ENT000434 Submitted: March 30, 2012 NOTE: This inspection report form is extracted from EN-EP-S-002-MULTI (Rev. 0 target o effective date 10/31/09)

ATTACHMENT 7.1 INSPECTION CHECKLIST Sheet 1 of 2 1G-lnch City Water Line from INSPECTION Piping 1 Tank _C~a~t~sk~I~II~W~a~~~r~S~u~p~pl~y_ _ _ _ _ DATE: 10/29/09 120' EL.

(approx. 9321-F-41933, ELEVATION: grade) LOCATION DWG: zone 0-5 INSPECTOR: J. Peterson NOTE YES

1. ANY BLISTERING (COATING)? NO~ _ _ _ _ _ _ _ _ ___

D YES

2. ANY PEELING (COATING)? NO ~

D YES -----------

3. ANY FLAKING (COATING)? NO ~ _ _ _ _ _ _ _ ___

D YES

4. ANY DELAMINATION (COATING)? D NO ~ _ _ _ _ _ _ _ ___

YES

5. ANY EMBRITTLEMENT (COATING)? NO~ _ _ _ _ _ _ _ _ ___

D YES

6. ANY EMBEDDED ROCKS (COATING AND/OR METAL)? NO ~

D YES -----------

7. ANY CRACKING (COATING AND/OR METAL)? D NO ~ _ _ _ _ _ _ _ ___

YES

8. ANY RUST (METAL)? NO~ _ _ _ _ _ _ _ _ ___

D YES

9. ANY CORROSION (METAL)? NO ~

D YES -----------

10. ANY FLAKING OR SCALING (METAL)? D NO ~ _ _ _ _ _ _ _ ___

YES

11. ANY MECHANICAL DAMAGE (METAL)? NO ~ _ _ _ _ _ _ _ _ ___

D YES

12. ANY NICKS. GOUGES OR ARC STRIKES (METAL)? NO ~ _ _ _ _ _ _ _ _ ___

D YES

13. ANY TUBERCLES (METAL -IF INTERNAL INSPECTION)? D NO 0 N/A-extemal inspection only GENERAL APPEARANCE (Inspector): Exterior pipe coating found in aood condition. with no observable discontinuities, peeling. blistering.

separation. embrittlemcnt. flaking. etc. Coating also having good adhesion to the pipe with no bubbled spots (i.e.* gaps between pipe and coating.).

Sec attached photo documentation and Notes. Photo included of the backfill material, showing absence of any large rocks. or foreign material.

DEGRADATION FOUND? YEsD NO~ CR-FURTHER EVALUATION REQUIRED? YESD NO~

COMMENTS (Inspector): IO-inch city water line from the City Watt r Storage Tank was inspected at ex.cavalcd location. Line runs approx.imately parallcl with the 16*inch city water line (also excavation under the same modification. F.e 13314). Approx. 8 loot length of pipe inspected.

o INSPECTOR(S) PRINTISIGNIDATE: J. Peterson V1_ ~

rtf'T7

  • I

o NOTE: This inspection report form is extracted from EN-EP-S-002-MULTI (Rev. 0 target effective date 10/31/09)

ATTACHMENT 7.1 INSPECTION CHECKLIST Sheet 2 of2 EVALUATION: ACCEPTABLE I:8J ACCEPTABLE WITH DEFICIENCIES D UNACCEPTABLE D RECOMMENDED ACTION (Program Owner):

Capture the results of this piping inspection in the BPT Program database (IDDEAL Scheduleworks).

FUTURE MONITORING: D None required. Future inspections of this line will be as scheduled and managed under the IPEG Buried Pipe and Tank Program. Based on results of this inspection. any future inspections of this line should be at other locations.

o PREVENTIVE MAINTENANCE:

None required.

D CORRECTIVE ACTIONS: D None required.

PHOTOGRAPHIC OR VIDEO RECORDS ATTACHED? YES I:8J NO D o

o o

o