ML20054K026
| ML20054K026 | |
| Person / Time | |
|---|---|
| Site: | Grand Gulf |
| Issue date: | 03/22/1982 |
| From: | MISSISSIPPI POWER & LIGHT CO. |
| To: | |
| Shared Package | |
| ML20054J949 | List:
|
| References | |
| 05-1-02-V-11, 5-1-2-V-11, NUDOCS 8206300312 | |
| Download: ML20054K026 (4) | |
Text
-..
.Y f
I' PLANT OPERATIONS MANUAL
- ]
Volume 5 05-1-02-V-11 Sect ion 02 Revis ion :
10 Date: 3-22-82 i
OFF-NORMAL EVENT PROCEDURE LOSS OF PLANT SERVICE WATER SAFETY RELATED k
Prepared:
N,,
.A a,,
Reviewed:
[,
-cc-
/ /
,-+
V. Technical' Review Nuclear' Plant Qualicy Superintendent Reviewed:
(
w --
Operationg Superintendent Approved:
frifL Ass is t at Plant nag PSRC:
3[/g /g d__
'~
v i
/
f( ~
l List of Ef fective Pages:
Page:
Rev is ion :
1-3 10 I
- k.."
B206300312 820625 PDR ADOCK 05000416 P
l N'
CRAND GULF NUCLEAR STATION OFF-NORMAL EVENT PROCEDURE lTi-le: Loss of Plant Se rv ice (No.:
05-1-02-V-11 l Rev is ion:
10 [Page:
1 l
l Water l
l l
l 1.0 PURPOSE / DISCUSSION 1.1 The purpose of this procedure is to provide the operator with the steps necessary to combat a complete loss of Plant Service Water.
1.2 This procedure may interface with the Emergency Plan and the Emergency Procedures.
1.3 The PSW System supplies the following components:
1.3.1 Circulating Water Pumps Seal Water and motor coolers 1.3.2 Component Cooling Water Heater Ixchangers 1.3.3 Turbine Building Cooling Water Heat Exchangers 1.3.4 Mechanical Vacuum Pump Coolers 1.3.5 Steam Jet Air Ejector Inner Condenser 1.3.6 Drywell Coolers 1.3.7 Steam Tunnel Coolers (2D 1.3.8 Plant Chillers 1.3.9 Service and instrument, air compressors.
~
1.3.10 Ctmt Leak Rate Test System compressor Aftercooler.
1.3.11' Standby ~ service water coolin~g~ tower"b~as~ ins makeup. ~ ~
~ ~ " "
I 1.3.12 Fire Water Storage Tanks makeup.
1.3.13 ESF Electrical switchgear room coolers.
1.3.14 Raw water for Water Treatment System The loss of PSW will cause a loss of Cire dater and a loss of Condenser air removal capabilities. Thus loss of PSW results in the loss of the Condenser as a heat sink. Also, loss of PSW will necess itate supplying CCW with an alternate means of cooling.
(:
l
4-GRAND _ GULF NUCLEAR STATION,
OFF-NORMAL EVENT PROCEDURE l
Title:
. Loss of Plant Service No.:
05-1-02-V-Il (Revision:
10 lPage:_,2
(.;
l Water l
I I
CAUTION Loss of PSW constitutes a loss of fire protection to the Radial Wells.
2.0 SYMPTOMS 2.1 PSW RADIAL WELL TROUBLE alarm 2.2 PSW UNIT 1 HDR PRESS LOW alarm 2.3 PSW UNIT 1 HDR PRESS LOW-LOW alarm 2.4 Loss of both Cire Water Pump 2.5 Decreas ing Condenser Vacuum 2.6 Loss of plant chillers 2.7 Deceasing level in circulating water cooling tower basin.
2.8 Instrument air or/SVCS Air Compressor Trip
(' '#
3.0 AUTOMATIC ACTIONS 3.1 Circulating Water Pumps will trip approximately 45 seconds af ter a loss of PSW.
4.0 IMMEDIATE OPERATOR ACTIONS 4.1 Attempt to start all Radial Well Pumps.
4.2 If PSW cannot be restarted 4.2.1 Manually scram the reactor and refer to ONEP 05-1-02-I-1 Reactor Scram.
4.2.2 Close the MSIV's and refer to EP-1, Level Control 4.2.3 Init iate Standby Service Water.
4.3 Not ify the Shif t Supervisor of plant cond it ions.
4.4 Refer to ONEP 05-1-02-V-8, Loss of condenser vacuum, with no circulat ing pump running.
(.
f GRAND GULF NUCLEAR STATION OFF-NORMAL EVENT PROCEDURE l
Title:
Loss of Plant Service lNo.: 0 5-1 V-11 I Revis ion :
10 lPage: 3 l
hj_!
l Water l
l l
l 4.5 Align SSW to supply the Air Compressors 4.5.1 Open IP41-F155A SSW OTBD SPLY TO AIR COMPRS (IH13-P870) 4.5.2 Open IP41-F155B SSW INBD SPLY TO AIR 00MPRS (lH13-P870)
~
4.5.3 Close SP44-F173 PSW Discharge Valve (Local Pancl) 4.5.4 Open IP41-F154 SSW RIN FM AIR COMPRS i
5.0 SUBSEQUENT ACTIONS 5.1 Align SSW to supply the CCW Heat exchangers and Drywell coolers.
5.1.1 Close IP44-F0ll PSW Normal return (local panel) i 5.1.2 Close IP44-F115 PSW Supply to chillers (local panel) 5.1.3 Close IP44-F068 PSW RIN HDR FM CTMT (lH13-PS70) 5.1.4 Open IP44-F054 SSW INBD SPLY TD DRWL CLR/CCW RXS (1H13-P870)
(4 5.1.5 Open IP44-F042 SSW OTBD SPLY TO DRWL CLRS/CCW HXS (IH13-P870)
~-~~ [e'n~1P44-F067 SSW RTN FM DRWL CLRS/CCW HXS (lH13-P870)
'-~ ~ [t, 6 0
.u-,
5.2 Implement the Emergency Plan, if directed by the Shift Supervisor or Shif t Superintendent.
5'. 3 betermine and' coh~re~ct the cause of the loss of PSW.
~
~ ~
1
~
_