Light Company ] Y(([f MADISON AVENUE AT PUNCH BOWL ROAD

  • MORRISTOWN, N.J.07960
  • 201539-6111 usana ar rue y,.

]

f,Z. Public Utilities Corporation cenerat

,rm, January 2, 1974

' ~.

o9 Mr. A.'Giambusso E'

97 Deputy Director for Reactor Projects t.t :

3 q

6(:"

Directorate of Licensing United States Atomic Energy Commission Washington, D. C. 20545 Q,

Dear Mr. Giambusso:

Subject:

Oyster Creek Station Docket No. 50-219 Unexplained Isolation of the "B" Isolation Condenser The purpose of this letter is to report to you, as a matter of ir.torcst, ar. unnplained isolation of une "B" isolat.lon condenser during a -

routine reactor cooldown operation that took, place on November 25, 1973.

Notification of this incident was verbally made to Mr. E. Greenman, AEC Region I, ' Directorate of Regulatory Operations on Monday, November 26. 1973.

Each of the two isolation condensers is equipped with flow sensing differential pressure (d/p) instrumentation on the condensate return and steam supply elbows.

The system is designed to isolate when the d/p instrumentation senses a flow three times rated which would be indicative of a ruptured line.

This condition corresponds to a d/p signal of 27 inches of water on the con-densate return line and 20 psi on the steam supply.

Experience has shown that during normal system initiation, the in-rush flow through the condensate elbow exceeds the isolation d/p set point significantly.

The peak had, in the past, caused the d/p sensor to exceed its-uppermost limit causing mechanical damage to the Barton sensor.

To. correct this problem, dampening snubbers were added to the instrument sensing lines which suppressed the peak to within the instrument limits.

The peak differential i

pressure sensed on the condensate elbow with the snubbers installed was measured to be approximately 64 inches of water and the time the set point was exceeded was approximately 15.5 seconds.

Since the inrush transient is intrinsic to the system, it was necessary to delay condenser isolation for a time period in excess of the pulse duration of 15.5 seconds.

A time delay relay set for 35 seconds was used to satisfy this condition and still permit isolation in the required 60 seconds.

4ekv*sw

/y

?

~~

}, _

3,.

e Mr.' Giambusso 6 - January 2, 1974 lit sho' uld be noted that the duration of the pulse is directly attributabic to the

  • time constant of the snubbers used and if the snubber characteristics change with ' time the appar'ent pulse-duration can be increased.

~-After the November 25, 1973 scram, the "B" isolation condenser was initiated in order to control reactor pressure by opening the DC drain valve,-

V-14-35.

The " rupture alarm" was reported to have. sounded inamediately upon initiation but an isolation of the condenser did not occur at this time.

Normally, isolation would commence' exactly the same time as the alarm comes in, since both the alarm and isolation are actuated when the time delay relay completes its cycle without the d/p sensor retu.n: ng to below 24 inches of water-(the reset point). _ lt was then reported that as the valve was being closed

'(approximately ono-half minute after initiation), an isolation occurred and the-rupture; alarm again sounded. The first alarm is thought to be spurious due to.

. adjacent relay " noise",~ a condition which has been observed in the past. How-ever, based on past experience with the system, it is felt that a true isolation

- signal was present coincidently at this same time which caused the condenser

. isolation time delay relay to start its cycle.

The relay timed out just as the condenser was being returned to the standby condition, hence the isola' ion t

and the second alarm actuation. This event indicated that the pulse duration, as sensed by the d/p instrumentation, exceeded the isolation set point for a period in excess 'of 35 seconds which is a marked increase over the normal pulse duration ~ of 15.5 seconds as measured previously.

The 4 -~

in pulse duration was traced to a corresponding increase in the condensate instrument sensing line snubbers time constant. There are two-snubbers per d/p sensor and there are four separate d/p sensors per condenser, two on each of the condensate and-steam legs. A pressure decay test was performed l

on each sensor for the condensate legs on both the "A" and "B" isolation condensers.

The test basically consisted of imposing a d/p of 60 inches of water on each sensor j

and, measuring the time required to decay down to the reset d/p of 24 inches of water through the two snubbers in the sensing lines. The following are the re-sults of these tests:

-Isolation Condenser "A" Sensor BilAl - 2 seconds i

Sensor B11A2 - 35 seconds

. Isolation Condenser "B" Sensor B1181 - 17 seconds Sensor B1182 - 10 seconds The ' time constants for both the "A" and "B" isolation condensers are felt to be I

large enough to cause an isolation during normal initiation.

It was initially report-

^

ed that both condensers had' isolated but it has since been determined that only the "B" isolation condenser did indeed isolate.

j i

The snubbers were replaced and the pressure decay tests yielded results

+

.which are as.follows:

4 J

w..

s s.

Mr. Giambusso January 2, 1974 Isolatiop Condenser "A" Sensor *BilAl - 2 seconds Sensor B11A2 - 4 seconds Isolation Condenser "B"

.-Sensor B11B1 - 3.5 seconds Sensor B11B2 - 3 seconds liad a bonifide condition existed whereby the isolation condensers were required to serve as a back-up heat sink under reactor isolation conditions, the "B" condenser would have isplated, thereby eliminating it as a back-up heat sink. The "A" condenser would have performed this function, however, since a single operable condenser is capable of removing the decay heat after a scram from 1950 MWt for 45 minutes before makeup is required and with approximately 107,500 gallons of makeup water ull cooldown could be achieved. The safety

. significance, therefore, is in tne loss of redundancy in the system.

It should be noted that the "B" isolation condenser was reinitiated and it again isolated under very much the same circumstances. After the third initiation, however, the condenser did not isolate and it was successfully used many times, along with the "A" condenser, throughout the reactor cooldown operation.

This was due to establishing " hot" condensate in the condenser which, because of its lower density reduces the magnitude and duration of the inrush flow transient.

This' was evidenced by a test run on November 14, 1973 which showed that the tran: lent peak was reduced from a cold condenser initial peak d/p of 64 inches of water and a duration of 15.5 steconds over the trip point to a peak of 32.2 inches of water and 4.1 seconds for a " hot" condenser.

i Furthermore, had a bonifide reactor isolation occurred, it should have been possibic to manually initiate and reset the "B" condenser until 1

isolation no longer occurred.

In the future, we plan to include the pressure decay tests wi.th the regular line break sensor surveillance test to permit early detection and correction of slow instrument response.

Enclosed are forty copies of this report.

Very truly yours, 7W W

Donald A. Ross Manager, Nuclear Generating Stations cs cc:

Mr. J. P. O'Reilly, Director Directorate of Regulatory Operations, Region I

/