ML081510893
| ML081510893 | |
| Person / Time | |
|---|---|
| Site: | Cook (DPR-058, DPR-074) |
| Issue date: | 05/28/2008 |
| From: | Tam P NRC/NRR/ADRO/DORL/LPLIII-1 |
| To: | Rencheck M Indiana Michigan Power Co |
| tam P, NRR/ADRO/DORL, 415-1451 | |
| Shared Package | |
| ML081510059 | List: |
| References | |
| TAC MD6317, TAC MD6318 | |
| Download: ML081510893 (2) | |
Text
AC Sources - Shutdown 3.8.2 SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.8.2.1 NOTE -------------------------------
The following SRs are not required to be performed:
SR 3.8..3, SR 3.8.1.10 through SR 3.8.1.12, SR 3.8.1.15 through SR 3.8.1.17, and SR 3.8.1.18.
For AC sources required to be OPERABLE, the SRs of Specification 3.8.1, "AC Sources -- Operating,"
except SR 3.8.1.9, SR 3.8.1.13, SR 3.8.1.14 (ESF actuation signal portion only), SR 3.8.1.19, SR 3.8.1.20, SR 3.8.1.21, and SR 3.8.1.22, are applicable.
In accordance with applicable SRs.
SR 3.8.2.2 One of the following SRs is applicable when the electrical distribution subsystem is being supplied by "backfeed" from an offsite source via the main transformer and a unit auxiliary transformer:
- a.
SR 3.8.1.9.a when the preferred offsite circuit is required to be OPERABLE by LCO 3.8.2.a, or
- b.
SR 3.8.1.9.b when the alternate offsite circuit is required to be OPERABLE by LCO 3.8.2.a.
In accordance with applicable SR Cook Nuclear Plant Unit 1 3.8.2-3 Amendment No. £87, 304 Corrected by letter of 5/28/08
AC Sources - Shutdown 3.8.2 SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY i
NOTE----------------
The following SRs are not required to be performed:
SR 3.8.1.3, SR 3.8.1.10 through SR 3.8.1.12, SR 3.8.1.15 through SR 3.8.1.17, and SR 3.8.1.18.
For AC sources required to be OPERABLE, the SRs of Specification 3.8.1, "AC Sources -- Operating,"
except SR 3.8.1.9, SR 3.8.1.13, SR 3.8.1.14 (ESF actuation signal portion only), SR 3.8.1.19, SR 3.8.1.20, SR 3.8.1.21, and SR 3.8.1.22, are applicable.
In accordance with applicable SRs i
SR 3.8.2.2 One of the following SRs is applicable when the electrical distribution subsystem is being supplied by "backfeed" from an offsite source via the main transformer and a unit auxiliary transformer:
- a.
SR 3.8.1.9.a when the preferred offsite circuit is required to be OPERABLE by LCO 3.8.2.a, or
- b.
SR 3.8.1.9.b when the alternate offsite circuit is required to be OPERABLE by LCO 3.8.2.a.
In accordance with applicable SR Cook Nuclear Plant Unit 2 3.8.2-3 Amendment No. -69, 287 Corrected by letter of 5/28/08