PLANT OPERATIONS MANUAL
..a Volume 5 0 5-1 IV-6 Section 02 Revision:
11 Date: 6-12-82 0FF-NORMAL EVENT PROCEDURE LOSS OF RPIS SAFETY RELATED
__._i_.
- W 3 Reviewed:
/
Nuclear Plant 0uality"Superint4ndent V i Technical Review
~
p Approved:
'Operagons perintend nt Concurrence:
4fa'n ag'e r' ss Vgt' ant P 'a d //B 2_
PSRC:
~'
[
f /
List of Effective Pages:
Page:
1 l
List of TCN's Incorporated:
Revision TCN No.
10 None 11 None t
8206300286 820625 l
PDR ADOCK 05000416 P
. _... _ _ = _,
diD CULF NUCLEAR STATION OFF-NORMAL EVENT PROCEDURE r
Title:
Los s of RPIS No.:
05-1-02-IV-6 Revision:
11 Page:
1 1.0 PURPOSE / DISCUSSION 1.1 The purpose of this procedure is to provide instructions for the operator during the loss of the RPIS.
1.2 This procedure will not interf ace with the Emergency Plan or Emergency Procedures.
1.3 RPIS supplies the operator with control rod position information which is required for all modes of operation.
The RPIS also supplies inputs to the computer and RWL and RPC Sys tem.
2.0 SYMPTOMS 2.1 Loss of one or more rod position indicators 2.2 Loss of the full core display.
2.3 Double image on rod position indicator 2.4 iC61S7 NOP alarm on 1H13 P'680 7
~ '
~
^
t 2.5 Control Rod Withdrawal Block alarm on lH13-P680 2.6 INSERT INHIBIT and/or WITHDRAWAL INHIBIT status lights ON.
2.7 " Data fault.
~
2.0 AUTOMATIC ACTIONS 3.1 Control rod withdrawal block and/or rod insert block.
4.0 IMMEDIATE OPERATOR ' ACTIONS 4.1 Obtain rod position data from computer or the alternate RPIS channel.
~
4.2 If possible, insert the control rod to a position with a operable position indication.
4.3 If all rod position indication is lost - rod motion is prohibited except by scram.
4.4 Notify the Shift Supervisor and if necessary to move rods, the Reactor Engineer.
5.0 SUBSEQUENT ACTIONS 5.1 Refer to Tech. Specs. section 3.1.3.5.
5.2 Initiate necessary action 'to have ;ne malfunction corrected.