RTS Instrumentation 3.3.1 Table 3.3.1-1 (page 1 of 6)
Reactor Trip System Instrumentation APPLICABLE MODES OR OTHER SPECIFIED REQUIRED SURVEILLANCE FUNCTION CONDITIONS CHANNELS CONDITIONS REQUIREMENTS ALLOWABLE VALUE
- 1. Manual ReactorTrip 1,2 2
B SR 3.3.1.17 NA 3(a) 4(8) da) 2 B
SR 3.3.1.17 NA
- 2.
Power Range Neutron Flux
- a. High 1,2 4
C SR3.3.1.1.
11% RTP SR 3.3.1.2 SR 3.3.1.8 SR 3.3.1.9 SR 3.3.1.19
- b.
Low 1 (b),2 4
D SR 3.3. 1.1 26% RTP SR 3.3.1.8 SR 3.3.1.9 SR 3.3. 1.1 9
- 3.
Power Range Neutron Flux -
1,2 4
D SR 3.3.1.8 S 5.5% RTP with time High Positive Rate SR 3.3.1.14 constant a 2 sec
- 4.
Intermediate Range Neutron I b),2(c) 2 E, F SR 3.3.1.1
£30 /oRTP Flux SR 3.3.1.11 SR 3.3.1.14
- 5.
Source Range Neutron Flux 2(d) 2 G, H SR 3.3. 1.1 5 1.31E5 cps SR 3.3. 1.11 SR 3.3.1.14 3(a) 4(8) 5(a) 2 H, I SR 3.3.1.1 51.3E5 cps SR 3.3.1.11 SR 3.3.1.14 (a) With Rod Control System capable of rod withdrawal or one or more rods not fully Inserted.
(b) Below the P-lO (Power Range Neutron Flux) Interlock (c) Above the P-6 (Intermediate Range Neutron Flux) interlock (d) Below the P-6 (Intermediate Range Neutron Flux) Interlock.
I Cook Nuclear Plant Unit I 3.3.1-11 Amendment No. 287, 293 1
I RTS Instrumentation 3.3.1 Table 3.3.1-1 (page 1 of 6)
Reactor Trip System Instrumentation APPLICABLE MODES OR OTHER SPECIFIED REQUIRED SURVEILLANCE FUNCTION CONDMONS CHANNELS CONDITIONS REQUIREMENTS ALLOWABLE VALUE
- 1. Manual Reactor Trip 1,2 2
B SR 3.3.1.17.
NA 3(), 4()
5(a) 2 B
SR 3.3.1.17 NA
- 2.
Power Range Neutron Flux
- a. High 1,2 4
C SR3.3.1.1 s 11I9O% RTP SR 3.3.1.2 SR 3.3.1.8 SR 3.3.1.9 SR 3.3.1.19
- b.
Low 1(b) 2 4
D SR 3.3.1.1 s 26% RTP SR 3.3.1.8 SR 3.3.1.9 SR 3.3.1.19
- 3.
Power Range Neutron Flux -
1.2 4
D SR 3.3.1.8 s 5.5% RTP with time High Positive Rate SR 3.3.1.14 constant 2 2 sec
- 4.
Intermediate Range Neutron 1(b). 2(e) 2 E. F SR 3.3.1.1 g 30% RTP Flux SR 3.3.1.11 SR 3.3.1.14
- 5.
Source Range Neutron Flux 2(d) 2 G. H SR 3.3.1.1 s 1.3E5 cps SR 3.3.1.11 SR 3.3.1.14 3(a). 4(a), 6(a) 2 H, I SR 3.3.1.1 s 1.3E5 cps SR 3.3.1.11 SR 3.3.1.14 (a) With Rod Control System capable of rod withdrawal or one or more rods not fully inserted.
(b) Below the P-I0 (Power Range Neutron Flux) Interlock (c) Above the P-6 (Intermediate Range Neutron Flux) Interlock.
(d) Below the P-6 (Intermediate Range Neutron Flux) Interlock.
I Cook Nuclear Plant Unit 2 3.3.1-11 Amendment No. 2M, 275 l