3' . -} .

, j l

Ronr:nx E. DrxroN Baltimore Gas and Electric Company Vice Pre.sident Calven Cliffs Nuclear Power Plant Nuclear Energy 1650 Calvert Cli[ts Parkway la.sby, Maryland 20657 410 586-2200 Ett. 4455l ocal 410 260-4455 Baltimore August 2,1994 U. S. Nuclear Regulatory Commission I Washington, DC 20555 l

ATTENTION: Document Control Desk

SUBJECT:

Calvert Cliffs Nuclear Power Plant Unit Nos.1 & 2; Docket Nos. 50-317 & 50-318 Request for Additional Information - AAC Power Design Report (TAC Nos. M89086 and M89087)

REFERENCE:

(a) Letter from Mr. D. G. Mcdonald, Jr. (NRC) to Mr. R. E. Denton (BGE),

dated June 17, 1994, Request for Additional Information Regarding Alternate AC Power Design Report In the referenced letter, additional information was requested to complete your review of the Alternate AC Power Design Report. The information requested is provided in Attachment (1). Should you have any further questions regarding this matter, we will be pleased to discuss them with you.

Very truly yours, w _

[ )

RED / PSF / dim l Attacimient: As Stated cc: (Without Drawings)

D. A. Brune, Esquire J. E. Silberg, Esquire .

M. K. Boyle, NRC D T. T. Martin, NRC P. R. Wilson, NRC [b R. I. McLean, DNR J.11. Walter, PSC /}I (With Drawings)

D. G. Mcdonald, Jr., NRC 94080B0096 940002 I{

PDR ADOCK 05000317 P

PDR

I ATTACIINfENT (1)

]

RESPONSE TO REQUEST FOR ADDITIONAL INFORh!ATION  ;

ALTERNATE AC POWER DESIGN REPORT '

)

Ouestion 1 ne last sentence on page 1 ofAttachment (2) states, "Such structures are designed and cc wnv.J so that the design basis earthquake (DBE), five operating basis earthquakes (OBEs) followea oy a safe shutdown earthquake (SSE) would not cause impairment ofsafety-relatedfeatures." The stafdoes not understand this. In the design ofa seismic category I structure, the DBE has been replaced by SSE and the earthquakes to be considered are the two earthquakes, OBE and SSE, specifIed by the ground spectra -

for the plant site. De staff does not understand how the five OBEs and one SSE are used. Please provide an explanation.

Response i The Station Blackout (SBO) Diesel Generator Building is conservatively designed for SSE loads and seismic Category I allowables.

In order to avoid confusion, the last sentence on page 1 of Attachment (2) should be revised to state: i Such stmetures are designed and constructed so that a safe shutdown earthquake (SSE) would not cause impairment of a safety-related feature. i Likewise, the second sentence of the second paragraph of the response to B.3 of Attachment (1) should be revised to state:

In order to preclude failure and impact on the adjacent Category I structure, the rnain girders, columns, and bracing for the SBO Diesel Generator Building have been analyzed to demonstrate that the SBO Diesel Generator Building will not collapse under safe shutdown earthquake loads.

Question 2 From the description of the SBO Diesel Generator Building in Section 2.2, it appears that the building is aframed steel structure supported on a reinforced concrete matfoundation with metal decking as the roofand metal sheets as sidmg. Provide a plan view and an elevation view showing the relation to the Emergency Diesel Generator Building.

Response

Two elevation views and one plan view (Drawings 64-051-E,64-055-E,64-056-E) showing the

I 1

l

ATTACllMENT (O RESPONSE TO REQUEST FOR ADDITIONAL INFORMATION ALTERNATE AC POWER DESIGN REPORT Ouestion 3 Since the SBO Diesel Generator Building is not designedfor tornado wind loading and its structural members may be broken off resulting in missiles more damaging to the EDG Building than those considered Indicate what design measures will be taken to avoid such an occurrence andprovide the details.

Response  ;

As stated in the Alternate AC (AAC) Diesel Generator Design Report, Section 2.2 of ,

Attachment (2):

The AAC structure is designed to remain intact, but not necessarily functional, following a design basis carthquake or under tornado-generated wind loads (Regulatory Guide 1.76). >

l The SBO Diesel Generator Building structural members which could become tornado missiles that would execed the design basis tornado missiles of the EDG Building were designed for the lateral tornado wind loads that would be generated by a tornado for Region I identified in Regulatory Guide 1.76. Therefore, these structural members will not become tornado missiles. The tube steel bracing is shown on drawings C-1114 and C-1115.

Question 4 From what is described in Section 2.3, Earthquake Analysis, it appears that the seismic design of the '

SBO Diesel Generator Building is in accordance to Standard Review Plan (SRP) 3.7.2 which is for category 1 structures, and is acceptable. However, in Section 2.0 it is indicated that the SBO Diesel Generator Building is designed to meet the structural requirements of the Standard Building Code (SBC), which according to B.3 of NUMARC 87-00, is the Uniform Building Code (UBC) equivalent design code ofrecordfor the area of the plant. Indicate if there is any such SBCfor the Calvert Cliffs area. If there is none and the UBC is the SBC, indicate which portions of the UBC are used in the design.

Response

The SBC is the governing Code for Calvert County:

1991 Edition Standard Buildina Code, Southern Building Code Congress International, Inc.

As recommended by NUMARC 87-00 and described in the AAC Diesel Generator Design Report, Section 2.0 of Attachment (2), at a minimum, the SBO Diesel Generator Building is designed to meet the requirements of the SBC.

However, since the SBO Diesel Generator Building is a non-Category I stmeture, interaction with the adjacent Category I Diesel Generator Building was also considered in its design. In cases where failure of the non-Category 1 SBO Diesel Generator Building could affect the adjacent Category I Diesel Generator Building (e.g., carthquakes and tornadoes), codes and standards more 2

ATTACIIMENT (1)

RESPONSE TO REQUEST FOR ADDITIONAL INFORMATION ALTERNATE AC POWER DESIGN REPORT AAC Diesel Generator Design Report, Sections 2.2 and 2.3 of Attachment (2), describe the design features and analysis performed to meet Acceptance Criteria 11.8 of SRP 3.7.2 and wind loads from a Region I tornado described in Regulatory Guide 1.76.

Ouestion 5 Ihe description on the SBO Diesel Generator Building seismic design, which is based on SRP 3.7.2, needs some clarification. On one hand it appears very detailed, such as consideration of three-component earthquakes, and on the other hand, a single degree offreedom system is usedfor the seismic analysis in the vertical direction. Provide the model usedfor the SB0 Diesel Generator Building and the analysis method in more details.

Response

The seismic analysis of the SB0 Diesel Generator Building was performed by hand calculations using the equivalent static load methodology described in Attachment (2), Section 2.3, of the AAC Diesel Generator Design Report and SRP Section 3.7.2. The hand calculations considered the following:

  • The design response spectra from Regulatory Guide 1.60, Revision 1, normalized to the maximum horizontal and vertical SSE Calvert Cliffs ground accelerations.

- Multi-mode factor of 1.5 for the horizontal response and 1.0 for the vertical response.

Seismic loads were incorporated in the building's lateral analysis by simultaneous consideration of the three directional responses.

Ouestion 6 Indicate ifother codes, such as the ACI-318 and AISC standards, are usedfor the structural design of the SBO Diesel Generator Building in addition to the SBC.

1 i

Response

Both ACI-318-89, Revised 1992, and the AISC Manual of Steel Construction, Allowable Stress Design, Ninth Edition, are used for the design of the SBO Diesel Generator Building.

l 3