Similar Documents at Salem |
---|
Category:REPORTABLE OCCURRENCE REPORT (SEE ALSO AO LER)
MONTHYEARLR-N980537, Special Rept:On 981006,train B of Reactor Vessel Level Indicating Sys Was Indicating Malfunction.Caused by Loss of Fill in Capillary Sensing Line.Extensive Troubleshooting Was Performed on Sys1998-11-16016 November 1998 Special Rept:On 981006,train B of Reactor Vessel Level Indicating Sys Was Indicating Malfunction.Caused by Loss of Fill in Capillary Sensing Line.Extensive Troubleshooting Was Performed on Sys LR-N980422, Special Rept:On 980816,RMS Channel 1R15 Inoperable for Greater than Seven Days.Cause Is Under Investigation. Replacement of Detector Assembly W/Higher Temperature Rated Detector to Mitigate Effects to Be Completed by 9810191998-08-31031 August 1998 Special Rept:On 980816,RMS Channel 1R15 Inoperable for Greater than Seven Days.Cause Is Under Investigation. Replacement of Detector Assembly W/Higher Temperature Rated Detector to Mitigate Effects to Be Completed by 981019 LR-N970729, Special Rept 97-15,on 971022,2A EDG Declared Inoperable. Caused by Moisture Build Up in Starting Air headers.2A EDG Equipment Inspected Just Subsequent to Aborted Start1997-11-21021 November 1997 Special Rept 97-15,on 971022,2A EDG Declared Inoperable. Caused by Moisture Build Up in Starting Air headers.2A EDG Equipment Inspected Just Subsequent to Aborted Start LR-N970649, Special Rept 97-02:on 970909,isolation of Fire Protection Water to Plant Auxiliary Bldgs & Containments Occurred Due to Closure of Valves 1PF186 & 1PF187.Valves Opened on 970916 & Locally Verified Open by Loss Prevention Personnel1997-09-30030 September 1997 Special Rept 97-02:on 970909,isolation of Fire Protection Water to Plant Auxiliary Bldgs & Containments Occurred Due to Closure of Valves 1PF186 & 1PF187.Valves Opened on 970916 & Locally Verified Open by Loss Prevention Personnel LR-N970418, Special Rept 97-01:on 970615,radiation Monitoring Sys Channel 1R15 Was Inoperable for More than Seven Days.Caused by Configuration of Plant.Required Operational Surveillances Will Be Completed on 2R15 & Channel Restored1997-06-30030 June 1997 Special Rept 97-01:on 970615,radiation Monitoring Sys Channel 1R15 Was Inoperable for More than Seven Days.Caused by Configuration of Plant.Required Operational Surveillances Will Be Completed on 2R15 & Channel Restored ML18101B3051996-03-25025 March 1996 Special Rept:On 960224,valid Failure of 1B EDG Was Identified During Surveillance Testing.Caused by Fatigue Due to Normal Machine Vibration.Replaced Threaded Nipple ML18101B1581995-12-29029 December 1995 Special Rept 95-02:on 951207,valid Failure of 1A EDG Identified Approx 23 & 1/2 H Into 24 H Endurance Surveillance Test.Caused by Lubricating Oil Leak at Threaded Piping Nipple.Threaded Nipple Replaced ML18101B1541995-12-27027 December 1995 Special Rept 95-001:on 951129,valid Failure of 1B EDG Identified During Routine Monthly Surveillance Test.Caused by Malfunction of Woodward Electronic Governor Control Unit. Unit Replaced & 1B EDG Tested Satisfactorily on 951214 ML18101A8061995-07-0303 July 1995 Special Rept:On 950607,identified That 950601 Failure of EDG 1B Potential Common Mode Failure.Util Unable to Determine Cause at Present Time.Ler Will Be Submitted to NRC ML18101A7341995-05-19019 May 1995 Special Rept:On 950506,RMS Declared Inoperable Due to Problems Encountered W/Operation of Victoreen Met Package. Caused by Met Package Inconsistencies.Appropriate Computer Software Corrections Being Researched & Will Be Implemented ML18101A5601995-02-15015 February 1995 Special Rept 95-01:on 950125,shortly After RCP Turned Off to Remove RCP from Svc,Momentary RCS Pressure Transient Occurred & Pressure Peaked 365.5 Psig Due to Pressure Equalization Through 21 RCS Loop.Procedures Will Be Changed ML18100B0421994-04-27027 April 1994 Special Rept 94-2:on 940329,valid Failure of 1A Diesel Generator Occurred.Caused by Buildup on Contacts of Breaker Position Switch 52HL,resulting in Excessive Electrical Resistance.Breaker Position Switch Replaced ML18100A8271994-01-20020 January 1994 Special Rept 94-01:on 940106,radiation Monitoring Channels 1R45B & 1R45C Declared Inoperable & Exceeded 7-day Time Frame for Restoring Inoperable Channels to Operable Status on 940113.Monitors Returned to Svc on 940118 ML18100A6211993-09-17017 September 1993 Special Rept 93-4:on 930910,radiation Monitoring Channels 2R45B & 2R45C Inoperable Greater than Seven Days.Caused by Design Deficiency.Corrected by Separating Monitors Reference & Chassis Grounds ML18100A4941993-07-21021 July 1993 Special Rept:On 930707,process Monitor - Noble Gas effluent- Condenser Exhaust Sys Was Removed from Svc Due to Observed Water in Its Sample Line.Sample Line 2R15 Drained & Dried ML18096B3511993-03-23023 March 1993 Special Rept 93-2:on 930310,RMS Channels 2R45B & 2R45C Removed from Svc to Functionally Test Low Flow Differential Pressure.Test Results Showed That Switch Inoperable.Caused by Design Deficiency.Design Mod Being Prepared ML20138H1741993-02-0909 February 1993 RO 25043:on 930208,PSE&G Reported That CRT Associated W/Salem Unit 1 Overhead Annunciator Sys Was Found to Be Inoperable for Approx 23 Minutes ML18096B2571993-02-0404 February 1993 Special Rept 93-1:on 930104,fire Barrier Penetration Seal Impaired to Support Welding of RHR Sys Drain Piping.Barrier Inoperable for More than 7 Days.Cables Removed & Access Hatch Closed to Restore Penetration to Operability ML18096B2331993-01-28028 January 1993 Special Rept 93-1:on 930114,RMS Channels 1R45B & 1R45C Declared Inoperable Upon Annuciation of External Fail Alarm.Cause Not Determined.Upon Completion,Corrective Actions Will Be Taken & Channels Will Return to Svc ML18096B1701992-12-21021 December 1992 Special Rept 92-9:on 921208,chilled Water Supply Could Not Be Restored Following Completion of RMS Channel Functional Surveillance.Caused by Blow Indication Panel Circuit Fuse. New Solenoid Valve Operator Ordered ML18096B1601992-12-18018 December 1992 Special Rept 92-9:on 921112,fire Barrier Impairment Initiated to Support Svc Water Sys Design Changes & Penetration Inoperable for More than 7 Days Through 921119. Penetrations Will Be Sealed Upon Completion of Work ML18096B1171992-11-23023 November 1992 Special Rept 92-8:on 921116,RMS Channels Declared Inoperable & Removed from Svc for More than 7 Days.Caused by Bad Ground Wire Connection on Three Wire Power Cable.Connector Repaired & post-maint Testing Successfully Completed ML18096B0861992-11-0505 November 1992 Special Rept 92-7:on 921008,discovered Door Misaligned & Would Not Close & Latch.Caused by Equipment Failure.Fire Door Declared Functional Upon Completion of Repairs & Testing ML18096B0731992-10-30030 October 1992 Special Rept 92-8:on 920924,fire Barrier Penetrations Impaired to Support Design Change Work.On 921001, Penetrations Exceeded seven-day Limit,Per TS 3.7.11.a. Impaired Penetrations Resealed & Inspected ML18096B0591992-10-23023 October 1992 Special Rept 92-6:on 920924,valid Failure,Involving DG 2B, Occurred During Monthly Surveillance Testing & Exhaust Smoke Observed Rising from Around Turbocharger.Caused by Loose Pipe Fasteners.Fasteners Torqued Appropriately ML18096B0021992-09-24024 September 1992 Special Rept 92-7:on 920826,auxiliary Bldg 100-ft Elevation Corridor Fire Door Found Impaired & Not Returned to Operability within 7 Days.Caused by Broken Internal Hinge Plate Welds.Damaged Door Will Be Replaced ML18096A9151992-08-21021 August 1992 Special Rept 92-6:on 920814,radiation Monitoring Channels 1R45B & 1R45C Declared Inoperable for More than 7 Days. Caused by Degradation on Impellers of Two Sample Pumps. Preventive Maint Applicability Review Will Be Performed ML18096A8841992-08-0707 August 1992 Special Rept 92-4-1:on 920430,fire Pump 1 Started Knocking 10 Minutes Into half-hour Run.Caused by sheared-off Follower Guide Pin.On 920514,fire Pump Developed Severe Oil Leak.Caused by Piston Failing to Contact Cylinder Head ML20099C1471992-07-23023 July 1992 Special Rept 92-5:on 920713,radiation Monitoring Sys Channels 2R45B & 2R45C Declared Inoperable & Removed from Svc.Caused by Equipment Failure.Channel Repairs Will Be Tested Upon Completion of Mod ML18096A8261992-07-0909 July 1992 Special Rept 92-5:on 920623,actuation Capability of 78-ft Lower Electrical Penetration CO2 Fire Protection Sys Inoperable for More than 14 Days.Caused by Required Maint Work.Sys Returned to Svc on 920702 ML18096A7431992-05-22022 May 1992 Special Rept 92-4:on 920430 & 0514,fire Pumps 1 & 2, Respectively,Inoperable for More than 7 Days.Caused by Sheared Cam Follower Pin & Severe Oil Leak.Fire Protection Sys cross-tie Valve Opened to Provide Backup Protection ML18096A7281992-05-22022 May 1992 Special Rept 92-3,on 920422,discovered That CO2 Sys Was Inoperable.Caused by Maint Work Activities.Upon Completion of Maint Diesel Generator Area CO2 Sys Will Be Returned to Svc ML18096A7351992-05-15015 May 1992 Ro:On 920423,fire Pump 1 Declared Inoperable & Remains Inoperable Due to Broken Crankshaft.Both Fire Suppression Sys Inoperable.On 920515,fire Pump 2 Declared Inoperable Due to Severe Oil Leak.Written Rept to Be Provided in 14 Days ML18096A7021992-05-11011 May 1992 Special Rept 92-2-1:on 920324,0414,15 & 25,fire Barriers Impaired for More than 7 Days to Support Planned Work in SW Sys,Sw Project Support & SW Pipe Replacement.Hourly Fire Watch Will Continue Until All Concerns Resolved ML18096A6501992-04-23023 April 1992 Special Rept 92-2:on 920324,0414 & 15,fire Barriers Impaired for Greater than Seven Days in Support of Planned Work. Hourly Fire Watch Will Continue Until Fire Protection Concerns Associated W/Areas Resolved ML18096A6491992-04-23023 April 1992 Special Rept 92-4:on 920318,two Fire Barrier Penetrations Were Impaired to Support Turbine/Generator Design Change Work for Greater than Seven Days.Caused by Outage Related Activities.Penetrations Were Resealed on 920326 ML18096A6051992-03-26026 March 1992 Special Rept 92-3:on 920302,jacket Water Leakage Developed After Loading DG 2A.On 920305,DG 2A Tripped on Low Lube Oil Pressure.Both Events Caused by Equipment Failure.Tube Connector Compression Fitting Replaced & Diesel Retested ML18096A5891992-03-23023 March 1992 Special Rept 92-2:on 920302 & 21,fire Barriers Impaired for More than 7 Days to Support Design Changes & outage-related Activities.Hourly Fire Watch Established & Fire Penetrations Will Be Sealed ML18096A5671992-03-12012 March 1992 Special Rept 92-1:on 920223,fire Barriers Found Impaired for Greater than Seven Days.Caused by Equipment Failure.Fire Door Will Be Replaced Upon Receipt of New Door ML18096A5101992-02-0606 February 1992 Special Rept 92-1 on 920104,06 & 25,fire Barriers Impaired for Greater than Seven Days in Support of Outage Related Activities Due to Time Required to Complete Work.Hourly Fire Watch Will Continue Until Concerns Re Areas Are Resolved ML18096A4231992-01-0909 January 1992 Special Rept 91-3,on 911210,26 & 27:fire Barriers Found Impaired for Greater than 7 Days.Cause of Occurrence Due to Support Outage Related Activities.Penetrations Will Be Sealed ML18096A4001991-12-23023 December 1991 Special Rept 91-4 Re Valid Failure of Diesel Generator 2B on 911122.Cause Unknown.Surveillance Procedure SP(O)4.8.1.1.2 Performed Satisfactorily ML18096A2301991-08-22022 August 1991 Special Rept 91-02:on 910725,reactor Trip Breaker Failure Occurred Duing Surveillance Testing of Reactor Trip Bypass Breaker.Detailed Investigation Rept Being Prepared & Breaker Being Replaced ML18096A0841991-06-20020 June 1991 Special Rept:On 910523 & 910525,valid Failure Re 2B Diesel Generator Occurred When pre-lube Pump Heater Circuit de-energized & non-valid Failure Occurred on 910525 Re Jacket Water Leak ML18095A8901991-04-17017 April 1991 Special Rept 91-1-1:on 910218,910220,910224 & 910322 Fire Barrier Penetration Seals Impaired for Greater than Seven Days.Cause of Impairment Was to Support Outage Activities. Hourly Fire Watch Will Continue ML18095A8111991-03-20020 March 1991 Special Rept:On 910211,910213 & 910217 Fire Barrier Impairments Greater than Seven Days in Support of Planned Work.Cause of Impairment of Fire Barrier Penetrations Was to Support Outage Related Activities ML18095A7831991-03-0707 March 1991 Special Rept 91-1:on 910211,Elevation 64 & 84 Ft Switchgear Rooms & Elevation 78 Ft Electrical Penetration Area CO2 Fire Protection Sys Inoperable for More than 14 Days.Caused by Required Design Work.Continuous Fire Watch Established ML18095A7521991-02-20020 February 1991 Special Rept 88-3-28:from 880720-910122,listed Fire Barrier Penetration Seal Impairments Occurred.Cause Not Positively Determined.Hourly Fire Watch Will Continue Until All Fire Protection Concerns Resolved ML18095A6751990-12-26026 December 1990 Special Rept 90-7:on 901210,switchgear Rooms & Electrical Penetration Area CO2 Fire Protection Sys Inoperable for More than 14 Days to Support Design Change Work on 901126. Adequate Precautions Taken to Ensure Design Capability ML18095A7511990-12-0505 December 1990 Revised Special Rept 90-10-1:on 900707,TS Action Statement 3.7.10.3c.a Entered When 64 Ft & 84 Ft Elevation Switchgear Room CO2 Fire Protection Sys Declared Inoperable.Caused by Equipment Failure.Sys Design Drawing Revised 1998-08-31
[Table view] Category:TEXT-SAFETY REPORT
MONTHYEARLR-N99-0448, Monthly Operating Rept for Sept 1999 for Salem,Unit 1.With1999-09-30030 September 1999 Monthly Operating Rept for Sept 1999 for Salem,Unit 1.With LR-N99-0449, Monthly Operating Rept for Sept 1999 for Salem,Unit 2.With1999-09-30030 September 1999 Monthly Operating Rept for Sept 1999 for Salem,Unit 2.With ML20217A9931999-09-30030 September 1999 NRC Regulatory Assessment & Oversight Pilot Program, Performance Indicator Data ML20212B7221999-09-14014 September 1999 Safety Evaluation Supporting Amends 224 & 205 to Licenses DPR-70 & DPR-75,respectively LR-N99-0415, Monthly Operating Rept for Aug 1999 for Salem,Unit 1.With 9909131999-08-31031 August 1999 Monthly Operating Rept for Aug 1999 for Salem,Unit 1.With 990913 LR-N99-0416, Monthly Operating Rept for Aug 1999 for Salem,Unit 2.With1999-08-31031 August 1999 Monthly Operating Rept for Aug 1999 for Salem,Unit 2.With 05000272/LER-1999-006-02, :on 990729,determined That SG Blowdown RMs Setpoint Was non-conservative.Caused by Inadequate ACs for Incorporating Original Plant Licensing Data Into Plant Procedures.Blowdown Will Be Restricted.With1999-08-26026 August 1999
- on 990729,determined That SG Blowdown RMs Setpoint Was non-conservative.Caused by Inadequate ACs for Incorporating Original Plant Licensing Data Into Plant Procedures.Blowdown Will Be Restricted.With
ML18107A5201999-08-12012 August 1999 Rev 0 to Sgs Unit 2 ISI RFO Exam Results (S2RFO 9) Second Interval,Second Period, First Outage (96RF) LR-N99-0380, Monthly Operating Rept for July 1999 for Salem,Unit 2.With1999-07-31031 July 1999 Monthly Operating Rept for July 1999 for Salem,Unit 2.With LR-N99-0379, Monthly Operating Rept for July 1999 for Salem,Unit 1.With1999-07-31031 July 1999 Monthly Operating Rept for July 1999 for Salem,Unit 1.With 05000311/LER-1999-008, :on 990714,determined That Limit Switch Cables Were Subject to Multiple Hot Shorts in Same Fire Area.Caused by Inadequate Original Post Fire Safe Shutdown Analysis.All Limit Switch Cables for MOVs Were Reviewed.With1999-07-28028 July 1999
- on 990714,determined That Limit Switch Cables Were Subject to Multiple Hot Shorts in Same Fire Area.Caused by Inadequate Original Post Fire Safe Shutdown Analysis.All Limit Switch Cables for MOVs Were Reviewed.With
ML20210B7371999-07-21021 July 1999 Safety Evaluation Supporting Amends 223 & 204 to Licenses DPR-70 & DPR-75,respectively ML18107A4411999-07-0909 July 1999 SER Denying Licensee 980730 & 990222 Requests to Revise TS 3/4.7.6, Control Room Emergency Air Conditioning Sys, & Associated Bases to Change Acceptable Criteria for Control Room Emergency Air Conditioning System 05000311/LER-1999-007, :on 990605,surveillance for Quadrant Power Tilt Ratio (QPTR) Was Missed.Caused by Human Error.Qptr Calculation Was Performed & Personnel Involved Have Been Held Accountable IAW Pse&G Policies.With1999-07-0606 July 1999
- on 990605,surveillance for Quadrant Power Tilt Ratio (QPTR) Was Missed.Caused by Human Error.Qptr Calculation Was Performed & Personnel Involved Have Been Held Accountable IAW Pse&G Policies.With
05000272/LER-1999-005-02, :on 990605,11 Containment Declared Inoperable. Caused by Valves 11SW72 & 11SW223 Both Leaking.Procedure S1.OP-ST.SW-0010(Q) Was Enhanced to Provide Specific Instructions to Ensure Proper Sequencing.With1999-07-0202 July 1999
- on 990605,11 Containment Declared Inoperable. Caused by Valves 11SW72 & 11SW223 Both Leaking.Procedure S1.OP-ST.SW-0010(Q) Was Enhanced to Provide Specific Instructions to Ensure Proper Sequencing.With
05000311/LER-1999-006, :on 990501,determined That There Was No Flow in One of Four Injection Legs.Caused by Sticking of Valve in Safety Injection Discharge Line to 21 Cold Leg.Valve Was Cut Out of Sys & Replaced.With1999-07-0101 July 1999
- on 990501,determined That There Was No Flow in One of Four Injection Legs.Caused by Sticking of Valve in Safety Injection Discharge Line to 21 Cold Leg.Valve Was Cut Out of Sys & Replaced.With
05000311/LER-1999-002, :on 990405,determined That 2SA118 Failed as Found Leakrate Test.Caused by Foreign Matl Found in 2SA118 valve.2SA118 Valve Was Cycled Several Times & Seat Area Was Air Blown in Order to Displace Foreign Matl.With1999-07-0101 July 1999
- on 990405,determined That 2SA118 Failed as Found Leakrate Test.Caused by Foreign Matl Found in 2SA118 valve.2SA118 Valve Was Cycled Several Times & Seat Area Was Air Blown in Order to Displace Foreign Matl.With
ML18107A5211999-07-0101 July 1999 Rev 0 to Sgs Unit 2 ISI RFO Exam Results (S2RFO 10) Second Interval,Second Period,Second Outage (99RF) LR-N99-0324, Monthly Operating Rept for June 1999 for Salem,Unit 1.With1999-06-30030 June 1999 Monthly Operating Rept for June 1999 for Salem,Unit 1.With ML20196H8621999-06-30030 June 1999 NRC Regulatory Assessment & Oversight Pilot Program, Performance Indicator Data, June 1999 Rept LR-N99-0325, Monthly Operating Rept for June 1999 for Salem,Unit 2.With1999-06-30030 June 1999 Monthly Operating Rept for June 1999 for Salem,Unit 2.With ML18107A3931999-06-23023 June 1999 Safety Evaluation Supporting Licensee Response to GL 95-07 ML18107A4161999-06-23023 June 1999 Safety Evaluation Accepting Licensee Response to GL 96-06, Assurance of Equipment Operability & Containment Integrity During Design Basis Accident Conditions 05000272/LER-1999-004-02, :on 990520,reactor Tripped from 100% Power,Due to Negative Flux Trip Signal from Nuclear Instrumentation. Cause Has Not Been Determined.Discoloration Was Identified on One of Penetrations.With1999-06-17017 June 1999
- on 990520,reactor Tripped from 100% Power,Due to Negative Flux Trip Signal from Nuclear Instrumentation. Cause Has Not Been Determined.Discoloration Was Identified on One of Penetrations.With
ML18107A3751999-06-15015 June 1999 Safety Evaluation Accepting Licensee Request for Approval of Proposed Changes to Nuclear Business Unit EP for Hope Creek & Salem Generating Stations,Iaw 10CFR50.54(q) 05000272/LER-1999-003-02, :on 990513,unplanned Entry Into TS 3.0.3 Was Made.Caused by Human error.Re-positioned Creacs Supply Fan Selector Switches & Revised Procedures S1 & S2.OP-ST.SSP-0001(Q).With1999-06-0909 June 1999
- on 990513,unplanned Entry Into TS 3.0.3 Was Made.Caused by Human error.Re-positioned Creacs Supply Fan Selector Switches & Revised Procedures S1 & S2.OP-ST.SSP-0001(Q).With
05000311/LER-1999-005-01, :on 990504,failure to Meet TS Action Statement Requirements for High Oxygen Concentration in Waste Gas Holdup Sys Occurred.Caused by Inability of Operators. Existing Procedures Will Be Evaluated.With1999-06-0202 June 1999
- on 990504,failure to Meet TS Action Statement Requirements for High Oxygen Concentration in Waste Gas Holdup Sys Occurred.Caused by Inability of Operators. Existing Procedures Will Be Evaluated.With
ML18107A3441999-06-0101 June 1999 Interim Part 21 Rept Re Premature Over Voltage Protection Actuation in Circuit Specific Application in Dc Power Supply.Testing & Evaluation Activities Will Be Completed on 990716 LR-N99-0278, Monthly Operating Rept for May 1999 for Salem Generating Station,Unit 2.With1999-05-31031 May 1999 Monthly Operating Rept for May 1999 for Salem Generating Station,Unit 2.With LR-N99-0275, Monthly Operating Rept for May 1999 for Salem Generating Station,Unit 1.With1999-05-31031 May 1999 Monthly Operating Rept for May 1999 for Salem Generating Station,Unit 1.With ML18107A3111999-05-21021 May 1999 SER Accepting GL-88-20,suppl 4, IPEEEs for Severe Accident Vulnerabilities, for Plant,Units 1 & 2 05000272/LER-1999-002-02, :on 990413,determined That Number 12 Auxiliary Bldg Exhaust Fan Was Rotating Backwards.Caused by mis-wiring of Motor Due to Human Error by Maint technician.Mis-wiring Was Corrected & Fan Was Returned to Svc.With1999-05-12012 May 1999
- on 990413,determined That Number 12 Auxiliary Bldg Exhaust Fan Was Rotating Backwards.Caused by mis-wiring of Motor Due to Human Error by Maint technician.Mis-wiring Was Corrected & Fan Was Returned to Svc.With
05000311/LER-1999-004-01, :on 990411,automatic Actuation of ESF Occurred During Reactor Vessel Head Removal in Support of Refueling Operations.Caused by High Radiation Condition.Containment Atmosphere Was Monitored.With1999-05-10010 May 1999
- on 990411,automatic Actuation of ESF Occurred During Reactor Vessel Head Removal in Support of Refueling Operations.Caused by High Radiation Condition.Containment Atmosphere Was Monitored.With
05000311/LER-1999-003-01, :on 990406,all Salem Unit 2 Chillers Rendered Inoperable.Caused by Human Error.Lessons Learned from Event Were Communicated to All Operators by Including Them in Night Orders.With1999-05-0404 May 1999
- on 990406,all Salem Unit 2 Chillers Rendered Inoperable.Caused by Human Error.Lessons Learned from Event Were Communicated to All Operators by Including Them in Night Orders.With
ML20206H2631999-05-0404 May 1999 Safety Evaluation Supporting Amend 222 to License DPR-70 05000311/LER-1999-002-01, :on 990405,determined That Containment Isolation Valve Failed as Found Leakrate Test.Caused by Foreign Matl Blocking Valves from Closing.Check Valve Mechanically Agitated.With1999-05-0303 May 1999
- on 990405,determined That Containment Isolation Valve Failed as Found Leakrate Test.Caused by Foreign Matl Blocking Valves from Closing.Check Valve Mechanically Agitated.With
ML18107A3151999-04-30030 April 1999 Submittal-Only Screening Review of Salem Generating Station Individual Plant Exam for External Events (Seismic Portion), Rev 1 LR-N99-0225, Monthly Operating Rept for Apr 1999 for Salem Unit 1.With1999-04-30030 April 1999 Monthly Operating Rept for Apr 1999 for Salem Unit 1.With ML18107A3711999-04-30030 April 1999 Corrected Monthly Operating Rept for Apr 1999 for Salem Generating Station,Unit 1 LR-N99-0226, Monthly Operating Rept for Apr 1999 for Salem Unit 2.With1999-04-30030 April 1999 Monthly Operating Rept for Apr 1999 for Salem Unit 2.With ML20206B4761999-04-26026 April 1999 Safety Evaluation Supporting Amends 220 & 202 to Licenses DPR-70 & DPR-75,respectively 05000311/LER-1999-001-03, :on 990330,MSSV Failed Lift Set Test.Caused by Setpoint Variance Which Is Result of Aging.Valves Were Adjusted & Retested to Ensure TS Tolerance.With1999-04-23023 April 1999
- on 990330,MSSV Failed Lift Set Test.Caused by Setpoint Variance Which Is Result of Aging.Valves Were Adjusted & Retested to Ensure TS Tolerance.With
ML18107A1791999-04-15015 April 1999 Safety Evaluation Supporting Changes to QA Program in That QA Program Continues to Meet Requirements of App B to 10CFR50 ML18107A2881999-04-0707 April 1999 Rev 0 to NFS-0174, COLR for Salem Unit 2 Cycle 11 ML18107A1601999-04-0707 April 1999 Safety Evaluation Accepting Request for Exemption from Update Requirements of 10CFR50.71(e)(4) ML18106B1461999-04-0101 April 1999 SER Accepting Util Proposed Request to Use 1992 Edition of ASME Boiler & Pressure Vessel Code,Section Xi,Article, IWA-4500,for Potential Repair of Feedwater Nozzles for Salem Nuclear Generating Station,Unit 2 LR-N99-0176, Monthly Operating Rept for Mar 1999 for Salem,Unit 1.With1999-03-31031 March 1999 Monthly Operating Rept for Mar 1999 for Salem,Unit 1.With LR-N99-0177, Monthly Operating Rept for Mar 1999 for Salem,Unit 2.With1999-03-31031 March 1999 Monthly Operating Rept for Mar 1999 for Salem,Unit 2.With 05000272/LER-1999-001-02, :on 990228,reactor Scram Was Noted as Result of Turbine Trip.Caused by Operator Error.Lesson Plans Revised to Explicitly Demonstrate Manner in Which Valve Functions. with1999-03-29029 March 1999
- on 990228,reactor Scram Was Noted as Result of Turbine Trip.Caused by Operator Error.Lesson Plans Revised to Explicitly Demonstrate Manner in Which Valve Functions. with
05000272/LER-1999-001-01, :on 990228,reactor Scram Resulted in Turbine Trip.Caused by Personnel Error.Revised Lesson Plans to Explicitly Demonstrate Manner in Which Valve Functions. with1999-03-29029 March 1999
- on 990228,reactor Scram Resulted in Turbine Trip.Caused by Personnel Error.Revised Lesson Plans to Explicitly Demonstrate Manner in Which Valve Functions. with
1999-09-30
[Table view] |
Text
Public Service Electric and Gas Company P.O. Box 236 Hancocks Bridge, New Jersey 08038 Salem Generating Station July 03, 1990 U. S. Nuclear Regulatory Commission Document Control Desk Washington, DC 20555
Dear Sir:
SALEM GENERATING STATION LICENSE NO. DPR-70 DOCKET NO. 50-272 UNIT NO. 1 SUPPLEMENTAL SPECIAL REPORT 88-3-23 This supplemental Special Report addresses additional fire barrier penetration seal impairments (for both Salem Unit 1 and Salem Unit 2} which have not been restored to functional status within seven (7) days.
Th~se impairments have been identified by the Penetration Seal Task Force.
This report has been prepared in accordance with the reporting requirements of Technical Specification Action Statement 3.7.11.a pursuant to Technical Specification 6.9.2.
MJP:pc Distribution 9007090067 900703
~6R ADOCK 05000272 S
PDC The Energy People
/
Sincerely yours,
/t:~
L. K. Miller General Manager -
Salem Operations jJit 11\\
95-2189 (10M) 12-89
UNIT 1 SPECIAL REPORT 8*3-23 PLANT IDENTIFICATION:
Salem Generating Station -
Units 1 & 2 Public Service Electric & Gas Company Hancock's Bridge, New Jersey 08038 IDENTIFICATION OF OCCURRENCE:
Technical Specification 3.7.11; Fire Barriers Impaired For Greater Than 7 Days Event Date(s):
7/20/88, 8/9/88, 9/7/88, 10/11/88, 11/7/88, 12/7/88, 1/5/89, 2/6/89, 3/7/89, 4/6/89, 5/9/89, 6/7/89, 7/12/89, 8/8/89, 9/7/89, 10/7/89, 11/8/89, 12/8/89, 1/9/90, 2/8/90, 3/14/90, 4/9/90, 5/8/90, 6/8/90 Report Date:
7/3/90 This report was initiated by Incident Report Nos.88-268, 88-531,88-536, 88-537,88-544, 89-050,89-075, 89-086,89-091, 89-092,89-127, 89-287,89-349, 89-472,90-357, and 90-359.
CONDITIONS PRIOR TO OCCURRENCE:
N/A DESCRIPTION OF OCCURRENCE:
As identified in PSE&G letter NLR-N88037 dated March 4, 1988, PSE&G has initiated a comprehensive review/inspection of fire barrier penetration seals.
Due to the additional review by the Penetration Seal Task Force, penetrations found impaired are not being repaired within seven days as specified by Technical Specification Action Statement 3.7.11.a.
This report summarizes the task force findings and Technical Specification 4.7.11 surveillance activity findings associated with inadequate penetration seals for both Unit 1 and Unit
- 2.
The inadequate penetration seals found, to the date of issue of this report, include:
On July 13, 1988 two fire Barrier cable penetration were found degraded.
The penetration contained electrical sleeving containing an electrical cable surrounded by foam type fire sealant.
The area (approximately 1/8" gap and 1/4" gap respectively) surrounding the electrical sleeves were not sealed thereby constituting an impaired seal.
The fire barrier is in the east wall of the 100' Elevation Relay Room.
On July 25, 1988 three (3) degraded fire barrier cable penetration seals were found on the south wall in the 100' Elevation Relay Room.
Two (2) of these penetrations are 3" in diameter and the other is 5.5" (located -is feet above the floor).
The 3 penetrations contain fire wrapped cabling.
This fire wrap extends over the penetration.
There is no foam behind the fire wrap.
It provides a 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> rated barrier, however, the wall is a 3 hour3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> barrier.
The 5.5" penetration contains a 4" conduit surrounded by foam.
The foam contains an 1/8" gap at the base of the conduit.
Unit 1 SPECIAL REPORT 88--23 DESCRIPTION OF OCCURRENCE:
(cont'd)
On July 28, 1988 one (1) 3.5" degraded fire barrier cable penetration seal was found on the north wall in the 100' Elevation Relay Room.
The penetration contains cabling surrounded by foam.
The foam contains an 1/2" diameter hole.
Between August 2; 1988 and August 30, 1988, 138 additional penetration seals were found impaired of which 134 penetrations are located in the Unit 1 Relay Room and 4 penetrations are located in the Unit 1 lA 125 V Battery Room.
The penetrations range in size from -3 inches to -6 inches in diameter.
The nature of the impairments include 6 with no seal, 14 with a hole in the seal (unknown cause), 2 with foreign material imbedded in the seal (one imbedded with a rag and the other with duct tape),
30 with a void in the seal (due to inadequate quantity of foam injection upon installation}, 6 with apparent degradation (e.g.,
cable pulled through) 47 with inadequate color/cell structure (reference LER 272/88-013-00) and 32 that are not deep enough into the penetration per design (less than 6 inches).
Between August 31, 1988 and June 30, 1990, 6894 Unit 1 penetration seals and 5175 Unit 2 penetration seals were reviewed. Of these, 2854 penetration seals were determined to be impaired.
The majority of penetrations range in size from -3 inches to -6 inches in diameter.
There were 334 penetrations which were larger than 6 inches in diameter.
These penetrations ranged from 3"x5" to 258"x36".
Page 3 of this report contains a table of the penetration seals found impaired, between August 2, 1988 and June 30, 1990, in relation to the fire zone where they were found.
The impairment designator terms include:
No Seal NOS Hole in Seal HOL Void in Seal VIS Depth Not Great Enough DPT Color/Cell Structure CEL Seal Degradation DEG Foreign Material Imbedded FMT Planned Impairment PIM An hourly fire watch patrol had been established for the above areas previously due to other fire protection concerns.
Therefore, the requirements of Tech. Spec. Action Statement 3.7.11.a are met.
Unit 1 Technical Specification 3.7.11 states:
"All fire penetrations (including cable penetration barriers, fire doors and fire dampers), in fire zone boundaries, protecting safety related areas shall be functional."
Unit 1 Technical Specification Action Statement 3.7.11.a states:
"With one or more of the above required fire barrier penetrations non-functional, within one hour either establish a
UNIT 1 SPECIAL REPORT 88--23 DESCRIPTION OF OCCURRENCE:
(cont'd) continuous fire watch on at least one side of the affected penetration, or verify the OPERABILITY of fire detectors on at least one side of the non-functional fire barrier and establish an hourly fire watch patrol.
Restore the non-functional fire barrier penetration(s) to functional status within 7 days or, in lieu of any other report required by Specification 6.9.1, prepare and submit a Special Report to the Commission pursuant to Specification 6.9.2 within the next 30 days outlining the action taken, the cause of the non-functional penetration and plans and schedule for restoring the fire barrier penetration(s) to functional status."
NOTE - Unit 1 Technical Specification 3.7.11 differs from Unit 2.
The words "functional" and "non-functional" are replaced by the words "OPERABLE and "inoperable".
TABLE OF INOPERABLE PENETRATION SEALS 8/02/88 -
6/30/90 AREA U-1 Relay Room U-1 lA D/G Control Room U-1 lB D/G Control Room U-1 lC D/G Control Room U-1 lA 125 V Battery Room u~1 lC 125 V Battery Room U-1 #1 250 V Battery Room U-1 #3 Stairwell U-1 64' Elevation, Aisle
- 1 Auxiliary Building U-1 84' Elevation, Aisle
- 1 Auxiliary Building U-1 122' Elevation, N2 Bottle Storage Area U-1 84' Corridor; Unit 1 &
2 Common East & West
- U-1 78' Electrical Penetra.
Area 15 2
1 1
2 20 13 6
1 U-1 100' Boric Acid Transfer 3
Pump Area 34 3
1 1
l 3
4 1
3 1
4 CEL 54 72 194 2
21 3
21 1
11 11 3
.1 1
1 5
1 5
1 6
17 7
7 3
1 1
7 5
7
- 3.
l**
2 2
2 1
1
UNIT 1 SPECIAL REPORT 8*3-23 TABLE OF INOPERABLE PENETRATION SEALS (cont'd) 8/02/$8 -
6/30/90 AREA NOS HOL VIS DPT CEL DEG FMT PIM U-1 100' El. Mechanical 1
5 2
8 3
1 Penetration Area -
Blowdown Tanks U-1 100' El. Corridor 2
3 3
2 1
Service Building U-1 100' Elevation, Aisle 4
4 2
6 14 1
- 1 Auxiliary Building U-1 100' Corridor; Unit 1 &
15 11 8
30 61 1
2 Common East & West
- U-1 84' Corridor; Unit 1 &
2 7
14 11 2
1 2 Common North & South U-1 84' Corridor; Unit 1 &
3 3
2 Common East & West
U-1 100' Lobby 1
1 U-1 64' Lobby 1
U-1 11/12 Containment Spray 4
4 6
19 2
Pumps & Spray Add. Tank Area U-1 100' Corridor; Unit 1 &
2 4
3 1
185 2
2 Common North & South U-1 100' Elevation Counting 6
1 1
Room U-1 #11 Diesel Oil Tk Room 1
1 3
U-1 #12 Diesel Oil Tk Room 2
5 U-1 84' Elev. Control Area 23 14 1
22 91 1
- 1 Transformer Bus Rm.
U-1 Spent Fuel Pit Heat 3
3 6
16 Exchanger & Pump Area U-1 lA Diesel Generator Area 5
1 1
U-1 lB Diesel Generator Area 1
1 7
1 7
U-1 lC Diesel Generator Area 4
1 2
3 U-1 Waste Evaporator Room 4
11 4
1 1
U-1 100' Elevation Mechanical 8 4
10 Penetration Area
UNIT 1 SPECIAL REPORT 88.23 e TABLE OF INOPERABLE PENETRATION SEALS (cont'd) 8/02/88 -
6/30/90 AREA NOS HOL VIS DPT CEL DEG FMT PIM U-1 UPS Battery Room 2
U-1 Containment Rad Mon Room 4
1 10 10 U-1 #11 Chg. & SI Pump Room 1
4 U-1 #12 Chg. & SI Pump Room 1
U-1 #13 Chg. & SI Pump Room 2
U-1 84' El. Pipe Trench 126 1
1 16 2
U-1 100' El. Baling & Storage 7 1
3 1
1 U-1 110' El. Control Console 1
- 9.
U-1 78' El. Contain. Rad 1
1 Mon. Room U-1 84' El. #11 Comp. Cool.
20 1
3 2
Heat Xgr. & 12 cc Pp Room U-1 100' Elec. Penetra. Area 14 4
17 6
5 U-1 Laundry, Chem* Pump Area 5
3 2
19 4
U:-1 64' El. Control Area #1 3
4 18 11 1
4KV Bus U-1 #1 Letdown Heat Exch.
1 U-1 84' El. #12 Comp. Cool.
3 3
3 Heat Xgr. & 12 & 13 CC Pp Room U-1 #11 SI Pump Room 1
1 U-1 Pipe Trench 14 3
3 20 16 3
U-1 Rx Coolant Filter Area 9
1 U-1 84' Spent Resin Xfer Pp Rm 2
U-1 11 & 12 Mon. Tank Room 8
1 5
2 U-1 84' Elevator Lobby 1
U-1 Aux Feed Pumps 3
U-1 Valve Alley 3
2 3
U-1 Seal Water Heat XChg 2
3 1
U-1 84' El. Corridor 2
2 1
UNIT 1 SPECIAL REPORT 88.-23.*.
TABLE OF INOPERABLE PENETRATION SEALS (cont'd) 8/02/88 - 6/30/90 AREA NOS
~OL VIS DPT c~
DEG FMT PI:f1 U-1 A/C & Boric Acid 5
1 10 81 1
Tank Room U-1 A/C Equipment Rm 1
2 4
U-1 Boric Acid Ev'ap. &
2 1
3 1
Gas Stripper Unit U-1 Water Recirc Heater 3
1 1
2 U-1 #1 Stairwell 6
5
\\
U-1 #1 Cone. Filter Area 1
U-1 Rm Next To #11 Chg Pp 2
2 U-1 Diesel Oil C02 Area 4
1 U-1 Motor Control Center 2
1 1
U-1 Elevator - El 2
1 1
U-1 N2 Bottle Storage 3
U-1 #12 RHR XGR Room*
1 U-1 55'.El. Walkway 2
U-1 Future Mixed Bed
- 1.
Dem in U-1 #11 Mixed Bed Deroin 2
U-1 #1 Cation Bed (NW) 2 U-1 #1 Cation Bed (SW) 8 U-1 #11 Debora ting Demin 3
U-1 #12 Debora ting Deroin 2
1 U-1 Primary Sampling Lab
- 3.
1 U-1 78' Piping Penetration 1
4 U-1 Vent Duct Shaft 1
6 U-1 Valve Room 4
U-1 Waste Evaporator Area 1
U-1 #11 Evap. Feed Ion Xchg.
3
UNIT 1 SPECIAL REPORT 8*-23 e TABLE OF INOPERABLE PENETRATION SEAI1S (cont'd) 8/02/88 -
6/30/90 AREA NOS HOL VIS DPT c~~
DEG FMT PIM U-1 #12 Evap. Feed Ion Xchg.
2 U-1 #13 Evap. Feed Ion Xchg.
4 U-1 #14 Evap. Feed Ion Xchg.
1 1
U-1 100' Aisle #1 N & s 2
U-1 122' Corridor 1
U-1 Ops File & Ref Rm 1
U-1 Watch Engineer Room 3
U-1 #1 Maint, Spare & Test 1
Equipment Room U-1 #2 Maint, Spare & Test 2
Equipment Room U-1 Janitors Closet 1
U-1 #1 Control Equip. Room 15 5
U-1 84' El. Pipe Alley 2
3 1
U-1 Sample Room 1
U-1 Data Logging Room 2
16 U-1 Work Control Center 1
2 1
U-1 #11 & #12 RHR Sump Pumps 1
Room U-1 #1 Control Room 4
2 U-1 AC Equip. Room 1
2 U-1 #1 Spent Fuel Pit Filter 1
U-1 Women's Toilet 5
U-1 Containment Rad Monitor 1
Room U-2 #5 Stairwell 3
1 U-2 #4 Stairwell*
7 1
1 U-2 #2 Stairwell 7
1 1
I
8A-23 UNIT 1 SPECIAL REPORT TABLE OF INOPERABLE PENETRATION SEALS (cont'd) 8/02/88 - 6/30/90 AREA NOS HOL VIS DPT
.(:~J::i.
DEG FMT PIM U-2 100' El. Mechanical Pene. 2 6
Area -
Blowdown Tanks U-2 100' El. Corridor 2
1 U-2 100' Elevation Mechanical 5 3
5 6
4 3
Penetration Area U-2 AC & Boric Acid Tank Room 9 9
21 4
1 U-2 Relay Room 23 27 4
61 132 1
r U-2 22 RHR Xgr Room 3
U-2 84' Control Area Trans-17 34 4
39 31 former Bus Room U-2 Rad. Detector Panel 1
U-2 _Battery Room 2C 125VDC 13 U-2 Battery Room 2B 125VDC 2
3 3
U-2 #2 250V Battery Room 3
U-2 Control Area #7 4KV 4
5 2
3 1
Vital Bus Area U-2 110' El. Control Console 1
3 U-2 78' Electrical Pen. Area 5
4 U-2 100' Electrical Pen.. Area 2 1
3 U-2 2A D/G Controi. Room 1
5 4
1 U-2 2B DIG Control Room 1
2 11 4
U-2 2C D/G Control Room 2
4 3
U-2 #21 Diesel Oil Tank Area 5
2 1
3 U-2 #22 Diesel Oil Tank Area 1
3 2
4 4
U-2 #21 Diesel Fuel Oil 1
1 Transfer Pump Area U-2 #22 Diesel Fuel Oil 1
Transfer Pump Area U-2 111' Vent. Equip. Area 19 4
- 9.
UNIT 1 SPECIAL REPORT 8&9-23 e TABLE OF INOPERABLE PENETRATION SEALS (cont'd) 8/02/88 -
6/30/90 AREA NOS HOL VIS DPT CEL_
DEG FMT PIM U-2 100' Vent Duct Shaft 1
1 U-2 64' Storage Area 2
1 19 6
U-2 84' Spent Fuel Pit Heat 4
1 4
XChgr. & Pump Room U-2 Boric Acid XFer Pump Area 9 1
1 2
U-2 Aisle #1 East Section 7
1 1
2 U-2 Aux. Feedwater Pumps 2
4 1
U-2 #21 & 22 Monitor Tank 3
1 1
2 Area U-2 21 & 22 Cont. Spray 11 4
1 1
Pumps & Spray Add Tank U-2 Aisle 2 East & West 1
1 U-2 Cou,n ting Room 1
5 U-2 #2 Control Room 13 7
2 1
1 I.
U-2 Pipe Alley 3
U-2 78' Containment Rad 6
5 Monitor Room U-2 21 & 22 SI Pump. Room 1
U-2 84' Piping Pene Area 5
U-2 Aisle 2 North & South 1
1 U-2 84' Corridor 1
U-2 Calibration Room 1
U-2 #21 Component Cooling 16 1
Heat Exchanger and Pumps U-2 #22 Component Cooling 5
Heat Exchanger and Pumps U-2 84' SW Piping Room 1
U-2 C02 Fire Equipment Area 1
U-2 Concentrates Holding Tank 1
U-2 Seal.Water Heat XChgr 1
UNIT 1 SPECIAL REPORT aAlt-23 U-2 U-2 U-2
8/02/88 -
6/30/90 NOS HOL VIS DPT CEL
- 2 Rx Coolant Filter Area 7
- 2 Control Equip Room 1
4 84' Valve Room 5
- 100 Rad Detector Panel 1
1 Waste Evaporator Area 1
2 3
Vent Duct Enclosure Shaft 2
Motor Control Center 1
Ref. Water Purifier Room 2
Data Logging Room 5
7 A/C Equipment Room 2
84' Pipe Alley 2
1 N2 Bottle Storage Area 1
- 24 Evap.. Feed Ion Xchgr 1
100' Cation Bed Deroin.
3 FMT 1
The opposite room for the north and east walls is the.Unit 2 Relay Room.
- - The Relay Room PIM was resealed thirteen days after opening_
APPARENT.CAUSE OF OCCURRENCE:
The cause of the degraded fire barrier penetrations could not be positively determined.
The east wall penetrations (discovered 7/13/88) from the Relay Room side 11 appeared 11 sealed visually due to th.e use of a. bushing on the sleeve which hid the gap.. The 3.5" south wall penetrations (discovered 7/25/88) also appeared sealed from the Relay Room side, as described in the Description of Occurrence section.
Closer inspection, as required by the Seal Penetration Review Group procedures, revealed the nature of the impairments.
Technical Specification Surveillance 4.7.11 requires verification of the functional status of fire barrier penetrations every eighteen months.
via a visual inspection.
This inspection would not necessaiily identify the non-functional status of the subject penetrations.
The 5.5 11 south wall penetration (found July 25) is located in a difficult to reach location.
The gap in the seal may h_ave formed due to shrinkage.
It does not appear as though a cable was pulled (forming the gap}.
I
UNIT 1 SPECIAL REPORT 8849-23 ~
APPARENT CAUSE OF OCCURRENCE:
(cont'd)
The 3.5" north wall penetration (found July 28) is also located in a difficult to reach location.
The gap in the seal appears to have formed as a result of a cable pull.
It has not been determined when or by whom the cable was pulled.
The penetrations with non-functional seals, found between August 2, 1988 and June 30, 1990, are similar in configuration (except as noted) to the penetrations identified in the original issue.of this Special Report.
The cause of their degraded condition also could not positively be determined.
ANALYSIS OF OCCURRENCE:
The functional integrity of the penetration fire barriers ensures that fires will be confined or adequately retarded from spreading to adjacent portions of the facility.
This design feature minimizes the possibility of a single fire involving several areas of the facility.
The fire barrier penetration seals are a passive element in the facility fire protection program and are subject to periodic inspections.
This report satisfies the reporting requirements of Technical Specification 3.7.11.a pursuant to Technical Specification 6.9.2 since the time between discovery and eventual repair of the fire barrier impairments is greater than seven (7) days.
Appropriate actions were already in place in accordance with the requirements of Technical Specification Action Statement 3.7.11.a to establish a one hour roving fire watch.for the impaired fire barriers once the impairments were identified.
The subject fire area contains detection in addition to the roving fire watch patrol.
Therefore, it is reasonable to assume that a fire in either area would be detected before it could involve an adjacent area.
This occurrence therefore involved no undue risk to the health or safety of the public.
CORRECTIVE ACTION:
The hourly fire watch, as addressed in the Description of Occurrence section, will continue until all fire protection concerns associated with these areas are resolved.
The repair of the penetrations was not accomplished within seven (7) days due to the additional review being conducted by the Penetration Seal Task Force.
Upon completion of this review the penetrations will be sealed.
Penetration seal repair work has been initiated.
The Unit 1 Relay Room was the first area worked.
To date, 3054 penetrations have been sealed and accepted by the Penetration Seal Task Force.
The majority of those penetrations in the Unit 1 and Unit 2 Relay Rooms (halon discharge areas) which either have no seal or holes through the seal have been sealed using approved station procedure M3Y, "Installation and Repair of Fire Barrier and Flood Protection Seals".
The review and corrective actions, conducted by the Penetration Seal Review Program, will be completed in accordance with the March 4, 1988
UNIT 1 SPECIAL REPORT 88~23 CORRECTIVE ACTION:
(cont'd)
PSE&G letter NLR-N88037 to the NRC, the August 26, 1988 telecommunication between PSE&G and the NRC Region 1 office, and the August 15, 1989 semi-annual management meeting conducted with the NRC.
MJP:pc SORC Mtg.90-079 General Manager -
Salem Operations