MONTHYEARML22046A2332022-06-21021 June 2022 Issuance of Amendment Nos. 360 and 342 Regarding Change to the Technical Specification Requirement for Containment Water Level Instrumentation ML21125A5762021-04-19019 April 2021 9 Technical Specification Bases, List of Effective Pages (Unit 2) ML21125A5482021-04-19019 April 2021 2 to Technical Specifications Bases, List of Effective Pages (Unit 1) ML20366A1552021-01-15015 January 2021 Issuance of Amendments Nos. 357 and 336 Regarding Revision to Technical Specifications Bases Control Program ML20329A0012021-01-12012 January 2021 Issuance of Amendment No. 356 Regarding Updating the Reactor Coolant System Pressure-Temperature Limits ML20322A4282021-01-0606 January 2021 Issuance of Amendment Nos. 355 and 335, Revision to Technical Specifications to Adopt Technical Specification Task Force Traveler 567, Revision 1, Add Containment Sump TS to Address GSI-191 Issues AEP-NRC-2020-78, License Amendment Request Regarding a Change to the Steam Generator (SG) Program to Allow for a One-Time Deferral of SG Inspections2020-12-14014 December 2020 License Amendment Request Regarding a Change to the Steam Generator (SG) Program to Allow for a One-Time Deferral of SG Inspections ML19170A3622019-08-0101 August 2019 Issuance of Amendment Approval of Application of Proprietary Leak-Before-Break Methodology for Reactor Coolant System Small Diameter Piping ML17131A2772017-06-0707 June 2017 Issuance of Amendments License Amendment Request Regarding Containment Leakage Rate Testing Program ML16195A0042016-08-0404 August 2016 Issuance of Amendments to Revise Technical Specifications to Adopt Technical Specifications Task Force - 523, Generic Letter 2008 01, Managing Gas Accumulation ML14197A0972015-11-30030 November 2015 Issuance of Amendment Regarding Restoration of Normal Reactor Coolant System Pressure and Temperature Consistent with Previously Licensed Conditions ML15328A4512015-11-19019 November 2015 Enclosures 1 - 5: Affirmation, Description of Proposed Changes, Probabilistic Risk Assessment Technical Adequacy, and CNP Units 1 & 2 TS Pages Marked to Show Proposed Changes ML15187A0022015-07-10010 July 2015 Issuance of Amendment No. 328 (Exigent) Regarding Revision to Technical Specifications for Engineered Safety Feature Actuation System AEP-NRC-2015-62, Exigent License Amendment Request Regarding Technical Specification 3.3.2, Engineered Safety Feature Actuation System (ESFAS) Instrumentation2015-06-29029 June 2015 Exigent License Amendment Request Regarding Technical Specification 3.3.2, Engineered Safety Feature Actuation System (ESFAS) Instrumentation ML15076A2262015-04-0606 April 2015 Issuance of Amendments Adoption of TSTF-427, Allowance for Non-Technical Specification Barrier Degradation on Supported System Operability, Revision 2 AEP-NRC-2015-05, Correction of Technical Specification Typographical Error2015-02-0202 February 2015 Correction of Technical Specification Typographical Error ML14282A1182014-11-20020 November 2014 Issuance of Amendments Regarding Containment Divider Barrier Seal AEP-NRC-2014-09, License Amendment Request to Revise Technical Specification Section 5.5.14, Containment Leakage Rate Testing Program2014-03-0707 March 2014 License Amendment Request to Revise Technical Specification Section 5.5.14, Containment Leakage Rate Testing Program ML13282A2142013-10-0909 October 2013 Issuance of Amendment Revision to Technical Specification 3.6.9, Distributed Ignition System (Dis) (Emergency Circumstances) AEP-NRC-2013-79, License Amendment Request Regarding Restoration of Normal Reactor Coolant System Operating Pressure and Temperature Consistent with Previously Licensed Conditions, with Enclosures 1 Through 52013-10-0808 October 2013 License Amendment Request Regarding Restoration of Normal Reactor Coolant System Operating Pressure and Temperature Consistent with Previously Licensed Conditions, with Enclosures 1 Through 5 ML11182A1782011-07-28028 July 2011 License Amendment, Issuance of Amendments Cyber Security Plan AEP-NRC-2009-71, Response to Request for Additional Information Regarding a License Amendment Request Associated with the Large-Break Loss-of-Coolant Accident Analysis Methodology2009-11-20020 November 2009 Response to Request for Additional Information Regarding a License Amendment Request Associated with the Large-Break Loss-of-Coolant Accident Analysis Methodology AEP-NRC-2009-23, License Amendment Request Regarding Large Break Loss-of-Coolant Accident Analysis Methodology2009-03-19019 March 2009 License Amendment Request Regarding Large Break Loss-of-Coolant Accident Analysis Methodology ML0903502102009-01-14014 January 2009 License Amendment Request to Revise Operating Licenses DPR-58 and DPR-74, Appendix B, Environmental Technical Specifications, Part II, Non-Radiological Environmental Protection Plan ML0826004692008-09-0404 September 2008 Supplement to Emergency Diesel Generator Maximum Steady State Frequency Amendment Request ML0815108932008-05-28028 May 2008 Correction of Amendment No. 304 for Unit 1 and 287 for Unit 2, (Tac Nos. MD6317 & MD6318) - Tech Specs ML0812302692008-04-28028 April 2008 Tech Spec Pages for Amendments 305 and 288 Regarding Maximum Ventilation System Filter Pressure Drop ML0812302702008-04-28028 April 2008 Tech Spec Pages for Amendments 304 & 287 to Add a Surveillance Requirement for When Offsite Power Is Provided Via Backfeed Through the Main Transformer and a Unit Auxiliary Transformer ML0806600672008-03-0505 March 2008 Tech Spec Page for Amendments 302 & 285 to Revise a Specification Inadvertently Omitted by Previous Amendments Power Range Neutron Flux High Negative Rate Trip Function ML0801106652008-01-11011 January 2008 Tech Spec Pages for Amendments 301 and 284 Regarding Operational Test of the Reactor Trip on Turbine Trip ML0800800492008-01-0404 January 2008 Technical Specifications, Correction of Amendment No. 282 Containment Sump Modifications Per Generic Letter 2004-02 ML0735204032007-12-17017 December 2007 Technical Specifications, Issuance of Amendment RTS and ESFAS Bypass Testing Capability ML0729501002007-10-18018 October 2007 Technical Specifications, Issuance of Amendments Containment Sump Modifications Per Generic Letter 2004-02 (TAC Nos. MD5901 & MD5902) ML0725306592007-09-19019 September 2007 Technical Specifications, Issuance of Amendment Replacement of Resistance - Temperature Detectors and Associated Piping ML0714200712007-05-11011 May 2007 Technical Specification Change of Conditional Surveillance Frequency ML0710100972007-04-0606 April 2007 Technical Specification Page Correction of Administrative Error in Amendment No. 298, Steam Generator Tube Integrity ML0708607652007-03-14014 March 2007 Corrections to Technical Specification Table of Contents ML0708101332007-03-14014 March 2007 D.C. Cook, Technical Specifications, Steam Generator Integrity ML0700305172006-12-26026 December 2006 Supplement to Application for Technical Specification (TS) Improvement Regarding Steam Generator Tube Integrity ML0628303132006-10-0606 October 2006 D.C. Cook, Tech Spec Pages for Amendment 296, Regarding Elimination of the Resistance Temperature Detector (RTD) Bypass Loop ML0624901142006-09-0101 September 2006 D.C. Cook, Technical Specification Pages Re AC Sources - Operating ML0618801572006-07-0505 July 2006 Technical Specifications Pages Regarding Leakage ML0616004492006-05-31031 May 2006 Application for Amendment to Revise Technical Specification Surveillance Requirement for Channel Calibration of Overtemperature Differential Temperature and Overpower Differential Temperature Reactor Protection System Functions ML0610805842006-04-21021 April 2006 Correction of Amendments Technical Specifications, Conversion to Improved Format ML0610404022006-04-13013 April 2006 Technical Specification - Issuance of Amendment Under Emergency Circumstances Regarding Diesel Generator Votage Limit Requirements ML0607603742006-03-0707 March 2006 Application for Amendment to Revise Technical Specification 5.5.2, Leakage Monitoring Program. ML0604400222006-02-10010 February 2006 Technical Specifications, Delete the Power Range Neutron Flux High Negative Rate Trip Function ML0601700302006-01-12012 January 2006 Tech Spec Pages for Amendments 292 and 274 Regarding Elimination of Requirements for Monthly Operating Reports and Occupational Radiation Exposure Reports ML0527303202005-09-30030 September 2005 Tech Spec Pages for Amendments 291 and 273 Safety Evaluation Regarding Allowed Outage Time Extension for the Emergency Diesel Generators ML0526900432005-09-23023 September 2005 Tech Spec Pages for Amendments 290 and 272 Requirements of Improved Technical Specification Surveillance Requirement 3.8.1.8 with the Wording of Previous Technical Specification SR 4.8.1.1.2.e.11 with Minor Editorial.. 2022-06-21
[Table view] |
Text
and radiation monitoring equipment calibration, and as fission detectors in amounts as required.
(4) Pursuant to the Act and 10 CFR Parts 30, 40, and 70, to receive, possess and use in amounts as required any byproduct, source or special nuclear material without restriction to chemical or physical form, for sample analysis or instrument and equipment calibration or associated with radioactive apparatus or components; and (5) Pursuant to the Act and 10 CFR 30 and 70, to possess,.but not separate, such byproduct and special nuclear materials as may be produced by the operation of the facility.
C. This renewed operating license shall be deemed to contain and is subject to the conditions specified in the following Commission regulations in 10 CFR Chapter I: Part 20, Section 30.34 of Part 30, Section 40.41 of Part 40, Section 50.54 and 50.59 of Part 50, and Section 70.32 of Part 70; and is subject to all applicable provisions of thee Act and to the rules, regulations, and orders of the Commission now or hereafter in effect; and is subject to the additional conditions specified or incorporated below:
(1) Maximum Power Level The licensee is authorized to operate the facility at steady state reactor core power levels not to exceed 3304 megawatts thermal in accordance with the conditions specified therein.
(2) Technical Specifications The Technical Specifications contained in Appendix A and Appendix B, as revised through Amendment No. 295, are hereby incorporated in the renewed operating license. The licensee shall operate the facility in accordance with the Technical Specifications.
(3) Less Than Four Loop Operation The licensee shall not operate the reactor at power levels above P-7 (as defined in Table 3.3.1-1 of Specification 3.3.1 of Appendix A to this renewed operating license) with less than four reactor coolant loops in operation until (a) safety analyses for less than four loop operation have been submitted, and (b) approval for less than found loop operation at power levels above P-7 has been granted by the Commission by amendment of this license.
(4) Indiana Michigan Power Company shall implement and maintain, in effect, all provisions of the approved Fire Protection Program as described in the Final Safety Analysis Report for the facility and as approved in the SERs dated December 12, 1977, July 31, 1979, January 10, 1981, February 7, 1983, November 22, 1983, December 23, 1983, March 16, 1984, August 27, 1985 Renewed License No. DPR-58 Amendment No. q ,.hoti.h 294, 295
AC Sources - Operating 3.8.1 SURVEILLANCE REQUIREMENTS (continued)
SURVEILLANCE FREQUENCY SR 3.8.1.11 -----------
NOTES---------------------------
- 1. This Surveillance shall not normally be performed in MODE 1 or 2. However, this Surveillance rnay be performed to reestablish OPERABILITY provided an assessment determines the safety of the unit is maintained or enhanced.
Credit may be taken for unplanned events that satisfy this SR.
- 2. If performed with DG synchronized with offsite power, it shall be performed at a power factor _0.86. However, if grid conditions do not permit, the power factor limit is not required to be met. Under this condition the power factor shall be maintained as close to the limit as practicable.
Verify each DG does not trip and voltage is 24 months maintained *5350 V during and following a load rejection Ž3150 kW and *3500 kW.
Cook Nuclear Plant Unit 1 3.8.1-10 Amendment No. 27, 291, 295