March 2017 GFE Post-Exam Final NRC Version - NRC Response to Monticello Comment
ML18086B671
Person / Time
Site: Monticello 
Issue date: 03/27/2018
From: Jacob Dolecki
NRC/NRR/DIRS/IOLB
To:
Dolecki J, NRR/DIRS, 415-2947
References
Download: ML18086B671 (4)


Text

NRC Response to Facility Comment on the March 2017 Generic Fundamentals Examinations Page 1 of 4 FACILITY:

Monticello EXAM:

BWR Form A/B QUESTION:

BWR 15/29 (Also applies to PWR 14/28)

An AC induction motor is operating with the following steady-state conditions:

Motor current

= 20 amps Stator temperature (average) = 130°F Ambient temperature

= 80°F If a change in motor load causes the motor current to increase to 40 amps, which one of the following will be the new steady-state average stator temperature?

A. 180°F B. 200°F C. 260°F D. 280°F PRELIMINARY ANSWER: D.

FACILITY COMMENT:

See pages 3 and 4.

NRC RESPONSE: The NRC agrees that choice D is not a correct answer to the question as written.

According to Joules Law of Heating, the rate of heat generation in an electrical conductor is proportional to the product of the square of the amount of current flowing through the conductor and the resistance of the conductor. Joules Law of Heating applies to any current-carrying conductor, including the stator windings of an AC induction motor. Joules Law of Heating is the basis for the equation, P = I2R (provided on the GFE Equation Sheet), where:

P is power, or heat generation I is current R is resistance The original correct answer, 280°F, can be determined by deriving P I2 from the above equation.

According to P I2, if motor current (I) doubles from 20 amps to 40 amps, then heat generation (P) in the stator will increase by a factor of four. In response to the four-fold increase in P, the motor differential temperature (T) will also increase four-fold from 50°F to 200°F. When 200°F is added to the fixed ambient temperature, 80°F, the result is 280°F (Choice D).

However, the facility comment correctly asserts the answer should be greater than 280°F because R will increase as stator temperature increases, thereby causing a greater increase in P. Using the

NRC Response to Facility Comment on the March 2017 Generic Fundamentals Examinations Page 2 of 4 equation/calculations for a common AC induction motor stator winding material, copper, as provided in the facility comment, and Joules Law of Heating as described above, R will increase by a factor of 1.38 while I2 will increase by a factor of 4. In other words, if the changes in both I and R are accounted for, the correct answer should be some value more than 280°F, as noted by the facility.

The change in R accounts for enough change in P to alter the answer significantly. The question stem does not ask the applicant to assume a fixed R value so, as the question is written, the change in R will also contribute to an increase in the stator temperature.

Therefore, the question will be deleted.

Page 3 of 4