ML18082A801

From kanterella
Jump to navigation Jump to search
Forwards LER 80-038/03L-0
Date released: 11/29/2018 Download: ML18082A801


LER 80-038/03L-0:on 800626,during Routine Insp,Svc Water Found in Charging Pump 12 Lube Oil Reservoir.Pump Declared Inoperable.Caused by Leak in Lube Oil Cooler Due to Tube Failure.Cooler Replaced & Tested Satisfactorily
ML18082A802
Person / Time
Site: Salem PSEG icon.png
Issue date: 07/23/1980
From: Murphy M
Public Service Enterprise Group
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
References
Download: ML18082A802 (1)
Forwards LER 80-038/03L-0
ML18082A800
Person / Time
Site: Salem PSEG icon.png
Issue date: 07/23/1980
From: Librizzi F
Public Service Enterprise Group
To: GRIER B H
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
References
Download: ML18082A800 (2)