REGULATOR> INFORMATION DISTRIBUTION S STEM (RIDS)

AOCESSION NBR:81,12210271 DOC ~ DA'TE: 81/12/14 NOTARI'ZED: NO DOCKET FACIL:50<<389 St. Lucie Planti Uniit 2< Florida Po~er 8 Light Co. 05000389

'AUTH, NAME AUTHOR AFFILIATION HAGANjJ ~ Eq Environmental Protection Agency R E<<C IP ~ N Ah(E RECIPIENT AFF ILIA'TION Division of Licensing

SUBJECT:

Forwards t'echnical comments re DES from facili[ty Normal ~

operation .will nest have >significant environ impact+Two areas need clarification Technical comments encl.@/o encl.

DISTRIBUTION CODE: <<C002S <<COPIES <<RECEIVED:LTR, ~ ENCL SZZE$ ,

TITLE: Environ, Comments.

NOTES:

REC IP IENT <<COP IES RECIPIENT COPIES ID CODE/NAPE LTTR ENCL ID CODE/NAME LTTR ENCL ACTION: LIC BR 03 BC 06 NL NERSESgY ~ 01 INTERNAL: ELD IE 13 '2 NRR/DE/AEAB 20 NRR/DE/EEB 16., 1 NRR/DE/HGEB 21 NRR/DE/SAB 18 1 NRR/DS I/AEB 19 NR ETSB 15 1 NRR/DSI/RAB 17 00 1 EXTERNAL: ACRS 1 LPDR 03 NATL LAB 21 5 NRC PDR 02 NSIC 05 1 NTIS TOTAL NUMBER OF COPIES REQUIRED: LTTR 30 ENCL

v It

~ i f ...r fI If 1 g

.L

~

W f k f (

III Il 'I

' I y

1 11 I

I

~

fl 4.

C i g

OEO SP4P UNITED STATES ENVIRONMENTALPROTECTION AGENCY

+ PRA~ REGION IV 345 COURTLAND STREET ATLANTA.GEORGIA 30365 lJ ~~le~

OCC 1.4 ]981 ~q g gQ+

Director, Division of Licensing, e~~~'~@ ~'..

Office of Nuclear Reactor Regulation U. S. Nuclear Regulatory Commission Washington, D. C. 20555

Dear Sir:

We have reviewed the Draft Environmental Impact Statement (DEIS) related to the operation of St. Lucie Plant, Unit No. 2, located in St. Lucie County, Florida. Our review suggest that the plant as designed should be capable of operating under normal conditions in such a manner as to meet EPA's Environmental Radiation Protection Standards for Nuclear Power Operations. (40 CFR 190)

We commend the NRC for expanding Section 5.10 of the DEIS to provide an adequate assessment of the accident characteristics,

..(including a class 9 accident) fission product release, exposure pathways, health effects, and accident consequences of the operating facility. We believe these additions greatly improve the operational DEIS over the Final EIS for construction of the facility.

In our review of the DEIS in respect to our NPDES responsibilities we suggest two areas need to be clarified.

These suggest,ions are included in our attached technical comments.

In conclusion we have rated the DEIS L0-2, i.e. we do not believe the normal operation of the nuclear facility will have a significant environmental impact but we are requesting change in the FElS as reflected in our attached technical comments.

Sine rely yours, J n E. Hagan III, P.E., Acting Chief, Environmental Assessment Branch CO<>>

5 81t221027I~sggpgg PDR ADOCK j

05000389 PDR

p

'k 1

1

TECHNICAL COMMENTS

1. Page 4-8, Section 4.2.7, first'aragraph,'ast. sentence.

Concentration limitations in the HPDES Permit is 0. 03 mg/1 during periods when condenser chlorination is not being conducted.

sentences Por'clarity, be replaced it is suggested that the last four with the following:. :"...by a licensed contrac or. PPEL has applied 'to EPA for authorization to chlorinate the auxiliary cooling ,water systems continuously, in .addition to their previous intermittent chloriniation of the condenser, coolingr request'or systems which was assessed" in the PES-CP revihw. The draft

.HPDES permit provides limitations for total residual oxidants. (TRO), which includes total residual 'hlorine, under outfall serial numbers 001 and 008. During periods.

when TRO is being discharged from condenser (and auxilliary system) chlorination, a maximum instantaneous TRO limitation at the terminus of the discharge canal of 0.19 - .

mg/1 is applicable. - However, during periods when TRO is being'ischarged only from the auxiliary systems, the limitation is 0.03 mg/l."

2. Page  :,5-10, Section 5.6.5, first paragraph. The word "there" should be replaced with "in Appendix C" at the end of the..fiist sentence, since NPDES permit limitations are not generally presented in Section 4.2.7. A brief j)P 'iscussion (or a't least a reference) of the 0.10 mg/1 TRO limitation is:suggested for inclusion in this basis for the

..paragraph and can be. reproduced f=-om Item II.A.2.a. of the NPDES Permit. Rationale which is on page C-32 of the DES.

Additionally the paragraph should include a'efe e."'.ce, to the continuous .chlorination of the auxiliary cooling systems .'as'oted-~for, Section '4.2.? above and the expected low lev'els.of TRO .releases.