W3F1-2015-0032, Annual Radiological Environmental Operating Report for the Period of January 1 Through December 31, 2014
ML15124A010 | |
Person / Time | |
---|---|
Site: | Waterford |
Issue date: | 04/29/2015 |
From: | Jarrell J Entergy Operations |
To: | Document Control Desk, Office of Nuclear Reactor Regulation |
References | |
W3F1-2015-0032 | |
Download: ML15124A010 (66) | |
Text
Entergy Operations, Inc.
17265 River Road Killona, LA 70057-3093 Tel 504 739 6685 SEntergy Fax 504 739 6698 jjarrel@entergy.com John P. Jarrell III Manager - Regulatory Assurance Waterford 3 W3F 1-2015-0032 April 29, 2015 U.S. Nuclear Regulatory Commission Attn: Document Control Desk Washington, DC 20555-0001
Subject:
Annual Radiological Environmental Operating Report -2014 Waterford Steam Electric Station, Unit 3 (Waterford 3)
Docket No. 50-382 License No. NPF-38
Dear Sir or Madam:
Attached is the Annual Radiological Environmental Operating Report for the period of January 1 through December 31, 2014. This report is submitted pursuant to the requirements of Waterford 3 Technical Specification Section 6.9.1.7.
This report contains no new commitments. Please contact John P. Jarrell, Regulatory Assurance Manager, at (504) 739-6685 if you have questions regarding this information.
Attachment:
Annual Radiological Environmental Operating Report - 2014 tj(-CU
W3Fl -2015-0032 Page 2 cc: Mr. Marc L. Dapas Regional Administrator U. S. Nuclear Regulatory Commission Region IV RidsRgn4MailCenter@nrc.gov NRC Senior Resident Inspector Waterford Steam Electric Station Unit 3 Frances. Ramirez@nrc.gov Chris. Speer@nrc.gov NRC/NRR Project Manager for Waterford 3 Michael.Orenak@nrc.gov Allyson Howie Entergy Legal, General Sr Councel AHowie@entergy.com
Attachment to W3F1-2015-0032 Annual Radiological Environmental Operating Report - 2014 (63 pages)
w
.Entergy I January 1,2014 - December 31,2014 1
Annual Radiological 2014 IAI f F- A 'I Qf 171 fl; Qf f; AnnrulRUI adilogcal aQI I 214
.I Originator:
Ann V. Dubois, Chemistry Technician Date Reviewed By:
dq- -c/9-f Clay M. Benton, Chemistry Supervisor Date Approved By:
Nicole K. Lawless, Cl'astryManager Date
Annual Radiological 2014 Environmental Operating Report Waterford 3 Steam Electric Station TABLE OF CONTENTS
SUMMARY
I
1.0 INTRODUCTION
5 1.1 Radiological Environmental Monitoring Program 5 1.2 Pathways Monitored 5 1.3 Land Use Census 5 2.0 INTERPRETATION AND TRENDS OF RESULTS 20 2.1 Air Particulate and Radioiodine Sample Results 20 2.2 Thermoluminescent Dosimetry Sample Results 20 2.3 Water Sample Results 21 2.4 Sediment Sample Results 21 2.5 Milk Sample Results 22 2.6 Fish Sample Results 22 2.7 Broad Leaf Vegetation Sample Results 22 2.8 Land Use Census Results 22 2.9 Interlaboratory Comparison Results 22 3.0 RADIOLOGICAL ENVIRONMENTAL MONITORING PROGRAM
SUMMARY
25 3.1 2014 Program Results Summary 25
- i-
Annual Radiological 2014 Environmental Operatinq Report Waterford 3 Steam Electric Station LIST OF TABLES TABLE 1.1 RADIOLOGICAL ENVIRONMENTAL SAMPLING PROGRAM 6 TABLE 2.1 BIENNIAL LAND USE CENSUS RESULTS 23 TABLE 3.1 RADIOLOGICAL ENVIRONMENTAL MONITORING PROGRAM
SUMMARY
26
- ii -
Annual Radiological 2014 Environmental Operating Report Waterford 3 Steam Electric Station LIST OF FIGURES FIGURE 1-1 REMP SAMPLES WITHIN 2 MILES OF WATERFORD 3 17 FIGURE 1-2 REMP SAMPLES WITHIN 10 MILES OF WATERFORD 3 18 FIGURE 1-3 REMP SAMPLES WITHIN 50 MILES OF WATERFORD 3 19 FIGURE 2-1 TLD RADIATION DOSE COMPARISON (BY YEAR) 24
- iii -
Annual Radiological 2014 Environmental Operatinq Report Waterford 3 Steam Electric Station LIST OF ATTACHMENTS ATTACHMENT 1 2014 RADIOLOGICAL MONITORING REPORT
SUMMARY
OF MONITORING RESULTS 30 ATTACHMENT 2 STATISTICAL COMPARISONS 50
- iv -
Annual Radiological 2014 Environmental Operating Report Waterford 3 Steam Electric Station Summary The Annual Radiological Environmental Operating Report presents data obtained through analyses of environmental samples collected for Waterford 3's (W3) Radiological Environmental Monitoring Program (REMP) for the period January 1 through December 31, 2014. This report fulfills the requirements of W3 Technical Specification 6.9.1.7.
During 2014, gross beta radioactivity was detected in air and drinking/surface water locations. Results obtained at the indicator locations were similar to those obtained at the control location. Therefore, levels continue to remain at background.
Radiological Environmental Monitoring Program W3 established the REMP prior to the station becoming operational (1985) to provide data on background radiation and radioactivity normally present in the area. W3 has continued to monitor the environment by sampling air, water, sediment, milk, fish and broad leaf vegetation, as well as measuring radiation directly.
The REMP includes sampling indicator and control locations within a 31-mile radius of the plant. The REMP utilizes indicator locations near the site to show any increases or buildup of radioactivity that might occur due. to station operation, and control locations farther away from the site to indicate the presence of only naturally occurring radioactivity. W3 compares indicator results with control, preoperational, and previous years operational results to assess any impact W3 might have on the surrounding environment.
In 2014, W3 collected environmental samples for radiological analysis. Based on the comparison results of indicator locations with control locations and previous studies, it was concluded that overall W3 operations had no significant impact on plant environs. The review of 2014 data, in many cases, showed undetectable radiation levels in the environment and near background levels in significant pathways associated with W3.
Harmful Effects or Irreversible Damaqe The REMP did not detect any harmful effects or evidence of irreversible damage in 2014. Therefore, no analysis or planned course of action to alleviate problems was necessary.
1
Annual Radiological 2014 Environmental Operating Report Waterford 3 Steam Electric Station Reporting Levels W3's review indicates that no samples equaled or exceeded reporting levels for radioactivity concentration in environmental samples, as outlined in Technical Requirements Manual (TRM)
Table 3.12-2 when averaged over any calendar quarter, due to W3 effluents. Therefore, 2014 results did not trigger any radiological monitoring program special reports.
Radioactivity Not Attributable to W3 The W3 REMP detected radioactivity attributable to other sources three times. These include the 25th Chinese nuclear test explosion in 1980, the radioactivity plume release due to reactor core degradation at the Chernobyl Nuclear Power Plant in 1986, and the airborne release from Dai-ichi, Fukushima following the Tohoku earthquake on March 11, 2011.
Comparison to State Program W3 compared REMP data to the monitoring program of the Environmental Radiological Laboratory -
Department of Environmental Quality Laboratory Services Division (ERL-DEQLSD). The ERL-DEQLSD and the W3 REMP entail similar radiological environmental monitoring program requirements. Both programs have obtained similar results over previous years.
Sample Deviations
- Milk Samples Since milk samples for indicator location MKE-3 were unavailable for all quarters of 2014, broad leaf vegetation sampling was performed as required by TRM Table 3.12-1. Broad leaf vegetation results are in section 2.7. Milk samples were collected from one control location and analyzed for Iodine-131 and gamma radionuclides. Results indicate that all measurements were below the calculated LLDs.
Therefore, W3 concluded that plant operations had no significant impact on this pathway during 2014.
- Air Samples The air sample locations listed below failed to meet the requirement for sample continuity. As described in footnote (1) of TRM Table 3.12-1, deviations are permitted from the required sampling schedule due to malfunction of sampling equipment and other legitimate reasons.
Location Sample Period Explanation of Deviation APQ-1 04/28/14 - 05/12/14 Sample pump running at low capacity 2
Annual Radiological 2014 Environmental Operating Report Waterford 3 Steam Electric Station
- Missed Samples One TLD located at station N-1 was missing at the time of the first quarter exchange. TLDs located at stations G-4, J-2 and N-1 were missing at the time of the second quarter exchange.
+ Required Lower Limit of Detection (LLD) Values All LLDs during this reporting period were within the acceptable limits required by the W3 TRM.
- Unavailable Results W3 received analytical results in adequate time for inclusion in this report. In addition, W3's review identified no missing results.
- Program Modifications No program modifications were made during 2014.
3
Annual Radiological 2014 Environmental Operating Report Waterford 3 Steam Electric Station Attachments contains results of air, TLD, water, sediment, milk, fish and broad leaf vegetation collected in 2014. TLDs were analyzed by Stanford Dosimetry. All remaining samples were analyzed by Teledyne Brown Engineering, Inc. Attachment 1 also contains Teledyne's participation in the interlaboratory comparison program during 2014. contains statistical comparisons of:
" TLD measurements from stations grouped by distance
" TLD radiation dose to historical data by location
" Gross beta activity measurements on air particulate filters
- Gross beta activity measurements in surface/drinking water samples 4
Annual Radiological 2014 Environmental Operating Report Waterford 3 Steam Electric Station 1.0 Introduction 1.1 Radiological Environmental Monitoring Program W3 established the REMP to ensure that plant operating controls properly function to minimize any associated radiation endangerment to human health or the environment. The REMP is designed for:
- Analyzing important pathways for anticipated types and quantities of radionuclides released into the environment.
- Considering the possibility of a buildup of long-lived radionuclides in the environment and identifying physical and biological accumulations that may contribute to human exposures.
" Considering the potential radiation exposure to plant and animal life in the environment surrounding W3.
" Correlating levels of radiation and radioactivity in the environment with radioactive releases from station operation.
1.2 Pathways Monitored The airborne, direct radiation, waterborne and ingestion pathways are monitored as required by W3 TRM Table 3.12-1. A description of the W3 REMP utilized to monitor the exposure pathways is described in Table 1.1 and shown in Figures 1-1, 1-2 and 1-3.
Section 2.0 of this report provides a discussion of 2014 sampling results with Section 3.0 providing a summary of results for the monitored exposure pathways.
1.3 Land Use Census W3 conducts a land use census biennially, as required by Section 3.12.2 of the TRM. The purpose of this census is to identify changes in uses of land within five miles of W3 that would require modifications to the REMP and the Offsite Dose Calculation Manual (ODCM). The most important criteria during this census are to determine the location in each sector of the nearest:
- 1) Residence
- 2) Animal milked for human consumption 2 2
- 3) Garden of greater than 50 m (500 ft ) producing broad leaf vegetation.
W3 conducts the land use census by:
" Field surveys in each meteorological sector out to five miles in order to confirm:
, Nearest permanent residence
- Nearest garden and approximate size
> Nearest beef cow
> Nearest food product
> Nearest milking animal
" Identifying locations on maps, measuring distances to W3 and recording results on data sheets.
" Comparing current census results to previous results.
5
Annual Radiological 2014 Environmental Ooeratina Report Waterford 3 Steam Electric Station Table 1.1 Radiological Environmental Sampling Program Exposure Requirement Sample Point Description, Sampling and Type and Frequency Pathway Distance and Direction Collection Frequency Of Analyses Airborne Radioiodine and Particulates Three samples from close to the three APQ-1 (NW, 0.81 Miles) - (West bank) Continuous sampler operation Radioiodine Canister 131 SITE BOUNDARY locations, in different Located in soybean/sugarcane field off with sample collection bi- analysis bi-weekly.
sectors, in or near sectors having the LA 18 east of LA 18/3141 intersection.
highest calculated annual average weekly, or more frequently if ground level D/Q. APF-1 (ESE, 0.35 Miles) - (West bank) required by dust loading. Particulate Sampler - Gross Located on north side of Secondary beta radioactivity analysis Meteorological Tower. following filter change. Gamma APC-1 (NE, 0.67 Miles) - (East bank) isotopic analysis of composite Located inside Little Gypsy Cooling Water (by location) quarterly.
Intake Structure fence.
Radioiodine and Particulates One sample from the vicinity of a APP-I (WNW, 0.84 Miles) - (West bank) community having the highest Located in soybean/sugarcane field on calculated annual average ground level Short St. in Killona.
D/Q.
Radioiodine and Particulates One sample from a control location, as APE-30 (E, 25.2 Miles) - (West bank) for example 15 -30 km distant and in Located on roof of Entergy Office building the least prevalent wind direction, on Delaronde St. in Algiers. (Control) 6
Annual Radiological 2014 Environmental Operating Report Waterford 3 Steam Electric Station Table 1.1 Radiological Environmental Sampling Program Exposure Requirement Sample Point Description, Sampling and Type and Frequency Pathway Distance and Direction Collection Frequency Of Analyses Direct TLDs Radiation An inner ring of stations, one in each A-2 (N, 1.27 Miles) - (East bank) Located Quarterly Gamma dose quarterly.
meteorological sector in the general on pole on LA 628 at Zephrin L. Perriloux area of the SITE BOUNDARY. Fire House.
B-I (NNE, 0.75 Miles) - (East bank)
Located on fence west of Little Gypsy.
C-1 (NE, 0.67 Miles) - (East bank) Located on fence at Little Gypsy Cooling Water Intake structure.
D-2 (ENE, 1.24 Miles) - (East bank)
Located on pole on levee at west entrance to Bonnet Carre Spillway.
7
Annual Radiological 2014 Environmental Operatinq Report Waterford 3 Steam Electric Station Table 1.1 Radiological Environmental Sampling Program Exposure Requirement Sample Point Description, Sampling and Type and Frequency Pathway Distance and Direction Collection Frequency Of Analyses Direct TLDs Radiation An inner ring of stations, one in each E-1 (E, 0.41 Miles) - (West bank) Located on Quarterly Gamma dose quarterly.
meteorological sector in the general pole on LA 18 east of Waterford 3 plant area of the SITE BOUNDARY. entrance.
F-2 (ESE, 1.15 Miles) - (West bank) Located on fence on LA 3142 south of LA 18.
G-2 (SE, 1.26 Miles) - (West bank) Located on fence on LA 3142 north of railroad overpass.
H-2 (SSE, 1.54 Miles) - (West bank) Located on fence on LA 3142 north of LA 3127/3142 intersection.
8
Annual Radiological 2014 Environmental Operating Report Waterford 3 Steam Electric Station Table 1.1 Radiological Environmental Sampling Program Exposure Requirement Sample Point Description, Sampling and Type and Frequency Pathway Distance and Direction Collection Frequency Of Analyses Direct TLDs Radiation An inner ring of stations, one in each J-2 (S, 1.38 Miles) - (West bank) Located on Quarterly Gamma dose quarterly.
meteorological sector in the general fence south of LA 3127 west of LA 3127/3142 area of the SITE BOUNDARY. intersection.
K-I (SSW, 1.06 Miles) - (West bank) Located on stop sign at entrance to Entergy Education Center on LA 3127.
L-1 (SW, 1.06 Miles) - (West bank) Located on gate on LA 3127 west of LA 3127/3142 intersection.
M-1 (WSW, 0.76 Miles) - (West bank)
Located on south gate of Waterford 1 and 2.
N-1 (W, 0.98 Miles) - (West bank) Located on pole at comer of Railroad Avenue and School House Road.
9
Annual Radiological 2014 Environmental Oeeratina Reoort Waterford 3 Steam Electric Station Table 1.1 Radiological Environmental Sampling Program Exposure Requirement Sample Point Description, Sampling and Type and Frequency Pathway Distance and Direction Collection Frequency Of Analyses Direct TLDs Radiation An inner ring of stations, one in each P-1 (WNW, 0.84 Miles) - (West bank) Located Quarterly Gamma dose quarterly.
meteorological sector in the general on fence enclosing air sample station APP-I.
area of the SITE BOUNDARY.
Q-1 (NW, 0.81 Miles) - (West bank) Located on fence enclosing air sample station APQ-1.
R-1 (NNW, 0.51 Miles) - (West bank) Located at Waterford 1 and 2 Cooling Water Intake Structure.
TLDs An outer ring of stations, 1 in 10 of the A-5 (N, 4.59 Miles) - (East bank) Located on meteorological sectors in the 6 to 8 km pole at intersection of Oswald Avenue and US ranges from the site. 61.
10
Annual Radiological 2014 Environmental ODeratina Report Waterford 3 Steam Electric Station Table 1.1 Radiological Environmental Sampling Program Exposure Requirement Sample Point Description, Sampling and Type and Frequency Pathway Distance and Direction Collection Frequency Of Analyses Direct TLDs Radiation An outer ring of stations, 1 in 10 of the B-4 (NNE, 3.75 Miles) - (East bank) Located Quarterly Gamma dose quarterly.
meteorological sectors in the 6 to 8 km on pole near weigh station on US 61.
ranges from the site.
D-5 (ENE, 4.09 Miles) - (East bank) Located on gate on shell road north of US61/LA48 intersection.
F-4 (ESE, 3.53 Miles) - (West bank) Located on pole behind house at 646 Aquarius St. in Hahnville.
11
Annual Radiological 2014 Environmental Ooeratino Reoort Waterford 3 Steam Electric Station Table 1.1 Radiological Environmental Sampling Program Exposure Requirement Sample Point Description, Sampling and Type and Frequency Pathway Distance and Direction Collection Frequency Of Analyses Direct TLDs Radiation An outer ring of stations, 1 in 10 of the E-5 (E, 4.08 Miles) - (East bank) Located on Quarterly Gamma dose quarterly.
meteorological sectors in the 6 to 8 km fence on Wesco Street off LA 48.
ranges from the site.
G-4 (SE, 3.30 Miles) - (West bank) Located on pole on LA 3160 north of railroad track.
H-8 (SSE, 8.13 Miles) - (West bank) Located on pole in front of Hahnville High School.
P-6 (WNW, 5.58 Miles) - (West bank) Located on fence at LA 640/railroad track intersection.
Q-5 (NW, 5.01 Miles) - (West bank) Located on pole on LA 18 across from Mississippi River marker 137.
12
Annual Radiological 2014 Environmental ODeratina Reoort Waterford 3 Steam Electric Station Table 1.1 Radiological Environmental Sampling Program Exposure Requirement Sample Point Description, Sampling and Type and Frequency Pathway Distance and Direction Collection Frequency Of Analyses Direct TLDs Radiation An outer ring of stations, 1 in 10 of the R-6 (NNW, 5.52 Miles) - (East bank) Located on Quarterly Gamma dose quarterly.
meteorological sectors in the 6 to 8 km fence on LA 3223 near railroad crossing.
ranges from the site.
TLDs The balance of the stations to be in F-9 (ESE, 8.18 Miles) - (East bank) Located on special interest areas such as fence north of railroad tracks on Jonathan Street.
population centers, nearby residences, schools, and in 1 or 2 areas to serve G-8 (SE, 7.74 Miles) - (West bank) Located on as control stations. back fence of Luling Entergy Office.
E-15 (E, 11.7 Miles) - (East bank) Located on fence on Alliance Avenue.
13
Annual Radiological 2014 Environmental Operatinq Report Waterford 3 Steam Electric Station Table 1.1 Radiological Environmental Sampling Program Exposure Requirement Sample Point Description, Sampling and Type and Frequency Pathway Distance and Direction Collection Frequency Of Analyses Direct TLDs Radiation The balance of the stations to be in J-15 (S, 11.7 Miles) - (West bank) Located on pole Quarterly Gamma dose quarterly.
special interest areas such as near LA 631/Hwy 90 intersection in Des Allemands.
population centers, nearby residences, schools, and in 1 or 2 areas to serve E-30 (E, 25.2 Miles) - (West bank) Located at as control stations. entrance to Entergy office on Delaronde St. in Algiers.
(Control)
Waterborne Surface Water One sample upstream SWP-7 (WNW, 7.37 Miles) - (West bank) Located at Composite sample over Gamma isotopic analysis St. John Parish Waterworks in Edgard. (Control) one quarter period, quarterly. Composite for SWF-2 (ESE, 1.51 Miles) - (West bank) Located at tritium analysis quarterly.
One sample downstream Dow Chemical Plant drinking water canal.
SWE-5 (E, 4.59 Miles) - (East bank) Located at St.
Charles Parish Waterworks in New Sarpy.
SWK-1 (SSW, 0.49 Miles) - (West bank) Located at 40 Arpent Canal south of the plant.
14
Annual Radiological 2014 Environmental Operating Report Waterford 3 Steam Electric Station Table 1.1 Radiological Environmental Sampling Program Exposure Requirement Sample Point Description, Sampling and Type and Frequency Pathway Distance and Direction Collection Frequency Of Analyses Waterborne Drinking Water One sample upstream DWP-7 (WNW, 7.37 Miles) - (West bank) Located Composite sample over one 1-131 analysis on each at St. John Parish Waterworks in Edgard. (Control) month period when 1-131 composite when the dose DWF-2 (ESE, 1.51 Miles) - (West bank) Located at analysis is performed, quarterly calculated for the consumption of One sample downstream Dow Chemical Plant drinking water canal. composite otherwise. the water is greater than one DWE-5 (E, 4.59 Miles) - (East bank) Located at St. mrem per year. Composite for Charles Parish Waterworks in New Sarpy. gross beta and gamma isotopic analyses quarterly. Composite for tritium analysis quarterly.
Sediment from Shoreline One sample upstream SHWQ-6 (NW, 5.99 Miles) - (East bank) Located on LA 628 east of Reserve ferry landing. (Control) Annually Gamma annually. isotopic analysis SHWE-3 (E, 2.99 Miles) - (West bank) Located at One sample downstream Foot Ferry landing on LA 18.
SHWK-1 (SSW, 0.49 Miles) - (West bank) Located at 40 Arpent Canal south of plant.
Ingestion Milk Samples from milking animals in the MKE-3 (E, 2.35 Miles) - (West bank) Located at the Quarterly Gamma isotopic and 1-131 three locations within 5 km distance Zeringue's house on LA 18 inTaft.
having the highest dose potential. If analysis quarterly.
there are none, then, one sample from milking animals in each of the three areas between 5 to 8 km distant where doses are calculated to be greater than 1 mrem per year.
15
Annual Radiological 2014 Environmental Operating Report Waterford 3 Steam Electric Station Table 1.1 Radiological Environmental Sampling Program Exposure Requirement Sample Point Description, Sampling and Type and Frequency Pathway Distance and Direction Collection Frequency Of Analyses Ingestion Milk One sample from milking animals at a MKA-31 (N, 31.2 Miles) - (East bank) Located at Quarterly Gamma isotopic and 1-131 control location 15 - 30 km distant and 18736 Sisters Road, Ponchatoula, LA. (Control) analysis quarterly.
in the least prevalent wind direction.
Fish and Invertebrates One sample of each commercially and FH-2 (Distance/Direction Not Applicable) - Sample in season, or Gamma isotopic analysis recreational important species in vicinity Downstream of the plant discharge structure. annually if they are not on edible portion.
of plant discharge area. seasonal FH-3 (Distance/Direction Not Applicable) -
(Westbank) Waterways downstream of plant discharge directed to 40 Arpent Canal.
One sample of same species in area FH-1 (Distance/Direction Not Applicable) -
not influenced by plant discharge. Upstream of the plant intake structure. (Control)
Broadleaf Samples of one to three different kinds BLQ-1 (NW, 0.83 Miles) - (West bank) Located near Quarterly Gamma isotopic and 1-131 of broadleaf vegetation grown nearest air sample station APQ-1. analysis.
each of two different off-site locations of highest predicted annual average BLB-1 (NNE, 0.81 Miles) - (East bank) Located west ground level D/Q if milk sampling is not of Little Gypsy on LA 628.
performed.
One sample of each of the similar BLE-20 (E, 19.7 Miles) - (West bank) Located on broadleaf vegetation grown 15 - 30 km property of Nine Mile Point in Westwego. (Control) distant in the least prevalent wind direction if milk sampling is not performed.
16
Annual Radiological 2014 Environmental Operating Report Waterford 3 Steam Electric Station FIGURE 1-1 17
Annual Radiological 2014 Environmental Operating Report Waterford 3 Steam Electric Station FIGURE 1-2 18
Annual Radiological 2014 Environmental Operating Report Waterford 3 Steam Electric Station FIGURE 1-3 RE MP Samples Within ...
St H010" N 10 to 50OMilesof Waterford-3R East Baton RougeolQ~Q rn/ ~ ,,St Tdlwýny
/ /
i~~;i~St I <.. aft.fe sc 11 I F--
L G
'I. ~+
0Lf~ce 10 .20 Mi le4/K 10 19
Annual Radiological 2014 Environmental Operating Report Waterford 3 Steam Electric Station 2.0 Interpretation and Trends of Results 2.1 Air Particulate and Radioiodine Sample Results Samples of airborne particulate and radioiodine were collected at four indicator locations and one control location and analyzed for gross beta radionuclides, Iodine-1 31 and gamma radionuclides (quarterly air particulate filter composites only). W3 did not detect any gamma radionuclides in the quarterly air particulate composites or Iodine-1 31 in the radioiodine cartridges during the reporting period as has been the case in previous years. Indicator gross beta air particulate results for 2014 were similar to those background levels obtained in previous years of the operational REMP and well below preoperational levels as seen below. Results are reported as 3
annual average pCi/mi Monitoring Period Result Preoperational 0.080 1983-2013 0.020 2014 0.020 Table 3.1, which includes gross beta concentrations for 2014, provides a comparison of the indicator and control means. It further emphasizes that the airborne pathway continues to remain at background levels. In addition, as shown in Attachment 2, the standard "t" test was used to compare average gross beta activity from each indicator station to the average gross beta activity at the control station. The results from this test show the average activity detected at all indicator stations is statistically the same as the average activity detected at the control station. Therefore, W3 concluded that plant operations had no significant impact on this pathway during 2014.
2.2 Thermoluminescent Dosimetry Sample Results The average exposure rates during 2014 are consistent with those from the preoperational program and the previous five years of operation as seen in Figure 2-1. In particular, the preoperational survey indicates that exposure rates ranged between 11 and 33 mrem/standard quarter with an average of 20 mrem/standard quarter. The range during the previous five years of operation was 9 to 16 mrem/standard quarter with an average exposure rate of 12 mrem/standard quarter.
A comparison of the indicator results to the control results, as seen in Table 3.1, shows that the average indicator is slightly higher than that of the control. As shown in Attachment 1, Table 2.1, several indicator locations are higher than the control by a few mrem with a maximum difference of six mrem.
As shown in Attachment 2, Table 2.1, the standard "t" test was used to compare average exposure rates for TLD stations located in groups 0-2 miles and 2-5 miles from the plant to those
> 5 miles. The results indicate that the average exposure rates 0-2 miles from the plant are statistically the same as >5 miles while those 2-5 miles are statistically higher.
The differences between indicator locations and the control, and TLD stations grouped by distance from the plant are expected due to a variety of factors not related to W3 plant operations that can affect background radiation in the vicinity of each TLD station. Direct radiation measurements at each TLD station have remained statistically the same in 2014 as previous years of operation as evidenced on Attachment 2, Table 2.2. In addition, Radiological Gaseous Effluents for 2014 were only a small fraction of the limits and are not expected to have any impact on environmental TLD measurements.
20
Annual Radiological 2014 Environmental Operating Report Waterford 3 Steam Electric Station 2.3 Water Sample Results Analytical results for 2014 drinking/surface water samples were similar to those reported in previous years.
DrinkinqlSurface Water Drinking water samples also serve as surface water samples for W3. Therefore, monthly and quarterly gamma spectroscopy and tritium analyses of drinking water also satisfy the surface water sampling requirement.
Composite drinking/surface water samples were collected from two indicators and one control location and analyzed for Iodine-1 31, gamma radionuclides and tritium. Results indicate that all measurements were below the calculated LLDs.
Although gross beta was detected in the drinking/surface water samples, results for the indicator locations were below preoperational years and slightly above previous operational years as seen below. Results are reported as annual average pCi/I.
Monitoring Period Result Preoperational 7.0 1983-2013 4.7 2014 5.4 Table 3.1, which includes gross beta concentrations for 2014, provides a comparison of the indicator and control means. It shows that the waterborne pathway continues to remain at background levels. In addition, as shown in Attachment 2, the standard "t" test was used to compare average gross beta activity from indicator stations to the average gross beta activity from the control station. The results from the test show the average activity detected at one indicator station is statistically the same as the average activity detected at the control station and one indicator station is statistically higher than the mean for the control location. Results are consistent with historical data stated above. Therefore, W3 concluded that plant operations had no significant impact on this pathway during 2014.
Surface Water Surface water samples were collected from one indicator location and analyzed for gamma radionuclides and tritium. Results indicate that all measurements were below the calculated LLDs. Therefore, W3 concluded that plant operations had no significant impact on this pathway during 2014.
2.4 Sediment Sample Results Sediment samples were collected from two indicator locations and one control location and analyzed for gamma radionuclides. Results indicate that all measurements were below the calculated LLDs. Therefore, W3 concluded that plant operations had no significant impact on this pathway during 2014.
21
Annual Radiological 2014 Environmental Operating Report Waterford 3 Steam Electric Station 2.5 Milk Sample Results Since milk samples for indicator location MKE-3 were unavailable for all quarters of 2014, broad leaf vegetation sampling was performed as required by TRM Table 3.12-1. Broad leaf vegetation results are in section 2.7. Milk samples were collected from one control location and analyzed for Iodine-1 31 and gamma radionuclides. Results indicate that all measurements were below the calculated LLDs. Therefore, W3 concluded that plant operations had no significant impact on this pathway during 2014.
2.6 Fish Sample Results Fish samples were collected from two indicators and one control location and analyzed for gamma radionuclides. Results indicate that all measurements were below the calculated LLDs.
Therefore, W3 concluded that plant operations had no significant impact on this pathway during 2014.
2.7 Broadleaf Vegetation Sample Results Broadleaf vegetation samples were collected from two indicators and one control location and analyzed for Iodine-1 31 and gamma radionuclides. Results indicate that all measurements were below the calculated LLDs. Therefore, W3 concluded that plant operations had no significant impact on this pathway during 2014.
2.8 Land Use Census Results In compliance with the Waterford 3 0DCM and TRM, the land use census was conducted September 22 - September 24, 2014. The nearest residence, garden, beef cow, food product and milk animal in each sector within a five mile radius of the plant was located by visual inspection and verbal inquiry.
Two new garden locations (sectors P and Q) were identified in 2014. Residence, milk cow, and goat locations remained unchanged for 2014. Beef cows located in sector E at a distance of 2.9 miles from the plant have been removed. A soybean field is located in sector N at a distance of 0.6 miles from the plant. Based upon the locations identified in this survey, the locations identified in previous surveys and the locations currently being used to calculate dose commitments from liquid and gaseous effluents released from W3, no REMP sampling location changes are necessary. Results of the 2014 biennial census are shown in Table 2.1.
2.9 Interlaboratory Comparison Results Teledyne Brown Engineering, Inc. analyzed interlaboratory comparison samples for W3 to fulfill the requirements of Section 5.7.2 of the ODCM. Attachment 1 contains these results.
22
Annual Radiological 2014 Environmental Ooerating Report Waterford 3 Steam Electric Station TABLE 2.1 Biennial Land Use Census Results Sector Direction Distance from Plant in Miles Milk Beef Food Residence Garden Cows Cows Goats Products A N 1.3 1.7 A 4.8 A 4.1 B NNE 1.1 1.3 A A A 1.3 C NE 0.9 1.0 A A A A D ENE 0.9 3.2 A A A A E E 2.2 2.2 **2.3 2.3
- 3.2 0.3 F ESE 3.1 2.2 A 2.3 A 0.3 G SE 4.0 4.1 A 2.4 A 0.3 H SSE A A A A A 0.3 J S A A A A A 0.5 K SSW A A A A A 0.5 L SW A A A A A 0.5 M WSW A 1.4 A 1.2 A 0.5 N W 1.0 1.1 A 1.0 A 0.6 P WNW 0.9 0.9 A A A 0.6 Q NW 0.9 0.8 A A A 0.6 R NNW 3.0 3.0 A 4.9 A 2.6 A Indicates that nothing was found in the sector within a five mile radius of Waterford 3
- Animals were located at this distance from Waterford 3, but the milk is not currently used for human consumption
- Samples are being obtained from animals at this location (MKE-3) for REMP 23
Annual Radiological 2014 Environmental ODeratina Reoort Waterford 3 Steam Electric Station FIGURE 2-1 TLD Radiation Dose Comparison By Year 40 40 35 35 J30 30 2Z 20 25 20 I5 15 E
0 E 10 10 5 5 0 0 YEAR 24
Annual Radiological 2014 Environmental Operating Report Waterford 3 Steam Electric Station 3.0 Radiological Environmental Monitoring Program Summary 3.1 2014 Program Results Summary Table 3.1 summarizes the 2014 REMP results. W3 did not use values reported as less than the lower limit of detection (< LLD) when determining ranges and means for indicator and control locations.
25
Annual Radiological 2014 Environmental Operatinq Report Waterford 3 Steam Electric Station TABLE 3.1 Radiological Environmental Monitoring Program Summary Name of Facility: Waterford 3 SES Docket No: 50-382 Location of Facility: St. Charles. Louisiana Reporting Period: January - December 2014 Sample Type Type & Number LLD b Indicator Locations Location with Highest Annual Control Number of (Units) Of Analyses a Mean (F ) c Mean Locations Nonroutine
[Range ] Mean (F) c Results e
[ Range]
Mean (F )C Location d [ Range ]
Airborne Particulates GB 130 0.01 0.020 ( 104 / 104) APF-1 0.021 ( 26 / 26) 0.020 ( 26 / 26) 0 (pCi/m 3 ) [0.008-0.042] (ESE, 0.35 mi.) [0.013- 0.0311 [0.011 -0.030]
GS 20 Cs-1 34 0.05 <LLD N/A N/A <LLD 0 Cs-1 37 0.06 <LLD N/A N/A <LLD 0 Airborne Iodine 1-131 130 0.07 <LLD N/A N/A <LLD 0
( pCi/m3)
Indicator TLDs Gamma 120 (f) 12(116/120) L-1 14(4/4) N/A 0 (mrem/Std. Qtr) [8.9-15.0] (SW, 1.06 mi.) [14.2-14.6]
Control TLDs Gamma 4 (f) N/A N/A N/A 10(4/4) 0 (mrem/Std. Qtr) [9.3 - 10.2]
26
Annual Radiological 2014 Environmental Operatinq Report Waterford 3 Steam Electric Station TABLE 3.1 Radiological Environmental Monitoring Program Summary Name of Facility: Waterford 3 SES Docket No: 50-382 Location of Facility: St. Charles, Louisiana Reporting Period: January - December 2014 Sample Type Type & Number LLD b Indicator Location Location with Highest Annual Mean Control Number of (Units) of Analyses a Mean ( F ) c Locations Nonroutine
[Range] Mean (F) c Results e
[ Range ]
Mean ( F ) c Location d [ Range ]
Surface Water & Gross Beta 12 4 5.4(8/8) DWF/SWF-2 5.6(4/4) 4.4(4/4) 0 Drinking Water [4.1 - 6.9] (ESE, 1.51 mi.) [4.5 - 6.9] [3.5 - 4.8]
( pCi~ll) 1-131 40 1 <LLD N/A N/A <LLD 0 H-3 12 2000 <LLD N/A N/A <LLD 0 GS 12 Mn-54 15 <LLD N/A N/A <LLD 0 Fe-59 30 <LLD N/A N/A <LLD 0 Co-58 15 <LLD N/A N/A <LLD 0 Co-60 15 <LLD N/A N/A <LLD 0 Zn-65 30 <LLD N/A N/A <LLD 0 Zr-95 15 <LLD N/A N/A <LLD 0 Nb-95 15 <LLD N/A N/A <LLD 0 Cs-134 15 <LLD N/A N/A <LLD 0 Cs-137 18 <LLD N/A N/A <LLD 0 Ba-140 15 <LLD N/A N/A <LLD 0 La-1 40 15 <LLD N/A N/A <LLD 0 27
Annual Radiological 2014 Environmental Operatinq Report Waterford 3 Steam Electric Station TABLE 3.1 Radiological Environmental Monitoring Program Summary Name of Facility: Waterford 3 SES Docket No: 50-382 Location of Facility: St. Charles, Louisiana Reporting Period: January - December 2014 Sample Type Type & LLD b Indicator Locations Location with Highest Annual Mean Control Locations Number of (Units) Number Mean (F) c Mean (F) c Nonroutine of Analyses a [Range] [Range] Results e Mean (F ) c Location d [Range]
Surface Water H-3 4 3000 <LLD N/A N/A N/A 0 (pCi/I)
GS 13 Mn-54 15 <LLD N/A N/A N/A 0 Fe-59 30 <LLD N/A N/A N/A 0 Co-58 15 <LLD N/A N/A N/A 0 Co-60 15 <LLD N/A N/A N/A 0 Zn-65 30 <LLD N/A N/A N/A 0 Zr-95 15 <LLD N/A N/A N/A 0 Nb-95 15 <LLD N/A N/A N/A 0 Cs-1 34 15 <LLD N/A N/A N/A 0 Cs-1 37 18 <LLD N/A N/A N/A 0 Ba-1 40 15 <LLD N/A N/A N/A 0 La-140 15 <LLD N/A N/A N/A 0 1-131 15 <LLD N/A N/A N/A 0 Shoreline GS 3 Sediment Cs-134 150 <LLD N/A N/A <LLD 0 (pCi/kg dry)
Cs-1 37 180 <LLD N/A N/A <LLD 0 28
Annual Radiological 2014 Environmental Operatinq Report Waterford 3 Steam Electric Station TABLE 3.1 Radiological Environmental Monitoring Program Summary Name of Facility: Waterford 3 SES Docket No: 50-382 Location of Facility: St. Charles. Louisiana Reporting Period: January - December 2014 Sample Type Type & Number LLD b Indicator Location Location with Highest Annual Mean Control Number of (Units) of Analyses a Mean (F ) C Locations Nonroutine
[Range] Mean (F) C Results e
[Range]
Mean ( F ) c Location d [Range ]
Milk 1-131 4 1 < LLD N/A N/A <LLD 0 (pCi/I)
GS 4 Cs-1 34 15 < LLD N/A N/A <LLD 0 Cs-1 37 18 < LLD N/A N/A <LLD 0 Ba-140 15 < LLD N/A N/A <LLD La-140 15 < LLD N/A N/A <LLD 0 0
Fish GS 13 (pCi/kg wet) Mn-54 130 <LLD N/A N/A <LLD 0 Fe-59 260 <LLD N/A N/A <LLD 0 Co-58 130 <LLD N/A N/A <LLD 0 Co-60 130 <LLD N/A N/A <LLD 0 Zn-65 260 <LLD N/A N/A <LLD 0 Cs-1 34 130 <LLD N/A N/A <LLD 0 Cs-1 37 150 <LLD N/A N/A <LLD 0 Broadleaf Vegetation 1-131 12 60 <LLD N/A N/A <LLD 0 (pCi/kg wet)
GS 12 Cs-1 34 60 <LLD N/A N/A <LLD 0 Cs-1 37 80 <LLD N/A N/A <LLD 0 a GB = Gross beta; 1-131 = Iodine-131; H-3 = Tritium; GS = Gamma scan.
b LLD = required lower limit of detection based on Waterford 3 TRM.
c Mean and range based upon detectable measurements only. Fraction of detectable measurements at specified locations is indicated in parenthesis (F).
d Locations are specified (1) by name and (2) degrees relative to reactor site.
e Non-routine results are those which exceed ten times the control station value. If no control station value is available, the result is considered non-routine if it exceeds ten times the preoperational value for the location.
f LLD is not defined in Waterford 3 TRM.
29
Annual Radiological 2014 Environmental Operating
- =
Report Waterford 3 Steam Electric Station Attachment 1 2014 Radiological Monitoring Report Summary of Monitoring Results 30
Annual Radiological 2014 Environmental Operating Report Waterford 3 Steam Electric Station TABLE OF CONTENTS TABLE 1.1 AIR PARTICULATE FILTER 32 TABLE 1.2 RADIOIODINE CARTRIDGE 33 TABLE 1.3 AIR PARTICULATE FILTER 34 TABLE 2.1 THERMOLUMINESCENT DOSIMETERS 35 TABLE 3.1 DRINKING/SURFACE WATER 36 TABLE 3.2 DRINKING/SURFACE WATER 37 TABLE 3.3 DRINKING/SURFACE WATER 38 TABLE 3.4 DRINKING/SURFACE WATER 39 TABLE 3.5 SURFACE WATER 40 TABLE 4.1 SEDIMENT 41 TABLE 5.1 MILK 42 TABLE 6.1 FISH 43 TABLE 7.1 BROADLEAF VEGETATION 44 TABLE 8.1 INTERLABORATORY COMPARISON 45 31
Annual Radiological 2014 Environmental Operating Report Waterford 3 Steam Electric Station Table 1.1 Sample Type: Air Particulate Filter Analysis: Gross Beta Units: pCi/m 3 End Date APF-1 APQ-1 APP-1 APC-1 APE-30 (Indicator) (Indicator) (Indicator) (Indicator) (Control)
Required LLD 0.01 0.01 0.01 0.01 0.01 01-06-14 0.025 0.024 0.027 0.029 0.028 01-20-14 0.013 0.013 0.013 0.015 0.016 02-03-14 0.022 0.020 0.022 0.021 0.022 02-17-14 0.020 0.021 0.021 0.019 0.021 03-03-14 0.021 0.021 0.016 0.020 0.018 03-17-14 0.015 0.016 0.015 0.015 0.015 03-31-14 0.017 0.021 0.015 0.021 0.023 04-14-14 0.018 0.016 0.017 0.016 0.018 04-28-14 0.019 0.021 0.018 0.017 0.020 05-12-14(l) 0.023 0.029 0.022 0.023 0.024 05-25-14 0.029 0.022 0.021 0.025 0.022 06-09-14 0.013 0.013 0.013 0.012 0.011 06-23-14 0.022 0.017 0.016 0.018 0.020 07-08-14 0.018 0.016 0.017 0.010 0.019 07-21-14 0.016 0.018 0.019 0.016 0.018 08-04-14 0.023 0.021 0.023 0.024 0.023 08-18-14 0.019 0.019 0.020 0.021 0.024 09-02-14 0.031 0.023 0.016 0.018 0.016 09-15-14 0.014 0.015 0.010 0.008 0.013 09-29-14 0.017 0.015 0.018 0.016 0.020 10-13-14 0.019 0.015 0.019 0.019 0.017 10-27-14 0.024 0.023 0.024 0.022 0.022 11-11-14 0.025 0.021 0.022 0.019 0.024 11-24-14 0.029 0.028 0.022 0.020 0.024 12-08-14 0.021 0.019 0.017 0.020 0.019 12-22-14 0.030 0.029 0.029 0.042 0.030 (1) Low volume due to sample pump running at low capacity 32
Annual Radiological 2014 Environmental Operatinq Report Waterford 3 Steam Electric Station Table 1.2 Sample Type: Radiolodine Cartridge Analysis: Iodine-131 Units: pCi/m3 End Date APF-I APQ-1 APP-1 APC-1 APE-30 (Indicator) (Indicator) (Indicator) (Indicator) (Control)
Required LLD -00. 0.07 0.07 0.07 0.07 0.07 01-06-14 < 0.027 < 0.026 < 0.010 < 0.025 < 0.025 01-20-14 < 0.036 < 0.034 < 0.033 < 0.034 < 0.019 02-03-14 < 0.029 < 0.028 < 0.027 < 0.011 < 0.028 02-17-14 < 0.037 < 0.035 < 0.034 < 0.036 < 0.019 03-03-14 < 0.025 < 0.024 < 0.023 < 0.024 < 0.010 03-17-14 < 0.042 < 0.039 < 0.038 < 0.039 < 0.021 03-31-14 < 0.011 < 0.027 < 0.026 < 0.027 < 0.027 04-14-14 < 0.040 < 0.038 < 0.036 < 0.038 < 0.020 04-28-14 < 0.025 < 0.009 < 0.023 < 0.024 < 0.024 05-12-14(")
< 0.028 < 0.032 < 0.025 < 0.027 < 0.026 05-25-14 < 0.033 < 0.030 < 0.030 < 0.031 < 0.013 06-09-14 < 0.023 < 0.021 < 0.009 < 0.022 < 0.022 06-23-14 < 0.029 < 0.026 < 0.026 < 0.028 < 0.011 07-08-14 < 0.028 < 0.026 < 0.026 < 0.010 < 0.022 07-21-14 < 0.037 < 0.033 < 0.033 < 0.037 < 0.019 08-04-14 < 0.009 < 0.021 < 0.021 < 0.022 < 0.009 08-18-14 < 0.034 < 0.033 < 0.033 < 0.034 < 0.018 09-02-14 < 0.019 < 0.032 < 0.033 < 0.033 < 0.034 09-15-14 < 0.034 < 0.012 < 0.032 < 0.032 < 0.032 09-29-14 < 0.011 < 0.010 < 0.010 < 0.010 < 0.004 10-13-14 < 0.026 < 0.024 < 0.013 < 0.025 < 0.024 10-27-14 < 0.044 < 0.040 < 0.042 < 0.042 < 0.023 11-11-14 < 0.015 < 0.035 < 0.037 < 0.037 < 0.037 11-24-14 < 0.026 < 0.044 < 0.045 < 0.033 < 0.046 12-08-14 < 0.043 < 0.039 < 0.040 < 0.018 < 0.041 12-22-14 < 0.027 < 0.024 < 0.025 < 0.030 < 0.014 (1) Low volume due to sample pump running at low capacity 33
Annual Radiological 2014 Environmental Operatinq Report Waterford 3 Steam Electric Station Table 1.3 Sample Type: Air Particulate Filter Analysis: Gamma Isotopic Units: pCi/mi Location Quarterly Cs-1 34 Cs-1 37 Composite Required LLD - 0.05 0.06 APF-1 (Indicator) 1st < 0.002 < 0.003 APQ-1 (Indicator) 1st < 0.002 < 0.001 APP-1 (Indicator) 1st < 0.002 < 0.002 APC-1 (Indicator) 1st < 0.003 < 0.002 APE-30 (Control) 1st < 0.003 < 0.003 APF-1 (Indicator) 2nd < 0.003 < 0.003 APQ-1 (Indicator) 2nd < 0.004 < 0.005 APP-1 (Indicator) 2nd < 0.004 < 0.004 APC-1 (Indicator) 2nd < 0.004 < 0.004 APE-30 (Control) 2nd < 0.002 < 0.002 APF-1 (Indicator) 3rd < 0.003 < 0.003 APQ-1 (Indicator) 3rd < 0.003 < 0.002 APP-1 (Indicator) 3rd < 0.003 < 0.002 APC-1 (Indicator) 3rd < 0.002 < 0.002 APE-30 (Control) 3rd < 0.002 < 0.002 APF-1 (Indicator) 4th < 0.003 < 0.003 APQ-1 (Indicator) 4th < 0.004 < 0.003 APP-1 (Indicator) 4th < 0.003 < 0.003 APC-1 (Indicator) 4th < 0.005 < 0 .004 APE-30 (Control) 4th < 0.003 < 0. 003 34
Annual Radiological 2014 Environmental Operatincl Report Waterford 3 Steam Electric Station Table 2.1 Sample Type: Thermoluminescent Dosimeters Analysis: Gamma Dose Units: mrem/Std. Qtr.
Indicator Locations Station 1st Qtr '14 2nd Qtr '14 3rd Qtr '14 4th Qtr '14 Annual Mean '14 A-2 13 12 13 13 13 A-5 12 11 13 12 12 B-1 13 12 14 13 13 B-4 14 13 14 14 13 C-1 9 9 10 9 9 D-2 12 13 13 13 13 D-5 11 11 12 12 12 E-1 11 11 11 12 11 E-5 12 12 13 13 12 E-1 5 10 10 10 11 10 F-2 11 12 12 13 12 F-4 14 14 14 15 14 F-9 12 12 13 13 13 G-2 11 12 11 11 11 G-4 (2) 12 11 11 11 G-8 11 11 12 11 11 H-2 13 11 12 11 12 H-8 13 14 13 13 13 J-2 11 (2) 11 11 11 J-1 5 13 13 13 13 13 K-1 11 11 11 11 11 (1)L-1 14 14 15 14 14 M-1 10 10 10 10 10 N-1 (2) (2) 14 14 14 P-1 10 10 10 10 10 P-6 13 13 14 13 13 Q-1 13 13 13 12 13 Q-5 13 13 15 13 13 R-1 10 10 10 10 10 R-6 10 10 10 10 10 Control Location Station 1 st Qtr '14 2nd Qtr '14 3rd Qtr '14 4th Qtr '14 Annual Mean '14 E-30 10 9 10 10 10 (1) Location with highest annual mean (2) No data - TLDs missing at time of exchange 35
Annual Radiological 2014 Environmental ODeratina ReDort Waterford 3 Steam Electric Station Table 3.1 Sample Type: Drinking/Surface Water Analysis: Gross Beta Units: pCi/I Quarterly DWF/SWF-2 DWE/SWE-5 DWP/SWP-7 Composite (Indicator) (Indicator) (Control)
Required LLD 4 4 4 1st. 6.92 6.03 4.81 2na 5.61 5.09 4.71 3 rd 4.45 4.07 3.48 4 th 5.55 5.36 4.49 36
Annual Radiological 2014 Environmental Operating Report Waterford 3 Steam Electric Station Table 3.2 Sample Type: Drinking/Surface Water Analysis: Iodine-131 Units: pCi/I Collection SWK-1 DWF/SWF-2 DWE/SWE-5 DWP/SWP-7 Date (Indicator) (Indicator) (Indicator) (Control)
LLD 15 I I I 01-27_14(l) < 0.50 01-27-14 < 5.55 < 0.44 < 0.40 < 0.43 02-25-14 < 2.70 < 0.57 < 0.69 < 0.61 03-25-14 < 3.62 < 0.58 < 0.74 < 0.64 04-23-14 < 4.35 < 0.63 < 0.62 < 0.61 05-20-14 < 4.36 < 0.67 < 0.66 < 0.65 06-17-14 < 3.28 < 0.72 < 0.71 < 0.72 07-15-14 < 3.88 < 0.69 < 0.70 < 0.62 08-12-14 < 3.59 < 0.50 < 0.45 < 0.63 09-10-14 < 2.59 < 0.84 < 0.90 < 0.76 10-07-14 < 5.59 < 0.63 < 0.53 < 0.65 11-04-14 < 3.37 < 0.07 < 0.80 < 0.59 12-02-14 < 5.54 <0.16 < 0.24 <0.18 12-30-14 < 4.23 < 0.65 < 0.59 < 0.61 (1)Duplicate sample 37
Annual Radiological 2014 Environmental Operating
, =
Report Waterford 3 Steam Electric Station Table 3.3 Sample Type: Drinking/Surface Water Analysis: Gamma Isotopic Units: pCi/I Location Collection Mn-54 Co-58 Fe-59 Co-60 Zn-65 Nb-95 Zr-95 Cs-134 Cs-137 Ba-140 La-140 Date Required LLD
- 15 15 30 15 30 15 15 15 18 15 15 DWFISWF-2 (Indicator) 1st < 2.36 < 2.22 <4.63 < 2.22 < 4.56 < 2.31 < 4.03 < 2.31 < 2.53 < 9.09 < 2.69 DWE/SWE-5 (Indicator) 1st < 2.52 < 2.41 < 4.74 < 2.55 < 5.54 < 2.46 < 4.36 < 2.41 < 2.74 < 9.26 < 2.64 DWPISWP-7 (Control) 1st < 2.81 < 2.53 < 5.57 < 2.85 < 4.86 < 2.58 < 4.58 < 2.75 < 2.89 < 11.40 < 3.02 DWF/SWF-2 (Indicator) 2nd < 2.72 < 2.75 < 5.79 < 2.59 < 4.94 < 2.89 < 5.11 < 2.55 < 2.85 < 14.11 < 4.28 DWE/SWE-5 (Indicator) 2nd < 2.36 < 2.28 < 4.63 < 2.52 < 5.40 < 2.29 < 5.18 < 2.76 < 3.39 < 14.10 < 5.36 DWPISWP-7 (Control) 2nd < 2.47 < 2.79 < 5.81 < 3.01 < 4.84 < 3.05 < 5.22 < 2.65 < 3.18 < 13.10 < 3.96 DWF/SWF-2 (Indicator) 3rd < 2.14 < 2.03 < 3.51 < 2.62 < 4.20 < 2.29 < 4.24 < 1.82 < 2.46 < 12.00 < 3.86 DWE/SWE-5 (Indicator) 3rd < 1.90 < 2.49 < 4.45 < 2.10 < 3.68 < 1.87 < 4.45 < 1.74 < 1.65 < 11.30 < 4.05 DWP/SWP-7 (Control) 3rd < 2.65 < 2.39 < 4.80 < 2.67 < 4.89 < 2.49 < 4.52 < 2.19 < 2.53 < 14.40 < 4.56 DWF/SWF-2 (Indicator) 4th < 1.76 < 2.00 < 4.22 < 1.83 < 3.70 < 2.04 < 3.23 < 1.68 < 1.84 < 12.50 < 3.97 DWE/SWE-5 (Indicator) 4th < 1.98 < 1.91 < 4.50 < 1.97 < 3.98 < 2.12 < 3.51 < 1.66 < 2.00 < 12.90 < 4.09 DWPISWP-7 (Control) 4th < 1.73 <2.04 < 4.87 < 1.96 < 3.96 < 1.97 < 3.55 < 1.79 < 2.00 < 13.70 < 4.54 38
Annual Radiological 2014 Environmental ODeratina ReDort Waterford 3 Steam Electric Station Table 3.4 Sample Type: Drinkinl/Surface Water Analysis: Tritium Units: pCi/I Quarter DWF/SWF-2 DWEISWE-5 SWK-1 DWP/SWP-7 (Indicator) (Indicator) (Indicator) (Control)
Required LLD - 2000 2000 3000 2000 1st < 588 < 592 < 593 < 599 2nd < 620 < 628 < 616 < 619 3 rd < 583 < 581 < 579 < 576 4 th < 547 < 519 < 546 < 546 39
Annual Radiological 2014 Environmental ODeratina Report Waterford 3 Steam Electric Station Table 3.5 Sample Type: Surface Water Analysis: Gamma Isotopic Units: pCi/I Location Collection Mn-54 Co-58 Fe-59 Co-60 Zn-65 Nb-95 Zr-95 Cs-134 Cs-137 Ba-140 La-140 Date Required LLD
- 15 15 30 15 30 15 15 15 18 15 15 SWK-1 01-27-14 < 2.78 < 2.91 < 5.57 < 2.67 < 5.13 < 2.86 < 4.93 < 2.80 < 2.99 < 14.80 < 4.01 (Indicator) 02-25-14 < 2.13 < 2.05 < 4.72 < 1.83 < 4.17 < 2.26 < 3.99 < 2.12 < 2.41 < 8.90 < 2.18 03-25-14 < 2.70 < 2.82 < 5.55 < 2.68 < 5.22 < 2.57 < 4.52 < 2.60 < 2.84 < 10.30 < 3.96 04-23-14 < 2.19 < 2.54 < 5.49 < 2.96 < 5.43 < 2.60 < 4.37 < 2.37 < 2.42 < 12.90 < 3.85 05-20-14 < 3.56 < 2.95 < 6.77 < 3.53 < 6.16 < 3.48 < 6.31 < 3.35 < 3.33 < 14.70 < 4.03 06-17-14 < 1.83 < 1.76 < 3.72 < 1.83 < 3.67 < 1.82 < 3.22 < 1.66 < 1.91 < 8.97 < 2.78 07-15-14 <2.50 <2.63 <5.14 <2.99 <5.11 <2.50 <3.99 <2.63 <2.74 <10.90 <4.16 08-12-14 < 1.74 < 1.88 < 3.97 < 1.95 < 3.92 < 1.83 < 3.25 < 1.85 < 1.93 < 9.60 < 3.11 09-09-14 < 1.52 < 1.52 < 3.01 < 1.52 < 2.91 < 1.70 < 2.69 < 1.47 < 1.56 < 6.98 < 2.18 10-07-14 < 2.61 < 2.58 < 5.66 < 2.78 < 4.71 < 2.97 < 4.58 < 2.66 < 2.80 < 14.00 < 4.18 11-04-14 < 1.49 < 1.67 < 3.30 < 1.81 < 3.98 < 1.84 < 3.04 < 1.53 < 1.44 < 8.94 < 1.47 12-02-14 < 2.94 < 2.91 < 5.80 < 2.93 < 5.74 < 3.38 < 5.58 < 2.86 < 3.39 < 14.60 < 4.87 12-30-14 < 3.85 < 3.60 < 7.28 < 3.55 < 7.27 < 3.88 < 6.53 < 3.66 < 4.04 < 14.30 < 4.08 40
Annual Radiological 2014 Environmental Operatincl Report Waterford 3 Steam Electric Station Table 4.1 Sample Type: Sediment Analysis: Gamma Isotopic Units: pCi/kg (dry)
Location Collection Cs-134 Cs-1 37 Date Required LLD 150 180 SHWK-1 (Indicator) 03-17-14 < 39.0 < 50.0 SHWE-3 (Indicator) 03-17-14 < 73.7 < 84.4 SHWQ-6 (Control) 03-17-14 < 23.8 < 49.4 41
Annual Radiological 2014 Environmental Operatincl Report Waterford 3 Steam Electric Station Table 5.1 Sample Type: Milk Analysis: Iodine-131 and Gamma Isotopic Units: pCi/I Location Collection 1-131 Cs-134 Cs-137 Ba-140 La-140 Date Required LLD-* I is 18 15 is MKE-3 (Indicator) (1)03-13-14 n/a n/a n/a n/a n/a (1)06_12_14 n/a n/a n/a n/a n/a (1)09-11-14 n/a n/a n/a n/a n/a (1)12-10-14 n/a n/a n/a n/a n/a MKA-31 (Control) 03-13-14 < 0.49 <3.10 4.27 < 14.60 <4.19 06-12-14 < 0.75 < 0.22 3.51 < 14.20 < 2.21 09-11-14 < 0.65 < 2.28 3.18 < 13.20 < 3.26 12-10-14 < 0.31 <2.13 3.26 < 12.50 < 3.09 (1)Sample not available. Cows not producing enough milk. See page 2 for details.
42
Annual Radiological 2014 Environmental Ooeratina Report Waterford 3 Steam Electric Station Table 6.1 Sample Type: Fish Analysis: Gamma Isotopic Units: pCi/kg (wet)
Location Collection Species Mn-54 Co-58 Fe-59 Co-60 Zn-65 Cs-134 Cs-137 Date Required LLD 130 130 260 130 260 130 150 FH-1 (Control) 11-05-14 Buffalo < 64.4 < 44.8 < 133.0 < 67.4 < 125.0 < 52.6 < 54.7 11-05-14 Carp <60.5 <70.9 <149.0 <61.3 <133.0 <48.1 <61.7 11-05-14 Catfish < 71.3 < 73.2 < 152.0 < 80.9 < 140.0 < 73.2 < 75.4 11-05-14 Drum <70.5 <98.2 <181.0 <76.5 <173.0 <94.6 <91.0 FH-2 (Indicator) 11-05-14 Buffalo < 54.8 < 61.3 <90.7 < 53.6 < 126.0 < 65.0 < 63.8 11-05-14 Carp <60.7 <78.0 <103.0 <53.2 <118.0 <66.1 <68.5 11-05-14 Catfish < 64.4 < 63.6 < 133.0 < 67.1 < 141.0 < 87.3 < 84.2 11-05-14 Drum <68.9 <78.9 <151.0 <63.5 <98.4 <60.9 <58.9 FH-3 (Indicator) 10-31-14 Buffalo < 78.0 < 76.7 < 180.0 < 73.0 < 215.0 < 84.0 < 82.5 10-31-14 Carp < 64.3 <69.4 < 120.0 < 79.3 < 153.0 <61.2 < 72.9 10-31-14 Catfish < 60.9 < 50.7 < 135.0 < 52.2 < 93.6 <49.1 < 62.8 10-31-14 Mullet < 48.2 < 61.0 < 104.0 < 64.2 < 124.0 < 56.1 <48.6 11-04-14 Mullet <66.8 <63.4 <164.0 <74.7 <159.0 <74.5 <76.1 43
Annual Radiological 2014 Environmental Operatinq Report Waterford 3 Steam Electric Station Table 7.1 Sample Type: Broad Leaf Vegetation Analysis: Iodine-131 and Gamma Isotopic Units: pCi/kg (wet) .
Location Collection 1-131 Cs-1 34 Cs-1 37 Date Required LLD 60 60 80 BLQ-1 (Indicator) 03-12-14 < 25.7 < 16.6 < 17.1 BLQ-1 (Indicator) 06-11-14 < 33.9 < 19.7 < 21.0 BLQ-1 (Indicator) 09-10-14 < 34.9 < 21.8 < 19.5 BLQ-1 (Indicator) 12-15-14 < 31.3 < 25.5 < 33.5 BLB-1 (Indicator) 03-12-14 < 32.2 < 18.1 < 27.4 BLB-1 (Indicator) 06-11-14 < 32.7 < 17.9 < 21.7 BLB-1 (Indicator) 09-10-14 < 34.1 < 19.2 < 22.7 BLB-1 (Indicator) 12-15-14 < 26.5 < 19.7 < 20.9 BLE-20 (Control) 03-12-14 < 36.1 < 23.9 < 25.2 BLE-20 (Control) 06-11-14 < 33.6 < 21.5 < 22.5 BLE-20 (Control) 09-10-14 < 41.0 < 26.0 < 24.7 BLE-20 (Control) 12-15-14 < 31.0 < 24.3 < 26.2 44
Annual Radiological 2014 Environmental Operating Report Waterford 3 Steam Electric Station Table 8.1 Sample Type: Interlaboratory Comparison Analysis: Gross Beta, Iodine-131, Tritium and Gamma Isotopic Units: pCi/kg (wet)
ANALYTICS ENVIRONMENTAL RADIOACTIVITY CROSS CHECK PROGRAM TELEDYNE BROWN ENGINEERING ENVIRONMENTAL SERVICES Month/Year ID Number Matrix Nuclide Units Reported Known Ratio (c) Evaluation Value (a) Value (b) TBE/Analytics (d)
March 2014 E10854 Milk 1-131 pCi/L 96.6 98.5 0.98 A Ce-141 pCi/L 112 119 0.94 A Cr-51 pCi/L 449 491 0.91 A Cs-134 pCi/L 186 210 0.89 A Cs-i 37 pCi/L 250 253 0.99 A I Co-58 pCi/L 248 268 0.93 A Mn-54 pCi/L 292 297 0.98 A Fe-59 pCi/L 230 219 1.05 A Zn-65 pCi/L 312 323 0.97 A Co-60 pCi/L 321 337 0.95 A E10857 AP Ce-141 pCi 53.0 53.9 0.98 A Cr-51 pCi 232 223 1.04 A Cs-i34 pCi 100 95.3 1.05 A Cs-137 pCi 122 115 1.06 A Co-58 pCi 122 121 1.01 A Mn-54 pCi 135 135 1.00 A Fe-59 pCi 111 99.3 1.12 A Zn-65 pCi 140 147 0.95 A Co-60 pCi 187 153 1.22 W E10856 Charcoal 1-131 Pci 74.1 76.4 0.97 A June 2014 E 10914 Milk 1-131 pCi/L 86.5 90.9 0.95 A Ce-141 pCi/L 111 124 0.90 A Cr-51 pCi/L 255 253 1.01 A Cs-134 pCi/L 147 162 0.91 A Cs-137 pCi/L 123 120 1.03 A Co-58 pCi/L 105 112 0.94 A I Mn-54 pCi/L 155 156 0.99 A Fe-59 pCi/L 106 102 1.04 A Zn-65 pCi/L 251 252 1.00 A Co-60 pCi/L 218 224 0.97 A E10916 AP Ce-141 pCi 95.1 92.6 1.03 A Cr-51 pCi 215 190 1.13 A Cs-134 pCi 122 122 1.00 A Cs-137 pCi 95.1 89.8 1.06 A Co-58 pCi 88.7 84.1 1.05 A Mn-54 pCi 115 116 0.99 A Fe-59 pCi 72.6 76.7 0.95 A Zn-65 PCi 193 189 1.02 A Co-60 pCi 179 168 1.07 A E10915 Charcoal 1-131 pCi 85.6 85.2 1.00 A E10947 Milk 1-131 pCi/L 92.0 97.6 0.94 A Ce-141 pCi/L 117 126 0.93 A Cr-51 pCi/L 281 288 0.98 A Cs-134 pCi/L 141 158 0.89 A Cs-137 pCi/L 186 193 0.96 A Co-58 pCi/L 137 143 0.96 A Mn-54 pCi/L 138 142 0.97 A Fe-59 pCi/L 162 158 1.03 A Zn-65 pCi/L 75.2 73.0 1.03 A Co-60 pCi/L 286 297 0.96 A 45
Annual Radiological 2014 Environmental Operating Report Waterford 3 Steam Electric Station Table 8.1 Sample Type: Interlaboratory Comparison Analysis: Gross Beta, Iodine-131, Tritium and Gamma Isotopic Units: pCi/kg (wet)
Month/Year ID Number Matrix Nuclide Units Reported Known Ratio (c) Evaluation Value (a) Value (b) TBE/Analytics (d)
September E10949 AP Ce-141 pCi 97.8 82.1 1.19 A 2014 Cr-51 pCi 212 188 1.13 A Cs-134 pCi 106 103 1.03 A Cs-137 pCi 131 126 1.04 A I Co-58 pCi 85.7 93.0 0.92 A Mn-54 pCi 92.8 92.8 1.01 A Fe-59 pCi 113 103 1.10 A Zn-65 pCi 53.2 47.5 1.12 A Co-60 pCi 202 193 1.05 A E10948 Charcoal 1-131 pCi 83.9 89.8 0.93 A E10951 Soil Ce-141 pCi/g 0.208 0.186 1.12 A Cr-51 pCi/g 0.398 0.425 0.94 A Cs-134 pCi/g 0.216 0.233 0.93 A Cs-137 pCi/g 0.398 0.365 1.09 A Co-58 pCi/g 0.197 0.211 0.93 A Mn-54 pCi/g 0.242 0.209 1.16 A Fe-59 pCi/g 0.238 0.233 1.02 A Zn-65 pCi/g 0.117 0.108 1.08 A Co-60 pCi/g 0.447 0.438 1.02 A December 2014 El1079 Milk 1-131 pCi/L 85.9 95.1 0.90 A Ce-141 pCi/L 205 219 0.94 A Cr-51 pCi/L 402 406 0.99 A Cs-134 pCi/L 156 164 0.95 A Cs-137 pCi/L 194 198 0.98 A Co-58 pCi/L 122 130 0.94 A Mn-54 pCi/L 220 225 0.98 A Fe-59 pCi/L 183 175 1.05 A Zn-65 pCi/L 287 297 0.97 A Co-60 pCi/L 224 235 0.95 A E11081 AP Ce-141 pCi 96.4 102 0.95 A Cr-51 pCi 171 190 0.90 A Cs-134 pCi 73.1 76.9 0.95 A Cs-137 pCi 99.0 92.6 1.07 A Co-58 PC! 57.5 60.8 0.95 A Mn-54 pCi 107 105 1.02 A Fe-59 pCi 74.2 81.6 0.91 A Zn-65 pCi 144 139 1.04 A Co-60 pCi 114 110 1.04 A E11080 Charcoal 1-131 pCi 93.5 98.2 0.95 A (a) Teledyne Brown Engineeringreportedresult.
(b) The Analytics known value is equal to 100% of the parameterpresent in the standardas determined by gravimetricand/or volumetric measurements made during standardpreparation.
(c) Ratio of Teledyne Brown Engineeringto Analytics results.
(d) Analytics evaluation based on TBE internal QC limits: A= Acceptable, reportedresult falls within ratio limits of 0.80-1.20. W-Acceptable with warning, reported result falls within 0. 70-0.80 or 1.20-1.30. N = Not Acceptable, reported results falls outside the ratio limits of <0. 70 and > 1.30.
46
Annual Radiological 2014 Environmental Operating Report Waterford 3 Steam Electric Station Table 8.1 Sample Type: Interlaboratory Comparison Analysis: Gross Beta, Iodine-131, Tritium and Gamma Isotopic Units: pCi/kg (wet)
DOE's MIXED ANALYTE PERFORMANCE EVALUATION PROGRAM (MAPEP)
TELEDYNE BROWN ENGINEERING ENVIRONMENTAL SERVICES Month/Year ID Matrix Nuclide Units Reported Known Acceptance Evaluation Number Value (a) Value (b) Range (c)
March 2014 14- Water H-3 Bq/L NR 321 225-417 N (1)
MAW30 Cs-134 Bq/L 20.7 23.1 16.2 - 30.0 A Cs-137 Bq/L 28.0 28.9 20.2 -37.6 A Co-57 Bq/L 26.5 27.5 19.3- 35.8 A Co-60 Bq/L 15.6 16.0 11.2-20.8 A Mn-54 Bq/L 13.5 13.9 9.7-18.1 A K-40 Bq/L NR False positive test N (2)
Zn-65 Bq/L -0.201 False positive test A 14-MaS30 Soil Cs-134 Bq/kg 2.02 False positive test A Cs-137 Bq/kg 1300 1238 867-1609 A Co-57 Bg/kg 1069 966 676- 1256 A Co-60 Bq/kg 1.32 1.22 Sensitivity A Mn-54 Bq/kg 1510 1430 1001 - 1859 A K-40 Bq/kg 669 622 435 - 809 A Zn-65 Bq/kg 763 695 487 - 904 A 14-RdF30 AP Cs-134 Bq/sample NR 1.91 1.34-2.48 N (1)
Cs-137 Bq/sample NR 1.76 1.23-2.29 N (1)
Co-57 Bq/sample NR False positive test N (1)
Co-60 Bq/sample NR 1.39 I 0.97- 1.81 N (1)
Mn-54 Bq/sample NR False positive test N (1)
Zn-65 Bq/sample NR False positive test N (1) 14-GrF30 AP Gr-B Bq/sample 0.7507 0.77 0.39 -1.16 A 14-RdV30 Vegetation Cs-134 Bq/sample 5.96 6.04 4.23-7.85 A Cs-137 Bq/sample 5.06 4.74 3.32-6.16 A Co-57 Bq/sample 11.8 10.1 7.1 -13.1 A Co-60 Bq/sample 7.34 6.93 4.85 - 9.01 A Mn-54 Bq/sample 8.95 8.62 6.03- 11.21 A Zn-65 Bq/sample 8.91 7.86 5.50-10.22 A September 14- Water Cs-134 Bq/L NR False positive test N (1) 2014 MaW31 Cs-137 Bq/L NR 18.4 12.9-23.9 N (1)
Co-57 Bq/L NR 24.7 17.3-32.1 N (1)
Co-60 Bq/L NR 12.4 8.7-16.1 N (1)
Mn-54 Bq/L NR 14.0 9.8-18.2 N (1)
K-40 Bq/L NR 161 113-209 N (1)
Zn-65 Bq/L NR 10.9 7.6-14.2 N (1) 14-MaS31 Soil Cs-134 Bq/kg NR 622 435-809 N (1)
Cs-137 Bq/kg NR False positive test N (1)
Co-57 Bq/kg NR 1116 781 -1451 N (1)
Co-60 Bq/kg NR 779 545-1013 N (1)
Mn-54 Bq/kg NR 1009 706- 1312 N (1)
K-40 Bq/kg NR 824 577- 1071 N (1)
Zn-65 Bq/kg NR 541 379-703 N (1) 47
Annual Radiological 2014 Environmental Operatinci Report Waterford 3 Steam Electric Station Table 8.1 Sample Type: Interlaboratory Comparison Analysis: Gross Beta, Iodine-1 31, Tritium and Gamma Isotopic Month/Year ID Number Matrix Nuclide Units Reported Known Acceptance Evaluation Value (a) Value (b) Range (c)
September 2014 14-GrF31 AP Gr-B Bq/sample 0.977 1.06 0.53-1.59 A 14-RdV31 Vegetation Cs-134 Bq/sample 7.31 7.38 5.17-9.59 A Cs-137 Bg/sample 8.93 8.14 5.70- 10.58 A Co-57 Bq/sample 10.8 9.2 6.4- 12.0 A Co-60 Bq/sample 6.31 6.11 4.28- 7.94 A Mn-54 Bq/sample 7.76 7.10 4.97 -9.23 A Zn-65 Bq/sample 7.16 6.42 4.49- 8.35 A In reviewing our environmental inter-laboratory crosscheck programs, we identified 1) duplication of efforts on some matrices and isotopes and 2) that we are performing crosscheck samples on some matrices and isotopes that we do not perform for clients. Since the DOE MAPEP is designed to evaluate the ability of analytical facilities to correctly analyze for radiological constituents representative of those at DOE sites, the needed changes were made to the MAPEP program. Therefore, the following isotopes were removed from the MAPEP program:
Soil - gamma - will be provided by Analytics twice per year, starting in 2015. For 2014, one soil gamma is provided by MAPEP, the 2rn soil gamma is provided by Analytics.
AP - gamma - is currently provided by Analytics.
Water - gamma, H-3, Sr-90, uranium, gross alpha and gross beta currently provided by ERA.
(1) MAPEP evaluates non-reports (NR) as failed if they were reported in the previous study (2) The K-40 in water result of 1.63 Bq/L was overlooked when reporting the data but would have passed the false positive test. NCR 14-04 (a) Teledyne Brown Engineeringreported result.
(b) The MAPEP known value is equal to 100% of the parameterpresentin the standardas determined by gravimetric and/or volumetric measurements made during standardpreparation.
(c) DOE/MAPEPevaluation: A=acceptable; W=acceptable with warning; N=notacceptable.
48
Annual Radiological 2014 Environmental Ooeratina Reoort Waterford 3 Steam Electric Station Table 8.1 Sample Type: Interlaboratory Comparison Analysis: Gross Beta, Iodine-1 31, Tritium and Gamma Isotopic Units: pCi/kg (wet)
ERA ENVIRONMENTAL RADIOACTIVITY CROSS CHECK PROGRAM TELEDYNE BROWN ENGINEERING ENVIRONMENTAL SERVICES Month/Year ID Number Matrix Nuclide Units Reported Known Acceptance Evaluation Value (a) Value (b) Limits (c)
May 2014 RAD-97 Water H-3 pCi/L 8435 8770 7610-9650 A Ba-133 pCi/L 89.1 87.9 74.0-96.7 A Cs-134 pCi/L 45.55 44.3 35.5-48.7 A Cs-137 pCi/L 91.15 89.1 80.2-101 A Co-60 pCi/L 65.10 64.2 57.8-73.1 A Zn-65 pCi/L 244 235 212 -275 A Gr-B pCi/L 27.95 33.0 21.4-40.7 A 1-131 pCi/L 23.75 25.7 21.3-30.3 A November 2014 RAD-99 Water H-3 pCi/L 6255 6880 5940-7570 A Ba-133 pCi/L 46.8 49.1 40.3-54.5 A Cs-134 pCi/L 88.0 89.8 73.7-98.8 A Cs-137 pCi/L 99.0 98.8 88.9-111 A Co-60 pCi/L 92.5 92.1 82.9- 104 A Zn-65 pCi/L 325 310 279- 362 A Gr-B pCi/L 27.5 27.4 17.3-35.3 A 1-131 pCi/L 15.8 20.3 16.8-24.4 N (1)
(1) Iodine-131 was evaluated as failed with a ratio of 0. 778. No cause could be found for the slightly low activity. TBE would evaluate this as acceptable with warning. A rerun was not possible due to 1-131 decay. All previous ERA 1-131 evaluations since 2004 have been acceptable.
NCR 14-08 (a) Teledyne Brown Engineeringreportedresult.
(b) The ERA known value is equal to 100% of the parameterpresent in the standardas determined by gravimetric and/or Volumetric measurements made during standardpreparation.
(c) ERA evaluation: A=acceptable. Reported result falls within the Warning Limits. NA=not acceptable. Reported result falls outside of the Control Limit. CE=check for Error. Reported result falls within the Control Limits and outside of the Warning Limits.
49
Annual Radiological 2014 Environmental ODeratina Report Waterford 3 Steam Electric Station ATTACHMENT 2 Statistical Comparisons 50
Annual Radiological 2014 Environmental Operating Report Waterford 3 Steam Electric Station TABLE OF CONTENTS TABLE 2.1 STATISTICAL COMPARISON OF 2014 TLD MEASUREMENTS FROM STATIONS GROUPED BY DISTANCE 54 TABLE 2.2 STATISTICAL COMPARISON OF 2014 TLD RADIATION DOSE TO HISTORICAL DATA BY LOCATION 55 TABLE 2.3 STATISTICAL COMPARISON OF 2014 GROSS BETA ACTIVITY MEASUREMENTS ON AIR PARTICULATE FILTERS 56 TABLE 2.4 STATISTICAL COMPARISON OF 2014 GROSS BETA ACTIVITY MEASUREMENTS IN DRINKINGISURFACE WATER SAMPLES 57 51
Annual Radiological 2014 Environmental Operatinq Report Waterford 3 Steam Electric Station Statistical Analyses Calculation of the Mean and Standard Deviation The mean and standard deviation for different groups of analyses are calculated using the following equations:
n=i-S= I X and
0.5 where
X = mean of sample population, S = standard deviation of sample population, n = number of samples in sample population, and Xi = value of the i'th sample.
52
Annual Radiological 2014 Environmental Operating Report Waterford 3 Steam Electric Station
- Comparing Two Sample Population Means The means of two sample populations are compared for statistical difference using the standard "t" test. The use of the test requires the assumption that the data within the populations are normally distributed and that the true standard deviations of the mean are equal for both populations. The standard "t" test tests the hypothesis that the true means of both populations are equal. The "t" value can be calculated from the equation below (obtained from the CRC Standard Mathematical Tables, 26th Edition (1981)):
X-Y 0.5
( _
n.= .xn+ -2 -2 0.5 I+ JI where:
t = calculated "t" value, X = mean of first data set, Y = mean of second data set,
/7 = number of variables in first data set, S, = standard deviation of first data set,
,7 y = number of variables in second data set, and SY = standard deviation of second data set.
The calculated "t" value is used to test the hypothesis that the true mean of the first population (m
,) is equal to the true mean of the second population (m y) assuming that the true standard deviation of.both populations are equal (m x = m y). The calculated "t" value is compared to a tabular "t" value such that:
a if t > t p,n then reject the hypothesis when m > m y,
- b. if t < -t p,n then reject the hypothesis when m. < m y,
- c. if t > t p/2,n then reject the hypothesis when mx = m y, where t p/2,n and t p,n are the tabular "t" values, with a preselected error (5%), confidence level (1 -
lp) or (1- p/2), and degrees of freedom n = nx + ny - 2. Tabular values of the "t" were obtained from the CRC Standard Mathematical Tables, 26th Edition (1981).
53
Annual Radiological 2014 Environmental Ooeratina Reoort Waterford 3 Steam Electric Station TABLE 2.1 STATISTICAL COMPARISON OF 2014 TL MASURMENTS FROM STATIONS GROUPED BY DISTANCE
.. Stations Station* Located 2- Stations L.ocated more than
................ .Miles.from.the. Pant Milesfromthe Ilant 5 Miles from the Plant Mean 12 13 12 (mRem/std.qtr.)
Standard Deviation 1.51 1.13 1.28 (mRem/std. qtr.)
Number in Sample 61 27 28 Calculated "t" Value 1.07 2.12 NA*
(comparison of stations 0-2 and 2-5 miles from the plant to stations >5 miles from the plant)
Tabular "t" Value at 1.991 (a) 2.007(b) NA*
95% Confidence(t0 .02 5 ,n)
(a) Results indicate the mean for stations located 0-2 miles from the plant are statistically identical to the mean for stations located more than 5 miles from the plant.
(b) Although the TLD stations located 2-5 miles from the plant are statistically higher than those located more than 5 miles from the plant, the quarterly doses measured in 2014 are consistent with historical data at each location as shown in Table 2.2.
Not Applicable 54
Annual Radiological 2014 Environmental Operatinq Report Waterford 3 Steam Electric Station TABLE 2.2 STATISTICAL COMPARISON OF 2014 TLD RADIATION DOSE TO HISTORICAL DATA BY LOCATION
. . *Units: mrem/Std. Qtr.
Station 1990- 2013 Avg* 1990-2013Std ev* 1990 2013 Range l 2014 Avg" 2014 Std Dov** 2014 Range22!
A-2 13 1.4 10 18 13 0.4 12 13 A-5 13 1.4 10 17 12 0.7 11 13 B-1 13 1.4 10 19 13 0.4 13 14 B-4 13 1.1 11 17 14 0.4 13 14 C-1 9 1.2 7 13 10 0.5 9 10 D-2 12 1.9 8 19 13 0.4 12 13 D-5 12 1.4 9 18 12 0.5 11 12 E-1 11 1.2 9 16 11 0.4 11 12 E-5 12 1.6 9 17 13 0.5 12 13 E-1_5 11 1.6 8 16 10 0.4 10 11 E-30* 11 1.5 8 17 10 0.4 9 10 F-2 12 1.1 10 17 12 0.7 11 13 F-4 14 1.4 11 19 15 0.5 14 15 F-9 12 1.4 7 17 13 0.5 12 13 G-2 14 1.8 10 19 11 0.4 11 12 G-4 11 1.3 9 16 11 0.5 11 12 G-8 12 1.9 8 19 11 0.4 11 12 H-2 13 1.2 10 18 12 0.8 11 13 H-8 12 1.2 9 17 13 0.4 13 14 J-2 12 1.5 10 17 11 0.0 11 11 J-15 13 1.2 11 17 13 0.0 13 13 K-1 11 1.2 9 16 11 0.0 11 11 L-1 13 1.4 10 16 14 0.4 14 15 M-1 12 1.5 9 18 10 0.0 10 10 N-1 13 1.5 8 18 14 0.0 14 14 P-1 10 1.2 7 15 10 0.0 10 10 P-6 14 1.3 10 19 13 0.4 13 14 Q-1 12 1.2 10 16 13 0.4 12 13 Q-5 13 2.1 9 18 14 0.9 13 15 R-1 10 1.9 6 15 10 0.0 10 10 R-6 12 2.4 8 18 10 0.0 10 10
- Control Location
- Significant outliers were removed from data sets.
PERS data indicates an average of 20 mrem for all indicator locations with a range of 11 to 33 and an average control of 18 mrem.
55
Annual Radiological 2014 Environmental Operatina Reoort Waterford 3 Steam Electric Station TABLE 2.3 Mean 21 20 19 19 20 3 3 (1O pCi/m )
Standard Deviation 5.04 4.41 4.28 6.33 4.24 (1O'3pCiIm 3 )
Number in Sample 26 26 26 26 26 Calculated "t" Value 0.48 0.35 1.14 0.54 NA*
(comparison of the indicator stations to the control station)
Tabular "t" Value at 2.011 (a) 2.011(a) 2.011(a) 2.011 (a) NA*
95% Confidence(t 0,025,n) i A I (a) Results indicate the mean for the indicator stations is statistically identical to the mean for the control station.
- Not Applicable 56
Annual Radiological 2014 Environmental Ooeratina ReDort Waterford 3 Steam Electric Station TABLE 2.4
- 1 Mean 5.6 5.1 4.4 (pCilliter)
Standard Deviation 0.88 0.70 0.53 (pCi/liter)
Number in Sample 4 4 4 Calculated "t" Value 2.47 1.74 NA*
(comparison of the indicator stations to the control station)
Tabular "t" Value at 2.447(b) 2.447(a) NA*
95% Confidence(t 0 .02 5 ,n)
I i (a) Results indicate the mean for the indicator station is statistically identical to the mean for the control station.
(b) Results indicate the mean for the indicator station is statistically higher than the mean for the control location. Results obtained in 2014 are consistent with historical data as stated in section 2.3.
- Not Applicable 57