AC Sources - Shutdown 3.8.2 SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY i
SR "'.2.1,
NOTE ------------ ---- - --------
The following SRs are not required to be performed:
SR 3.8.1.3, SR 3.8.1.10 through SR 3.8.1.12, SR 3.8.1.15 through SR 3.8.1.17, and SR 3.8.1.18.
For AC sources required to be OPERABLE, the SRs of Specification 3.8.1, "AC Sources -- Operating,"
except SR 3.8.1.9, SR 3.8.1.13, SR 3.8.1.14 (ESF actuation signal portion only), SR 3.8.1.19, SR 3.8.1.20, SR 3.8.1.21, and SR 3.8.1.22, are applicable.
In accordance with applicable SRs SR 3.8.2.2 IN-,.4 I E------------------------------
Not required to be performed.
One of the following SRs is applicable when the electrical distribution subsystem is being supplied by "backfeed" from an offsite source via the main transformer and a unit auxiliary transformer:
- a.
SR 3.8.1.9.a when the preferred offsite circuit is required to be OPERABLE by LCO 3.8.2.a, or
- b.
SR 3.8.1.9.b when the alternate offsite circuit is required to be OPERABLE by LCO 3.8.2.a.
In accordance with applicable SR Cook Nuclear Plant Unit 1 3.8.2-3 Amendment No. 2-87, 304
AC Sources - Shutdown 3.8.2 SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SRN 3 NOTE --
The following SRs are not required to be performed:
SR 3.8.1.3, SR 3.8.1.10 through SR 3.8.1.12, SR 3.8.1.15 through SR 3.8.1.17, and SR 3.8.1.18.
For AC sources required to be OPERABLE, the SRs In accordance of Specification 3.8.1, "AC Sources -- Operating,"
with applicable except SR 3.8.1.9, SR 3.8.1.13, SR 3.8.1.14 (ESF SRs actuation signal portion only), SR 3.8.1.19, SR 3.8.1.20, SR 3.8.1.21, and SR 3.8.1.22, are applicable.
SR 3.8.2.2 NOTE Not required to be performed.
One of the following SRs is applicable when the In accordance electrical distribution subsystem is being supplied by with applicable "backfeed" from an offsite source via the main SR transformer and a unit auxiliary transformer:
- a.
SR 3.8.1.9.a when the preferred offsite circuit is required to be OPERABLE by LCO 3.8.2.a, or
- b.
SR 3.8.1.9.b when the alternate offsite circuit is required to be OPERABLE by LCO 3.8.2.a.
Cook Nuclear Plant Unit 2 3.8.2-3 Amendment No. 2-99, 287