ML20092G715

From kanterella
Jump to navigation Jump to search
Rev 18 to VEGP-13011-1, RHR Sys. Supporting Documentation Encl
ML20092G715
Person / Time
Site: Vogtle Southern Nuclear icon.png
Issue date: 03/11/1990
From: Bumaki W
GEORGIA POWER CO.
To:
Shared Package
ML20092F288 List: ... further results
References
CON-IIT05-058-90, CON-IIT05-059-90, CON-IIT5-58-90, CON-IIT5-59-90, RTR-NUREG-1410 VEGP-13011-1, NUDOCS 9202200306
Download: ML20092G715 (34)


Text

I' voeu. si.cw o.n.rseng Plent i_i

[

NUCLEAR OPERATIONS

'~

18 o.m Georgia Power unn i

ew. so.

f //g 1 of 32 e p 3P-9D

~

RESIDUAL HEAT REMOVAL SYSTEM i

da 1.0 PURPOSE This procedure provides the necessary instructions for operation of the Residual Heat Removal System (RHRS).

This procedure also provides instructions for filling the Reactor Coolant System (RCS) and/or the Refueling

>==

- --J l-Cavity and for draining the Refueling Cavity using the anE RHRS.

Instructions are included in the following C"lll3 steps:

E 4.1 Placing A Train Of RHR In Standby Readinoss 4.2 Placing The RHRS'In Service For RCS Cooldown F. -

8:Z"

'4 g

4.3 Establishing RHR Letdown i

4.4 Shifting RHR Trains 4.5 Two Train RHR Operatic,n During RCS Recirculation 4.6 Filling And Venting The RHRS E2 4.7 Filling The RCS (And The Refueling Cavity _For

~

Refueling) 4.8 Draining The Refueling Cavity 4.9 Operating RHR With One Train of Cold Leg Discharge With Its Cold Leg Flowpath Isolated For Maintenance 2.0 PRECAUTIONS AND LIMITATIONS 2.1 PRECAUTIONS 2.1.1 To prevent overheating the Cogonent Cooling Water System (CCWS), cooling water flow to the RHR Heat Exchanger should not be throttled.

2.1.2 To avoid thermal shock of the RCS components, the flow through the RHRS should be initiated and reduced slowly.

2.1.3 The RCS pressure and temperature should not exceed o' psig and 350*F when the RHRS is in service.

9202200306 920116 wou.<:sim PDR ADOCK 05000424 S

PDR

m O

FOoCEDUPE NO REVIStoN pAGE No.-

~~9 VEGP 13011-1 18 2 of 32 2.1.4 Thoroughly fill and vent all applicable RHR eomponents prior to returning them to service after maintenance.

h is minimizes system performance degradation and water hammer due to gas entrainment.

2.1.5 Only one RHR train should be altered at a time when changing system configuration.

This helps maintain RHRS operability.

2.1.6 Whenever the RCS is at 188 feet (one foot above mid-nozzle) the RHRS flow chould be limited to the lower end of a range from 3000 to 3500 gpm.

This minimizes potential loss of RHR Pump suction due to gas entrainment from vortex formation.

2.1.7 Valves 1-HV-8716A and 1-HV-8716B have a vent hole drilled on the RHR Pump side of the disc.

The valves are not capable of a leak tight seal when pressurized from the opposite Train RHR Pump, 2.1.8 When cooling down the RCS using one Train of RHR, the Recycle Evaporator should be shut down or sump 11ed from the Unit 2 ACCW System.

This minimizes the heat loads on the NSCW System.

2.2 LIMITATIONS 2.2.1 With the RCS Tavg greater than or equal to 350dF, the RMRS is required to be operable per Technical Specification 3.5.2.

2.2.2 With the RCS in Hot Shutdown, the RHRS is required to be operable or in operation per Technical Specification 3.4.1.3.

2.2.3 With the RCS Tavg less than 350'F, the RHRS is required to be operable per Technical Specification 3.5.3.

2.2.4 With RCS in Cold Shutdown, the RHRS is required to be operable or in operation per Technical Specification 3.4.1.4.1 and 3.4.1.4.2.

2.2.5 During refueling operations, the RHRS is required to be operable and in operation per Technical Specification 3.9.8.1 and 3.9.8.2.

D 2.2.6 If required for Cold Overpressure Protection, two RHR Technical Specification 3.4. quired operable per Suction Relief Valves are re 9.3.

o 2.2.7 When in Mode 1, 2, or 3 1-HV-8809A/B and 2-HV-8816A/B must remain open.

However, one valve at a time may be closed for surveillance testing.

wn m

PAOCEDUXE No.

$;EVISloN FAGE No.

VEGP 13011-1 18 3 of 32 2.2.8 The RHR Suetions From Hot Lega Loops 1 and 4 (1-HV-8701A, 1-HV-8701B, 1-HV-8702A, 1-HV-8702B) are separately interlocked to prevent from being opened with RCS pressure greater than 365 psig and to automatically close before RCS pressure exceeds 750 psig.

2.2.9 The RHR Suetions From Hot Legs Loops 1 and 4 cannot be opened unless the following valves are closed, a.

RHR PMP-A DISCH TO CHG PMPS SUCT l-HV-8804A, b.

RER TO SI PMP-B ISO VLV l-HV-8804B, c.

RWST TO RHR PMP SUCTION 1-HV-8812A/B, d.

CNMT SUMP TO RHR PMP A(B) SUCTION 1-HV-8811A/B.

2.2.10 RHR Pump Motor start limitations:

a.

Three consecutive starts from ambient temperature, b.

Two Starts from'o'perating temperature, c.

Subsequent start permitted after 15 minutes if the motor is left running or 45 minutes if motor is left at standstill.

2.2.11 Fire event safe shutdown analysis requires 1-HV-8804A and 1-HV-8804B to be de-energized while RHR is in service.

3.0 PREREQUISITES OR INITIAL--CONDITIONS 3.1 Nuclear Service Cooling Water (NSCW) is supplying cooling water to the RHR Pump Motor Coolers.

3.2 The CCWS is available and supplying cooling water to the RKR Heat Exchangers and ? ump Seal Coolers.

The RHR Pumps may be operated without CCW to the_ Seal Cooler if the system temperature-is-less than 150*F.

6L

I h

KOCEDUAE No r.Evt$loN eAGE NO.

VEGP 13011-1 18 4 of 32 4.0 INSTRUCTIONS 4.1 PLACING A TRAIN OF RHR IN STANDBY READINESS NOTE This procedure is written using Train A component designations.

Train B designations are shown in parentheses.

4.1.1 If the RHR Train is being placed in standby following maintenance, FILL and VENT the train per Step 4.6.

4.1.2 If the RHRS is being placed in standby, COOL DOWN the operating RHR Train (s) to below 200*F as follows:

a.

CLOSE Letdown From RHR l-HV-0128, b.

ADJUST Low Pressure Letdown Controller 1-PIC-0131 and charging flow as necessary to maintain desired pressurizer levdr.

MAINTAIN RCP seal injection between 8 to 13 gpm using 2-HC-0182, c.

CLOSE RHR To CVCS Letdown Isolation 1-1205-U4-021 (022),

d.

Slowly CLOSE the RHR HEAT EXCH OUTLET for Train A (B) 1-HV-0606 (0607),

e.

Slowly CLOSE RHR HEAT EXCH BYPASS for Train A (B) 1-FV-0618 (0619),

NOTE Due to leak by of RHR Heat Exchanger Outlet and Bypass Valves flowrate to RCS may be above auto open miniflow setpoint for 1-FV-0610 (1-FV-0611).

f.

If RHR PMP-A (B) MINIFLOW ISO VLV l-FV-0610 (1-FV-0611) does not auto open, PLACE l-HS-0610 (1-HS-0611) to OPEN and RELEASE and ENSURF that 1-FV-0610 (1-FV-0611) OPENS, g.

MONITOR RHR Heat Exchanger Train A(B) Inlet Temperature 1-TR-0612 (0613),

mun

'P4oCEDUAE No-LEVISioN F AGE No.

VEGP 13011-1 18 5 of 32 NOTE Allow pump to run for approximately one hour at less than or equal to 200'F for cooldown of piping, h.

When RHR Train A(B) is below 200'F, STOP RHR PUMP A(B).

4.1.3 RESTORE power to the RHR Train A (B) to CCP (SIP) suction as follows:

a.

CLOSE 1ABB-05 to valve 1-HV-8804A, b.

CLOSE IBBB-05 to valve ;-HV-8804B, c.

REMOVE tags and CLOSE "he K2 link for breaker lABB-05 and IBBB-05.

4.1.4 ALIGN the RHR train for standby per Checklist 2.

4.1.5 If RHR is bein placed in standby for MODE 3 entry, PERFORM the fo lowing: independent verification required:

a.

SHUT DOWN Inverter ICDlI5 (lDD116) per 13405-1, "125V DC lE Electrical Distribution System",

b.

OPEN the K2 links for breaker lABE-15 (lBBE-13) and TAG per 00306-C, " Temporary Jumper And Lifted Wire Control",

c.

OPEN and LOCK the power supplies to the RHR Loop 1(4) Inlet Isolaqions:

lABE-15 (IBBE-13) for 1-HV-8701A (8702B),

d.

At 1CD1I5N (ICD 1I6N) OPEN, LOCK and TAG the disconnect for 1-HV-8701B (1-HV-8702A).

4.1.6 If depressurization of the RHR System is required, either:

a.

OPEN the following:

(1)

OPEN SIS CHECK VALVE TEST CNMT ISO 1-HV-8964, (2)

OPEN SIS CHECK VALVE TEST CNMT ISO l-HV-8871, (3)

OPEN SIS RHR PMP A(B) CHECK VALVE TEST i-HV-8890A(B),

-OR-b.

HAVE Chemistry OPEN RHR TRAIN A(B) SAMPLE VALVE l-HV-3520(21).

4.1.7 If required, when RHR deprt.3surization is complete, CLOSE all valves opened in Step 4.1.63 independent verification required.

i FC W S 1

~

~

P;.OCEDunU Id~' ~ '

LEVISloN FAGE No e

VEGP 13011-1 18 6 of 32 4.2 PLACING THE RHRS IN SERVICE FOR RCS C00LDOWN 4.2.1 RESTORE power to both of the RHR PMP-A (B) SUCTION FROM HOT LEG LOOP 1(4) Inlet Isolations as follows:

independent verification required:

a.

If shut down, PLACE Inverter ICD 1I5 (1D0116) in service per 13405-1, "125V DC lE Electrical Distribution System",

b.

At ICDlI5N (ICDlI6N) REMOVE tag, UNLOCK and CLOSE the disconnect for 1-HV-8701B (1-HV-8702A),

c.

UNLOCK and CLOSE RHR PMP A(B) SUCTION FROM HOT LEG LOOP 1(4), 1-HV-8701A (8702B) Supply Breakers LADE-15 (IBBE-13),

d.

REMOVE tags and CLOSE the K2 link for breaker 1ABE-15 (lBBE-13).

NOTES a.

Removing power from 1-HV-8804A/B will also affect 1-HV-8812A/B, 1-HV-8920 and 1-HV-8702B operability from the Control Room.

Information tags should be installed on handswitches 1-HV-8812A/B, 1-HV-8920 and 1-HV-8702B stating that the valves can only be operated from the Remote Shutdown Panel.

b.

When in Mode 1, 2 or 3 ensure that 1-HV-8809A/B are not shut simultaneously.

4.2.2 ALIGN the RHRS for shutdown cooling as follows:

a.

CLOSE both of the RHR TRAIN A(B) TO HOT LEG CROSSOVER ISO l-HV-8716A and 1-HV-8716B, b.

CLOSE both of the RHR HEAT EXCH OUTLET for Train A (B) 1-HV-0606 and 1-HV-0607, c.

CLOSE both of the RHR HEAT EXCH BYPASS for Train A (B) 1-FV-0618 and 1-FV-0619, d.

CLOSE both of the RWST TO RHR PMP A(B) SUCTION 1-HV-8812A and 1-HV-8812B, e.

ENSURE OPEN both of the RER PMP A(B) TO COLD LEG 1&2 (3&4) ISO VLVs 1-HV-8809A and 1-HV-8809B independent verification required, ws

PROCEDUCE NO-REWSiON pAGE No.

=

VEGP 13011-1 18 7 of 32 f.

OPEN both of the RHR PMP A(B) UPSTREAM SUCTION FROM HOT LEG LOOP 1(4) Valves 1-HV-8701B and 1-HV-8702B, g.

OPEN both of the RHR PMP A(B) DOWNSTREAM SUCTION FROM HOT LEG LOOP 1(4) 1-HV-8701A and 1-HV-8702A.

4.2.3 REMOVE power from the RHR to Charging and SI Pump Isolation Valves as follows:

a.

OPEN the K2 ' Links for breakers lABB-05 and IBBB-05 and TAG per 00306-C, " Temporary Jumper And Lifted Wire Control",

b.

OPEN breaker lABB-05 to valve 1-HV-8804A, c.

OPEN breaker 1BBB-05 to valve 1-RV-8804B.

4.2.4 START UP one train of RHR as follows:

a.

VERIFY OPEN the RHR PMP-A (B) MINIFLOW ISO l-FV-0610 (1-FV-0611),

b.

START RHR PUMP A(B),

c.

ESTABLISH RER Letdown per Step 4.3.

4.2.5 WARM UP the RHRS as follows:

NOTE The recommended RHR to RCS temperature difference for the completion of RHR warmup is 25'F: however, the Unit Shift Supervisor (USS) may allow a greater temperature difference at his discretion.

a.

ADJUST the LOW PRESSURE LETDOWN Controller 1-PIC-0131 and/or LETDOWN FROM RHR Control Valve 1-HV-0128 as required to maintain desired letdown

flow, b.

MONITOR RHR Heat Exchanger Train A(B) Inlet Temperature 1-TR-0612 (0613) and Wide Range RCS Hot Leg Temperatures 1-TI-0413A, 1-TI-0423A, 1-TI-0433A, and 1-TI-0443A.

i g

PAoCEDUAE No A EVISioN

  • AGE No.

j VEGP 13011-1 18 8 of 32 4.2.6 When RHR warmup is completed, INITIATE full flow to the RCS as follows:

a.

THROTTLE OPEN the RHR HEAT EXCH BYPASS for Train A (B) 1-FV-0618 (0619) to establish a minimum flow rate of 3000 gpm, b.

VERIFY the RER PMP-A(B) MINIFLOW ISO VLV l-FV-0610 (0611) CLOSES, CAUTION The RHR Heat Exchanger Train A(B) Bypass Flow Controller Potentiometer should be set for a minimum flow of 3000 gym prior to placing controller in AUTO.

The potentiometer settingisapproximate{yequal to (Desired Flow /5000) c.

PLACE the RHR HEAT EXCH BYPASS for Train A (B)

Flow Controller'l*-FIC-0618A (0619A) in AUTO if

desired, d.

ADJUST the LOW PRESSURE LETDOWN Controller 1-PIC-0131 and/or LETDOWN FROM RHR Control Valve 1-HV-0128 as required to maintain desired letdown

flow, e.

Slowly THROTTLE OPEN RER HEAT EXCH OUTLET for Train A (B) 1-HV-0606 (0607) to establish desired RCS cooling.

4.2.7 If RCS cooling using both RHR trains is desired, PLACE the second train in service as follows:

a.

VERIFY the applicable RHR Train aligned per Step 4.2.2, b.

VERIFY OPEN the RHR PMP-A (B) MINIFLOW ISO VLV l-FV-0610 (1-FV-0611),

c.

START RHR PUMP A(B).

ws

PAOCEDUKE NO Revision PAGE No.

VEGP 13011-1 18 9 of 32 NOTE The recommended RHR to RCS temperature difference for the completion of RRR warmup is 25'F: however, the USS may allow a greater temperature difference at his discretion.

4.2.8 When RHR warmup is completed, INITIATE full flow to the RCS as follows:

a.

THROTTLE OPEN the RHR HEAT EXCH BYPASS for Train A (B) 1-FV-0618 (0619) to establish a minimum flow rate of 3000 gpm, b.

VERIFY the RHR PMP-A (B) MINIFLOW ISO l-FV-0610 (0611) CLOSES, CAUTTON The RHR Heat Exchanger Train A(B) Bypass Flow Controller Potentiometer should be set for a minimum flow of 3000 gpm prior to placing controller in AUTO.

The potentiometer settingisapproximate}yequal to (Desired Flow /5000)

PLACE the RHR Train A(B) Heat Exchanger Bypass c.

Flow Controller 1-FIC-0618A (0619A) in AUTO if

desired, d.

ADJUST the LOW PRESSURE LETDOWN Controller 1-PIC-0131 and/or LETDOWN FROM RHR Control Valve 1-HV-0128 as required to maintain desired letdown

flow, e.

Slowly THROTTLE OPEN RHR HEAT EXCH OUTLET for Train A (B) 1-HV-0606 (0607) to establish desired RCS cooling.

4.2.9 ESTABLISH RCS Cooldown per 12006-C, " Unit Cooldown To Cold Shutdown".

mun

PAoCEDUAE N MEVISloN PAGE No.

VEGP

-13011-1 18 10-of 32 4.3 ESTABLISHING RHR LETDOWN 4.3.1 CLOSE the LETDOWN-FROM RHR Control Valve 1-HV-0128.

NOTE Only one train of RHR should be aligned for letdown operation to prevent pressurizing the suction of an idle RHR Pump from the operating RHR train.

4.3.2 OPEN the RHR to CVCS Letdown Isolation of the-operating RHR train that will~be used for letdown -independent verification required:

a.

1-1205-U4-021 if Train A will be used for RHR

letdown, b.

1-1205-U4-022-if Train B'will be used for RHR letdown.

4.3.3 If CVCS letdown is not in service, CLOSE LOW PRESSURE LETDOWN Control Valve 1-PV-03.31.

NOTES a.

Design maximum letdown flow is 120 gpa.

b..

The Low Pressure Letdown Relief Valve lifts at 600-psig.

4.3.4 Slowly OPEN the LETDOWN FROM RHR-1-HV-0128.

4.3.5 ADJUST the LOW PRESSURE LETDGWN Controller 1-PIC-0131 and the LETDOWN FROM RHR Control Valve 1-HV-0128 as required to obtain the desired Letdown Flow 1-FI-0132C.

nnus a

p;,0CEDUME NO.

F,EVISION PAGE NO.

VEGP 13011-1 18 11 of 32' 4.4 SHIFTING RHR TRAINS 4.4.1 VERIFY the lineup on the idle RHR Train as followsi f

a.

CLOSE the RWST TO RHR PMP A(B) SUCTION 1-HV-8812A (8812B),

b.

OPEN the RHR PMP-A (B) DOWNSTREAM AND UPSTREAM SUCTION FROM HOT LEG l-HV-8701A (8702A) and 1-HV-8701B (8702B),

c.

ENSURI the RHR REAT EXCH BYPASS for Train A (B) 1-FV-0618 (0619) is.in MAN and CLOSED, d.

CLOSE the RHR TRAIN A(B) TO HOT LEG CROSSOVER ISO 1-HV-8716A (8716B),

e.

CLOSE the RHR HEAT EXCH OUTLET for Train A (B) 1-HV-0606 (0607),

f.

ENSURE OPEN the RHR PMP-A (B) MINIFLOW ISO VLV 1-FV-0610 (0611),

CAUTION Starting an RHR Pump at RCS water level below 216 foot elevation and with 1-HV-8809A (B) closed will cause water hammer in the discharge piping.

g.

ENSURE OPEN RHR PUMP A (B) TO COLD LEG 1 & 2 (3 & 4) ISO VLV 1-HV-8809A (8809B).

4.4.2 START the RHR PUMP A(B).

resu s

~PAoCEDUAE No_

OEVISION

> AGE No.

VEGP 13011-1 18 12 of 32 4.4.3 SHIFT RHR letdown to the train which is operating on minimum flow as follows:

a.

MONITOR Letdown Flow 1-FI-0132C while shifting letdown and ADJUST the LOW PRESSURE LETDOWN Controller 1-PIC-0131 and/or LETDOWN FROM RHR Control Valve 1-HV-0128 as required to maintain desired letdown flow, b.

OPEN the RHR To CVCS Letdown Isolation of the RHR train which is operating on minimum flows independent verification required:

(1) 1-1205-U4-021 if Train A is operating on minimum flow, (2) 1-1205-U4-022 if Train B is operating on minimum flow, c.

CLOSE the RHR To CVCS Letdown Isolation of the opposite trains independent verification required.

4.4.4 SHIFT flow to the RHR

  • train that was just started as follows:

a.

ENSURE OPEN the RHR PUMP A(B) TO COLD LEG 1&2 (3&4) ISO VLV, 1-HV-8809A (8309B),

b.

MONITOR RHR Train A and Train B Flow 1-FI-0618A and 1-FI-0619A and MAINTAIN total RHR flow between 3000 and 3500 gpm throughout the remainder of this

step, c.

ENSURE the RHR HEAT EXCH BYPASS for Train A (B) 1-FV-0618 (0619) of the train being removed from service is in MAN, d.

MONITOR Letdown Flow 1-FI-0132C while shifting RHR flow and ADJUST the LOW PRESSURE LETDOWN Controller 1-PIC-0131 and/or LETDOWN FROM RHR Control Valve 1-HV-0128 as required to maintain desired letdown flow, e.

Slowly THROTTLE the RHR HEAT EXCH A(B) OUTLET 1-ny-0606 (0607) and Bypass of the train being removed from service CLOSED and the RHR Heat Exchanger Bypass of the train being placed in service OPEN while maintaining total RER flow between 3000 and 3500 gpm, f.

If RHR PMP-A(B) MINIFLOW ISO VLV l-FV-0610 (1-FV-0611) does not auto open, if required, PLACE 1-HS-0610 (1-HS-0611) to OPEN and RELEASE and ENSURE that 1-FV-0610 (1-FV-0611) opens, mm

PAoCEDUAE No.

LEVISloN PAG 3 NO, VEGP 13011-1 18 13 of 32 g.

When the Heat Exchanger Outlet and Bypass-of the

,RER train being removed from service are both fully closed, MONITOR RHR Heat Exchanger Inlet Temperature 1-TR-0612 (0613),

h.

When the RHR train has cooled to below 200'F, STOP the RHR Pump, i.

ADJUST Heat Exchanger Bypass Flow Controller 1-FIC-0618A (0619A) as required to obtain approximately 3000 gpm, then PLACE it in AUTO if desired.

4.4.5 Slowly THROTTLE OPEN the RHR HEAT EXCH OUTLET for Train A (B) 1-HV-0606 (0607) to establish desired RCS cooling.

4.4.6 ENSURE the RHR HEAT EXCH BYPASS for Train A (B) 1-FV-0618 (0619) maintains a minimum total RHR flow of 3000 gpm.

4.4.7 If required, PLACE the idle train in standby per Step 4.1.

4.5 TWO TRAIN RHR OPERATION DURING RCS RECIRCULATION 4.5.1 VERIFY the lineup on the idle RHR Train as follows:

a.

CLOSE the RWST TO RHR PUMP A(B) SUCTION 1-HV-8812A (8812B),

b.

OPEN the RHR PMP A(B) DOWNSTREAM AND UPSTREAM SUCTION FROM HOT LEG l-HV-8701A (8702A) and 1-HV-8701B (8702B),

c.

CLOSE the RHR TRAIN A(B) TO HOT LEG CROSSOVER ISO 1-HV-8716A (8716B),

d.

ENSURE the RHR HEAT EXCH BYPASS for Train A (B) 1-FV-0618 (0619) is in MAN and CLOSED, e.

CLOSE the RHR HEAT EXCH OUTLET for Train A (B) 1-HV-0606 (0607),

f.

ENSURE OPEN the RHR PMP-A (B) MINIFLOW ISO VLV l-FV-0610 (0611),

1 roues

PAoCEDUAE NO HEVISION

-AGE NO.

VEGP 13011-1 18 14 of 32 CAUTION Starting an RHR Pump at RCS water level below 216 foot elevation and with 1-HV-8809A (E) closed will cause water hammer in the discharge piping.

g.

ENSURE OPEN RHR PUMP A (B) TO COLD LEG 1 & 2 (3 & 4) ISO VLV l-HV-8809A (8809B).

4.5.2 START the RHR PUMP A(B).

4.5.3 If desired, SHIFT RRR letdown to the alternate train as follows:

MONITOR Letdown Flow 1-FI-0132C while shifting a.

letdown and ADJUST the LOW PRESSURE LETDOWN Controller 1-PIC-0131 and/or LETDOWN FROM RHR Control Valve 1-HV-0128 as required to maintain desired letdown flow, b.

OPEN the RHR To CVCS Letdown Isolation of the RHR train which is to be used for letdown independent verification required:

(1) 1-1205-U4-021 if Train A is operating on minimum flow, (2) 1-1205-U4-022 if Train B is operating on minimum flow, c.

CLOSE the kHR To CVCS Letdown Isolation of the opposite trains independent verification required.

4.5.4 THROTTLE OPEN RHR REAT EXCH BYPASS for Train A (B) 1-FV-0618 (0619) until a. minimum flowrate of 3000 gpm is established.

4.5.5 VERIFY RHR PMP A (B) MINIFLOW ISO VLV l-FV-0610 (0611) closes.

CAUTION The RHR Heat Exchanger Train A(B) Bypass Flow Controller Potentiometer should be set for a flow of 3000 gpm prior to placing controller in AUTO.

Potentiometer setting is approximately equal C (desired flow /5000)2.

4.5.6 PLACE RHR HEAT EXCH BYPASS for Train A (B) Flow Controller 1-FIC-0618A (0619A) in AUTO if desired, mus

w w

PWoCEDUGE NO.

QEVISloN pAGE No.

1 VEGP 13011-1 18 15 of 32 4.5.7 Slowly THROTTLE OPEN RHR HEAT EXCH OUTLET for Train A (B) 1-HV-0606 (0607) to establish desired RCS cooling.

4.5.8 When two train RHR operation is no longer desired, SHUT DOWN one train of RHR as follows:

a.

If the train being removed from service is providing RHR letdown, SHIFT RHR letdown to the alternate train per 4.5.3, b.

Slowly THROTTLE CLOSED the RHR HEAT EXCH OUTLET 1-HV-0606 (0607) and RHR HEAT EXCH BYPASS for Train A (B) 1-TV-0618 (0619) of the train being removed from service, c.

STOP RHR PUMP A(B),

d.

If required, PLACE the idle train in standby per Step 4.1.

4.6 FILLIF.G AND VENTING THE RHRS CAUTION All vented effluent should be handled as potentially contaminated fluid.

NOTE The 1-HV-8812A(B) valve should be opened using motor operator simultaneously with the System Vents open, as detailed below to achieve a successful vent of the RHR Ex.

4.6.1 INSTALL Tygon hoses at the following vent pointst a.

RNR To CCP (SI Pump) 1-1205-X4-141(124),

Suction Header Vent, b.

RHR Train A(B) Cold Leg 1-1205-X4-013(030),

Inj ection Vent, c.

RHR Hot Leg Injection 1-1205-X4-120, Crossover Vent, d.

RHR Pump Suction Flush 1-1205-X4-196(400),

Connection Vent, e.

RHR Pump Seal Water Vent, 1-1205-U4-235(236).

4.6.2 ROUTE the Tygon hoses to contain the potentially contaminated vented effluent.

nnus

'PeoCEDUAE No, KEVISioN PAGE No.

VEGP 13011-1 18 16 of 22 4.6.3 If power has been removed from the RHR Loop Inlet Isolations, PERFORM the following: independent verification required:

a.

If shut down, PLACE Inverter ICD 115 (IDDlI6) in service per 13405-1, "125V DC 1E Electrical Distribution System",

b.

At 1CD115N (ICDlI6N) REMOVE tag, UNLOCK and CLOSE the disconnect for 1-HV-8701B (1-HV-8702A),

c.

UNLOCK and CLOSE RHR Loop 1(4) Inlet Isolation 1-HV-8701A (8702B) Supply Breakers lABE-15-1 (1BBE-13-1) and 1ABE-15-2 (IBBE-13-2),

d.

REMOVE tags and CLOSE the links for the K2 Relay for breaker 1ABE-15-1, lABE-15-2, 1BBE-13-1 and IBBE-13-2.

4.6.4 ALIGN the RHR train remote-operated components for filling and venting per Checklist 1.

4.6.5 If required, ALIGN the' RHR train for filling and venting per 11011-1, " Residual Heat Removal System Alignment".

4.6.6 CLOSE the RHR TRAIN A(B) TO HOT LEG CROSSOVER IS0s of the opposite train 1-HV-8716A if train A is the opposite train, a.

t b.

1-HV-87168 if train B is the opposite train.

4.6.7 OPEN the RHR TRAIN A(B) TO HOT LEG CROSSOVER ISO 1-HV-8716A (8716B).

4.6.8 OPEN the RHR HEAT EXCH OUTLET l-HV-0606 for Train A (B)

(0607).

4.6.9 CLOSE the RHR HEAT EXCH BYPASS for Train A-(B) 1-FV-0618 (0619).

PAoCEDurE No.

REVISloN pagg No,

].

VEGP 13011-1 18 17 of 32 CAUTIONS a.

If vent 1-HV-10465 is not closed when venting is complete, venting

-RER Train A will result in overflowing contaminated water from the Vent Valve Room down into the Auxiliary Building vestibule R-C131 (Level C).

b.

If vent 1-HV-10466 is not closed when venting is complete, venting RHR Train B will result in contaminated water on the floor of the room containing the Train B vent, and actuation of the room sump level switch light on Panel QPCP.

NOTE RHR Suction' Vent Valves 1-HV-10465 (10466) are in sealed rooms and therefore cannot be visually observed as vented.

Personnel at these locations should stand outside the knockout wall and verify adequate venting by listening for a change in the sound indicating that the airuis vented.

4.6.10 Prior to opening RHR Suction Vent Valves 1-HV-10465 (10466), NOTIFY Health-Physics Department to monitor Room R-Cl31 (R-B08) in Auxiliary Building to contain spillage and minimize room contamination.

4.6.11 STATION 1 personnel at the following valve-locations and OPEN the valves:

a.

RHR TO CCP (SI PUMP) 1-1205-X4-141(124),

Suction Header Vent, b.

RHR TRAIN A(B) Cold Leg-1-1205-X4-013(030),

Injection Vent, c.

RHR Hot Leg Injection 1-1205-X4-120, Crossover Vent, d.

RHR SUCT VENT LINE l-HV-10465(10466).

TRN-A (B),

?C34*S

i AOCEDUT.E NO.

LEVISloN pAgg No.

VEGP 13011-1 18 18 of 32 4.6.12 VERIFY CLOSED the RHR PMP A(B) UPSTREAM SUCTION FROM HOT LEG 1(4) 1-HV-8701B (8702B).

4.6.13 OPEN the RHR PMP A(B) DOWNSTREAM SUCTION FROM HOT LEG LOOP 1(4) 1-HV-8701A (8702A).

4.6.14 CLOSE and HOLD CLOSED handswitch for RHR Pump 1(2)

Miniflow Isolation Valve 1-FV-0610 (0611).

RELEASE the handswitch approximately 10 seconds after performing Step 4.6.15.

4.6.15 COMMENCE RHR Fill by opening RWST TO RHR PMP A(B)

SUCTION 1-HV-8812A (8812B).

4.6.16 When a solid stream of water issues from the Vent Valves listed in Step 4.6.11, CLOSE the associated Vent Valve.

4.6.17 REOPEN all of the Vent Valves that are listed in Step 4.6.1.

4.6.18 When a solid stream of water issues from the vent, CLOSE the associated Vent Valve.

4.6.19 CLOSE 1-HV-8701A (8702A).

4.6.20 When all venting is completed, ENSURE the vent points are in the condition listed belows independent verification required:

a.

RHR To CCP (SIP) Suction Header Vent 1-1205-X4-141 (124) CLOSED and vent line capped, b.

RHR Train A(B) Cold Leg Injection Vent 1-1205-X4-013 (030) CLOSED and vent line capped, c.

RHR Hot Leg Injection Crossover Vent 1-1205-X4-120 CLOSED with vent line capped, d.

RHR Pump Suction Vent 1-HV-10465 (10466) CLOSED, e.

RHR Pump Suction Flush Connection Vent 1-1205 X4-196 (400) CLOSED and vent line c.apped, f.

RHR Pump Seal Water Vent 1-1205-U4-235 (236)

CLOSED with vent line capped, hh

PAOCEDUAE NO GEVISION nGENO.

VEGP 13011-1 18 19 of 32 NOTE The following Step is to be performed if in the judgment of the USS the line may be airbound.

4.6.21 VENT the Containment A Suction Line back to the Containment Sump as follows:

1 4.6.21.1 HAVE the Electrical Department connect a jum)er from Terminal C6 to C7, 1ABD29W in MCC1ABD to enable CNMT SUMP TO RHR PMP-A 1-HV-8811A to open with RWST TO RHR PMP-A SUCTION 1-HV-8812A open, Jumper And Lif ted Wire Control"per 00306-C, " Temporary 4.6.21.2 OPEN CNMT SUMP TO RHR PMP-A 1-HV-8811A.

4.6.21.3 OPEN RHR BYPASS FROM CNMT EMERG SUMPS 1-1205-U4-120 to Bypass Check Valve 1-1205-U4-122.

4.6.21.4 OBSERVE the Containment Sump for water entering from the Containment Suctio'n Line.

4.6.21.5 When water is observed entering the Containment Sump, CLOSE l-HV-8811A.

4.6.21.6 CLOSE 1-1205-U4-120, 4.6.21.7 HAVE the Electrical Department remove the jumper placed in Step 4.6.21.1 per 00306-C, " Temporary Jumper And Lifted Wire Control".

NOTE The following Step is to be performed if in the judgment of the USS the'line may be airbound.

4.6.22 VENT the Containment B Suction Line back to the Containment Sump as follows:

4.6.22.1 HAVE the Electrical Department connect a jumper from Terminal C6 to C7, 1BBD29W in McClBBD to enaile CNMT SUMP TO RHR PMP-B l-HV-8811B to open with RWST TO RHR Jumper And Lifted Wire Control"per 00306-C, " Temporary PMP-B SUCTION 1-HV-8812B open, 4.6.22.2 OPEN CNMT SUMP TO RHR PMP-B 1-HV-8811B.

muas 3

PAOCEDUAE NO.

REVISION F AGE NO.

VEGP 13011-1 18 20 of 32 t

4.6.22.3 OPEN RHR BYPASS FROM CNMT EMERG SUMPS 1-1205-U4-121 to Bypass Check Valve 1-1205-U4-123.

4.6.22.4 OBSERVE the Containment Sump for water entering from the Containment Suction Line.

4.6.22.5 When water is observed entering the Containment Sump, CLOSE 1-HV-8811B.

4.6.22.6 CLOSE 1-1205-U4-121.

4.6.22.7 HAVE the Electrical Department remove the jumper placed in Step 4.6.22.1 per 00306-C, " Temporary Jumper And Lifted Wire Control".

4.6.23 PLACE the RHR train in a configuration appropriate to plant conditions as follows:

a.

If RCS temperature is greater than or equal to 350*F, PERFORM the following:

(1)

ENSURE OPEN the RHR TRAIN A (B) TO HOT LEG CROSSOVER ISO l-HV-8716A (8716B) of the opposite train, (2)

PERFORM Step 4.1 starting at Step 4.1.3 to place the train in standby.

b.

If RCS temperature is less than 350*F, ALIGN the RHR train for RCS circulation as follows:

(1)

CLOSE the RWST TO RHR PHP A(B) SUCTION 1-HV-8812A (8812B),

(2)

OPEN the RHR PMP'A(B) DOWNSTREAM SUCTION FROM HOT LEG 1(4) 1-HV-8701A (8702A),

(3)

OPEN the RHR PMP A(B) UPSTREAM SUCTION FROM HOT LEG 1(4) 1-HV-8701B (8702B),

(4)

CLOSE the RHR TRAIN A(B) TO HOT LEG CROSSOVER ISO l-HV-8716A (8716B),

(5)

OPEN the RHR PUMP A(B) TO COLD LEG 1&2 (3&4)

ISO VLV 1-HV-8809A (8809B): independent verification required.

mun

PMXEDUQE No.

QEVISloN PAGE NO.

VEGP 13011-1 18 21 of 32 4,7 FILLING THE RCS (AND THE REFUELING CAVITY FOR REFUELING)

CAUTIONS a.

Maintain seal injection flow whenever RCS level is at or above the level of the a RCP Seals (elevation 190 feet).

This prevents crud infiltration into the seal chambers.

b.

Airborne activity should be monitored when filling the Refueling Cavity from RNR until the level is above the Reactor Vessel Flange.

NOTES a.

With the water level in the Refueling Cavity less than 217 feet 0 inches elevation (23 feet above the vessel flange), both trains'of the RHRS are required to be operable with one train in operation, b.

Performance of this step assumes use of the RNR train that is operable but not operating, c.

To minimize airborne activity, it is preferred to fill the Refueling Cavity by gravity to the Reactor Vessel Flange prior to atarting an RHR Pump.

4.7.1 ESTABLISH RCS or Refueling Cavity level monitoring as applicable.

4.7.2 CLOSE the RHR PUMP A(B) TO COLD LEG 1&2 (3&4) ISO VLV 1-HV-8809A (8809B).

4.7.3 ENSURE the RHR HEAT EXCH BYPASS for Train A (B) 1-FV-0618 (0619) is in MANUAL and CLOSED.

4.7.4 CLOSE the RHR HEAT EXCH OUTLET for Train A (B) 1-HV-0606 (0607).

i

?0344S

(..

DROCEDUQE NO.

GEVISION DQGE NO.

VEGP 13011-1 18 22 of 32 4.7.5 CLOSE the'RHR PMP A(B) SUCTION FROM HOT LEG 1(4) 1-HV-8701A (8702A) and 1-HV-8701B (8702B).

4.7.6 OPEN the RWST TO RHR PMP A(B) SUCTION 1-HV-8812A (8812B).

4.7.7 VERIFY OPEN the RHR PMP A(B) MINIFLOW ISO VLV l-FV-0610 (0511).

4.7.8 OPEN the RHR PUMP A(B) TO COLD LEG ISO VLV l-HV-8809A (8809B) to start gravity fill from the RWST.

4.7.9 If desired, START RHR PUMP A(B).

NOTE Fill the Refueling Cavity slowly to the 200 foot elevation to prevent airborne activity and to maintain water clarity.

4.7.10 Slowly THROTTLE OPEN'tte RHR HEAT EXCH OUTLET for Train A (B) 1-HV-0606 (0607) to obtain the desired flow rate.

4.7.11 At the desired level, CLOSE the RHR HEAT EXCH OUTLET 1-HV-0606 (0607).

4.7.12 CLOSE the-RHR PUMP A(B) TO COLD LEG 1&2 (3&4) ISO VLV l-HV-8809A (8809B).

4.7.13 If running, STOP RHR PUMP A(B).

4.7.14 CLOSE the RWST TO RHR PMP A(B) SUCTION 1-HV-8812A (8812B).

4.7.15 OPEN the RHR PMP A(B)-SUCTION FROM HOT LEGS 1-HV-8701A (8702A) and 1-HV-8701B (8702B),

4.7.16 OPEN the RHR PUMP A(B) TO COLD LEG Isolation 1-HV-8809A (8809B): independent verification required.

wo

F- - - - - --------- -- - --~

PAOCEDUAE No-REvi$loN

' > AGE No.

VEGP 13011-1 18 23 of 32' 4.8 DRAINING THE REFUELING CAVITY CAUTION Excessive flowrate during pumpdown with Upper Internals Assembly installed could lead to void formation in RHR Pump suction.

Trend RHR Pump parameters on ERF for early detection of possible RHR Pump degradation due to vortexing.

NOTES a.

With the water level in the Refueling Cavity less than 217 feet 0 inches elevation (23 feet above the vessel flange), both trains of the RHRS are required to be operable with one train

-operating, b.

Performance of this step assumes use of the RHR train that is operable but not operating.

4.8.1 ENSURE OPEN the RHR Pump A(B) TO COLD LEG 1&2 (3&4) ISO VLV l-HV-8809A (8809B).

4.8.2 CLOSE the RHR TRAIN A(B) TO HOT LEG CROSSOVER ISO of the operatina RHR Train a.

1-HV-8716A if Train A is operating, b.

1-HV-8716B if Train B is operating.

4.8.3 ENSURE CLOSED the RHR TO HL ISO VLV l-HV-8840.

4.8.4 ENSURE the RHR HEAT EXCH BYPASS for Train A (B) 1-FV-0618 (0619) is in MANUAL and CLOSED.

4.8.5 CLOSE the RHR HEAT EXCH OUTLET for Train A (B) 1-HV-0606 (0607).

4.8.6 UNLOCK and OPEN-RHR Test Recirculation To RWST l-1205-U6-027 and 1-1205-U4-226: independent verification required.

4.8.7 CLOSE the RWST TO RHR PMP A(B) SUCTION 1-HV-8812A g

(8812B).

?03445

s

[PAOCEDUAE NO.

RiivisioN PAGE No. ~

VEGP 13011-1 18 24 Of 32 4.8.8 OPEN the RHR PMP A(B) DOWNSTREAM AND UPSTREAM SUCTION FROM HOT LEG Isolations 1-HV-8701A (8702A) and 1-HV-8701B (8702B).

4.8.9 VERIFY OPEN the RHR PMP A(B) MINIFLOW ISO VLV l-FV-0610 (0611),

4.8.10 START the RHR PUMP A(B).

4.8.11 CLOSE the RHR PUMP A (B) TO COLD LEG 1 & 2 (3 & 4) ISO VLV 1-HV-8809A (8809B).

4.8.12 OPEN the RHR TRAIN A(B) -TO HOT LEG CROSSOVER ISO 1-HV-8716A (8716B) for th' RHR Loop to be used for pumping.

4.8.13 Slowly OPEN the RHR HEAT :XCH OUTLET for Train A (B) 1-HV-0606 (0607) to obta. the desired flow rate.

4.8.14 At the desired level in the Refueling Cavity, CLOGE the RHR HEAT EXCH OUTLET for Train A (B) 1-HV-0606 (0607).

4.8.15 STOP the RHR PUMP A(Br.

4.8.16 OPEN the RER PUMP A(B) TO COLD LEG 1&2 (3&4) ISO VLV 1-HV-8809A (8809B): independent verification required.

4 3.17 CLOSE and LOCK RRR Test Recirculation RWST l-1205-U6-027 and 1-1205-U4-226: independent verification required.

4.9 OPERATING RHR WITH ONE TRAIN OF COLD LEG DISCHARGE WITH ITS COLD LEG FLOWPATH ISOLATED FOR MAINTENANCE 4.9.1 ENSURE both RHR trains are lined up for recirculation per Step 4.5.

4.9.2 ENSURE opposite RHR PMP-A (B) TO COLD LEG 1 & 2 (3 & 4)

ISO VLV l-HV-8809A(B) OPEN: independent verification required.

4.9.3 OPEN RER TRAIN A (B) TO HOT LEG CROSSOVER ISO Valves 1-HV-8716A and 1-HV-8716B: independent verification required.

4.9.4 OPEN breakers for RHR X-TIE Valves independent verification required:

Valve Breaker a.

1-HV-8716A 1ABD-20, b.

1-HV-8716B 1BBD-20, i

70h41

'PAOCEDUAE NO-AEVISION pagg No.

VEGP 13011-1 18 25 of 32 4.9.5 OPEN breaker for cold leg discharge path in services independent verification required:

Valve Breaker a.

1-HV-8809A 1ABB-14, b.

1-HV.18098 18B8-14.

4.9.6 CLOSE valve and OPEN breaker for train to be isolated for maintenance: independent verification required:

Valve Breaker a.

1-HV-8809A 1ABB-14,

\\

I 1BBB-14.

b.

1-HV-8809B 4.9.7 MAINTAIN the running RHR Pump in service and OPERATE the system as necessary to maintain the desired flow race.

4.9.8 When RRR System Cross tie operation is no longer l

desired and maintenance is completed, PERFORM the followings independent vorification required:

4.9.8.1 CLOSE the following breakers independent verification required:

Breaker Valve a.

1ABB-14 1-HV-8809A, b.

1BBB-14 1-HV-88098, c.

1ABD-20 1-HV-8716A, d.

15tTr.7 A 1-HV-8716B.

rwn

s P-OCEDunE NO LE WISION PAGE NO VEGP 13011-1 18 26 of 32 4.9.8.2 ENSURE the idle RRR Train is aligned as follows:

a.

RWST TO RHR A (B) SUCTION CLOSED 1-HV-8812A (6812B) b.

RHR PMP A (B) DOWNSTREAM AND OPEN UPSTREAM SUCTION rROM HOT LEC 1-HV-8701A (8702A) AND 1-HV-8701B (8702B) c.

P.HR HEAT EXCH BYPASS FOR TRAIN A CLOSED (B) 1-TV-0618 (0619)

IN MANUAL d.

RHR HEAT EXCH OUTLET FOR TRAIN A CLOSED (B) 1-HV-0606 (0607) e.

RHR PHP A (B) MINIFLOW ISO VLV OPEN 1-FV-0610 (0611) 4.9.8.3 START RHR Pump A (B).

4.9.8.4 If required, SHIFT RHR letdown to the train which is to be maintained on cold' leg recirculation as follows:

a.

MONITOR Letdown Flow 1-FI-0132C while shifting letdown and ADJUST the LOW PRESSURZ LETDOWN Controller 1-PIC-0131 and/or LETDOWN FROM RHR Control Valve 1-HV-0128 as required to maintain desired letdown flow, b.

OPEN the RHR To CVCS Letdown Isolation of the RHR train which is operating on minimum flows independent verification required:

(1) 1-1205-04-021 if Train A is operating on minimum flow, (2) la1205-U4-022 if Train B is operating on minimum flow, c.

CLOSE the RHR To CVCS Letdown Isolation of the opposite trains independent Verification required.

4 l

AOCEDUwE NO-l G EVisioN

~~' "

& AGE No VEGP 13011-1 18 27 of 32 4.9.8.5 SHIFT flow to the RHR train that was just started as follows:

a.

MONITOR RHR Train A and Train B Flow 1-FI-0618A and 1-FI-0619A and MAINTAIN total RHR flow between 3000 and 3500 gpm throughout the remainder of this

step, b.

ENSURE the RHR HEAT EXCH BYPASS for Train A (B) 1-FV-0618 (0619) of the train being removed from service is in MAN, c.

MONITOR Letdown Flow 1-FI-0132C while shifting RHR flow and ADJUST the LOW PRESSURE LETDOWN Controller 1-PIC-0131 and/or LETDOWN FROM RHR Control Valve 1-HV-0128 as required to maintain desired letdown flow, d.

Slowly THROTTLE the RHR HEAT EXCH A(B) OUTLET 1-ny-0606 (0607) and Bypass of the train being removed from service CLOSED and the RHR Heat Exchanger Bypass of the train being placed in 1

service OPEN whf1*e maintaining total RHR flow between 3000 and 3500 gpm, e.

If RHR PMP-A(B) MINIFLOW ISO 7LV 1-FV-0610 (1-FV-0611) does not auto open, if required, PLACE 1-HS-0610 (1-HS-0611) to OPEN and RELEASE and ENSURE that 1-FV-0610 (1-FV-0611) opens, f.

When the Heat Exchanger Outlet and Bypass of the RHR train being removed from service are both fully closed, MONITOR RER Heat Exchanger Inlet Temperature 1-TR-0612 (0613),

g.

When the RHR train has cooled to below 200*F, STOP the RER Pump, h.

ADJUST Heat Exchanger Bypass Flow Controller 1-FIC-0618A (0619A) as required to obtain approximately 3000 gpm, then PLACE it in AUTO if desired.

4.9.8.6 CLOSE the RHR TRAIN A (B) TO HOT LEG CROSSOVER ISO VALVES 1-HV-8716A and 1-HV-8716B.

l l

'wn

{

- ~....

. -. ~ -.. - _. - ~. ~. _ -.... -. -. ~.... -.. _.. -. - - _.... -, ~

F40CEDUAE No AEvi$loN pang No.

VEGP 13011-1 18 28 of 32 NOTE i

The following steps will slowly refill the downstream section of the RHR loop that was drained.

4.9.8.7 CLOSE 1-HV-8701A (8702A) and 1-HV-8701B (8702B) for the idin train.

4.9.8.8 OPEN 1-HV-8812A (B) for the idis train.

4.9.8.9 Manually OPEN 1-HV-8809A (8809B) for the train that was drained independent verification required.

4.9.8.10 OPEN SIS CHECK VALVE TEST CNMT ISO VALVES 1-HV-8871 and 1-HV-8964.

4.9.8.11 OPEN RNR PMP A (B) CHECK VALVE TEST VALVE 1-HV-8890A (88905).

4.9.8.12 OPEN ACCUM-1 (3) CHECf; VLV TEST 1-HV-8879A (8879C).

4.9.8.13 OPEN ACCUM-2 (4) CHECK VLV TEST 1-HV-88795 (8879D).

4.9.8.14 When venting is completed, CLOSE the following:

Train A Train B a.

1-HV-8890A 1-HV-88908, b.

1-HV-8879A 1-HV-8879C, c.

1-HV-88795 1-HV-8879D.

4.9.8.15 CLOSE 1-HV-8871 and 1-HV-8964.

4.9.8.16 CLOSE 1-HV-8812A (8812B).

4.9.8.17 OPEN 1-HV-8701A (8702A) and 1-HV-87015 (8702B).

l 1

I row.

I

PAOCEDUAE NO.

Levi $ ION

  • AGE NO VEGP 13011-1 18 29 of 32 5.0

. REFERENCES 5.1 P&ID's 5.1.1 1X4DB121 Safety Injection System 5.1.2 1X4DB122 Residual Heat Removal System 5.2 ELEMENTARY DIAGRAMS 5.2.1 1X3D-BD-D02L 1-HV-8804A Safecy Injection System 5.2.2 1X3D-BD-D02M 1-HV-8804B Safety Injection System 5.2.3 1X3D-BD-D02V 1-HV-8809A Safety Injection System 5.2.4 1X3D-BD-D02W 1-KV-8809B Safety Injection System 5.2.5 1X3D-BD-D03J 1-HV-8840 Safety Injection Syntem 5.2.6 1X3D-BD-E01A RHR Pump 001-M01 5.2.7 1X3D-BD-E01B RHR Pump 002-M01 5.2.8 1X3D-BD-E02C 1-FV-0610 Residual Heat Removal System 5.2.9 1X3D-BD-E02D 1-TV-0611 Residual Heat Removal System 5.2.10 1X3D-BD-E02E 1-HV-8812A Residual Heat Removal System 5.2.11 1X3D.BD-E02F 1-HV-8812B Residual Heat Removal System 5.2.12 1X3D-BD-E02G 1-HV-8701A Residual Heat Removal System 5.2.13 1X3D-BD-E02H 1-HV-8701B Residual Heat Remoedl System 5.2.14 1X3D-BD-E02J 1-HV-8702A Residual Heat Removal System 5.2.15 1X3D-BD-E02K 1-HV-8702B Residual Heat Removal System 5.2.16 1X3D-BD-E02L 1-HV-8986A Residual Heat Removal System 5.2.17 1X3D-BD-E02M 1-HV-8986B-Residual Heat Removal System 70 Mal

PaOCEDURE No.

KEVISION paog No, VEGP 13011-1 18 30 of 32 l

5.2.18 113D-BD-E02N 1-HV-8716A Residual Heat Removal System j

5.2.19 IX3D-BD-E02P 1-HV-8716B Residual Heat Removal System 5.2.20 1X3D-BD-E03F 1-HV-8811A Residual Heat Removal System 5.2.21 1X3D-BD-E030 1-HV-8811B Residual Heat Removal System 5.2.22 1X3D-BD-E03H 1-HV-10465/

Residual Heat Removal 10466 System 5.3 PROCEDURES 5.3.1 11011-1

" Residual Heat Removal System Alignment" 5.3.2 13405-1 "125V DC 1E Electrical Distribution System" 5.3.3 13427-1 "4160V 'AC 1E Electrical Distribution System" 5.3.4 13429-1 "480V AC 1E Electrical Distribution 1

System" 5.3.5 13711-1

" Instrument Air System" 5.3.6 13715-1

" Component Cooling Water System" 5.3.7 13150-1

" Nuclear Service Cooling Water" 5.4 CORRESPONDENCE 5.4.1 GP-12615 RNRS Open Permissive Setpoint 5.4.2 PTEO-01628 Operation of The Recycle Evaporator During Single Train Cooldown 5.4.3 PFEO-805 Fire Induced Opening Of HV-8804A And 1

-HV-8804B 5.4.4

-BW-4979 Fire Induced Opening Of HV-8804A And HV-8804B END OF PROCEDURE TEXT 4

NCCEDU%E NO-REYlSION PAGE NO, VEGP 13011-1 18 31 of 32 Sheet 1 of 1 CHECKLIST 1 RHR ALIGNMENT FOR FILLING AND VENTING CONTROL SWITCH /

VALVE NUMBER DESCRIPTION P_0SITION 1-HS-0620(0621)

RHR PMP A(B)

PULL-TO-LOCK 1-HV-8701A(8702A)

RHR PMP A(B) DOWNSTREAM CLOSED SUCTION FROM HOT LEG LOOP 1(4) 1-HV-8701B(87025)

RHR PMP A(B) UPSTREAM CLOSED SUCTION FROM HOT LEG LOOP 1(4) 1-HV-10465(10466)

RHR SUCT VENT LINE TRN A(B)

CLOSED 1-HV-8812A(88125)

RWST TO RHR PUMP A(B)

CLOSED SUCTION 1-HV-8811A(88118)

CNMT SUMP TO RHR PMP A(B)

CLOSED SUCTION 1-HV-8809A(88095)

RHR PUMP A(B) TO COLD LEG CLOSED 1&2 (3&4) ISO VLV 1-HV-8804A(8804B)

RHR PMP A DISCH TO CHG CLOSED PMPS SUCT (RHR TO SI PMP B ISO VLV) 1-HV-8716A(8716B)

RHR TRAIN A(B) TO HOT LEG CLOSED CROSSOVER ISO 1-HV-8840 RHR TO HL ISO VLV

-CLOSED i

4

NOCEDUAE NO i HEvlSIGN PAug No j

VEGP 13011-1 18 32 of 32

=

Sheet 1 of 1 CHECKLIST 2 RHR ALIGNMENT FOR STANDBT READINESS CONTROL SWITCH /

POSITIONED VALVE NUMBER DESCRIPTION P_0SITION BY I/V 1-HS-0620(0621)

RHR PMP A(B)

AUTO 1-HV-8701A(8702A)

RJIR PMP A(B) DOWNSTREAM CLOSED SUCTION FROM 110T LFG LOOP 1(4) 1-HV-8701B(87025)

RHR PMP A(B) UPSTREAM CLOSED SUCTION FROM HOT LEC LOOP 1(4) 1-HV-10465(10466)

RHR SUCT VENT LINE TRN CLOSE A(B) 1-HV-8812A(8812B)

RWST TO RRR PUMR A(B)

OPEN SUCTION 1-HV-8811A(88118)

CNMT SUMP TO RER PMP CLOSE A(B) SUCTION 1-HV-8809A(88095)

RRR PUMP A(B) TO COLD OPEN LEG 162 (364) ISO VLV 1-HS-8809C(88090)

RER PUMP A(B) TO COLD OFF LEG 162 (3&4) ISO VLV 1-HV-8804A(88048)

RER PMP A DISCH TO CHG CLOSED PMPS SUCT (RRR TO S1 PMF B ISO VLV) 1-HV-8716A(87168)

RER TRAIN A(B) TO HOT OPEN LEG CROSE0VER ISO 1-HV-8840 RER TO EL ISO VLV CLOSED 1-HS-8840A RER TO HL ISO VLV 0FF 1-HV-0606(0607)

RER RRAT EXCHANGER TRAIN OPEN A(B) OUTLET 1-FV-0618(0619)

P.HR REAT EXCHANGER TRAIN MAN &

A(B) BYPASS CLOSED REVIEWED BY

/DATE f014al

--___--_-__--_---i

m O f ~~ f j'[1 m

v.ee rs, 12 of 15 m no 8

VEGP 90015-C

?;

w,.

y Sheet 1 of I

!Wj

?~$5 s

DATA SHEET I

~

p EXAMPLE VOCTLE NUCLEAR STAT!ON VENICLE ACCESS REQUEST a

MON-DESIGNATED I

VENICLE DESCRIPTION VENICLE INRMU1ATION 1

l DRIVER INFORMAT100t 7nuA' C0"r * **"E: 6 f f-G,A C Ten'u nAnE: Do HNia W:HL h M E:

16.,2,n(/ /sf O[

MODEL: 5'6'##

BADCE i:

/

COLOR: 8/ag.-

CITT/ STATE: ghyg, fcfo 6g DEFT: f f,fff A

/

~f r

STATION CONTACT: 3$d/

TAC i:,D /7 9 73 I W.N I: D z K - 4 9 0 0 3 FURFOSE

~

ga g/ pfm,,,-

STATE REASON VEHICLE REqutRES PROTECTED AREA ACCESS:

fug-f f jf f,.

/

/

/

At!TMORIZATION cL TIME: $$-J)e-40 TINE:

l$ed Date of Authorization: From:

C605 To:

3 at-90 Approval Date: 'S,Aa.9f Approved by: di. 95c[

Balm l's C 7 (.y]

VAR OFFICER:

' d M9v i

. p crine) 6t P9a-3 RAIM l'S

$91,2 n uici t unin t -

/

m e

5 u

r n

~

g

~

~

~

s

.;t a

t

_3 s

t t

x 3

s T

=

u.

o I

Ik b

4 C

h) n 3

o gg A

4 a

^.=

=

h g

4 L

4,,

2 3

t 5

I a

g N

W

~N Y

5 R

C t q".4

+

~

x es ks I'

2 E

I*

g5 n

o e

r j

g 4

w I

g y

g s

n

S 6

o\\

U N

Q 3

~

~

a$w E,

m 3

m l

g w$

a."

y

==

t s

s e

A m

"d s

g U

5 g

w M

A t

S 2

9

'4 4

?

it t Ci R

'd

  • s w

s s

s s

4 r

ts 7

e A

g s

s s

~

s 199'<

t

.Q h

h

.D y

O g

g I

f bi * " 7@!Dj l}"

'g

)

k

(...

~

I M

a t,

e s

a p

.s y

a s-

- II P

4 3

e e

d i

t e

a 9 ;

I

_g 2

y 1

1 e

1 g x.

n o

s 4

u 5

f.

s O

W E

b b

'k Q

k k

'4 u

th W

w b

.s

.e m

b g

g

~.

g2 v

,l, s a_,s_... g e_-.

g

..;;s,g.s+ y :,

J s

y S Ei n.

1 o

s, l _ _ i._ i_, m...

J

.i

!j

,