ML18347A680

From kanterella
Jump to navigation Jump to search
Information Submitted in Addition to That Provided in Consumers Power Company Submittals of March 26, 1976 and April 5, 1976
ML18347A680
Person / Time
Site: Palisades 
Issue date: 04/05/1976
From:
Consumers Power Co
To:
Office of Nuclear Reactor Regulation
References
Download: ML18347A680 (9)


Text

' I I

1.

INFORMATION SUBMITTED IN ADDITION TO THAT PROVIDED IN CONSUMERS POWER COMPANY SUBMITTALS OF MARCH 26, 1976 AND APRIL 5, 1976 The response to Question 6 of the March 26, 1976 letter indicated that procedures and/or design changes are presently under development to proclude the "undesirable function" failure of the mini-flow valves (CV-3027 and CV-3056) and that a response would be submitted at a later date.

Circuitry changes have been*initiated and will be completed prior to start-up to in-sure that a single failure will not cause a mini-flow valve to shut during the short-term cooling phase and also to insure that a single failure will not preclude the shutting of at least one mini-flow valve during the long-term cooling phase.

There are two mini-flow valves installed in series at the Palisades Plant.

The purpose of these valves is to provide a bypass flow path during safety injection pump deadheaded operations.

In most, if not all, of the break spectrum, initial safety injection pump operation occurs before primary system pressure is reduced to a value below all the safety injection pump discharge heads.

For this reason it is necessary for the mini-flow valves to be open to provide a recirculation path when the pumps are operating deadheaded such that pump damage does not occur.

The recirculation path is back to the SIRW tank

  • Upon transfer to the recirculation mode of cooling, it is desirable to close these mini-flow valves to preclude placing some of the water from the sump back into the SIRW tank.

Thus, for this case at least, one of the two valves in series must be capable of being closed.

The transfer to the recirculation phase occurs about 30 minutes following a Loss of Coolant Accident.

The valves are Walworth gate valves with a Miller piston operator.

Air pres-sure is re~uired to alter the position of the valves.

Two three-way d-c operated solenoid valves are provided, one on the opening side and one on the closing side, to supply and vent air from the valve such that commanded operations are achieved.

The solenoid valves, as originally installed, would cause the valve to fail closed on loss of electric power.

Loss of air supply would result in the valve failing as is.

A stick diagram of the valve operator and solenoid valve arrangement is shown on the following figure.

This stick diagram provides a good representation of how the valve is actuated.

On the same diagram the existing electrical scheme is also shown.

As can be seen from that scheme, a single electrical failure (closing of the contac'ts of HS-3027 or HS-3056) would cause the ap-propriate valve to go closed as..,:well as any failure which causes the de-energization of both solenoids of each valve.

  • The same figure shows a stick diagram of the proposed modification to the solenoid valves and a proposed circuit modification.

The result of these proposed modifications is that on a loss of electrical power the* solenoid 1

RAS CV...3027 8:V... 3056.

RA-S

~

7 PROPOSED M'ODIFICATION 7

I I

-~-

NE NE SV 3027 B* *.

SV 3027 A A/S

'FROM M-225& 204 SCHEMES 513, Si4 IDENTICAL NO.

PRESENT

'FROM E-246 SIRWT LOW LEVEL 214 t.OGIC ENERGIZE ON LOW LEVEL 3l

_t C03 CONTACTS CLOSED

  • /WITH SWITCH IN OPEN POSITION 4LI I

HS13027 4L3 C03

~1i21 Cl3 C03 ~C03

~-----<1'\\o-('I' -o--.J I

-.L-ND*.

ND SV 3027 A SV 3027 B A/S N.O.

PROPOSED SI,RWT LOW LEVEL 214 LOGIC ENERGtZl ON LOW LEVEL 4LI I

4LI C03 r

J ()3 CONT~CTS OP'

/

WITH SWITCH OPEN POsrr10 HS3027

  • C03 NI C.13 C03 Q C03 i--~--~Nl-o-----1
  • valves for 3027 and 3056 are powered from different d-c buses resulting in the valve failing open.

The modified circuit eliminates any electrical single failure which will cause the valve to fail shut.

The two valves in series and their separate circuits provide protection against a postulated single failure causing both valves to remain open and thus the mini-flow line not being isolated during the recirculation phase.

The rearrangement of this circuit now requires that. operator action be taken to close the mini-flow valves prior to initiation of the recirculation phase (approximately 30 minutes after the LOCA event).

In addition, operator ac-tion to close these valves is not desirable until the primary coolant system

.pressure*is-decreased below the discharge head capability of both the high-and low-pressure safety injection pumps.

The closure of the contacts asso-ciated with this hand switch in conjunction with a low level in the SIRW tank will initiate mini-flow valve* closure.

Thus, the closure of the hand switch contacts in conjunction with a nonvalid low level SIRW tank signal could cause the mini-flow valves to go closed prematurely.

Thus, we will include in the appropriate operating procedures a requirement that the hand switch associated with the mini-flow valves be positioned such that the mini-flow valves will close automatically on a low level in the SIRW tank after the primary coolant system pressure has decreased to a value below the shutoff discharge pressure of the high-pressure and low-pressure safety injection pumps and prior to SIRW tank low level.

The modifications described in this response are being completed in a?cordance with the provisions of 10 CFR 50.59.

These modifications will be completed prior to plant start-up as will the procedural changes described above.

During a telephone conversation on April 5, 1976 with members of the NRC staff, it was suggested that indicating lights be installed to monitor the status of the contacts associated with the valve actuation circuitry.

This would preclude an undetected contact failure followed by a single failure in the other contacts or circuitry associated with this actuation scheme causing a mini-flow valve to shut.

Because of the series contact arrange-ment we have not been able to identify a satisfactory manner of providing the contact status indicator lights.

The only arrangements we have been able to devise that would appear to work in a satisfactory manner from the standpoint of the lights involve placing a trickle current on the solenoid valve operating coils.

As these coils pick up under very light current con-ditions which would cause the mini-flow valves to go closed, we do not believe that this is desirable.

The switch and relay types that are_ used in the mini-flow valve circuitry are types that have been used extensively throughout the Palisades Plant.

With respect to contact failures, these switches and relays have proven very reliable.

We, therefore, have concluded that there is not a need for continuous monito:ring of the contact position and instead are incorporating in plant procedures a requirement that contact operability be verified during refueling outages as well as proper contact position.

We believe that this will provide reasonable assurance that undetected contact closure will not occur.

2

2.
3.

In addition, during the same telephone conversation, we were requested to provide information with respect to the design of the air system which provides operating air to these valves.

This information is located in Amendment 28 to the FSAR, Section 9.5.l.

In our response of April 5, 1976 to Question 5.20 regarding including re-quirements for power lockout of certain valves in the Technical Specifica-tions, we indicated that the two mini-flow bypass valves were still under review and that further response would be provided at a later date.

Item l of this attachment describes the modifications and procedural controls that will b~ implemented prior to start-up.

As the actions taken to preclude undesirable ECCS single failure effects do not include power lockout, we do not believe that additional Technical Specifications are required.

Our March 26, 1976 response to Question 4 of the "Generic Information Request for Review of ECCS in the Electrical Instrumentation and Control Areas" at-tached to USNRC's March 26, 1976 letter stated that a response would be provided at a later date.

Question 4 stated:

"Identify all electr_ical _equipment, both safety and nonsafety, that may become submerged.asia result of a LOCA.

For all such equipment that is not qualified for service. in such an environ-ment, provide an analysis to determine the following:

(l) The safety significance of the failure of the equipment (eg, spurious operation, loss of function, loss of accident/postaccident moni-toring, etc) as a result of flooding, (2) the effects on Class IE electrical power sources serving this equipment as a result of such failures, and (3) the proposed design changes resulting from your analysis.

Your response to Item (2) should specifically ad-dress breaker and fuse coordination and the isolation capabilities of this aspect of your design."

In order to identify all electrical equipment that might become submerged as a result of a LOCA (excluding submerged valves, refer to CP Co letter dated February 25, 1976), a survey was made of the containment building and all electrical equipment which was below the LOCA flood level was identified.

A detailed review of this equipment and its associated circuitry was then performed to determine if there was any safety significance as a result of flooding and to determine the effects on Class IE electrical power sources serving this equipment.

Breaker and fuse coordination was specifically addressed in this review.

T~e results of this review are summarized in the table contained on the following three pages.

As a result of this review, we have concluded that there is reasonable assurance that flooding of elec-trical equipment due to the postulated LOCA event will not result in a reduction of ECCS system capability and, therefore, no design changes are required, except PS-0103 identified as part of the long-term cooling evalu-ation.

Our evaluation and any proposed changes will be included with our report on that subject.

3

4.

Our March 26, 1976 response to Question 7 of the "Generic Information Request for' Review of ECCS in the Electrical, Instrumentation and Control

  • Areas" attached to the *USNRC March 26, 1976 letter stated.that a response would be provided at a later date.

Question 7 stated:

"Identify any electrical interlocks between redundant portions of the ECCS and supporting subsystems.

Define the consequence of fail~e of any interlock on the capability of the ECCS to perform its safety function.

Describe any proposed design modifications resulting from this review."

.Plant electrical drawings have been reviewed fer interlocks between redundant portions of the ECCS and supporting subsystems.

As a result of this review, three cross-train interti.es were identified.

These three interties are the interlock between breakers No 52-1217 and No 52-1118 (buses No 11 and No 12),

the interties between the Instrument A-C Bus (YOl) and MCC No 1 and No 2 and the intertie between MCC No 1 and No :4 via the battery charger.

The intertie between Buses 11 and 12 is an electrical interlock which prevents manual initiation of breaker closure (there is no automatic transfer action) that would tie the two buses together when Breakers 52-1102 and 52-1202 are closed.

This permissive signal is provided to preclude tieing two redundant energized buses together.

As a fault on either Bus 11 or 12 would trip its incoming breaker and operator action might be to attempt to close the tie breakers which might cause transfer of the fault to the other redundant bus, procedural changes will be implemented prior to plant start that require the operator (on loss of one of these buses during a LOCA situation) to attempt to clear the fault and close the incoming breaker prior to taking other action. If there is a fault that cannot be cleared, he will be instructed not to attempt to close the two tie breakers.

..,~

4

PALISADES

~ 0,_,M rnG-.D

- '""- - L I -

t:... L..t:. (.......

i \\..._;f\\ L I o *"*

-~ ' '

EQ0iPMENT (DoC"s

/).,"T'

// )-.:._*,cJ<J£

.S*:..1£:,:-,,* _F;~GE i !,/£

_.:TU.:.~ - )

POWER SUPPL'-;' Powsl( fEEt.:. lo C::tY_"(

TAG SCIJEMATll:.

Tll.G No.

IJENDoR FusE DllTP.

1.r.._;;:_f.jL,;:,_

LCCAT*oN S/"i:~

Ne.

No AMP PDT-01<.z. cB E-9(,, (4) F-0102.B f

~<t,f*

t-lf,_,.....

Y20- 5 z_o I

cc

\\

r-0102. c.

{.,.,. -

)/30-5 D..i..,-p.Jr C.D F-01oz D

}r""~-

Y<to-s I DB F-0102.&

foi:.n:~

'{ 2~-5 I

DC i r-0102c..

Y3o-s t

~ '°

F-0102 D

'(4o*S Pur- ::i 104 E-84 (4)

N/A N/A YDl-8 PT-O!OI A E" (1) f-0101A Y10-1o z.o PT- 010\\ B E-84(1)

P-0101B Y20-r;,

!=OXBcRo 1-'e Ar.,r -1 fll l'uT PT-c102.AI E-84(2.) f-0102A N\\opCL Yto-s P*01oz.!>

010A

~1\\.-.11'-ovrPu~ Yzo-5 1 1 ~1 I P-01 oz.c.

(<..u 1?..REl-lT" lliof' Y3()-S v-OI0?..1' v~-s

?T-0103 E-84{3) 'VLTlfL R:>x~ogo Fo<< ~I JNPIJ,...

Yo1-2.Co PT- 0131 A E-97(4)

  1. 4-SA~p

~ B 1£'

c,..,l._

0/32.. A

  1. 2

""'T'Pv'!"'"

t B

  1. 3 Y10 "'"'P 0133 A

~

i B 117 0111 ~

fil\\ILTlfLE

  • -IE" o I 42. A
itl/

i B

jiJL 0\\13 ~

t'/3 tild.

111(,I b~uk.t,~$ = JoA PT-O{OZ.

E-t,(_;}

Fo<.. l'w ~

Sys-Y10-3o-~ z.o

".1, 0'104

.j,

,.. D*ll*DwU..

Lde.p.s//Av~

y';a.4o-g~~4 l.O 5,..,#h.1., r...ise.5 TT; Er f-01s1 A 3/a AM('-,..ip.rr Y10--::- r P. 01s-1 B }fu"'~

YUJ-t:

Mooi;L f-o7SI C.

!;,10"'

YB AMP-ov.Pur y3,,.£

o-ois1n IVJn-5" F~P lir.,A"'<' aoT"?c.Jr

'(01-Z. l

'PT* 1001 f::-1-L ('2,\\ I Pis 10Bc>

Mot TlfLE:

PS-olo I I' 7 <>()

Ps-o IO!S E-242 52-11,,7 F'S- 0~35 E-2 '

7 "A

"A 52-/71 FS-092 I E-183 30 A""'r.>

2.52-lo3 o9 Z.8 I 252-2.03 09 29 NA N~ I 25'2.- 104-0930 I

1.5'2-2.o4 FT-o?o I E-b,9(/)

loo*~ b,e,k*'*' IDfj Yt~*Bh4 r O(DZ.

J f., N 12.<.~:* sy<°h>A t

0703 1NDLVtOLlfH... !('lop-:

  • .~:t( Yw-Jo ">' 4.

Orri.d.

!1u~ti.rose~

L'

'i?F"- \\!'loQ

~=~.1.3(1)

V1tTOU.fN

~A... r,,..

.~~..... r A.... r Q... 1.

IV4o-14 z_O Y-01-:;4 RE-1611 f>228fz V1c.'tOfe=.W I? E-ll'l 11 ""'" t.-22811.S l256.-R

/\\\\~TE. I: C..LAS~ IE.

Pi.I) l\\:)DT E'X.\\ST AT T1ME.

oF p,;.L1sAD£.::: bE!: 1GA!. Fol?.

PtH1.F'6$S SA'i'"ET'{ RELATEJ),

OF Ttfl.S STUDY Ir L<JA.s DEF11\\JEP A.S

A~E7'1' I KEU\\'e" Cv R.11..1
.N-r-Loops i.n.J~f!.OV--Jt' £b I

Yrs I

l No

'-lo VAlGKOtir.IDt:O No l

YE5.

i f.,Jo

~o Yrs """T"D'D NCJ r/~ C-) 6ND

/<Jo YES NO r tJO l YES

--*-~ --

i-.lo NO BRE..A-il-ER C..o /V11"1E N-r'.S FUSE.

CO-O.""'NATION cugg.EN.,..

Loop F<.1-,,e;-

OK_

we.u1.-o i31..ow

' 0(

Yo 1 - Nor 9FETY k~LA-TCJ)

Pl/!ECT FEE.O Tc TR/IN.SM 17--rEP 01(

R ti JrJP r.t:

Amfl'c..* r=>c(l..

01(.

'/01 - tJn SA"'ETY f?EnATQD FcEDWATC.e.

6-J,-~<-

1K S'r'ST1':M T~

IJ5.M I rr.EE C.ul!.eeNT Loo/" Fu-s.'E. vJ.oULt> r

&LoVll C Vl?.i1.£"'T LI 1<A 1-rE"R...

ON ol(

Pov-> E.!<.. S vf P'l.l?.'I',.,. tJ., SAFE1Y fu*n lloT.,~....,....iuN.c::. H'T'DR..

ci=re.crs Lctl6 TB2"" CMt1t-IG o~

0(.

oi::_

FE.B>w A-Te'R. CaAJTf!-PL

~ V.S TE:M r TRAl')5f1;1rr"E(S oK Yc1 Na1

':~-l,V RE.ll\\1"£.b -- ----~:J;__ ____

l-lG~,--1NG f-;_}r:(L-Nm-.-::1-\\:-£1y,~f[ll':!::O O~-

  • l~*

3 SAFE.TY E.FFcc..T of../

SiGIJIFlc.AklC:.:

cU>S!O.

IE

,u,,d 0,

ELEc/. E<t>1J1P, EQ~,P, Z-AILtJ/!£ IJ 01JE R.~S,;Tf!..IP P~/, U>oP Fl.41<1 JAJl)lc,A.TJt::tN W~tJc.Q 13E' t.JOsT F~M "'!'til?S..E TRA~sm fTTE1Z.S.

/JO") E r*

I I

NOl\\IE 1'\\or=

i R.r.s. TRIP

, -S.I.. l: PP!.

LD.:>P Pil:EO::.$, 11J!),

. \\.UitHJLf> i!> fE L:>'t'r

'*I?

F=E.ll...., Tl<fese ;l?.A.JJS.

NDAJE:

NONI:

I No/Jc JJo"'1E i

tV~r:

R.P,S, Te..\\P

{.

Los! at: *r'F.ES~

INCL oN E*C'ZJA S,G,

/.:JONE NONE

  • \\~ **t:

NO!J'O SEC: "1oTE 2..

sec: NoTE 2._

NONE.

NOAIE" NoNt j

NOIJE° T'

"T'E 1-)olJE.

l:4~';~{ ~~~,Qr--.

ki(,,* '~

1.iQ1"*-:=

f.: 101, [;.

/.1,:: 1.1 E

T1'&

~o.

LT- 0101/>,

010\\B c:'.1102-f\\

I l ~

I ! v LT-0103

+ 01 I~

I LT-o--rot l 0(02 0(03 i

0704 I

1rn LT* too/

L \\- \\o I 2-l \\O I<\\-

lo I~

1018 LS-03sa

.I, 1).$ (.,ri LS-oa 17 l OBIDS° 08t.8 0870 s v-0101 014B C'/5'0 015Z 5V-V8Co2..

08b4-0805 D8b7 oM,9 0876 O>l73 SY-0934 sv-1819 1820

\\821 182.2-SV-l~J3 SV-232/

~32Z-2323 PA 1-i S'- _'::) E::,

(:._:in*~:

~,') '.

'-l**,-*-

.. -r*

  • t) :-:.~- *J ~:>~

Po" rr::o SUPPLY PC.W H.. FEEL> TO :0:'J_PPL\\l SCHEM/\\nC.

T/\\G VEN Doi<!

F1Jst: P)'..TA.

LocAr10,J

~lE..o1'LI!~

re1P

.1~E
fJo, No A1>1P e,Le'Hi::Nt

~t--,.. pr.

E-82 (1) L-0101 A y10- &,

z.o

'1-&ti.Of ~ IN/~fJI

'(20-0 E-82.(1) L-0101 B E-82(4; L-0162.A i~... ~ ~*An:.... * ':J/JTJ 1U"7' y10 -s--

1--

MODEL I

L-0 loz.B

(, \\0"'

(ctJl<.RE~T" locoP)

Yz..o-~

L-O 10'2.c_

y 30-5' l

L-OJOZ..D

,y,1,,.,.c E-84-(3) /'111)1.Tlf'I.~

Foxaoeo

'(ol-2Jo 0111f'11T~JroA. t E..-12. (z,) MOLTlf'Lf.

h>xBolib f,;s~ -1118

/

""[

lo<~I b.-e~~ers ~10 A 'rio-Y3o-g~e4 T

., fW R,,~ sysk"'-

~

Yw *1J;* B~R4 1No1111DVAL.. 1.o*p' JiA.'1,._

~MAH. F.J 5-/t'.l T

L*075\\ f>,

1'&AMP-11.JPUT Y10 - 5 2.0 L-07518 mv&~

Y20- 5' l L-015\\C.

01oD.-L

)8 AMP -ollTfUT (3o-5 l--O(SlD (plO A ft:...vtz.f!...E,.,,,. L->1")

'( 4o-5 E-b3 (Z) P/S 1080 F.f P

-1'1. Arv..P ~d*Ti'GT - Yo/ -z.7 E-r(!) '"'T6 "T"'

h'.'.

£-9.9 E-zq3 NA N/..

YDJ-13 l I L

  • l '

I.I~

V/\\l *1:1 T3

/.l A r "f--*

72-219 3o

)..('() MAG l

t J 11 E-189 Nr I 10 A...,p \\rnM-10) 72--Z-1 'f 31l

2. 70 IYIM*

E-Zr4-J

~*T***I 7Z-2.0'J

.3D

i_ 7o (MIU\\

],

J J

(Ttt-)

E-2.lb t.JA NA 30 A~f,2Sli 52* 1208 I 2. 5""

1..T'::. 90 INST'"f'UO l

52-)209 52-12D9 E-2.17 52--1108

~

52-J l08 E..-f-1(:,

S'--14\\o 5'2--1210 E-23V)

I ---,

e:.R.EA~R..

SAfnY El=FEc.T O>-/

'SP.Fen'

[Ra.P\\it:D C.u!{\\<,tC;,...)T" l....tJ.cP COMMcNl,S FUSE S IGNIFICAAJGI!

C.LASS IE

<>F (t)-oRDlllAT*OA/ !Qll*f'. f'41L~R.1'

£LE.Cl, E~U1P.'

1 r I.,,""'_,,,,,

OK NoNE

,Vo.¥£

~

1

~

'!ttJ/-)JoT 5AF<'TJ'f~U NO

/(E>>'"T~ AmfL11=*1ce. T Ar£

JoAJE; 1

tJ 0 UN tS!eoufo/0£.()

ND Feed.w--lcr C..,;f.,,7 r "T r l

s.ys k..._

Tl!/'t~SM1r1Ef3 CvK_~1VT

~-I' ksc-

/i!.,f.S. 7,e~

YES U/J61!<Hl0ED T 11/1!)(.h.o Bt..*W T T t.

t S.G. LEv'[t.. JNIJ, F/lom r>JG t r-a7s1

5Ef!l£S T,£1/J.J5hl*TT8 j,A)ocll..J) 8,El.J';>S.f NO P/s IJEGAT1V£ G2a.JNDEJ> I. CuRR,'i!"Ui LIM1TEJ?.

OK NONE No NE P/s IJEGAT11i£ Gl'-OVIJl>W.

"' fow&R- > V('ft-V

>. ~t>wA!;.T. 6..-r;<* L

,\\Ne' fYlh, __ fw*Sv-1 Yo1

,;,GT ~(',R;r( Rot.Aru

,:i ()

OK No,~£ iJof £ t:JoNi=_

NoNE

/JD 61(

[

l 1

1.

No

'T

~r NT t

i'ass 1 SLE'

'{ES.

O/l NONI<

Los:s: or CD'JT!lt<>~ 'fl/JR IF Vl\\LVE HS IS 1>J <-LO<l:ll f,.

Co~ C,,-;;,"Ei r~:i~

kl'LC.. Ner TJZ.1P-

.<!AN' 8£ t
;fEIZ//r~

~

!IT Gt:!!?- !IF"" NEr<HM YES C>K.

1')oAJE

>.JoJJF r

bi:'.-

T" "r NO 01:'..

!JoA!E AlcAlE NO 0 I(

/JON~-

,'l,TJE i

t I

Bus E.Qv1P.

C..o~ 1*~ 1 £ J+J TS B~*E'Jl~Ef...SAF~"'TY E~t!-T O"\\

17\\G f£:.H ENI,4 TC. Su.PP LY Bus

/i\\lC6M1"1G 5AfETY FlJ sE:

.5 I 6,IJ J #'.'Cffifti - ct-A~.:: 1c-or spv11'.

NQ No BJ?EAKER.

B~~ Rl.lATlll co--o/lP.

e<JtJJIJ. ~""1.11.

P77A E-2..33

  • 52..-2 q I Mc.c..:I! 2.

152..-12.0.3. NO 0 K:.

NONE tjOAIE'

?r1R.

E-Z33 52-j7/

Mcc..4! l J.$2.., I \\ t>' )

fRESSuer~EIL 1$2-302.

I E*BUS * )S.NoT f+Te ~FrrJE~ 15 E.-2.~3 \\52.-305 1E 1.52.-303 No A.sAFEr'(

~

.o-~

.N~NE

/\\}t'JA} (£ R. ELA7FJ>: 'is vs 1J.P..o" 12.1 > s \\ 5 I

0[.

!Jo/\\) E f>l(~v~r ~c;f. *

/52.-ZO~

  • "JD!JE I-Ii J?. }(f"n?t~'l~~ E-2.S3 I 52-21 I*

D

/S2-22)"2... No

/S2--Z,l,3 4-eo" Rvs lb

t. :;q -N GT.SJtffn' RelJd

. CD#JT", 8LP<;

t

A~* 1.
i1--i1 LJ6>1'rJN 6 of
rJ~tJ t

,.;o~ti

/tNA-l..'t~ER. *. E-fe,2-~ (4) '1 l1u*vi.t., IOI'

~c.- 7'2.-2,l_'f NO F.is'i:. = ff\\M-S (Kii)

SAM pl.£

£-2,qz_

(K...'5'"3) -

PA1\\J6L C-IOZ.

'l.2 -Z.

l>C..

SA.,.... fl.E f'/l.NEi.~.P'

~ii

'I S uf PL,V

L The second intertie involves the automatic transfer to an alternate power supply of the Instrument A-C Bus (YOl),

The alternate power supplies are MCCl and MCC2 through a breaker on each MCC.

480-120 V transformers are

  • also installed in each of the power supplies.

Based on our review, we have concluded that it is necessary for four single failures to occur at the same time to cause a loss of redundant power supply.

First, it is necessary to postulate a fault on the YOl bus.

Second, the feeder breaker on MCCl must be postulated to fail to trip which then assumes that the fault is of significant magnitude to cause a voltage reduction such that an automatic transfer would occur, Third, it must be assumed that the automatic transfer device fails to disconnect YOl from the MCCl feeder and, fourth, that when the automatic transfer shifts to the MCC2 feeder, the feeder breaker to MCC2 fails to trip.

As four single failures must be postulated, we have concluded that there is reasonable assurance that re-dundant portions of the electrical system will not be lost due to a fault on YOl.

Therefore, no design modifications are planned.

The interties between MCCl and MCC2 via the battery chargers have been re-viewed.

Two battery chargers are provided for each of the two 125 V d-c buses.

One of the battery chargers is fed through two breakers (one internal to the charger) from MCCl and the second charger from MCC2 (also through two breakers).

In addition, the one breaker is provided between each charger and its d-c bus.

In order to postulate a failure which would disable redundant buses, the following single failures must occur simultaneously:

1.

Fault on d-c bus.

2 & 3.

Failure of both charger output breakers to trip.

4 & 5.

Failure of the two charger incoming breakers to trip on one charger.

6 & 7.

Failure of the two charger incoming breakers to trip on the redundant charger.

As seven failures must occur to result in a loss of redundant ECCS power supplies, we have concluded there is reasonable assurance that redundant ECCS power supplies will not be jeopardized in the event of a fault on a 125 V d-c bus.

Therefore, no design changes are required.

5