DSAR CHAPTER 6 - ENGINEERED SAFEGUARDS SYSTEMS TABLE 6-1 Revision 36 Page 1 of 1 SAFETY INJECTION AND REFUELING WATER TANK DESIGN PARMETERS Nominal Volume 285,000 Gallons Diameter/Height 46 Feet/24 Feet Material Aluminum Design Temperature 125°F Design Pressure Atmospheric

DSAR CHAPTER 6 - ENGINEERED SAFEGUARDS SYSTEMS TABLE 6-2 Revision 36 Page 1 of 1 LOW PRESSURE SAFETY INJECTION PUMP DATA

SUMMARY

Quantity 2

Type Single Stage, Horizontal, Centrifugal Design Pressure 500 psig Design Temperature 350°F Design Flow Rate 3,000 gpm Design Head 350 ft Shutoff Head 410 ft Basic Material 316 SS (see Table 6-10)

Horsepower 400 Seals Mechanical Acceleration Time 4 Seconds Minimum Flow 163 gpm NPSH Required at 3,000 gpm 11 ft

DSAR CHAPTER 6 - ENGINEERED SAFEGUARDS SYSTEMS TABLE 6-3 Revision 36 Page 1 of 1 HIGH PRESSURE SAFETY INJECTION PUMP DATA

SUMMARY

Quantity 2

Type Multistage, Horizontal, Centrifugal Design Pressure 1,750 psig Design Temperature 350°F Design Flow Rate 300 gpm Design Head 2,500 ft Shutoff Head 2,800 ft Material Stainless Steel Horsepower 400 Shaft Seal Mechanical Acceleration Time 4 Seconds Minimum Recirc Flow 25 gpm NPSH Required at 600 gpm 17 ft

DSAR CHAPTER 6 - ENGINEERED SAFEGUARDS SYSTEMS TABLE 6-4 Revision 36 Page 1 of 1 SHUTDOWN COOLING HEAT EXCHANGER DATA

SUMMARY

Quantity 2

Type Shell and Tube Code ASME,Section III, Class C, 1965, TEMA, Class R Tube Side Design Pressure 500 psig Design Temperature 400°F Materials Austenitic Stainless Steel Shell Side Design Pressure 150 psig Design Temperature 200°F Pressure Loss, 2,000,000 lb/h 10 psi Materials Carbon Steel

DSAR CHAPTER 6 - ENGINEERED SAFEGUARDS SYSTEMS TABLE 6-5 Revision 36 Page 1 of 1 SAFETY INJECTION TANK DESIGN PARAMETERS Quantity 4

Type Vertical Right Cylinder Design Pressure 250 psig Design Temperature 200°F Height 34 Feet 6 Inches Outside Diameter 9 Feet 2 Inches Material Carbon Steel With Type 304L Stainless Steel Clad

DSAR CHAPTER 6 - ENGINEERED SAFEGUARDS SYSTEMS TABLE 6-6 Revision 36 Page 1 of 2 CONTAINMENT SPRAY SYSTEM COMPONENT DESCRIPTION

1.

Containment Spray Pumps Number of Units - 3 Type Vertically Split, Horizontal Centrifugal With Mechanical Seals and Backup Packed Gland Material -

316 Stainless Steel Code Motor, NEMA; Pump, Standards of the Hydraulics Institute, 11th Edition, 1965, ASA B31.1-1955; ASA B16.5-1961 Injection Recirculation Design Capacity (Each) 1,340 gpm 1,800 gpm Design Head 450 ft 405 ft Design NPSH Required 13.2 ft 17.8 ft Motor 250 hp, 3 Ph, 60 Hz, 2,300 V

2.

Shutdown Cooling Heat Exchangers Number of Units - 2 Capacity (Each) 83.5 x 106 Btu/h Based on 4,000 gpm of Cooling Water at 114°F Inlet Temperature and 1,420 gpm of Spray Water at 283°F Inlet Temperature

3.

Piping, Fittings and Valves A.

Suction Material - Type 304 Stainless Steel Pipe Sizes Wall Thickness 2" and Smaller Sch 40S 2-1/2" Through 12" Sch 10S 14" Through 20" 0.250" Nominal Wall 24" 0.375" Nominal Wall Design Pressure - 60 psig Design Temperature - 300°F Construction 2-1/2" and Larger Butt-Welded Except at Flanged Equipment

DSAR CHAPTER 6 - ENGINEERED SAFEGUARDS SYSTEMS TABLE 6-6 Revision 36 Page 2 of 2 CONTAINMENT SPRAY SYSTEM COMPONENT DESCRIPTION 2" and Smaller Socket Welded Except at Screwed Equipment Valves 2" and Larger Stainless Steel, Butt-Welded, 150 lb 1-1/2" and Smaller Stainless Steel, Socket Welded, 150 lb Testing 100% Radiography of Welded Joints Code ASA B31.1-1955 and Code Cases N2 and N10 B.

Discharge Material - Type 304 Stainless Steel Pipe Sizes Wall Thickness 8" and Smaller Sch 40S 10" Through 14" 0.250" Nominal Wall Design Pressure - 500 psig Design Temperature - 350°F Valves 2" and Larger Stainless Steel, Butt-Welded, 300 lb 1-1/2" and Smaller Stainless Steel, Socket Welded, 600 lb Testing 100% Radiography of Welded Joints Code ASA B31.1-1955 and Code Cases N2 and N10

4.

Spray Nozzles Type

- Sprayco, Model 1713A Material

- 304 Stainless Steel Number

- 77 Nozzles on A Spray Header

- 83 Nozzles on B Spray Header

DSAR CHAPTER 6 - ENGINEERED SAFEGUARDS SYSTEMS TABLE 6-7 Revision 36 Page 1 of 2 CONTAINMENT AIR COOLER COMPONENT DESCRIPTION Coils (VHX-1, VHX-2 and VHX-3 Safety Related & VHX-4 Non-Safety)

Coils per Cooler Unit 4

Rows of Tubes per Coil 12 Face Area of Each Coil 20.54 ft2 Total Coil Face Area per Cooler Unit 82.16 ft2 Tubes per Row 36 Tube Description 5/8" OD Copper x 0.049" Wall Tube Design Pressure 150 psig Fin Description 3/8" High x.012 Thick Copper Plate with 9.4 Fins per Inch (Mechanical Bond)

Fans (V1, V2, V3 and V4)

Fan Speed 1,750 r/min Number of Fans per Cooler Unit 2

Motor Design Totally Enclosed Air Overcooled Insulation NEMA Class H for Fans Rated for the Post-DBA Condition NEMA Class B for Fans Rated for Normal Duty Rating 75 hp for Fans Rated for the Post-DBA Condition 30 hp for Fans Rated for Normal Duty Filters (VF-1, VF-2, VF-3, VF-4)

Capacity 60,000 ft3/min at 0.33" H2O Differential Pressure Drop (Clean) 0.33" H2O Size of Each Filter Module 19.25" x 19.25" x 1.75" Thick

DSAR CHAPTER 6 - ENGINEERED SAFEGUARDS SYSTEMS TABLE 6-7 Revision 36 Page 2 of 2 CONTAINMENT AIR COOLER COMPONENT DESCRIPTION Number of Filter Modules per Cooler Unit 32 Efficiency 65%

Type Stainless Steel Mesh, Framed

DSAR CHAPTER 6 - ENGINEERED SAFEGUARDS SYSTEMS TABLE 6-10 Revision 36 Page 1 of 2 ECCS COMPONENT SYSTEMS Piping -

Stainless Steel-304 Valves -

Stainless Steel or other equivalent corrosion resistant material Gaskets - Asbestos or Grafoil Grade GTTMB (eg, Flexitallic or Flexicarb) with 300 Series SS Component LP Pump HP Pump Spray Pump Casing ASTM A351 SS, Mod CF8A ASTM A351 SS, Mod CF8 SS, CF8M Impeller ASTM A217 SS, CF8 ASME SA 351, Grade CA15 SS SS, CF8M Casing Wear Ring ASTM A479, Gr S21800 17-4 PH SS, CF8M Shaft A479, 316 SS AISI 416 316 SS Shaft Sleeve ASTM A479, 316 SS 316 SS Gland Seal 316 SS Pumping Ring P-67A - Internal to Seal Cartridge P-67B -

18-8 SS on Shaft Sleeve 18-8 SS Seal Cartridge 316 SS 316 SS 316 SS Face Seal Rotating Element Carbon 316 SS with Tungsten Carbide Carbon Face Seal Stationary Element P-67A - Silicon Carbide P-67B - Tungsten Carbide Carbon Tungsten Carbide Throttle Bushing P-67A - Bronze P-67B - Carbon Carbon Backup Ring Viton Valves and Piping 304 SS 304 SS 304 SS Gaskets Asbestos or Grafoil Grade GTTMB (eg, Flexitallic Flexicarb) with 300 Series SS Asbestos or Grafoil Grade GTTMB (eg, Flexitallic Flexicarb) with 300 Series SS Flexitallic with 300 Series SS

DSAR CHAPTER 6 - ENGINEERED SAFEGUARDS SYSTEMS TABLE 6-10 Revision 36 Page 2 of 2 ECCS COMPONENT SYSTEMS SHUTDOWN HEAT EXCHANGERS Component Material Head Gasket 304 SS Jacket Asbestos Tubes ASME SA 249, Grade TP-304 Tube Sheet Cladding 304 SS Channel Cover 304 SS Channel Partition ASME SA 240, Type 304 SS

DSAR CHAPTER 6 - ENGINEERED SAFEGUARDS SYSTEMS TABLE 6-12 Revision 36 Page 1 of 3 ISI MAJOR COMPONENTS AND/OR SYSTEMS LIST ASME CLASS 1 Components Reactor Pressure Vessel, N-50 Reactor Pressure Vessel Closure Head, N-50 Steam Generators - Primary Side, E-50A and E-50B Pressurizer, T-72 Regenerative Heat Exchangers, E-56A and E-56B Piping Primary Coolant System Engineering Safeguards System Chemical and Volume Control System Pumps Primary Coolant Pumps, P-50A, B, C, D Valves ASME CLASS 2 Components Safety Injection and Refueling Water Tank, T-58 Safety Injection Tanks, T-82A, B, C, D Steam Generators - Secondary Side, E-50A, B Regenerative Heat Exchangers, E-56A, B Shutdown Cooling Heat Exchangers, E-60A, B

DSAR CHAPTER 6 - ENGINEERED SAFEGUARDS SYSTEMS TABLE 6-12 Revision 36 Page 2 of 3 ISI MAJOR COMPONENTS AND/OR SYSTEMS LIST Piping Main Steam System Feedwater System Engineered Safeguards System Chemical and Volume Control System Component Cooling System Pumps Containment Spray Pumps, P-54A, B, C High-Pressure Safety Injection Pumps, P-66A, B Low-Pressure Safety Injection Pumps, P-67A, B SIRW Recirculation Pump, P-74 ASME CLASS 3 Components Letdown Heat Exchanger, E-58 Condensate Storage Tank, T-2 Component Cooling Surge Tank, T-3 Spent Fuel Pool Heat Exchangers, E-53A, B Component Cooling Heat Exchangers, E-54A, B Shutdown Cooling Heat Exchangers, E-60A, B Engineered Safeguards Room Coolers, VHX-27A, B Control Room Air Conditioning Units, VC-10, VC-11 Containment Air Coolers, VHX-1, 2, 3, 4 Condensate Storage Tank Heat Exchanger, E-27

DSAR CHAPTER 6 - ENGINEERED SAFEGUARDS SYSTEMS TABLE 6-12 Revision 36 Page 3 of 3 ISI MAJOR COMPONENTS AND/OR SYSTEMS LIST Piping Main Steam System Feedwater System Chemical and Volume Control System Service Water System Component Cooling System Spent Fuel Pool System Condensate System Diesel Jacket Water Cooling System Pumps Service Water Pumps, P-7A, B, C Auxiliary Feedwater Pumps, P-8A, B, C Fuel Pool Cooling Pumps, P-51A, B Component Cooling Pumps, P-52A, B, C Diesel Generator Cooling Pumps P-211A, B