PLANT OPERATIONS MANUAL i
l Volume 05 05-1-02-11-12 Section 02 Revis ion:
10 Date: 3-17-82 i
i i
OFF-NORMAL EVENT PROCEDURE SOLID RADWASTE SPILL SAFETY RELATED p
l.
I c
s h BS h.') Preparea,:
4.t.
( jato be I
Reviewed :
_/
/-
4 Nuclear Plant Quality Superintendent y Technical Review l
Reviewed:
k!E V-j Operatio(s Superintendent 3//d/b Approved:
/
M A X
_a Assistant Plant Manager PSRC:
/d List of Ef fective Pages:
Page:
Revision:
1 10 8206300265 820625 PDR ADOCK 05000416 PDR p
CRAjiD CULF NUCLEAR STATION OFF-NORMAL EVENT PROCEDURE
~
3
',lT it le :
Solid Raswaste Spill lNo.:
05-1-02-11-12 l Revision:
10 lPage:
1 l
l l
l l
l
~
1.0 PURPOSE / DISCUSSION 1.1 The purpose of this procedure is to provide instruction to the operator in.the event of a Solid Radwaste Spill.
l.2 This procedure may interface with the emergency plan.
1.3 This procedure will discuss actions to be taken if a spil1 of solidified waste occurs. The failure of the cannister may be due to a fall or metal
- fatigue, b
- . O Sn PTo.;s 2.1 Abnormal radiat ion levels indicated on the radwaste building area radiation monitors.
2.2 Visual observation of spilled solid radwaste.
j 2.3 Possible inc rease in airborne activity.
3.0 AUTOMATIC ACTIONS 3.1 None (p 4.0 IMMEDIATE OPERATOR ACTIONS 4.1 Evacuate the affected area and restrict access to the area.
4.2 Contact Health Physics to survey the area of the spill.
5.0 SUBSEQUENT ACTIONS
}
5.1 Proceed to implement the emergency' plan if directed by the Shift Supervisor or Shift Superintendent.
5.2 If high airborne exists, implement ONEP 05-12-01-II-9, High Airborne.
5.3 Following proper Radiation Control measures, place the solid spill in a container for later processing.
1 J