LER-1980-038, Forwards LER 80-038/03L-0
Event date:
Report date:
2721980038R00 - NRC Website

text

  • '

OPS~G Public Service Electric and Gas Company 80 Park Place Newark, N.J. 07101 Phone 201/430-7000 Mr. Boyce H. Grier Director of USNRC Off ice of Inspection and Enforcement Region 1 631 Park Avenue King of Prussia, Pennsylvania 19406

Dear Mr. Grier:

LICENSE NO. DPR-70 DOCKET NO. 50-272 REPORTABLE OCCURRENCE 80-38/03L July 23, 1980 Pursuant to the requirements of Salem Generating Station Unit No. 1 Technical Specifications, Section 6.9.1, we are submitting Licensee Event Report for Reportable Occurrence 80-38/03L.

This report is required within thirty (30) days of the occurrence.

sincerely yours'

/

(...

.... _\\_ ('._._

. } i *,,

F. P. Librizzi General Manager -

Electric Production CC:

Director, Office of Inspection and Enforcement (30 copies)

Director, Office of Management Information and Program Control (3 copies) 95-2001 l200M) 2-78 j

l l

Report Number:

80-38/03L Report Date:

7/23/80 Occurrence Date:

6/26/80 Facility:

Salem Generating Station, Unit 1 Public Service Electric & Gas Company Hancock's Bridge, New Jersey*

08038 IDENTIFICATION OF OCCURRENCE:

12 Charging Pump Inoperable CONDITIONS PRIOR TO OCCURRENCE:

Mode 1 Reactor Power 100%

DESCRIPTION OF OCCURRENCE:

During normal operation, it was observed that there was service water in the lube oil reservoir.

At 0100 hours0.00116 days <br />0.0278 hours <br />1.653439e-4 weeks <br />3.805e-5 months <br />, the pump was declared inoperable and Action Statement 3.5.2a was entered requiring, with one ECCS subsystem inoperable, to restore the inoperable subsystem to operable status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> or be in hot shutdown within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />.

DESIGNATION OF APPARENT CAUSE OF OCCURRENCE:

A tube failure in the lube oil cooler.

ANALYSIS OF OCCURRENCE:

Investigation revealed there was a tube failure in the lube oil cooler resulting in a service water to lube oil leak.

CORRECTIVE ACTION

The cooler was replaced in kind with one from stock, tested satis-factorily and the Action Statement was terminated at 1445 hours0.0167 days <br />0.401 hours <br />0.00239 weeks <br />5.498225e-4 months <br /> on June 27, 1980.

FAILURE DATA:

Ross Manufacturing Heat Exchanger Mod.el HCP-501-2 Prepared By M. J. Murphy SORC Meeting No.

50-80 Manager ::'~~ting Station