s"%-

L}_ .

.* CONTAIFNENT SYSTEMS SURVEILLANCE REQUIREMENTS (Continued)

1. Starting (unless _already operating) each cooling unit from the control room.
2. Verifying that each cooling unit operates for at least 15 minutes.
3. -Verifying a service water flow rate of. > 2500 gpm to any group of two cooling units.
4. Verifying a service water flow rate of > 1250 gpm to any group containing one cooling unit.
b. At least once per 18 months by verifying that each cooling unit starts automatically on a CCAS test signal.

ARKANSAS - UNIT 2 3/4 6-15

~

L.

8009180.4 K 7-