Request for Additional Information Regarding Request for Extended Power Uprate
ML080160570
Person / Time
Site: Hope Creek 
Issue date: 01/23/2008
From: John Lamb
NRC/NRR/ADRO/DORL/LPLI-2
To: Levis W
Public Service Enterprise Group
Lamb John G./NRR/DORL, 415-3100
References
TAC MD3002
Download: ML080160570 (7)


Text

January 23, 2008 Mr. William Levis President & Chief Nuclear Officer PSEG Nuclear LLC-N09 Post Office Box 236 Hancocks Bridge, NJ 08038

SUBJECT:

HOPE CREEK GENERATING STATION - REQUEST FOR ADDITIONAL INFORMATION REGARDING REQUEST FOR EXTENDED POWER UPRATE (TAC NO. MD3002)

Dear Mr. Levis:

By letter dated September 18, 2006,1 as supplemented by additional letters,2 PSEG Nuclear, LLC (PSEG or the licensee) submitted an amendment request for an extended power uprate (EPU) for the Hope Creek Generating Station (Hope Creek). The proposed amendment would increase the authorized maximum power level by approximately 15 percent, from 3,339 megawatts thermal (MWt) to 3,840 MWt.

The Nuclear Regulatory Commission (NRC) staff has been reviewing the submittal and has determined that additional information is needed to complete its review. The specific questions are found in the enclosed request for additional information (RAI). The questions were sent by e-mail to your staff and were discussed on a phone call on January 14, 2008, to ensure that the questions were understandable, the regulatory basis was clear and to determine if the information was previously docketed.

Mr. Jeff Keenan of your staff agreed to respond by January 25, 2008, to the enclosed RAI questions.

1 Agencywide Documents Access and Management System (ADAMS) Accession No. ML062680451 2 Letters dated: October 10, 2006 (ML062920092); October 20, 2006 (ML063110164); February 14, 2007 (ML070530099);

February 16, 2007 (ML070590182); February 28, 2007 (ML070680314); March 13, 2007 (ML070790508 & ML070810360);

March 22, 2007 (ML070930442); March 30, 2007 (ML071010243 & ML070960103); April 13, 2007 (ML071140157); April 18, 2007 (ML071160121); April 30, 2007 (ML071290559); May 10 (ML071360375); May 18, 2007 (ML071500294, ML071720368, &

ML071500317); May 24, 2007 (ML071630305); June 22, 2007 (ML071840167); July 12, 2007 (ML072110215); August 3, 2007 (ML072250369); August 17, 2007 (ML072480515, ML072480515); August 27, 2007 (ML072480570); August 31, 2007 (ML072540651); September 11, 2007 (ML072640410); October 10, 2007 (ML073100791); October 23, 2007 (ML073040393);

November 15, 2007 (ML073320601); November 30, 2007 (ML073460793); December 31, 2007 (ML080080577); January 14, 2008; January 15, 2008; and January 18, 2008.

Please note that if you do not respond to this letter within the prescribed response times or provide an acceptable alternate date in writing, we may reject your application for amendment under the provisions of 10 CFR, Part 2, Section 2.108. If you have any questions, I can be reached at (301) 415-3100.

Sincerely,

/ra/

John G. Lamb, Senior Project Manager Plant Licensing Branch 1-2 Division of Operating Reactor Licensing Office of Nuclear Reactor Regulation Docket No. 50-354

Enclosure:

As stated cc: See next page

Please note that if you do not respond to this letter within the prescribed response times or provide an acceptable alternate date in writing, we may reject your application for amendment under the provisions of 10 CFR, Part 2, Section 2.108. If you have any questions, I can be reached at (301) 415-3100.

Sincerely,

/ra/

John G. Lamb, Senior Project Manager Plant Licensing Branch 1-2 Division of Operating Reactor Licensing Office of Nuclear Reactor Regulation Docket No. 50-354

Enclosure:

As stated cc: See next page DISTRIBUTION:

PUBLIC Lpl1-2 R/F RidsNrrDORLLpl1-2 RidsOgcRP RidsNrrLAABaxter RidsAcrsAcnwMailCenter TScarbrough JQuichocho RidsNrrPMJLamb RidsNrrDORLDpr RidsRgn1MailCenter GPurciarello ADAMS Accession Number: ML080160570 OFFICE LPL1-2/PM LPL1-2/LA EMCB/BC LPL1-2/BC NAME JLamb ABaxter KManoly HChernoff DATE 1/22/08 1/22/08 1/22/08 1/23/08 OFFICIAL RECORD COPY

Enclosure REQUEST FOR ADDITIONAL INFORMATION REGARDING PROPOSED LICENSE AMENDMENT EXTENDED POWER UPRATE HOPE CREEK GENERATING STATION DOCKET NO. 50-354 By letter dated September 18, 2006,1 as supplemented by additional letters,2 PSEG Nuclear, LLC (PSEG or the licensee) submitted an amendment request for an extended power uprate (EPU) for the Hope Creek Generating Station (Hope Creek). The proposed amendment would increase the authorized maximum power level by approximately 15 percent, from the current licensed thermal power (CLTP) of 3,339 megawatts thermal (MWt) to 3,840 MWt.

The Nuclear Regulatory Commission staff has reviewed the information the licensee provided that supports the proposed amendment and would like to discuss the following issues to clarify the submittal.

RAI 14.66 2nd Follow-Up - I Page 22 of Continuum Dynamics, Inc. (CDI) Report 07-27P, Finite Element Modeling Bias and Uncertainty Estimates Derived from the Hope Creek Unit 2 Dryer Shaker Test, Rev. 0, presents damping values computed for the finite element (FE) model to best match FE and measured acceleration response function peaks. CDI states that the inferred FE damping values are consistent with measured damping values in STI Technologies Report PA2168, Hope Creek Steam Dryer Vibration Test. However, no damping values (other than those for low frequency rigid body modes) are presented in the STI report.

(a)

Provide and plot the damping values from the measurements as a function of shaker location and frequency. Also include minimum, maximum, mean, and root mean square values (computed over frequency) for each shaker location consistent with those in Table 3 in CDI Report 07-27P.

(b)

Plot and compare the measured damping values and FE damping values inferred in CDI Report No.07-27P as a function of frequency and shaker location.

1 Agencywide Documents Access and Management System (ADAMS) Accession No. ML062680451 2 Letters dated: October 10, 2006 (ML062920092); October 20, 2006 (ML063110164); February 14, 2007 (ML070530099);

February 16, 2007 (ML070590182); February 28, 2007 (ML070680314); March 13, 2007 (ML070790508 & ML070810360);

March 22, 2007 (ML070930442); March 30, 2007 (ML071010243 & ML070960103); April 13, 2007 (ML071140157); April 18, 2007 (ML071160121); April 30, 2007 (ML071290559); May 10 (ML071360375); May 18, 2007 (ML071500294, ML071720368, &

ML071500317); May 24, 2007 (ML071630305); June 22, 2007 (ML071840167); July 12, 2007 (ML072110215); August 3, 2007 (ML072250369); August 17, 2007 (ML072480515, ML072480515); August 27, 2007 (ML072480570); August 31, 2007 (ML072540651); September 11, 2007 (ML072640410); October 10, 2007 (ML073100791); October 23, 2007 (ML073040393);

November 15, 2007 (ML073320601); November 30, 2007 (ML073460793); December 31, 2007 (ML080080577); January 14, 2008; January 15, 2008; and January 18, 2008.

(c) Reconcile the differences between the measured and inferred FE damping values, and provide the resulting FE bias and uncertainty.

RAI 14.66 2nd Follow-Up - II STI Technologies Report PA2168, Hope Creek Steam Dryer Vibration Test states on page 7 that a Hanning window was applied to the measured vibration response. Hanning windows reduce peak amplitudes in Fourier Transforms. Was the Hanning window used during the peak response measurements conducted by driving the shaker at a single frequency? If so, how has the peak amplitude reduction been accounted for?

Hope Creek Generating Station cc:

Mr. Thomas Joyce Senior Vice President - Operations PSEG Nuclear P.O. Box 236 Hancocks Bridge, NJ 08038 Mr. Dennis Winchester Vice President - Nuclear Assessment PSEG Nuclear P.O. Box 236 Hancocks Bridge, NJ 08038 Mr. Carl Fricker Vice President - Operations Support PSEG Nuclear P.O. Box 236 Hancocks Bridge, NJ 08038 Mr. John Perry Plant Manager - Hope Creek PSEG Nuclear P.O. Box 236 Hancocks Bridge, NJ 08038 Mr. James Mallon Manager - Licensing PSEG Nuclear P.O. Box 236 Hancocks Bridge, NJ 08038 Mr. Jeffrie J. Keenan, Esquire PSEG Nuclear - N21 P.O. Box 236 Hancocks Bridge, NJ 08038 Mr. Michael Gaffney Manager - Hope Creek Regulatory Assurance PSEG Nuclear P.O. Box 236 Hancocks Bridge, NJ 08038 Township Clerk Lower Alloways Creek Township Municipal Building, P.O. Box 157 Hancocks Bridge, NJ 08038 Mr. Paul Bauldauf, P.E., Asst. Director Radiation Protection Programs NJ Department of Environmental Protection and Energy CN 415 Trenton, NJ 08625-0415 Mr. Brian Beam Board of Public Utilities 2 Gateway Center, Tenth Floor Newark, NJ 07102 Regional Administrator, Region I U.S. Nuclear Regulatory Commission 475 Allendale Road King of Prussia, PA 19406 Senior Resident Inspector Hope Creek Generating Station U.S. Nuclear Regulatory Commission Drawer 0509 Hancocks Bridge, NJ 08038