05000395/LER-1982-060, Forwards LER 82-060/03L-0.Detailed Event Analysis Encl

From kanterella
(Redirected from ML20028D989)
Jump to navigation Jump to search
Forwards LER 82-060/03L-0.Detailed Event Analysis Encl
ML20028D989
Person / Time
Site: Summer South Carolina Electric & Gas Company icon.png
Issue date: 01/14/1983
From: Dixon O
SOUTH CAROLINA ELECTRIC & GAS CO.
To: James O'Reilly
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
Shared Package
ML20028D990 List:
References
NUDOCS 8301200217
Download: ML20028D989 (2)


LER-1982-060, Forwards LER 82-060/03L-0.Detailed Event Analysis Encl
Event date:
Report date:
3951982060R00 - NRC Website

text

.

g.

SOUTH CAROLINA ELECTRIC & GAS COMPANY g

g POST OFFICE 784 Z

J.,

COLUMalA, SOUTH CAROLINA 29218 O

..)

.[

O. W. DixON, JR.

p

~

Nuc EAR OPERAT NS January 14, 1983

~

N re Mr. James P. O'Reilly, Director U.S. Nuclear Regulatory Commission Region II, Suite 3100 101 Marietta Street, N.W.

Atlanta, Georgia 30303

SUBJECT:

Virgil C.

Summer Nuclear Station Docket No. 50/395 Operating License No. NPF-12 Thirty Day Written Report LER 82-060

Dear Mr. O'Reilly:

Please find attached Licensee Event Report #82-060 for Virgil C.

Summer Nuclear Station.

This Thirty Day Report is required by Technical Specification 6.9.1.13.(c) as a result of not performing the monthly surveillance requirement of Technical Specification 3.3.3.6, Table 4.3-7, Item 22.

Should there be any questions, please call us at your convenience.

Very tru

yours, x
0. W. Dpon, CJM:0WD:dwr Attachment cc:

V.

C.

Summer A.

R. Koon T.

C. Nichols, Jr.

G.

D. Moffatt E.

C.

Roberts Site QA

0. W. Dixon, Jr.

C. L. Ligon (NSRC)

H.

N.

Cyrus G. J. Braddick H. T. Babb J. L.

Skolds D.

A. Nauman J. B. Knotts, Jr.

M.

B. Whitaker, Jr.

B.

A.

Bursey W.

A. Williams, Jr.

I&E (Washington)

O.

S.

Bradham Document Management Branch R.

B. Clary INPO Records Center M. N.

Browne NPCF File u&ICIAh S 8301200217 830114 fgO PDR ADOCK 05000395 C

S PDR

Mr. James P.

O'Reilly LER No.82-060 Page Two January 14, 1983 DETAILED DESCRIPTION OF EVENT On December 15, 1982, with the Plant in Mode 1, it was discovered that the Licensee had not been in total compliance with Surveillance Requirement 4.3.3.6, (Table 4.3-7, Item 22) of Technical Specification 3.3.3.6.

A channel check of the Acoustical Monitors was performed per Surveillance Test Procedure (STP) 135.001, " Post Accident Monitoring Instruments Channel check," rather than a monthly verification of the Pressurizer Safety Valve Position Indicator.

The verification of valve position had not been documented since the Plant's entry into Mode 3 on September 30, 1982.

PROBABLE CONSEQUENCES There were no adverse consequences from this event.

Using STP-135.001 the operability of the Acoustic Monitor, which would have activated an alarm in the Control Room if flow had been detected downstream of the safety valves, was verified on a monthly-basis.

CAUSE(S) OF THE OCCURRENCE The cause of the occurrence was due to personnel error.

The procedure was not revised when Technical Specification 3.3.3.6 was changed to include Safety Valve Position Indication, just prior to license issue.

The specification was changed due to our desire to use Position Indication Switches, versus the Acoustic Monitor, to meet NUREG 0737 requirements.

IMMEDIATE CORRECTIVE ACTIONS TAKEN STP-135.001 was revised on December 21, 1982, to include the verification of Pressurizer Safety Valve Position Indication on a monthly basis while in Modes 1, 2, and 3.

The applicable portion of the procedure dealing with the safety valves was satisfactorily performed on the same day.

ACTION TAKEN TO PREVENT RECURRENCE The Licensee plans no additional action in regards to this event.