Forwards Response to 10CFR50.49 Rulemaking Re Environ Qualification of Electrical Equipment.When Master List of Equipment Is Coupled W/Recent Response to Ser,More Complete Overview Is Presented
ML20071G832
Person / Time
Site: Beaver Valley
Issue date: 05/19/1983
From: Carey J
DUQUESNE LIGHT CO.
To: Varga S
Office of Nuclear Reactor Regulation
References
TAC-42459, NUDOCS 8305240401
Download: ML20071G832 (40)


Text

i e

'A@

Telephone (412) 4564000 Nuclear Division P.O. Box 4 Shippingport, PA 150770)04 May 19, 1983 Director of Nuclear Reactor Regulation United States Nuclear Regulatory Commission Attn:

Mr. Steven A. Varga, Chief Operating Reactors Branch No. 1 Division of Licensing Washington, DC 20555

Reference:

Beaver Valley Power Station, Unit No.1 Docket No. 50-334, License No. DPR-66 Environmental Qualification of Electrical Equipment Response to 10 CFR 50 Section 50.49 Rulemaking Gentlemen:

In accordance with the NRC's January 20, 1983 Rulemaking relating to electrical equipment qualification, we are providing the attached response as required for Beaver Valley Unit 1.

This response provides a Master List of Equipment for which qualification is required in order to answer the specific request of 10 CFR 50.49.

When this Master List Response is coupled with our recent response to the NRC's Equipment Qualification Safety Evaluation Report, a more complete overview of our equipment qualification program is presented. The Master List of Equip-ment for which qualification is required contains some recent equip-ment additions which we have referred to as the Phase 2 Listing. This additional equipment was added during the refueling outage in 1982.

As in previous submittals to the NRC, we have included an Executive Summary Section which identifies those equipment items for which further qualification action is being taken. We are continuing in our efforts l

to obtain either the necessary qualification documentation or qualified equipment by the deadline date required by 10 CFR 50.49.

If specific difficulties in complying with this schedule should occur, we will keep you informed of the situation on a case-by case basis.

If you have any further questions on this response, please contact l

my office.

1 Very tr ly yours, fod J.

. Carey Vice President, 11 clear Attachment 8305240401 830519 DR ADOCK 05000334 p

PDR

A Beaver Valley Power Station, Unit No. 1 Docket No. 50-334, License No. DPR-66 Environmental Qualification of Electrical Equipment Response to 10 CFR 50 Section 50.49 Rulemaking Page 2 cc:

U. S. Nuclear Regulatory Commission Office of Inspection and Enforcement Attn:

Mr. J. M. Allen, Acting Regional Administrator Region 1 631 Park Avenue King of Prussia, Pennsylvania 19406 Mr. Peter Tam, Project Manager U. S. Nuclear Regulatory Commission Phillips Building Washington, DC 20555 Mr. W. M. Troskoski, Resident Inspector U. S. Nuclear Regulatory Commission Beaver Valley Power Station Shippingport, PA 15077 U. S. Nuclear Regulatory Commission (4) c/o Document Managment Branch Washington, DC 20555 J

h&

'Af DUQUESNE LIGHT COMPANY NUCLEAR DIVISION NUCLEAR SAFETY AND LICENSING DEPARTMENT RESPONSE TO THE NRC l

EQUIPMENT QUALIFICATION RULEMAKING (10CFR50, SECTION 50.49 )

i l'

BEAVER VALLEY POWER STATION t

UNIT 1

MAY 20,1983 l

Response to the NRC Equipment Qualification Rulemaking (10CRF50, Section 50.49) 1-

d j

RESPONSE TO THE NRC EQUIPMENT QUALIFICATION RULEMAKING (10CRF50, Section 50.49)

CONTENTS 1.

BACKGROUND II.

EXECUTIVE

SUMMARY

III.

METHODOLOGY FOR MASTER LIST DEVELOPMENT IV.

MASTER LIST V.

FUTURE UPDATING OF THE MASTER LIST VI.

REFERENCES l

l i

i i

i l

203.39.1 i

"o-I.

BACKGROUND i

L 1

l-

I.

BACKGROUND The NRC Rulemaking for Equipment Qualification that was published on January 21, 1983, in the l'ederal Register which became effective on Februsry 22, 1983, required that licensees or operating plants provide a response to the 10CFR50.49 Rulemaking by.May 20, 1983.

It is the intent of this response to identify the electrical equipment for Duquesne Light company's Beaver Valley Power Station Unit I that is required to be quahtted.

This listing is based on the harsh area equipment items that have been previously submitted to the NRC, as well as additional harsh area equipment that has been installed during recent plant outages.

The recent additions include electrical items that are either replacement quahfied equipment, or equipment required to meet NUREG 0737 TMI Action Plan requirements.

Duquesne Light Company is continuing to maintain an on-going qualification program to address any equipment items for (i) those items for which qualification has yet to be established or (ii) any new equipment items or replacement parts that are needed in the future.

In addition, Duquesne Light Company will continue to update its listing or safety-related equipment for which qualification is required as plant or procedural changes are made, in order to assure that the necessary qualification documentation is acquired, reviewed, and maintained.

The Master Listing of safety-related electrical equipment does not include electrical safety-related equipment located in mild areas or equipment related to certain cold shutdown systems since tney have been excluded from the scope of the final rule. Duquesne Light Company is continuing, however, to identify mild area equipment as part of its. efforts to review this equipment on an overall system basis in order to assess system safety and operability.

In

addition, replacement equipment and spare parts for mild areas are procured, evaluated, and documented in accordance with Regulatory Guide 1.33, as suggested by the Rulemaking.

.g 10CFM50.49 also requires that tne licensee provide a schedule to qualify electrical equipment for which qualification has not yet been established.

The Executive Summary portion of this response outlines actions being taken by Duquesne Light Company. At the present time, we are targeting our efforts to nave the qualification issues and documentation areas addressed by the early part of 1985 for F

the majority of the electrical equipment.

If we encounter any problems with this schedule that are not currently known, we will advise the NRC on a case-by-case basis. -

.~

Duquesne Light Company has placed a considerable amount of qualitication documentation in its Equipment Quahtication File and is keeping this file current as equipment is upgraded or as spare parts are procured.

In accordance with the Rulemaking, the equipment that has been identified in this response's Master Listing has been evaluated against the DOR Guidelines and NUREG 0588 and will not be required to be requalified.

As pointed out in our March 1983 Response to the NRC's Safety Evaluation Report,

Duquesne Light Company is currently addressing the outstanding issues raised by the Franklin Research Center and NRC review.

Traceability concerns are being investigated with the original equipment suppliers, certain transmitters are being replaced, and other equipment items are going to be tested.

In addition, several equipment items are currently being independently assessed from an aging review standpoint in order to establish spare part replacement frequencies.

l l

I l

l h

l l

l l !

t

7 e

e 5

II. EXECUTIVE

SUMMARY

)

II.

EXECUTIVE

SUMMARY

The Executive Summary identifies Duquesne Light Company's (DLC) on-going plan to attain a qualified status for those equipment items that have been assessed by the NRC and DLC as requiring further follow-up action in order to achieve qualification.

The follow-up action will take different courses ranging from obtaining traceability information from the manufacturer to actually testing some of the equipment. In other instances, replacement of equipment for which qualification documentation has not been completely obtained is currently underway, it should be noted that the equipment presented in the Executive Summary is a subset of the overall equipment listing identified in the Master List in Section IV of this response, because only items rr: quiring follow-up action are included in the Executive Summary.

The balance of the equipment items have been evaluated and judged to be qualified for their BVPS-1 application.

e.

II. EXECUTIVE

SUMMARY

I EQUIP FRC EQUIPMENT EQUIPMENT PLANNED ACTION

. ITEM TAB MANUFACTURER /

DESCRIPTION NO.

NO.

MODEL NUMBER 5

72 Continental Cable Retest for chemical spray and radiation 6

75 Viking Penetration Retert penetration for higher radiation dosage 7

79 Buchanan Terminal Retest may be scheduled 0211 Block depending on outcome of 0511 1983 walkdown 8

80 Penn Union Terminal Conduct aging analysis and Series 1000 Block determine replacement cycle 10 29 ASCO Solenoid Install qualified seal at NP8320A184E conduit interface 10 30 ASCO Solenoid Install qualified seal at NP8320A188E conduit interface 10 31 ASCO Solenoid Install qualified seal at NP8320A186E conduit interface 10 32 ASCO Solenoid Install qualified seal at NP8320A186E conduit interface 10 33 ASCO Solenoid Install qualified seal at NP8320A186E conduit interface 10 34 ASCO Solenoid Install qualified seal at NP831654 E conduit interface 10 35 ASCO Solenoid Install qualified seal at NP8316A74E conduit interface

II. EXECUTIVE

SUMMARY

EQUIP FRC EQUIPMENT EQUIPMENT PLANNED ACTION ITEM TAB MANUFACTURER /

DESCRIPTION NO.

NO.

MODEL NUMBER 11 59 NAMCO Limit Switch Install qualified conduit EA180 seals at interface 13 57 NAMCO Limit Switch Install qualified conduit EA740 seals at interface 14 38 Fischer &

Transmitter Replace with qualified Porter Barton Lot 5 transmitters 10B2496 15 36 Barton Transmitter Replace with qualified 386 Barton Lot 5 transmitter 16 49 Barton Transmitter Investigate test program 764 LOT 2 anomaly. Investigate need for connector soldering 18 83 Mason-Nellan Transmitter Replace with qualified 12522 Barton Lot 5 transmitter 19 47 Fischer &

Transmitter Replace with qualified Porter Barton Lot 5 transmitter 50EP1031 19 91 Fischer &

Transmitter Replace with qualified Porter Barton Lot 5 transmitter 50EP1071 20 46 Barton Transmitter Perform aging analysis.

763 Lot 2 Investigate need for connector soldering L

21 40 Barton Transtr. liter Replace with qualitied 386 Barton Lot 5 transmitter 22 53 Sostman Resistance Replace with RDF Corpora-119018-2 Temperature tion RTD's Device 25 2

Limitorque Motor Replace valve MOV-CH-310 SMB-00 Operated with qualified operator Valve - -.

II. EXECUTIVE

SUMMARY

a EQUIP FRC EQUIPMENT EQUIPMENT PLANNED ACTION ITEM TAB MANUFACTURER /

DESCRIPTION NO.

NO.

MODEL NUMBER 25 5

Limitorque Motor Identify materials of SMB-00 Operated construction, establish Valve similarity and perform aging analysis 1

25 90 Limitorque Motor Replace valve MOV-SI-842 SMB-00 Operated with qualified operator l

Valve 26 56 G.E.

Motor Perform aging analysis SK6319XJ20 A on the lead splice, lead cable insulation, bearings, and lubricant 27 51 Unholtz Charge Retest the accoustical Dickie Amplifier monitoring system or 22CA-2TR procure a different system 35 65 Allis Chalmer Motor Perform aging analysis 480V Control of control transformer Center 37 24 ASCO Solenoid Install qualified seal at NP831655E conduit interface 39 84 NAMCO Limit Switch Install qualified seals EA740 at conduit interface 40 39 Fischer a Transmitter Replace with qualified i

Porter Barton Lot 5 transmitter 10B2496 3

41 37 Fischcr &

Transmitter Replace with qualified Porter Barton Lot 5 transmitter 50EP1071B CXB 50EN1071BCXB

II. EXECUTIVE

SUMMARY

EQUIP FRC EQUIPMENT EQUIPMENT PLANNED ACTION ITEM TAB MANUFACTURER /

DESCRIPTION NO.

NO.

MODEL NUMBER 44 22 Limitorque Motor Performed aging analysis l

SMB-2T Operated Valve 45 10 Limitorque Motor Obtain traceability SMB-00 Operated documents and motor brake Valve details 45 12 Limitorque Motor Obtain traceability SMB-00 Operated documents and motor brake Valve details 45 13 Limitorque Motor Perform aging analysis SMB-00 Operated and identify motor brake Valve details 47 63 Westinghouse Motor Analyze motor constituent S.O.71F13335 parts for thermal, radiation, and wear aging 48 64 Westinghouse Motor Analyze constituent FR58085 parts for thermal, S.O.70FG7723 radiation, and wear aging ASCO Solenoid Install qualified seal at 2008 NP8320A189E conduit interface f

2021 NAMCO Limit Switch Install qualified seals EA180-11302 at conduit interface ASCO Solenoid Install qualified seal at 2022 NP8320A187E conduit interface 2073 41 Gems Level Replace with qualified XM-3G495 Transmitter transmitter

\\ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

y w

f III. METHODOLOGY FOR MASTER LIST DEVELOPMENT f

t

....-,pi,.,...ig,-

.,,g

.,,,7ii...

4 i

i.i

..q iq

.g i.,i i i,

p.,.

p-H III. METHODOLOGY FOR MASTER LIST DEVELOPMENT l

The Master List of qualifled equipment presented in Section IV of this response was developed in two phases.

The first phase was limited to safety-related electrical equipment which was originally installed in the plant.

The second phase pertained to safety-related electrical equipment which has been installed as replacement or new equipment during recent outages.

Duquesne Light Company had presented the first phase listing of equipment in several previous I

submittals to the NRC and it was this list of equipment that had been reviewed by the NRC and FRC in 1982.

The second phase listing of equipment items had not been previously identified to the NRC because the equipment had been placed in operation in 1982.

The methodology for the development of the original plant equipment listing (first phase) involved a system review of several different plant documents including the following:

S Electrical Schematics S Electrical Physical Drawings i

S Emergency Operating Procedures

]

$ Final Safety Analysis Report S Electrical Equipment Lists S Cable and Raceway Schedules After this first phase listing was developed, Duquesne Light Company operations personnel then reviewed the list.

This review resulted in the addition of some equipment items and the deletion of other equipment that were not required to mitigate the consequences of an accident or bring the plant to a safe shutdown condition.

The second phase listing was developed by examining safety-related design change packages of Duquesne Light Company to determine the equipment's function in the plcnt, the type of environmental exposure, and what specific equipment was required to be qualified because of NRC regulations.

The majority of this equipment was associated with NUREG 0737, TMI Action Plan, and Regulatory Guide 1.97, Instrumentation for Light-Water-Cooled Nuclear Plants to Assess Plant and Environmental Conditions During and Following Accident.

l

]

The metMdology which was implemented, determined if the equipmer t was safety-related and was required to be qualified.

It involved reviewing, in detail, the various plant change modification documents.

] l 1

1 i

This process involved the review of numerous types of plant documents including the following:

5 Design Change Package Design Concept 5

System Summary 5

Index for Design Output 5

Purchase Orders and Specifications 5

System Diagrams 5

Electrical Schematics 5

Electrical Physical Drawings 5

Cable and Raceway Schedules 5

Equipment Location Drawings As a result of this review to determine which equipment required qualification, all harsh area equipment identified as fultilling a safety-related function for accident mitigation, containment isolation, post accident monitoring, off-site radiation release, or to shut down the reactor, were incorporated in the Phase 2 Master List.

The determination of whether or not certain auxiliary equipment was to be considered as safety-related, for which qualification would be needed, was based on the equipment's particular safety-related

function, location,

and basic design concept parameters.

In addition, NUREG 0737 and Regulatory Guide 1.97 were reviewed in-depth to determine Duquesne Light Company compliance with the NRC requirements.

At this time,

Duquesne Light Company is continuing to review specific equipment associated with Reg. Guide 1.97 to determine which instrument systems have a

high probability of attaining qualification status.

The Phase 2 Master Listing of equipment utilized a 2000 series of equipment item identification numbers in order to segregate new or replacement equipment changes from the original plant equipment items in the plant's qualification record keeping system.

2

.,e IV.

MASTER LIST OF EQUIPMENT REQUIRING QUALIFICATION

\\

MASTElt LIST PHASE 1 4

OF EQUIPMENT REQUIRING QUALIFICATION 5'

'4 J l

l l

  1. 5, MAY 1983

DUQUESNE LIGHT COMPANY HARSH AREA REPORT DATE 5/19/83 PAGE 1

EQ ITEM DESCRIPTI0tl MANUFACTURER MARK NUMDER 1

POWER CABLE KERITE NFB-16 2

POWER CABLE CEPRO WIRE NFB-65 3

POWER CABLE OKONITE VARIOUS 4

CNTRL CABLE OK0tlITE VARIOUS S

INSTRUMENT CBL CONTINENTAL W8C VARIOUS 6

PENE. TYPE I VIKING NONE 6

PENE. TYPE III VINING N0tlE 6

PENE. TYPE II VIKING N0ilE 6

PENE. TYPE VIII VIKING NONE 6

PENE. TYPE V VIKIllG NONE 6

PENE. TYPE IX VINING NONE 6

PENE. TYPE IV VIKINO NONE 7

TERMINAL BLKS BUCHANAN VARIOUS 8

TERMINAL BLKS PENN UNION VARIOUS 9

SIS WIRE ROCKBESTOS VARIOUS 10 SOLENOID ASCO SOV-CC-103A1 10 SOLENDID ASCO SOV-CC-103B1 10 SOLENDID ASCO SOV-CC-103C1 10 SOLEN 0ID ASCO SOV-CC-105D1 10 SOLEN 0ID ASCO SOV-CC-105El 10 SOLEN 0ID ASCO SOV-CC-107D1 10 SOLENDID ASCO SOV-CC-107El 10 SOLENDID ASCO SOV-CC-110D 10 SOLENDID ASCO SOV-CC-110E3 10 SOLEN 0ID ASCO SOV-CC-111A2 10 SOLENDID ASCO SOV-CC-111D1 10 SOLENDID ASCO SOV-CH-200A1 10 SOLENDID ASCO SOV-CH-200B1 10 SOLENDID ASCO SOV-CH-200C1 10 SOLENDID ASCO SOV-CV-102-1 10 SOLEN 0ID ASCO SOV-DA-100A 10 SOLEtl0ID ASCO SOV-DG-10SA 10 SULENDID ASCO SOV-DG-10VA2 10 SOLENDID ASCO SOV-LM-101A 10 SOLENDID ASCO SOV-LM-101D 10 SOLEN 0ID ASCO SOV-RC-450C1 10 SOLENDID ASCO SOV-RC-455C2 10 SOLENDID ASCO S O V -- R C - 4 5 5 D 1 10 SOLENDID ASCO SOV-RC-455D2

(

10 SOLENDID ASCO SOV-RC-456-1 10 SOLENDID ASCO SOV-RC-456-2 10 SOLEN 0ID ASCO SOV-SI-101-2 10 SOLEN 0ID ASCO SOV-SS-000A 11 LIMIT SWITCH NAMCO LMS-CC-105D1 11 LIMIT SWITCH NAMCO LMS-CC-111D 11 LIMIT SWITCH NAMCO LMS-CH-200A 11 LIMIT SWITCH NAMCO LMS-CH-200B 11 LIMIT SWITCH NAMCO LMS-CH-200C 11 LIMIT SWITCH NAMCO LMS-RC-455C 11 LIMIT SWITCH NAMCO LMS-RC-455D 11 LIMIT SWITCH NAMCO LMS-RC-456 11 LIMIT SWITCH NAMCO LMS-SI-101-2 R E PDAL_RD R T En _DR_JEnU IPMm T-- T T m -

DUQUESNE '_IGHT COMPANY HARSH AREA REPORT DATE 5/19/83 PAGE 2

CO ITEM DESCRIPTION MANUFACTURER MARK NUMDER

______-_________________~____________________________--_

11 LIMIT SWITCH NAMCO LMS-SI-865A 11 LIMIT SWITCH NAMCO LMS-SI-865B 11 LIMIT SWITCH NAMCO LMS-SI-865C 13 LIMIT SWITCH NAMCO LMS-CC-103A1 13 LIMIT SWITCH NAMCO LMS-CC-103B1 13 LIMIT SWITCH NAMCO LMS-CC-103C1 13 LIMIT SUITCH NAMCO LMS-CC-105El 13 LIMIT SWITCH NAMCO LMS-CC-107D1 13 LIMIT SWITCH NAMCO LMS-CC-107El 13 LIMIT SWITCH NAMCO LMS-CC-110D 13 LIMIT SWITCH NAMCO LMS-CC-110E3 13 LIMIT SWITCH NAMCO LMS-CC-111A2 13 LIMIT SWITCH NAMCO LMS-CV-102-1 13 LIMIT SWITCH NAMCO LMS-DA-100A 13 LIMIT SWITCH NAMCO LMS-DG-108A 13 LIMIT SWITCH NAMCO LMS-DG-109A-2 14 FLOW TRANS FISCHER PORTER FT-MS-474 14 FLOW TRANS FISCHER PORTER FT-MS-475 14 FLOW TRANS FISCHER PORTER FI-MS-484 14 FLOW TRANS FISCHER PORTER FT-MS-485 14 FLOW TRANS FISCHER PORTER FT-MS-494 14 FLOW TRANS FISCHER PORTER FT-MS-495 15 FLOW TRANS BARTON FT-SI-961 15 FLOW TRANS BARTON FT-SI-962 15 FLOW TRANS SARTON FT-SI-963 16 LEVEL TRANS BARTON LT-FW-474 16 LEVEL TRANS BARTON LT-FW-475 16 LEVEL TRANS BARTON LT-Fu-476 16 LEVEL TRANS BARTON LT-FW-484 16 LEVEL TRANS BARTON LT-FW-485 L.-FW-486 T

16 LEVEL TRANS BARTON 16 LEVEL TRANS BARTON LT-FW-494 16 LEVEL TRANS BARTON LT-FW-495

.6 LEVEL TRANS BARTON LT-FW-496 16 LEVEL TRANS BARTON LT-RC-45?

16 LEVEL TRANS BARTON LT-RC-460 16 LEVEL TRANS BARTON LT-RC-461 17 LEVEL TRANS GEMS LT-RS-151A 17 LEVEL TRANS GEMS LT-RS-151B 18 LEVEL TRANS MASON-NEILAN LT-RC-470 l

19 PRESS TRANS FISCHER PORTER PT-RC-472 19 PRESS TRANS FISCHER PORTER PT-RS-152A 19 PRESS TRANS FISCHER PORTER PT-RS-152B 20 PRESS TRANS BARTON PT-RC-402 20 PRESS TRANS BARTON PT-RC-403 20 PRESS TRANS BARTON PT-RC-455 20 PRESS TRANS BARTON PT-RC-456 20 PRESS TRANS BARTON PT-RC-457 21 LEVEL TRANS BARTON LT-FW-477 21 LEVEL TRANS BARTON LT-FW-487 21 LEVEL TRANS BARTON LT-FW-497 22 TEMP RES BULB SOSTMAN TRB-RC-410

DUQUESNE LIGHT COMPANY HARSH AREA REPORT DATE 5/19/83 PAGE 3

EG ITEM DESCRIPTION MANUFACTURER MARK NUMBER 22 TEMP RES BULB SOSTMAN TRB-RC-412B 22 TEMP RES BULB SOSTMAN TRB-RC-412D 22 TEMP RES BULB SOSTMAN TRB-RC-413 22 TEMP RES BULB SOSTMAN TRB-RC-420 22 TEMP RES BULB SOSTMAN TRB-RC-422D 22 TEMP RES BULD SOSTMAN TRB-RC-422D 22 TEMP RES BULB SOSTMAN TRB-RC-423 22 TEMP RES BULB SOSTMAN TRB-RC-430 22 TEMP RES BULB SOSTMAN TRB-RC-432B 22 TEMP RES BULB SOSTMAN TRB-RC-432D 22 TEMP RES BULB SOSTMAN TRB-RC-433 24 DAMPER MOTOR LIMITOROUE VS-D-5-3B 24 DAMPER MOTOR LIMITOROUE VS-D-5-5B 25 MOTOR OP VALVE LIMITOROUE MOV-CH-310 25 MOTOR OP VALVE LIMITORQUE MOV-CH-378 25 MOTOR OP VALVE LIMITOROUE MOV-RC-535 25 MOTOR OP VALVE LIMITORQUE MOV-RC-536 25 MOTOR OP VALVE LIMITOROUE MOV-RC-537 25 MOTOR OP VALVE LIMITOROUE MOV-SI-842 25 MOTOR OP VALVE LIMITOROUE MOV-SI-856B 25 MOTOR OP VALVE LIMITOROUE MOV-SI-863A 25 MOTOR OP VALVE LIMITORQUE MOV-SI-865C 26 PUMP MOTOR GENERAL ELEC RS-P-1A 26 PUMP MOTOR GENERAL ELEC RS-P-1B 27 ACCELEROMETER ENDEVCD FE-RC-100A-1 27 ACCELEROMETER ENDEVC0 FE-RC-100A-2-1 27 ACCELEROMETER ENDEVC0 FE-RC-100D-1 27 ACCELEROMETER ENDEVC0 FE-RC-100B-2 27 ACCELEROMETER ENDEVC0 FE-RC-100C-1 27 ACCELEROMETER ENDEVC0 FE-RC-100C-2 27 ACCELEROMETER ENDEVC0 FE-RC-101A-1 27 ACCELEROMETER ENDEVC0 FE-RC-101A-2 27 ACCELEROMETER ENDEVC0 FE-RC-101B-1 27 ACCELEROMETER ENDEVC0 FE-RC-101D-2 27 ACCELEROMETER ENDEVCD FE-RC-101C-1 27 ACCELEROMETER ENDEVCD FE-RC-101C-2 27 CRG AMPLIFIER UNHOLTZ-DICKIE FY-RC-100A-3 27 CRG AMPLIFIER UNHOLTZ-DICKIE FY-RC-100A-2 27 CRG AMPLIFIER UNHOLTZ-DICK'IE FY-RC-100D-1 27 CRG AMPLIFIER UNHOLTZ-DICKIE FY-RC-100B-2 27 CRG AMPLIFIER UNHOLTZ-DICKIE FY-RC-100C-1 27 CRG AMPLIFIER UNHOLTZ-DICKIE FY-RC-100C-2 27 CRG AMPLIFIER UNHOLTZ-DICKIE FY-RC-101A-1 27 CRG AMPLIFIER UNHOLTZ-DICKIE FY-RC-101A-2 27 CRG AMPLIFIER UNHOLTZ-DICKIE FY-RC-101B-1 27 CRG AMPLIFIER UNHOLTZ-DICKIE FY-RC-1010-2 27 CRG AMPLIFIER UNHOLTZ-DICKIE FY-RC-101C 1 27 CRG AMPLIFIER UNHOLTZ-DICKIE FY-RC-101C-2 30 600V CBL SPLICE OKONITE NONE 32 SIS UIRE GENERAL ELEC NONE 33 SIS UIRE GENERAL ELEC NONE 35 MTR CNTRL CNTR ALLIS CHALMERS MCC-1-E12 EQUIPMENT ITEM

DUQUESNE LIGHT COMPANY HARSH AREA REPORT DATE 5/19/83 PAGE 4

EO ITEM DESCRIPTION MANUFACTURER MARN NUMBER 35 MTR CNTRL CNTR ALLIS CHALMERS MCC-1-E3 35 MTR CNTRL CNTR ALLIS CHALMERS MCC-1-E4 35 MTR CNTRL CNTR ALLIS CHALMERS MCC-1-E5 35 MTR CNTRL CNTR ALLIS CHALMERS MCC-1-E6 39 LIMIT SWITCH NAMCO LMS-FW-103A 39 LIMIT SWITCH NAMCO L M S - F W - 1031:

40 FLOW TRANS FISCHER PORTER FT-FW-100A 40 FLOW TRANS FISCHER FORTER FT-FW-100U 40 FLOW TRANS FISCHER PORTER FT-FW-100C 40 FLOW TRANS FISCHER PORTER FT-RW-102A 40 FLOW TRANS FISCHER PORTER FT-RW-102D 41 PRESS TRANS FISCHER FORTER PT-LM-100A il PRESS TRANS FISCHER PORTER PT-LM-100B 41 PRESS TRANS FISCHER PORTER PT-LM--100C 41 PRESS TRANS FISCHER PORTER PT-LM-100D 41 PRESS TRANS FISCHER PORTER PT-RS-156A 41 PRESS TRANS FISCHER PORTER PT-RS-156B 42 PRESS TRANS FISCHER PORTER PT-MS-474 42 PRESS TRANS FISCHER PORTER P T-MS-175 42 PRESS TRANS FISCHER PORTER

- PT-MS-476 42 PRESS TRANS FISCHER PORTER PT-MS-484 42 PRESS TRANS FISCHER PORTER PT-MS-485 42 PRESS TRANS FISCHER PORTER PT-MS-486 42 PRESS TRANS FISCHER PORTER PT-MS-494 42 PRESS TRANS FISCHER PORTER PT-MS-495 42 PRESS TRANS FISCHER PORTER PT-MS-496 43 MOTOR OP VALVE LIMITOROUE MOV-FW-151A 43 MOTOR OP VALVE LIMITOROUE M O V -F L'- 151 B 43 MOTOR OP VALVE LIMITOROUE MOV-FW-151C 43 MOTOR OP VALVE LIMITOROUE HOV-FW-151D 43 MOTOR OP VALVE LIMITOROUE MOV-FW-151E 43 MOTUR OP VALVE LIMITOROUE MOV-FW-151F 43 MOTOR OP VALVE LIMITOROUE MOV-FW-156A 43 MOTOR OP VALVE LIMITOROUE MOV-FW-156D 43 MOTOR OP VALVE LIMITOROUE MOV-FU-1'st 13 MOTOR OP VALVE LIMITOROUE MOV-MS-J C' 13 MOTOR OP VALVE LIMITOROUE MOV-RS '5LA 43 MOTOR OP VALVE LIMITOROUE MOV-RS-15LB

)

43 MOTOR OP VALVE LIMITOROUE MOV-RS-156A l

43 MOTOR OP VALVE LIMITOROUE MOV-RS-156B 43 MOTOR OP UALVE LIMITOROUE MOV-RW-103A 43 MOTOR OP VALVE LIMITOROUE MOV-RW-103B 43 MOTOR OP VALVE LIMITOROUE MOV-RW-103C 43 MOTOR OP VALVE LIMITOROUE MOV-RW-103D 45 MOTOR OP VALVE LIMITOROUE MOV-RW-104A 43 MOTOR OP VALVE LIMITOROUE MOV-RW-104B 43 MOTOR OP VALVE LIMITOROUE MOV-RW-104C 43 MOTOR OP VALVE LIMITOROUE MOV-RW-104D 43 MOTOR OP VALVE LIMITOROUE MOV-RW-105A 43 MOTOR OP VALVE LIMITOROUE MOV-RW-105B 43 MOTOR OP VALVE LIMITOROUE MOV-RW-105C 43 MOTOR OP VALVE LIMITOROUE MOV-RW-105D 3EEDRL_RQRTETL D iLJE Q UI P M E N T___ I T E M

DUGUESNE LIGHT COMPANY HARSH AREA REPORT DATE 5/19/83 FADE 5

EO ITEM DESCRIPTION MANUFACTURER MARK NUMBER i

I 43 MOTOR OP VALVE LIMITOROUE MOV-RW-106A

(

43 MOTOR OP VALVE LIMITOROUE MOV-RW-106B l

43 MOTOR OP VALVE LIMITOROUE MOV-RW-114A l

43 MOTOR OP VALVE LIMITOROUE MOV-RW-114B 44 MOTOR OP VALVE LIMITOROUE MOV-SI-863A 44 MOTOR OP VALVE LIMITOROUE MOV-SI-863B 44 MOTOR OP VALVE LIMITORQUE MOV-SI-8646 44 MOTOR OP VALVE LIMITOROUE MOV-SI-864B 44 MOTOR OP VALVE LIMITORQUE MOV-SI-885A 44 MOTOR OP VALVE '

LIMITORQUE MOV-SI-885B 44 MOTOR OP VALVE LIMITOROUE MOV-SI-885C 44 MOTOR OP VALVE LIMITOROUE MOV-SI-885D 44 MOTOR OP VauVE LIMITOROUE MOV-SI-870A 44 MOTOR OP VALVE LIMITOROUE MOV-SI-890B 44 MOTOR OP VALVE LIMITORGUE MOV-SI-890C 45 MOTOR OP VALVE LIMITOROUE MOV-CH-115B 45 MOTOR OF VALVE LIMITOROUE MOV-Cd-113C 45 MOTOR OP VALVE LIFITORQUE MOV-CH-115D 45 MOTOR OP VALVE LIMITOROUE M O V -C M.'/15 E 45 MOTOR OP VALVE LIMITOROUE MOV-CH-275A 45 MOTOR OP VALVE LIMITOROUE MOV-CH-275B 45 MOTOR OP VALVE LIMITOROUE MOV-CH-275C 45 MOTOR OP VALVE LIMITORQUE MOV-CH-289 45 MOTOR OP VALVE LIMITORGUE MOV-CH-370 45 MOTOR OP VALVE LIMITORQUE MOV-CH-373 45 MOTOR OP VALVE LIMITORGUE MOV-CH-3S1 45 MOTOR OP VALVE LIMITORQUE MOV-SI-856.

45 MOTOR OP VALVE LIMITOPOUE MOV-SI-860A 45 MOTOR OP VALVE LIMITOROUE MOV-SI-860B 45 MOTOR OP VALVE LIMITORQUE MOV-SI-862A 45 MOTOR OP VALVE ' LIMITORQUE MOV-SI-862B 45 MOTOR OP VALVE LIMITORQUE MOV-SI-867A 45 MOTOR OP VALVE LIMITOROUE MOV-SI-867B 45 MOTOR OP VALVE LIMITORQUE r.0V-SI-867C 45 MOTOR OP VALVE LIMITORGUE

. ~V-SI-867D

. '. - S I - 3 6 7 A 45 MOTOR OP VALVE LIMITORGUE 45 MOTOR OP VALVE LIMITORGit MOV-SI-86?B 46 PUMP MOTOR LOUIS ALL

f'W-P-3A 46 PUMP MOTOR LOUIS ALL;0 FW-P-3B 47 PUMP MOTOR WESTINGHOUSE SI-P-1A 47 PUMP MOTOR WESTINGHOUSE SI-P-1B 48 PUMP MOTOR WESTINGHOUSE CH-P-1A 48 PUMP MOTOR WESTINGHOUSE CH-P-1B 48 FUMP MOTOR WESTINGHOUSE CH-P-1C REPORT SORTED ON EQUIPMENT ITEM J

d m

MASTER LIST PHASE 2 OF EQUIPMENT REQUIRING QUALIFICATION ff MAY 1983

DUQUESNE LIGHY COMPANY

~

HARSH AREA REPORT JATE 5/18/83 PAGE 1

ITEM DESCRIPTION MANUFACTURER MARK NUMBER u______________________________________________________

2008 SOLENDID ASCO SOV-BD-100A 2008 SOLENOID ASCO SOV-BD-100B 2008 SOLENDID ASCO SOV-BD-100C

' 2008 SOLEN 0ID ASCO SOV-FW-102 2008 SOLENDID ASCO SOV-FW-103A 2008 SOLEN 0ID ASCO SOV-FW-103B 2009 PUMP MOTOR SEIMENS ALLIS RS-P-2A 2009 PUMP MOTOR SEIMENS ALLIS RS-P-2B 2010 SOLENOID VALCOR SOV-FW-478A l

2010 SOLEN 0ID VALCOR SOV-FW-478B 2010 SOLENOID VALCOR SOV-FW-488A 2010 SOLEN 0ID VALCOR SOV-FW-488B 2010 SOLENDID VALCOR SOV-FW-498A 2010 SOLEN 0ID VALCOR SOV-FW-4988 2015 RAD MONITOR VICTOREEN RM-RM-219A 2015 RAD MONITOR VICTOREEN RM-RM-219B 2018 SOLENDID VALCOR TV-CV-150-A 2018 SOLEN 0ID VALCOR TV-CV-150-B 2018 SOLEN 0ID VALCOR TV-SS-102-A1 2018 SOLENDID VALCOR TV-SS-102-A2 2018 SOLEN 0ID VALCOR TV-S.S-105A1 2018 SOLENOID VALCOR TV-SS-105A2 2019 FLOW TRANS ROSEMOUNT FT-MS-102A

.2019 FLOW TRANS ROSEMOUNT FT-MS-102B 2019 FLOW TRANS ROSEHOUNT FT-MS-102C 2020 LIMIT SWITCH NAMCO LMS-CC-103A 2020 LIMIT SWITCH NAMCO LMS-CC-103B 2020 LIMIT SWITCH NAMCO LMS-CC-103C 2020 LIMIT SWITCH NAMCO LMS-CC-110D 2020 LIMIT SWITCH NAMCO LMS-CC-111A2

~

2020 LIMIT SWITCH NAMCO LMS-DA-100A 2020 LIMIT SWITCH NAMCO LMS-DG-108A 2020 LIMIT SWITCH NAMCO LMS-FP-105 2920 LIMIT SWITCH NAMCO LMS-FP-106 2020 LIMIT SWITCH NAMCO LMS-FP-107 2021 LIMIT SWITCH NAMCO LMS-BD-100A 2021 LIMIT SWITCH NAMCO LMS-BD-100B 2021 LIMIT SWITCH NAMCO LMS-BD-100C 2021 LIMIT SWITCH NAMCO LMS-BD-101A1 2021 LIMIT SWITCH NAMCO LMS-BD-101A2 2021 LIMIT SWITCH NAMCO LMS-BD-101B1 2021 LIMIT SWITCH NAMCO LMS-BD-101B2 2021 LIMIT SWITCH NAMCO LMS-BD-101C1 2021 LIMIT SWITCH NAMCO LMS-BD-101C2 2021 LIMIT SWITCH NAMCO LMS-MS-105A l

2021 LIMIT SWITCH NAMCO LMS-MS-105B 1

2022 SOLEN 0ID ASCO SOV-FP-105 2022 SOLEN 0ID ASCO SOV-FP-106 2022 SOLEN 0ID ASCO SOV-FP-107 2024 REST. TEMP DET.

CONAX TRB-RS-150A l

2024 REST. TEMP DET.

CONAX TRB-RS-150B 2025 CABLE SPLICE KERITE COMPANY NONE REPORT SORTED ON EQUIPMENT ITEM

DUQUESNE LIGHT COMFANY HARSH AREA REPORT DATE 5/18/83 PAGE 2

l0 ITEM DESCRIPTION MANUFACTURER MARK NUMBER 2027 SOLEN 0ID TARGET ROCK SOV-RC-102A 2027 SOLEN 0ID TARGET ROCK SOV-RC-102B 2027 SOLEN 0ID TARGET ROCK SOV-RC-103A 2027 SOLEN 0ID TARGET ROCK SOV-RC-103B 2027 SOLENDID TARGET ROCK SOV-RC-104 2027 SOLEN 0ID TARGET ROCK SOV-RC-105 2031 PRESS TRANS GOULD PT-RC-104 2036 TRANSFORMER HEVI DUTY TRF-PWR-29 2038 TEMP SWITCH FLUID COMPONENT TS-AS-101A 203C TEMP SWITCH FLUID COMPONENT TS-AS-101B 2038 TEMP SWITCH FLUID COMPONENT TS-AS-102A 2038 TEMP SWITCH FLUID COMPONENT TS-AS-102B 2038 TEMP SWITCH FLUID COMPONENT TS-AS-103A 2038 TEMP SWITCH FLUID COMPONENT TS-AS-103B 2038 TEMP SWITCH FLUID COMPONENT TS-AS-104 2038 TEMP SWITCH FLUID COMPONENT TS-AS-105 2038 TEMP SWITCH FLUID COMPONENT TS-AS-106 2038 TEMP SWITCH FLUID COMPONENT TS-AS-107 2038 TEMP SWITCH FLUID COMPONENT TS-AS-108 2038 TEMP SWITCH FLUID COMPONENT TS-AS-109 2038 TEMP SWITCH FLUID COMPONENT TS-AS-110 2038 TEMP SWITCH FLUID COMPONENT TS-AS-111 2038 TEMP SWITCH FLUID COMPONENT TS-AS-112 2038 TEMP SWITCH FLUID COMPONENT TS-AS-113 2038 TEMP SWITCH FLUID COMPONENT TS-AS-114 2038 TEMP SWITCH FLUID COMPONENT TS-BD-100A 2038 TEMP SWITCH FLUID COMPONENT TS-BD-100B 2042 SOLEN 0ID VALCOR SOV-HY102A1 2.042 SOLEN 0ID VALCOR SOV-HY102A2 2042 SOLEN 0ID VALCOR SOV-HY102B1 2042 SOLENDID VALCOR SOV-HY102B2 2042 SOLENDID VALCOR SOV-HY103A1 2042 SOLENDID VALCOR SOV-HY103A2 2042 SOLENOID VALCOR SOV-HY103B1 2042 SOLENOID UALCOR SOV-HY103B2 2042 SOLENOID VALCOR SOV-HY104A1 2042 SOLENDID VALCOR SOV-HY104A2 l

2042 SOLEN 0ID VALCOR SOV-HY104B1 2042 SOLEN 0ID VALCOR SOV-HY104D2 2042 SOLENOID VALCOR TV-CV-102 2042 SOLEN 0ID VALCOR TV-CV-102-1 2044 SOLEN 0ID ASCO SOV-CH-204 2044 SOLEN 0ID ASCO SOV-SI-884A 2044 SOLENDID ASCO SOV-SI-884B 2044 SOLENOID ASCO SOV-SI-884C 2045 CABLE SPLICE RAYCHEM NONE 2046 TERMINAL BLK PENN UNION NONE 2046 TERMINAL BLK PENN UNION NONE 2047 CABLE SPLICE RAYCHEM NONE 2051 RELAY AMERACE CORP NONE 2051 RELAY AMERACE CORP NONE 2051 RELAY AMERACE CORP NONE

~

REPORT SORTED ON EQUIPMENT ITEM

e-DUQUESNE LIGHT COMPANY HARSH AREA REPORT

=

DATE 5/18/83 PAGE 3

0 ITEM DESCRIPTION MANUFACTURER MARK NUMBER 2051 RELAY AMERACE CORP NONE 2031 RELAY AMERACE CORP NONE 2051 RELAY AMERACE CORP NONE 2064 TERMINAL BLK MARATHON NONE 2064 TERMINAL BLK MARATHON NONE 2066 PRESS TRANS ROSEMOUNT PT-LM-101A 2066 PRESS TRANS ROSEMOUNT PT-LM-101B 2067 RAD MONTOR KAMAN RIS-NSC-05A 2067 RAD MONTOR KAMAN RIS-NSC-05B 2068 HICR0 PROCESSOR KAMAN NONE 2068 MICROPROCESSOR KANAN NONE 2073 LEVEL TRANS GEMS LT-DA100 2073 LEVEL TRANS GEMS LT-RS151A 2073 LEVEL TRANS GENS LT-RS151B 2074 CNTRL TERMINAL EBERLINE RM-CON-1 2081 SELECTOR SWITCH WESTINGHOUSE CS-30 2081 SELECTOR SWITCH WESTINGHOUSE CS-31 2081 SELECTOR SWITCH WESTINGHOUSE CS-32 2081 SELECTOR SWITCH WESTINGHOUSE CS-33 2081 SELECTOR SWITCH WESTINGHOUSE CS-39 2081 SELECTOR SWITCH WESTINGHOUSE HS-C.V-102-1X 2081 SELECTOR SWITCH WESTINGHOUSE HS-CV-102X 2001 SELECTOR SWITCH WESTINGHOUSE HS-CV-150AX 2081 SELECTOR SWITCH WESTINGHOUSE HS-CV-150BX 2081 SELECTOR SWITCH WESTINGHOUSE HS-SS-102A1X 2081 SELECTOR SWITCH WESTINGHOUSE HS-SS-102A2X 2081 SELECTOR SWITCH WESTINGHOUSE HS-SS-105A1X 2081 SELECTOR SWITCH WESTINGHOUSE H3-SS-105A2X 2081 SELECTOR SWITCH WESTINGHOUSE NONE 2081 SELECTOR SWITCH WESTINGHOUSE NONE 2081 SELECTOR SWITCH WESTINGHOUSE NONE 2081 SELECTOR SWITCH WESTINGHOUSE NONE 2081 SELECTOR SWITCH WESTINGHOUSE NONE 2081 SELECTOR SWITCH WESTINGHOUSE NONE 2081 SELECTOR SWITCH WESTINGHOUSE NONE 2081 SELECTOR SWITCH WESTINGHOUSE NONE 2081 SELECTOR SWITCH WESTINGHCUSE NONE 2081 SELECTOR SWITCH WESTINGHOUSE NONE 2081 SELECTOR SWITCH WESTINGHOUSE NONE 2081 SELECTOR SWITCH WESTINGHOUSE NONE 2081 SELECTOR SWITCH WESTINGHOUSE NONE 2081 SELECTOR SWITCH WESTINGHOUSE NONE p-------------------m-----m---memmmmmmmmmmagemmmmmegggg REPORT SORTED ON EQUIPMENT ITEM

o l

l l

l V.

FUTURE UPDATING OF THE MASTER LIST l

4

V.

FUTURE UPDATING OF THE MASTER LIST Duquesne Light Company maintains a current record of the j

equipment items for which qualification is required within its overall qualification program.

All of the safety-related electrical equipment is listed and maintained current in the Equipment Qualification file.

As equipment items are added or replaced, changes to the file and to the Master List are made accordingly.

Unless specifically requested by the NRC through future submittal requests, Duquesne Light Company will not re-transmit the Master List, but rather keep it current and on file at the plant.

I VI.

REFERENCES P

l l

VI. REFERENCES Duquesne Light Company has provided several submittals to the NRC that summarized the status of the Beaver Valley Power Station Unit 1

electrical equipment for which environmental qualitication was required.

These sub.nittals also defined the various aspects of the overall program that are currently being implemented.

The following is a list identifying the previous Duquesne Light Company submittals:

i Submittal Date Environmental Qualification December 31, 1980 Documentation Report for the NRC I.E. Bulletin 79-01B Response to SER tor October 15, 1981 Environmental Qualification of Safety-Related Electrical Equipment Environmental Qualification March 24,1983 Documentation Report for NRC SER 90 Day Response 1983

DUQUESNE LIGHT COMPANY HARSH AREA REPORT PAGE 1

DATE 5/18/83 EO ITEM DESCRIPTION MANUFACTURER MARK NUFBER 1

POWER CABLE KERITE NFB-16 2

POWER CABLE CERRO WIRE NFB-65 i

3 POWER CABLE OKONITE VARIOUS 4

CNTRL CABLE OKONITE VARIOUS S

INSTRUMENT CBL CONTINENTAL W3C VARIOUS 6

PENE. TYPE I VIKING NONE 6

PENE. TYPE III VIKING NONE 6

PENE. TYPE II VIKING NONE 6

PENE. 1YPE VIII VIKING NONE

~

6 PENE. TYPE V VIKING NONE 6

PENE. TYPE IX VIKING NONE 6

PENE. TYPE IV VIKING NONE 7

TERMINAL BLKS BUCHANAN VARIOUS 8

TERMINAL BLKS PENN UNION VARIOUS 9

SIS WIRE ROCKBESTOS VARIOUS 10 SOLENDID ASCO SOV-CC-103A1 10 SOLENDID ASCO SOV-CC-103B1 10 SOLENDID ASCO SOV-CC-103C1 10 SOLENDID ASCO SOV-CC-105D1 10 SOLENOID ASCO SOV-CC-105El 10 SOLEN 0ID ASCO SOV-CC-107D1 10 SOLENDID ASCO SOV-CC-107E1 10 SOLEN 0ID ASCO SOV-CC-110D 10 SOLEN 0ID ASCO SOV-CC-110E3 10 SOLEN 0ID ASCO SOV-CC-111A2 10 SOLENDID ASCO SOV-CC-111D1 10 SOLEN 0ID ASCO SOV.-CH-200A1 10 SOLENOID ASCO SOV-CH-200B1 10 SOLENDID ASCO SOV-CH-200C1 10 SOLENDID ASCO SOV-CV-102-1 10 SOLEN 0ID ASCO SOV-DA-100A 10 SOLEN 0ID ASCO SOV-DG-108A 10 SOLENOID ASCO SOV-DG-109A2 10 SOLENOID ASCO SOV-LM-101A 10 SOLENDID ASCO SOV-LM-101B 10 SOLENDID ASCO SOV-RC-455C1 10 SDLENDID ASCO SOV-RC-455C2 l

10 SOLENDID ASCO SOV-RC-455D1 10 SOLENDID ASCO SOV-RC-455D2 10 SOLENDID ASCO SOV-RC-456-1 10 SOLEN 0ID ASCO SOV-RC-456-2 10 SOLENOID ASCO SOV-SI-101-2 10 SOLEN 0ID ASCO SOV-SS-000A 11 LIMIT SWITCH NAMCO LMS-CC-105D1 11 LIMIT SWITCH NAMCO LMS-CC-111D 11 LIMIT SWITCH NAMCO LMS-CH-200A 12 LIMIT SWITCH NAMCO LMS-CH-200B 11 LIMIT SWITCH NAMCO LilS-CH-200 C 11 LIMIT SWITCH NAMCO LMS-RC-455C 11 LIMIT SWITCH NAMCO LMS-RC-455D 11 LIMIT SWITCH NAMCO LMS-RC-456 11 LIMIT SWITCH NAMCO LMS-SI-101-2 REPORT SORTED ON EQUIPMENT ITEM

~

DUQUESNE LIGHT COMPANY HARSH AREA REPORT DATE 5/17/83 PAGE 2

EQ ITEM DESCRIPTION MANUFACTURER MARK NUMBER l

11 LIMIT SWITCH NAMCO LMS-SI-865A 11 LIMIT SWITCH NANCO LMS-SI-865B 11 LIMIT SWITCH NAMCO LMS-SI-865C 13 LIMIT SWITCH NANCO LMS-CC-103A1 13 LIMIT SWITCH NAMCO LMS-CC-103B1 13 LIMIT SWITCH NAMCO LMS-CC-103C1 13 LIMIT SWITCH NAMCO LMS-CC-10SE1 13 LIMIT CWITCH NAMCO LMS-CC-107D1 13 LIMIT SWITCH NAMCO LMS-CC-107El 13 LIMIT SWITCH NAMCO LMS-CC-110D' 13 LIMIT SWITCH NAMCO LMS-CC-110E3 13 LIMIT SWITCH NAMCO LMS-CC-111A2 13 LIMIT SWITCH MAMCO LMS-CV-102-1 13 LIMIT SWITCH NAMCO LMS-DA-100A 13 LIMIT SWIlCH HAMCO LMS-DG-108A 13 LIMIT SWITCH NAMCO LHC-DG-109A-2 14 FLOW TRANS FISCHER PORTER FT-MS-474 14 FLOW TRANS FISCHER PORTER FT-MS-475 14 FLOW TRANS FISCHER PORTER FT-MS-484 14 FLOW TRANS FISCHER PORTER FT-MS-485 14 FLOW TRANS FISCHER PORTER FT-MS-494 14 FLOW TRANS FISCHER PORTER FT-MS-495 15 FLOW TRANS BARTON FT-SI-961 15 FLOW TRANS BARTON FT-SI-962 15 FLOW TRANS BARTON FT-SI-963 16 LEVEL TRANS BARTON LT-FW-474 16 LEVEL TRANS BARTON LT-FW-475 16 LEVEL TRANS BARTON LT-FW-476 16 LEVEL TRANS BARTON LT-FW-484 16 LEVEL TRANS BARTON LT-FW-485 16 LEVEL TRANS BARTON LT-FW-486 16 LEVEL TRANS BARTON LT-FW-494 16 LEVEL TRANS BARTON LT-FW-495 16 LEVEL TRANS BARTON LT-FW-496 16 LEVEL TRANS BARTON LT-RC-459 16 LEVEL TRANS BARTON LT-RC-460 16 LEVEL TRANS BARTON LT-RC-461 17 LEVEL TRANS MASON-NEILAN LT-RS-151A 17 LEVEL TRANS MASON-NEILAN LT-RS-151B 18 LEVEL TRANS MASON-NEILAN LT-RC-470 17 LEVEL TRANS MASON-NEILAN LT-RC-470 19 PRESS TRANS FISCHER PORTER PT-RC-472 l

19 PRESS TRANS FISCHER FORTER PT-RS-152A 19 PRESS TRANS FISCHER PORTER PT-RS-152B 20 PRESS TRANS BARTON PT-RC-402 20 PRESS TRANS BARTON PT-RC-403

.0 PRESS TRANS BARTON PT-RC-455 2

20 PRESS TRANS BARTON PT-RC-456 20 PRESS TRANS BARTON PT-RC-457 21 LEVEL TRANS BARTON LT-FW-477

(

21 LEVEL TRANS BARTON LT-FW-487 21 LEVEL TRANS BARTON LT-FW-497 REPORT SORTED ON EQUIPMENT ITEM

DUQUESNE LZGHT COMPANY HARSH AREA REPORT DATE 5/18/83 PAGE 3

EQ ITEM DESCRIPTION MANUFACTURER MARK NUMBER 22 TEMP RES BULB SOSTMAN TRB-RC-410 22 TEMP RES BULB SOSTMAN TRB-RC-412B 22 TEMP RES BULB SOSTMAN TRB-RC-412D 22 TEMP RES BULB SOSTMAN TRB-RC-413 22 TEMP RES BULB SOSTMAN TRB-RC-420 22 TEMP RES BULB SOSTMAN TRB-RC-122B 22 TEMP RES BULB SOSTMAN TRB-RC-422D 22 TEMP RES BULB SOSTMAN TRB-RC-423 22 TEMP RES BULB SOSTMAN TRB-RC-430 22 TEMP RES BULB SOSTMAN TRB-RC-432B 22 TEMP RES BULB SOSTMAN TRB-RC-432D 22 TEMP RES BULB SOSTMAN TRB-RC-433 24 DAMPER MOTOR LIMITORGUE VS-D-5-3B 24 DAMPER MOTOR LIMITOROUE VS-D-5-5B 25 MOTOR OP VALVE LIMITOROUE MOV-CH-310 25 MOTOR OP VALVE LIMITOROUE HOV-CH-378 25 MOTOR OP VALVE LIMITORGUE HOV-RC-535 25 MOTOR OP VALVE LIMITOROUE MOV-RC-536 25 MOTOR OP VALVE LIMITORGUE MOV-RC-537 25 MOTOR OP VALVE LIMITOROUE MOV-SI-842 25 MOTOR OP VALVE LIMITOROUE MOV-SI-856B 25 MOTOR OP VALVE LIMITORGUE MOV-SI-865A 25 MOTOR OP VALVE LIMITOROUE MOV-SI-865C 26 PUMP MOTOR GENERAL ELEC RS-P-1A 26 PUMP MOTOR GENERAL ELEC RS-P-1B 27 ACCELEROMETER ENDEVC0 FE-RC-100A-1 27 ACCELEROMETER ENDEVCD FE-RC-100A-2-1 27 ACCELEROMETER ENDEVC0 FE-RC-100B-1

, 27 ACCELEROMETER ENDEVC0 FE-RC-100B-2 27 ACCELEROMETER ENDEVC0 FE-RC-100C-1 27 ACCELEROMETER ENDEVCD FE-RC-100C-2 27 ACCELEROMETER ENDEVC0 FE-RC-101A-1 27 ACCELEROMETER ENDEVCD FE-RC-101A-2 27 ACCELEROMETER ENDEVC0 FE-RC-101B-1 27 ACCELEROMETER ENDEVCD FE-RC-101B-2 27 ACCELEROMETER ENDEVCD FE-RC-101C-1 27 ACCELEROMETER ENDEVC0 FE-RC-101C-2 27 CRG AMPLIFIER UNHOLTZ-DICKIE FY-RC-100A-1 27 CRG AMPLIFIER UNHOLTZ-DICKIE FY-RC-100A-2 27 CRG AMPLIFIER UNHOLTZ-DICKIE FY-RC-100D-1 27 CRG AMPLIFIER UNHOLTZ-DICKIE FY-RC-100B-2 1

27 CRG AMPLIFIER UNHOLTZ-DICKIE FY-RC-100C-1 27 CRG AMPLIFIER UNHOLTZ-DICKIE FY-RC-100C-2 27 CRG AMPLIFIER UNHOLTZ-DICKIE FY-RC-101A-1 27 CRG AMPLIFIER UNHOLTZ-DICKIE FY-RC-101A-2 27 CRG AMPLIFIER UNHOLTZ-DICKIE FY-RC-101B-1 27 CRG AMPLIFIER UNHOLTZ-DICKIE FY-RC-101B-2 27 CRG AMPLIFIER UNHOLTZ-DICKIE FY-RC-101C-1 27 CRG AMPLIFIER UNHOLTZ-DICKIE FY-RC-101C-2 30 600V CBL SPLICE OKONITE NONE 32 SIS WIRE GENERAL ELEC NONE 33 SIS WIRE GENERAL ELEC NONE REPORT SORTED ON EQUIPMENT ITEM L

DUQUESNE LIGHT COMPANY HARSH AREA REPORT DATE 5/17/83 PAGE 4

EQ ITEM DESCRIPTION MANUFACTURER MARK NUMBER 35 HTR CNTRL CNTR ALLIS CHALMERS MCC-1-E12 35 HTR CNTRL CNTR ALLIS CHALMERS MCC-1-E3 35 MTR CNTRL CNTR ALLIS CHALMERS MCC-1-E4 35 MTR CNTRL CNTR ALLIS CHALMERS MCC-1-E5 35 MTR CNTRL CNTR ALLIS CHALMERS MCC-1-E6 39 LIMIT SWITCH NAMCO LMS-FW-103A 39 LIMIT SWITCH NAMCO LMS-FW-103B 40 FLOW TRANS FISCHER PORTER FT-FW-100A 40 FLOW TRANS FISCHER PORTER FT-FW-100B 40 FLOW TRANS FISCHER PORTER FT-FW-100C

~

40 FLOW 1RANS FISCHER PORTER FT-RW-102A 40 FLOW TRANS FISCHER PORTER FT-RW-102B 41 PRESS TRANS FISCHER PORTER PT-LM-100A 41 PRESS TRANS FISCHER PORTER PT-LM-100B 41 PRESS TRANS FISCHER PORTER PT-LM-100C c

l 41 PRESS TRANS FISCHER PORTER PT-LM-100D l

41 PRESS TRANS FISCHER PORTER PT-RS-156A 41 PRESS TRANS FISCHER PORTER PT-RS-156B 42 PRESS TRANS FISCHER PORTER PT-MS-474 42 PRESS TRANS FISCHER PORTER PT-MS-475 42 PRESS TRANS FISCHER FORTER PT-MS-476 42 PRESS TRANS FISCHER PORTER PT-MS-484 42 PRESS TRANS FISCHER PORTER PT-MS-485 42 PRESS TRANS FISCHER PORTER PT-MS-486 42 PRESS TRANS FISCHER PORTER PT-MS-494 42 PRESS TRANS FISCHER PORTER PT-MS-495 42 PRESS TRANS FISCHER PORTER PT-MS-496 43 MOTOR OP VALVE LIMITORQUE HOV-FW-151A MOTOR OP VALVE LIMITOROUE MOV-FW-151B

- 43 43 MOTOR OP VALVE LIMITORQUE MOV-FW-151C 43 MOTOR OP VALVE LIMITOROUE MOV-FW-151D 43 MOTOR OP VALVE LIMITORQUE MOV-FW-151E 43 MOTOR OP VALVE LIMITOROUE MOV-FW-151F 43 MOTOR OP VALVE LIMITORQUE HOV-FW-156A 43 MOTOR OP VALVE LIMITOROUE MOV-FW-156B l

43 MOTOR GP VALVE L'MITORQUE MOV-FW-156C 43 MOTOR OP VALVE LIMITORQUE MOV-MS-105 43 MOTOR OP VALVE LIMif0 ROUE MOV-RS-155A 43 MOTOR OP VALVE LIMITOROUE MOV-RS-155B 43 MOTOR OP VALVE LIMITORQUE MOV-RS-156A 43 MOTOR OP VALVE LIMITORGUE HOV-RS-156B 43 MOTOR OP VALVE LIMITORQUE MOV-RW-103A 43 MOTOR OP VALVE LIMITORGUE MOV-RW-103B l

43 MOTOR OP VALVE LIMITOROUE MOV-RW-103C 43 MOTOR OP VALVE LIMITOROUE MOV-RW-103D 43 MOTOR OP VALVE LIMITOROUE MOV-RW-104A l

43 MOTOR OP VALVE LIMITORGUE MOV-RW-104B 43 MOTOR OP VALVE LIMITORQUE MOV-RW-104C 43 MOTOR OP VALVE LIMITOROUE MOV-RW-104D l

43 MOTOR OP VALVE LIMITORQUE MOV-RW-105A l

43 MOTOR OP VALVE LIMITOROUE MOV-RW-105B l

43 MOTOR OP VALVE LIMITORQUE HOV-RW-105C

DUQUESNE LIGHT COMPANY HARSH AREA REPORT DATE 5/17/83 PAGE 5

EG ITEM DESCRIP' di MANUFACTURER MARK NUMBER 1--

43 MOTOR OP VALVE LIMITOROUE MOV-RW-105D 43 MOTOR OP VALVE LIMITORQUE MOV-RW-106A 43 MOTOR OP VALVE LIMITORQUE MOV-RW-106B 43 MOTOR OP VALVE LIMITOROUE MOV-RW-114A 43 MOTOR OP VALVE LIMITOROUE MOV-RW-114B 44 MOTOR OP VALVE LIMITORGUE MOV-SI-863A 44 HOTOR OP VALVE LIMITOROUE MOV-SI-863B 44 MOTOR OP VALVE LIMITOROUE MOV-SI-864A 44 MOTOR OP VALVE LIMITOROUE MOV-SI-864B 44 MOTOR OP VALVE LIMITORQUE MOV-SI-885A 44 MOTOR OP VALVE LIMITOROUE MOV-SI-885B 44 MOTOR OP VALVE LIMITOROUE MOV-SI-885C 44 MOTOR OP VALVE LIMITORGUE MOV-SI-885D 44 MOTOR OP VALVE LIMITOROUE MOV-SI-890A 44 MOTOR OP VALVE LIMITOROUE MOV-SI-890B 44 MOTOR OP VALVE LIMITOROUE MOV-SI-890C 45 MOTOR OP VALVE LIMITOROUE MOV-CH-115B 45 MOTOR OP VALVE LIMITOROUE MOV-CH-115C 45 MOTOR OP VALVE LIMITORQUE MOV-CH-115D 45 MOTOR OP VALVE LIMITOROUE MOV-CH-115E 45 MOTOR OP VALVE LIMITORGUE MOV-CH-275A 45 MOTOR OP VALVE LIMITOROUE MOV-CH-275B 45 MOTOR OP VALVE LIMITORQUE MOV-CH-275C 45 MOTOR OP VALVE LIMITOROUE MOV-CH-289 45 MOTOR OP VALVE LIMITOROUE MOV-CH-370 45 MOTOR OP VALVE LIMITORGUE MOV-CH-373 45 MOTOR OP VALVE LIMITORQUE MOV-CH-381 45 MOTOR OP VALVE LIMITORQUE MOV-SI-836 45 MOTOR OP VALVE LIMITORQUE MOV-SI-860A 45 MOTOR OP VALVE LIMITORQUE MOV-SI-860B 45 MOTOR OP VALVE LIMITORGUE MOV-SI-862A 45 MOTOR OP VALVE LIMITOROUE MOV-SI-862B 43 MOTOR OP VALVE LIMITOROUE MOV-SI-867A l

45 MOTOR OP VALVE LIMITOROUE HOV-SI-867B l

45 MOTOR OP VALVE LIMITOROUE MOV-SI-867C l

45 MOTOR OP VALVE LIMITORGUE MOV-SI-867D 45 MOTOR OP VALVE LIMITORQUE MOV-SI-869A 45 MOTOR OP VALVE LIMITORQUE MOV-SI-869B 46 PUMP MOTOR LOUIS ALLIS FW-P-3A 46 PUMP MOTOR LOUIS ALLIS FW-P-3B 47 PUMP MOTOR WESTINGHOUSE SI-P-1A 47 PUMP MOTOR WESTINGHOUSE SI-P-1B 48 PUMP MOTOR WESTINGHOUSE CH-P-1A 48 PUMP MOTOR WESTINGHOUSE CH-P-1B 48 PUMP MOTOR WESTINGHOUSE CH-P-1C i

1 G

REPORT SORTED ON EQUIPMENT ITEM

J DUQUESNE LIGHT COMPANY HARSH AREA REPORT 1 ATE 5/18/83 PAGE 1

2008 EOLENDID ASCO SOV-BD-100A 2008 SOLENDID ASCO SOV-BD-100B 2008 SOLENDID ASCO SOV-BD-100C 2008 SOLENOID ASCO SOV-FU-102 2008 SOLENDID ASCO SOV-FW-103A 2008 SOLENDID ASCO SOV-FW-103B 2009 PUMP MOTOR SEINENS ALLIS RS-P-2A 2009 PUMP MOTOR SEIMENS ALLIS RS-P-2B 2010 SOLENDID VALCOR SOV-FW-478A 2010 SOLENDID VALCOR SOV-FW-478B 2010 SOLEN 0ID VALCOR SOV-FW-488A 2010 SOLENDID VALCOR SOV-FW-488B 2010 SOLENOID VALCOR SOV-FW-498A 2010 SOLENDID VALCOR SOV-FW-49SB 2015 RAD MONITOR VICTOREEN RM-RM-219A 2015 RAD MONITOR VICTOREEN RM-RM-219B 2018 SOLEN 0ID VALCOR TV-CV-150-A 2018 SOLENDID VALCOR TV-CV-150-B 2018 SOLENDID VALCOR TV-SS-102-A1 2018 SOLEN 0ID VALCOR TV-SS-102-A2 2018 SOLENDID VALCOR TV-SS-105A1 2018 SOLENOID VALCOR TV-SS-105A2 2019 FLOW TRANS ROSEMOUNT FT-MS-102A 2019 FLOW TRANS ROSEMOUNT FT-MS-102B 2019 FLOW TRANS ROSEMOUNT FT-MS-102C 2020 LIMIT SWITCH NAMCO LMS-CC-103A 2020 LIMIT SWITCH NAMCO LMS-CC-103B 2020 LIMIT SWITCH NAMCO LMS-CC-103C 2,020 LIMIT SWITCH NAMCO LMS-CC-110D 2020 LIMIT SWITCH NAMCO LMS-CC-111A2 2020 LIMIT SWITCH NAMCO LMS-DA-100A 2020 LIMIT SWITCH NAMCO LMS-DG-108A 2020 LIMIT SWITCH NAMCO LMS-FP-105 2020 LIMIT SWITCH NAMCO LMS-FP-106 2020 LIMIT SWITCH NAMCO LMS-FP-107 2021 LIMIT SWITCH NAMCO LMS-BD-100A 2021 LIMIT SUITCH NAMCO LMS-BD-100B o

2021 LIMIT SWITCH NAMCO LMS-BD-100C l

2021 LIMIT SWITCH NAMCO LMS-BD-101A1 2021 LIMIT SWITCH NAMCO LMS-BD-101A2 2021 LIMIT SWITCH NAMCO LMS-BD-101B1 2021 LIMIT SWITCH NAMCO LMS-BD-101B2 2021 LIMIT SWITCH NAMCO LMS-BD-101C1 2021 LIMIT SWITCH NAMCO LMS-BD-101C2 2021 LIMIT SWITCH NAMCO LMS-MS-105A 2021 LIMIT SWITCH NAMCO LMS-MS-105B 2022 SOLEN 0ID ASCO SOV-FP-105 2022 SOLENOID ASCO SOV-FP-106 2022 SOLEN 0ID ASCO SOV-FP-107 2024 REST. TEMP DET.

CONAX TRB-RS-150A 2024 REST. TEMP DET.

CONAX TRB-RS-150B 2025 CABLE SPLICE KERITE COMPANY NONE REPORT SORTED ON EQUIPMENT ITEM

DUQUESNE LIGHT COMPANY HARSH AREA REPORT MATE 5/18/83 PAGE 2

e ITEM DESCRIPTION MANUFACTURER MARK NUMBER 2027 SOLENOID TARGET ROCK SOV-RC-102A 2027 SOLEN 0ID TARGET ROCK SOV-RC-102B 2027 SOLENDID TARGET ROCK SOV-RC-103A 2027 SOLEN 0ID TARGET ROCK SOV-RC-103B 2027 SOLEN 0ID TARGET ROCK SOV-RC-104 2027 SOLENOID TARGET ROCK SOV-RC-105 2031 PRESS TRANS GOULD PT-RC-104 2036 TRANSFORMER HEVI DUTY TRF-PUR-29 2038 TEMP SWITCH FLUID COMPONENT TS-AS-101A 2038 TEMP SWITCH FLUID COMPONENT TS-AS-101B 2038 TEMP SWITCH FLUID COMPONENT TS-AS-102A 2038 TEMP SWITCH FLUID COMPONENT TS-AS-102B 2038 TEMP SWITCH FLUID COMPONENT TS-AS-103A 2038 TEMP SWITCH FLUID COMPONENT TS-AS-103B 2038 TEMP SWITCH FLUID COMPONENT TS-AS-104 2038 TEMP SWITCH FLUID COMPONENT TS-AS-105 2038 TEMP SWITCH FLUID COMPONENT TS-AS-106 2038 TEMP SWITCH FLUID COMPONENT TS-AS-107 2038 TEMP SWITCH FLUID COMPONENT TS-AS-10S 2038 TEMP SWITCH FLUID COMPONENT TS-AS-109 2038 TEMP SUITCH FLUID COMPONENT TS-AS-110 2038 TEMP SWITCH FLUID COMPONENT TS-AS-111 2038 TEMP SWITCH FLUID COMPONENT TS-AS-112 2038 TEMP SWITCH FLUID COMPONENT TS-AS-113 2038 TEMP SWITCH FLUID COMPONENT TS-AS-114 2038 TEMP SWITCH FLUID COMPONENT TS-BD-100A 2038 TEMP SWITCH FLUID COMPONENT TS-BD-100B 2042 SOLENDID VALCOR SOV-HY102A1 2042 SOLEN 0ID VALCOR SOV-HY102A2 2042 SOLENDID VALCOR SOV-HY102B1 2042 SOLENOID VALCOR SOV-HY102B2 2042 SOLEN 0ID VALCOR SOV-HY103A1 2042 SOLENDID VALCOR SOV-HY103A2 2042 SOLENDID VALCOR SOV-HY103B1 2042 SOLEN 0ID VALCOR SOV-HY103B2 2042 SOLENOID VALCOR SOV-HY104A1 2042 SOLEN 0ID VALCOR SOV-HY104A2 2042 SOLEN 0ID VALCOR SOV-HY104B1 l

2042 SOLEN 0ID VALCOR SOV-HY104B2 2042 SOLEN 0ID VALCOR TV-CV-102 2042 SOLENDID VALCOR TV-CV-102-1 2044 SOLENOID ASCO SOV-CH-204 2044 SOLENDID ASCO SOV-SI-884A 2044 SOLENDID ASCO SOV-SI-884B 2044 SOLEN 0ID ASCO SOV-SI-884C 2045 CABLE SPLICE RAYCHEM NONE 2046 TERMINAL BLK PENN UNION NONE 2046 TERMINAL BLK PENN UNION NONE 2047 CABLE SPLICE RAYCHEM NONE 2051 RELAY AMERACE CORP NONE 2051 RELAY AMERACE CORP NONE 2051 RELAY AMERACE CORP NONE REPORT SORTED ON EQUIPMENT ITEM

._____l s

DUQUESNE LIGHT COMPANY i

HARSH AREA REPORT

.ATE 9/18/83 PAGE 3

ITEM DESCRIPTION MANUFACTURER-MARK NUMDER 2051 RELAY AMERACE CORP NONE 2051 RELAY AMERACE CORP NONE 2051 RELAY-AMERACE CORP NONE 2064 TERMINAL BLK MARATHON NONE 2064 TERMINAL BLK MARATHON NONE 2066 PRESS TRANS ROSEMOUNT PT-LM-101A 2066 PRESS TRANS ROSEMOUNT PT-LM-101B 2067 RAD MONTOR KAMAN RIS-NSC-05A 2067 RAD MONTOR KAMAN RIS-NSC-05B 2068 MICROPROCESSOR KAMAN NONE 2068 MICROPROCESSOR KANAN NONE 2073 LEVEL TRANS GENS LT-DA100 2073 LEVEL TRANS GEMS LT-RS151A 2073 LEVEL TRANS GEMS LT-RS151B 2074 CNTRL TERMINAL EBERLINE RM-CON-1 2081 SELECTGR SWITCH WESTINGHOUSE CS-30 2081 SELECTOR SWITCH WESTINGHOUSE CS-31 2081 SELECTOR SWITCH WESTINGHOUSE CS-32 2081 SELECTOR SWITCH WESTINGHOUSE CS-33 2081 SELECTOR SWITCH WESTINGHOUSE CS-39 2081 SELECTOR SWITCH WESTINGHOUSE HS-CV-102-1X 2001 SELECTOR SWITCH WESTINGHOUSE HS-CV-102X 2081 SELECTOR SWITCH WESTINGHOUSE HS-CV-150AX 2081 SELECTOR SWITCH WESTINGHOUSE HS-CV-150BX 2081 SELECTOR SWITCH WESTINGHOUSE HS-SS-102A1X 2081 SELECTOR SWITCH WESTINGHOUSE HS-SS-102A2X 2081 SELECTOR SWITCH WESTINGHOUSE HS-SS-105A1X 2081 SELECTOR SWITCH WESTINGHOUSE HS-SS-105A2X 2081 SELECTOR SWITCH WESTINGHOUSE NONE 2081' SELECTOR SWITCH WESTINGHOUSE NONE 2081 SELECTOR SWITCH WESTINGHOUSE NONE 2081 SELECTOR SWITCH WESTINGHOUSE NONE 2081 SELECTOR SWITCH WESTINGHOUSE NONE 2081 SELECTOR SWITCH WESTINGHOUSE NONE 2081 SELECTOR SWITCH WESTINGHOUSE NONE 2081 SELECTOR SWITCH WESTINGHOUSE NONE 2081 SELECTOR SWITCH WESTINGHOUSE NONE i

2081 SELECTOR SWITCH WESTINGHOUSE NONE 2081 SELECTOR SWITCH WESTINGHOUSE NONE

~2081 SELECTOR SWITCH WESTINGHOUSE NONE

( 2081 SELECTOR SWITCH WESTINGHOUSE NONE 2081 SELECTOR SWITCH WESTINGHOUSE NONE g______________________________________________________

REPORT SORTED ON EQUIPMENT ITEM

-