ML052980008
| ML052980008 | |
| Person / Time | |
|---|---|
| Site: | Clinton (NPF-062) |
| Issue date: | 10/21/2005 |
| From: | NRC/NRR/DLPM |
| To: | |
| References | |
| TAC MC3295 | |
| Download: ML052980008 (76) | |
Text
SR Applicability 3.0 3.0 SURVEILLANCE REQUIREMENT (SR) APPLICABILITY SR 3.0.1 SRs shall be met during the MODES or other specified conditions in the Applicability for individual LCOs, unless otherwise stated in the SR.
Failure to meet a Surveillance, whether such failure is experienced during the performance of the Surveillance or between performances of the Surveillance, shall be failure to meet the LCO.
Failure to perform a Surveillance within the specified Frequency shall be failure to meet the LCO except as provided in SR 3.0.3.
Surveillances do not have to be performed on inoperable equipment or variables outside specified limits.
SR 3.0.2 The specified Frequency for each SR is met if the Surveillance is performed within 1.25 times the interval specified in the Frequency, as measured from the previous performance or as measured from the time a specified condition of the Frequency is met.
For Frequencies specified as "once," the above interval extension does not apply.
If a Completion Time requires periodic performance on a "once per.
basis, the above Frequency extension applies to each performance after the initial performance.
Exceptions to this Specification are stated in the individual Specifications.
SR 3.0.3 If it is discovered that a Surveillance was not performed within its specified Frequency, then compliance with the requirement to declare the LCO not met may be delayed, from the time of discovery, up to 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> or up to the limit of the specified Frequency, whichever is greater.
This delay period is permitted to allow performance of the Surveillance.
A risk evaluation shall be performed for any Surveillance delayed greater than 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> and the risk impact shall be managed.
If the Surveillance is not performed within the delay period, the LCO must immediately be declared not met, and the applicable Condition(s) must be entered.
(continued)
I CLINTON 3.0O-4 Amendment No.169
SLC System 3.1.7 SURVEILLANCE REQUIREMENTS (continued)
SURVEILLANCE FREQUENCY SR 3.1.7.7 Verify each pump develops a flow rate In accordance 2 41.2 gpm at a discharge pressure with the 2 1220 psig.
Inservice Testing Program SR 3.1.7.8 Verify flow through one SLC subsystem from 24 months on a pump into reactor pressure vessel.
STAGGERED TEST BASIS SR 3.1.7.9 Verify all piping between storage tank and 24 months pump suction is unblocked.
AND Once within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> after pump suction piping temperature is restored to
. 700F I
CLINTON 3.1-22 Amendment No.169
SDV Vent and Drain Valves 3.1.8 SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.1.8.1
NOTE--------------------
Not required to be met on vent and drain valves closed during performance of SR 3.1.8.2.
Verify each SDV vent and drain valve is 31 days open.
SR 3.1.8.2 Cycle each SDV vent and drain valve to the 92 days fully closed and fully open position.
SR 3.1.8.3 Verify each SDV vent and drain valve:
24 months
- a.
Closes in
- 30 seconds after receipt of an actual or simulated scram signal; and
- b.
Opens when the actual or simulated scram signal is reset.
I CLINTON 3.1-25 Amendment No. 1 6 9
RPS Instrumentation 3.3.1.1 SURVEILLANCE REQUIREMENTS (continued)
SURVEILLANCE FREQUENCY SR 3.3.1.1.11
NOTES-----------------
- 1. Neutron detectors are excluded.
- 2. For function 2.a, not required to be performed when entering MODE 2 from MODE 1 until 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> after entering MODE 2.
Perform CHANNEL CALIBRATION.
184 days SR 3.3.1.1.12 Perform CHANNEL FUNCTIONAL TEST.
24 months SR 3.3.1.1.13
NOTES-----------------
- 1. Neutron detectors are excluded.
- 2. For IRMs, not required to be performed when entering MODE 2 from MODE 1 until 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> after entering MODE 2.
Perform CHANNEL CALIBRATION.
24 months SR 3.3.1.1.14 Verify the APRM Flow Biased Simulated 24 months Thermal Power-High time constant is within the limits specified in the COLR.
SR 3.3.1.1.15 Perform LOGIC SYSTEM FUNCTIONAL TEST.
24 months (continued)
CLINTON 3.3-5 Amendment No-16 9
RPS Instrumentation 3.3.1.1 SURVEILLANCE REQUIREMENTS (continued)
SURVEILLANCE FREQUENCY SR 3.3.1.1.16 Verify Turbine Stop Valve Closure and 24 months Turbine Control Valve Fast Closure Trip Oil Pressure-Low Functions are not bypassed when THERMAL POWER is > 33.3%
RTP.
SR 3.3.1.1.17
NOTES------------------
- 1.
Neutron detectors are excluded.
- 2.
For Functions 3, 4, and 5 in Table 3.3.1.1-1, the channel sensors are excluded.
- 3.
The STAGGERED TEST BASIS Frequency for each Function shall be determined on a per channel basis.
Verify the RPS RESPONSE TIME is within 24 months on a limits.
STAGGERED TEST BASIS V
CLINTON 3.3 -6 Amendment NoI69
SRM Instrumentation 3.3.1.2 SURVEILLANCE REQUIREMENTS (continued)
SURVEILLANCE FREQUENCY SR 3.3.1.2.4
NOTE-------------------
Not required to be met with less than or equal to four fuel assemblies adjacent to the SRPI.
and no other fuel assemblies in the associated core quadrant.
Verify count rate is a 3.0 cps.
12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> during CORE ALTERATIONS AND 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> SR 3.3.1.2.5
NOTE-------------------
Not required to be performed until 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> after IRMs on Range 2 or below.
Perform CHANNEL FUNCTIONAL TEST.
31 days SR 3.3.1.2.6
NOTES------------------
- 1.
Neutron detectors are excluded.
- 2.
Not required to be performed until 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> after IRMs on Range 2 or below.
Pf CH_____NEL_
CALIB__ATION._
24__months_
Perform CHANNEL CALIBRATION.
24 months I
CLINTON 3.3 -13 Amendment No. 169
Control Rod Block Instrumentation 3.3.2.1 SURVEILLANCE REQUIREMENTS (continued)
SURVEILLANCE FREQUENCY SR 3.3.2.1.4
NOTE-------------------
Not required to be performed until 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> after THERMAL POWER is 5 16.7% RTP in MODE 1.
Perform CHANNEL FUNCTIONAL TEST.
92 days SR 3.3.2.1.5 Calibrate the low power setpoint analog 92 days trip modules.
The Allowable Value shall be > 16.7% RTP and s 29.2% RTP.
SR 3.3.2.1.6 Verify the RWL high power Function is not 92 days bypassed when THERMAL POWER is > 70% RTP.
SR 3.3.2.1.7 Perform CHANNEL CALIBRATION.
24 months SR 3.3.2.1.8
NOTE-------------------
Not required to be performed until 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> after reactor mode switch is in the shutdown position.
Perform CHANNEL FUNCTIONAL TEST.
24 months SR 3.3.2.1.9 Verify the bypassing and movement of Prior to and control rods required to be bypassed in during the Rod Action Control System (RACS) is in movement of conformance with applicable analyses by a control rods second licensed operator or other bypassed in qualified member of the technical staff.
RACS I
I CLINTON 3.3 -17 Amendment No. 169
PAM Instrumentation 3.3.3.1 SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.3.3.1.1
NOTE---------------------
Applicable for each Function in Table 3.3.3.1-1.
Perform CHANNEL CHECK.
31 days SR 3.3.3.1.2 Deleted SR 3.3.3.1.3
NOTE---------------------
Applicable for each Function in Table 3.3.3.1-1.
Perform CANEL CAIRAIN 24 months_______
Perform CHANNEL CALIBRATION.
24 months I
CLINTON 3.3-21 Amendment No.169
Remote Shutdown System 3.3.3.2 SURVEILLANCE REQUIREMENTS (continued)
SURVEILLANCE FREQUENCY SR 3.3.3.2.2 Verify each required control circuit and 24 months transfer switch is capable of performing the intended functions.
SR 3.3.3.2.3 Perform CHANNEL CALIBRATION for each 24 months required instrumentation channel.
I I
CLINTON 3.3-24 Amendment No. 169
EOC-RPT Instrumentation 3.3.4.1 SURVEILLANCE REQUIREMENTS (continued)
SURVEILLANCE FREQUENCY SR 3.3.4.1.2 Perform CHANNEL CALIBRATION.
The 24 months Allowable Values shall be:
- a.
- b.
TCV Fast Closure, Trip Oil Pressure-Low: t 465 psig.
SR 3.3.4.1.3 Perform LOGIC SYSTEM FUNCTIONAL TEST, 24 months including breaker actuation.
SR 3.3.4.1.4 Verify TSV Closure and TCV Fast Closure, 24 months Trip Oil Pressure-Low Functions are not bypassed when THERMAL POWER is 2 33.3%
RTP.
NOTE-----------------
The STAGGERED TEST BASIS Frequency shall be determined on a per Function basis.
Verify the EOC-RPT SYSTEM RESPONSE TIME 24 months on a is within limits.
STAGGERED TEST BASIS CLINTON
- 3. 3-27 Amendment No. 169
ATWS-RPT Instrumentation 3.3.4.2 ACTIONS (continued)_
CONDITION REQUIRED ACTION COMPLETION TIME C.
Required Action and C.l Remove the associated 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> associated recirculation pump from Completion Time not service.
met.
OR C.2 Be in MODE 2.
6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.3.4.2.1 Perform CHANNEL CHECK.
12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> SR 3.3.4.2.2 Perform CHANNEL FUNCTIONAL TEST.
92 days SR 3.3.4.2.3 Calibrate the trip units.
92 days SR 3.3.4.2.4 Perform CHANNEL CALIBRATION. The 24 months Allowable Values shall be:
- a. Reactor Vessel Water Level-Low Low, Level 2: 2 -50.0 inches; and
- b. Reactor Steam Dome Pressure-High:
- 1143 psig.
SR 3.3.4.2.5 Perform LOGIC SYSTEM FUNCTIONAL TEST, 24 months including breaker actuation.
I CLINTON 3.3 -29 Amendment No.169
ECCS Instrumentation 3.3.5.1 SURVEILLANCE REQUIREMENTS
NOTES------------------------------------
- 1.
Refer to Table 3.3.5.1-1 to determine which SRs apply for each ECCS Function.
- 2. When a channel is placed in an inoperable status solely for performance of required Surveillances, entry into associated Conditions and Required Actions may be delayed as follows:
(a) for up to 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> for Functions 3.c, 3.f, 3.g, and 3.h; and (b) for up to 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> for Functions other than 3.c, 3.f, 3.g, and 3.h, provided the associated Function or the redundant Function maintains ECCS initiation capability.
SURVEILLANCE FREQUENCY SR 3.3.5.1.1 Perform CHANNEL CHECK.
12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> SR 3.3.5.1.2 Perform CHANNEL FUNCTIONAL TEST.
92 days SR 3.3.5.1.3 Calibrate the analog trip module.
92 days SR 3.3.5.1.4 Perform CHANNEL CALIBRATION.
24 months SR 3.3.5.1.5 Perform LOGIC SYSTEM FUNCTIONAL TEST.
24 months SR 3.3.5.1.6 Perform CHANNEL CALIBRATION.
18 months I
I I
CLINTON 3.3 -38 Amendment No-169
ECCS Ins trumentat ion 3.3.5.1 Table 3.3.5.1-1 (page 1 of 5)
Emergency Core Cooling System Instrumentation APPLICABLE CONDITIONS MODES OR REFERENCED OTHER REQUIRED FROM SPECIFIED CHANNELS REQUIRED SURVEILLANCE ALLOWABLE FUNCTION CONDITIONS PER ACTION A.1 REQUIREMENTS VALUE FUNCTION
- 1. Low Pressure Coolant Injection-A (LPCI) and Low Pressure Core Spray (LPCS)
Subsystems
- a. Reactor Vessel Water Level-Low Low Low, Level 1 1,2,3, 4 (tx, 5 ()
2 lb)
B SR SR SR SR SR 3.3.5.1.1 3.3.5.1.2 3.3.5. 1.3 "
3.3.5.1.5 3.3.5.1.6"'
2 -148.1 inches I
- b. Drywell Pressure-High 1,2,3 2
Mlb B
SR SR SR SR SR 3.3.5.1.1 3.3.5.1.2 3.3.5.1.3 3.3.5.1.4 3.3.5.1.5 5 1.88 psig C. LPCI Pump A Start-Time Delay Logic Card
- d. Reactor Vessel Pressure-Low (Injection Permissive)
- e. LPCS Pump Discharge Flow-Low (Bypass) 1,2,3, 4(), 5(0) 1,2,3 4Vl, 5(03 1,2,3, 4(o, 5'&
1 4
4 1
C SR 3.3.5.1.2 SR 3.3.5.1.4 SR 3.3.5.1.5 C
SR SR SR SR SR B
SR SR SR SR SR E
SR SR SR SR SR E
SR SR SR SR SR 3.3.5.1.1 3.3.5.1.2 3.3.5.1.34' 3.3.5.1.4 3.3.5.1.5 3.3. 5. 1.1 3.3.5.1.2 3.3.5.1.34e 3.3.5.1.410
- 3. 3.5.1.5 3.3.5.1.1 3.3.5.1.2 3.3.5.1. 3 3.3.5.1.4 3.3.5.1.5 3.3.5.1.1 3.3.5.1.2 3.3.5.1.3 3.3.5.1.4 3.3. 5.1.5 2 4.5 seconds and S 5.5 seconds 2 454 psig and 5 494 psig 2 454 psig and 5 494 psig 2 750 gpm
- f.
LPCI Pump A Discharge Flow-Low (Bypass) 1,2,3, 401,5(&)
1 2 900 gpm
- g.
Manual Initiation 1,2,3, 4(&0, 51(0 1
C SR 3.3.5.1.5 NA (continued)
(a) When associated subsystems) are required to be OPERABLE.
(b) Also required to initiate the associated diesel generator.
{e) 1. If the as-found channel setpoint is conservative with respect to the Allowable Value but outside its predefined As-Found Tolerance band, then the channel shall be evaluated to verify that it is functioning as required before returning the channel to service.
If the as-found instrument channel setpoint is not conservative with respect to the Allowable Value, the channel shall be declared inoperable.
- 2. The instrument channel setpoint shall be reset to a value within the As-Left Tolerance of the Actual Trip Setpoint; otherwise, the channel shall be declared inoperable.
- 3. The Nominal Trip Setpoint and the methodology used to determine the Nominal Trip Setpoint, the predefined As-Found Tolerance and As-Left Tolerance bands shall be specified in the ORM.
CLINTON 3.3 -3 9 Amendment No.169
ECCS Instrumentation 3.3.5.1 Table 3.3.5.1-1 (page 2 of 5)
Emergency Core Cooling System Instrumentation APPLICABLE CONDITIONS MODES OR REFERENCED OTHER REQUIRED FROM SPECIFIED CHANNELS PER REQUIRED SURVEILLANCE ALLOWABLE FUNCTION CONDITIONS FUNCTION ACTION A.1 REQUIREMENTS VALUE
- 2.
- a. Reactor Vessel Water 1,2,3, 2 IbI B
SR 3.3.5.1.1 2 -148.2 Level-Low Low Low, SR 3.3.5.1.2 inches Level 1 4' ',5' '
SR 3.3.5.13.3 SR 3.3.5.1.5 SR 3.3.5.1.6s
- b. Drywell Pressure-High 1.2,3 2tb)
B SR 3.3.5.1.1 S 1.88 psig SR 3.3.5.1.2 SR 3.3.5.1.3 SR 3.3.5.1.4 SR 3.3.5.1.5
- c. LPCI Pump B 1,2.3.
1 C
SR 3.3.5.1.2 2 4.5 seconds Start-Time Delay SR 3.3.5.1.4 and Logic Card 4 &),S'^
SR 3.3.5.1.5 S 5.5 seconds
- d. Reactor Vessel 1.2.3 4
C SR 3.3.5.1.1 2 454 psig Pressure-Low SR 3.3.5.1.2 and (Injection SR 3.3.5.-13
< 494 si Permissive)
SR 3.3.5.1.4'e P 9 SR 3.3.5.1.5 41-1,5(I) 4 B
SR 3.3.5.1.1 2 454 psig SR 3.3.5.1.2 and SR 3.3.5.1.34")
SR 3.
.14.
- 5 49 psig SR 3.3.5.1.5
SR 3.3.5.1.1 2 900 gpm Pump C Discharge SR 3.3.5.1.2 Flow-Low (Bypass) 4' ',5'l' SR 3.3.5.1.3 SR 3.3.5.1.4 SR 3.3.5.1.5
- f. Manual Initiation 1,2,3, 1
C SR 3.3.5.1.5 NA 4 (a), 5)
(continued)
I (a) When associated subsystems) are required to be OPERABLE.
(b) Also required to initiate the associated diesel generator.
(e) 1. If the as-found channel setpoint is conservative with respect to the Allowable Value but outside its predefined As-Found Tolerance band, then the channel shall be evaluated to verify that it is functioning as required before returning the channel to service.
If the as-found instrument channel setpoint is not conservative with respect to the Allowable Value, the channel shall be declared inoperable.
- 2. The instrument channel setpoint shall be reset to a value within the As-Left Tolerance of the Actual Trip Setpoint; otherwise, the channel shall be declared inoperable.
- 3. The Nominal Trip Setpoint and the methodology used to determine the Nominal Trip Setpoint, the predefined As-Found Tolerance and As-Left Tolerance bands shall be specified in the ORM.
CLINTON 3.3 -40 Amendment No. 169
ECCS Instrumentation 3.3.5.1 Table 3.3.5.1-1 (page 3 of S)
Emergency Core Cooling System Instrumentation APPLICABLE CONDITIONS MODES OR REFERENCED OTHER REQUIRED FROM SPECIFIED CHANNELS PER REQUIRED SURVEILLANCE ALL4WABLE FUNCTION CONDITIONS FUNCTION ACTION A.1 REQUIREMENTS VALUE
- 3. High Pressure Core Spray (HPCS) System
- a. Reactor Vessel Water Level-Low Low, Level 2
- b.
Drywell Pressure - High
- c. Reactor Vessel Water Level-High, Level 8 1,2,3, 1,2.3 1.2,3, 4
.5 (.
4 lb) 2
- d. RCIC Storage Tank Level-Low
- e. Suppression Pool Water Level-High
- f. HPCS Pump Discharge Pressure-High (Bypass)
- g.
HPCS System Flow Rate-Low (Bypass) 1,2,3, 1.2,3 1,2,3, 4 t*,51) 1,2,3,
- 41. 5 (4) 2 2
1 1
B SR SR SR SR SR B
SR SR SR SR SR C
SR SR SR SR SR D
SR SR SR SR SR D
SR SR SR SR SR E
SR SR SR SR SR E
SR SR SR SR SR 3.3.5.1.1 3.3.5. 1. 2 3.3.5.1.3 3.3.5.1.5 3.3.5.1.6 3.3.5.1.1 3.3.5.2.2 3.3.5.1.3 3.3.5.1.4 3.3.5.1.5 3.3.5.1.1 3.3.5.1.2 3.3.5.2.3 3.3.5.1.5 3.3.5. 1.060 3.3.5.1.1 3.3.5.1.2 3.3.5.1.3"'
3.3.5.1.4 t 3.3.5.1.5 3.3.5.1.1 3.3.5.1.2 3.3.5.1.354' 3.3.5.1.4 3.3.5.1.5 3.3.5.1.1 3.3.5.1.2 3.3.5.1.3 3.3.5.1.4 3.3.5.1.5 3.3.5.1.1 3.3.5.1.2 3.3.5.1.3 3.3.5.1.4 3.3.5.1.5 I
Z -48.1 inches I
S 1.88 psig S 54.6 inches 2 3.0 inches 5 11 inches 2 120 psig 2 500 gpm
- h. Manual Initiation 1,2,3, 4 (s),514 I
C SR 3.3.5.1.5 NA (continued)
(a)
(b)
{c)
(e)
When associated subsystem(s) are required to be OPERABLE.
Also required to initiate the associated diesel generator.
When HPCS is OPERABLE for compliance with LCO 3.5.2, *ECCS-Shutdown," and aligned to the RCIC storage tank while tank water level is not within the limits of SR 3.5.2.2.
- 1. If the as-found channel setpoint is conservative with respect to the Allowable Value but outside its predefined As-Found Tolerance band, then the channel shall be evaluated to verify that it is functioning as required before returning the channel to service.
If the as-found instrument channel setpoint is not conservative with respect to the Allowable Value, the channel shall be declared inoperable.
- 2. The instrument channel setpoint shall be reset to a value within the As-Left Tolerance of the Actual Trip Setpoint; otherwise, the channel shall be declared inoperable.
- 3. The Nominal Trip Setpoint and the methodology used to determine the Nominal Trip Setpoint, the predefined As-Found Tolerance and As-Left Tolerance bands shall be specified in the ORM.
CLINTrON 3.3 -4 1 Amendment No.169
ECCS Instrumentation 3.3.5.1 Table 3.3.5.1-1 (page 4 of 5)
Emergency Core Cooling System Instrumentation APPLICABLE CONDITIONS MODES OR REFERENCED OTHER REQUIRED FROM SPECIFIED CHANNELS PER REQUIRED SURVEILLANCE ALLOWABLE FUNCTION CONDITIONS FUNCTION ACTION A.1 REQUIREMENTS VALUE
- 4. Automatic Depressurization System (ADS) Trip System 1 (Logic A and E)
- a. Reactor Vessel Water 1, 2Cd), 3 d) 2 F
SR 3.3.5.1.1 2 -148.1 inches Level-Low Low Low, SR 3.3.5.1.2 Level 1 SR 3.3.5.1.3{"
SR 3.3.5.1.5 SR 3.3.5.1.6"'
- b. Drywell 1, 2 d, 3Id 2
F SR 3.3.5.1.1 5 1.88 psig Pressure-Nigh SR 3.3.5.1.2 SR 3.3.5.1.3 SR 3.3.5.1.4 SR 3.3.5.1.5
- c. ADS Initiation Timer 1, 2 1d), 3Id) 1 G
- 117 seconds SR 3.3.5.1.4 SR 3.3.5.1.5
- d. Reactor Vessel Water 1, 21d, 3 'dl 1
F SR 3.3.5.1.1 2 8.3 inches Level-Low, Level 3 SR 3.3.5.1.2 (Confirmatory)
SR 3.3.5.1.3 SR 3.3.5.1.4 SR 3.3.5.1.5
- e. LPCS Pump Discharge 1 2Id) 3Id) 2 G
SR 3.3.5.1.1 2 125 psig and Pressure-High SR 3.3.5.1.2 176.3 psig SR 3.3.5.1.3'.1 SR 3.3.5.1.4"'
- f. LPCI Pump A 1,2 WI 3 WI 2
G SR 3.3.5.1.1 2 115 psig and Discharge Pressure-SR 3.3.5.1.2
< 135 psig High SR 3.3.5.1.31 SR 3.3.5.1.4' SR 3.3.5.1.5
- g.
ADS Drywell Pressure 1,2 d,3Id) 2 G
SR 3.3.5.1.2 5 6.5 minutes Bypass Timer SR 3.3.5.1.4 SR 3.3.5.1.5
- h. Manual Initiation 1 21d, 31d) 2 G
SR 3.3.5.1.5 NA (continued)
I (d) With reactor steam dome pressure > 150 psig.
(e) 1.
If the as-found channel setpoint is conservative with respect to the Allowable Value but outside its predefined As-Found Tolerance band, then the channel shall be evaluated to verify that it is functioning as required before returning the channel to service.
If the as-found instrument channel setpoint is not conservative with respect to the Allowable Value, the channel shall be declared inoperable.
- 2. The instrument channel setpoint shall be reset to a value within the As-Left Tolerance of the Actual Trip Setpoint; otherwise, the channel shall be declared inoperable.
- 3. The Nominal Trip Setpoint and the methodology used to determine the Nominal Trip Setpoint.
the predefined As-Found Tolerance and As-Left Tolerance bands shall be specified in the ORM.
CLINTON 3.3 -4 2 Amendment No.169
ECCS Instrumentation 3.3.5.1 Table 3.3.5.1-1 (page 5 of 5)
Emergency Core Cooling System Instrumentation APPLICABLE CONDITIONS MODES OR REFERENCED OTHER REQUIRED FROM SPECIFIED CHANINELS PER REQUIRED SURVEILLANCE ALLOWABLE FUNCTION CONDITIONS FUNCTION ACTION A. 1 REQUIREMENTS VALUE
- 5. ADS Trip System 2 (Logic B and F)
- a. Reactor Vessel Water 1, 2(d, 3(d 2
F SR 3.3.5.1.1 2 -148.1 Level-Low Low Low, SR 3.3.5.1.2 inches Level 1 SR 3.3.5.1.3
SR 3.3.5.1.5 SR 3.3.5.1.6"'
- b. vrywell Pressure-High 1,2 (d), 3 (d) 2 F
SR 3.3.5.1.1 2 1.88 psig SR 3.3.5.1.2 SR 3.3.5.1.3 SR 3.3.5.1.4 SR 3.3.5.1.5
- c.
ADS Initiation Timer 1, 2 1dI 3Id' 1
G SR 3.3.5.1.2 S 117 seconds SR 3.3.5.1.4 SR 3.3.5.1.5
- d. Reactor Vessel Water 1,2 td),3cd) 1 F
SR 3.3.5.1.1 2 8.3 inches Level-Low, Level 3 SR 3.3.5.1.2 (Confirmatory)
SR 3.3.5.1.3 SR 3.3.5.1.4 SR 3.3.5.1.5
- e.
LPCI Pumps B & C 1, 2d, 3Ed) 2 per pump G
SR 3.3.5.1.1 2 115 psig Discharge SR 3.3.5.1.2 Pressure -High SR 335 and 1
135 SR 3.
.4.
psig SR 3.3.5.1.5
- f. ADS Drywell Pressure 12 2
G SR 3.3.5.1.2 6.5 minutes Bypass Timer SR 3.3.5.1.4 SR 3.3.5.1.5
- g. Manual Initiation 1
2d), 3 d) 2 G
SR 3.3.5.1.5 NA I
(d)
With reactor steam dome pressure > 150 psig.
(e) 1.
If the as-found channel setpoint is conservative with respect to the Allowable Value but outside its predefined As-Found Tolerance band, then the channel shall be evaluated to verify that it is functioning as required before returning the channel to service.
If the as-found instrument channel setpoint is not conservative with respect to the Allowable Value, the channel shall be declared inoperable.
- 2.
The instrument channel setpoint shall be reset to a value within the As-Left Tolerance of the Actual Trip Setpoint; otherwise, the channel shall be declared inoperable.
- 3.
The Nominal Trip Setpoint and the methodology used to determine the Nominal Trip Setpoint, the predefined As-Found Tolerance and As-Left Tolerance bands shall be specified in the ORM.
CLINTON 3.3-4 3 Amendment No. 169
RCIC System Instrumentation 3.3.5.2 SURVEILLANCE REQUIREMENTS
NOTES-------------------------------------
- 1. Refer to Table 3.3.5.2-1 to determine which SRs apply for each RCIC Function.
- 2. When a channel is placed in an inoperable status solely for performance of required Surveillances, entry into associated Conditions and Required Actions may be delayed as follows:
(a) for up to 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> for Functions 2 and 5; and (b) for up to 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> for Functions 1, 3, and 4 provided the associated Function maintains RCIC initiation capability.
SURVEILLANCE FREQUENCY SR 3.3.5.2.1 Perform CHANNEL CHECK.
12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> SR 3.3.5.2.2 Perform CHANNEL FUNCTIONAL TEST.
92 days SR 3.3.5.2.3 Calibrate the analog trip module.
92 days SR 3.3.5.2.4 Perform CHANNEL CALIBRATION.
24 months SR 3.3.5.2.5 Perform LOGIC SYSTEM FUNCTIONAL TEST.
24 months SR 3.3.5.2.6 Perform CHANNEL CALIBRATION.
18 months I
I I
CLINTON 3.3-46 Amendment No.169
RCIC System Instrumentation 3.3.5.2 Table 3.3.5.2-1 (page 1 of 1)
Reactor Core Isolation Cooling System Instrumentation CONDITIONS REQUIRED REFERENCED FROM CHANNELS PER REQUIRED ACTION SURVEILLANCE ALLOWABLE FUNCTION FUNCTION A.1 REQUIREMENTS VALUE
- 1. Reactor Vessel Water 4
B SR 3.3.5.2.1 2 -48.1 inches Level-Low Low, Level 2 SR 3.3.5.2.2 SR 3.3.5.2.3 SR 3.3.5.2.5 SR 3.3.5.2.6
- 2.
Reactor Vessel Water 2
C SR 3.3.5.2.1 S 52.6 inches Level-High, Level 8 SR 3.3.5.2.2 SR 3.3.5.2.3 SR 3.3.5.2.4 SR 3.3.5.2.5
- 3.
RCIC Storage Tank 2
D SR 3.3.5.2.1 2 3.0 inches Level-Low SR 3.3.5.2.2 SR 3.3.5.2.3 SR 3.3.5.2.4 SR 3.3.5.2.5
- 4. Suppression Pool Water 2
D SR 3.3.5.2.1 LI -5 inches Level-High SR 3.3.5.2.2 SR 3.3.5.2.3 SR 3.3.5.2.4 SR 3.3.5.2.5
- 5. Manual Initiation 1
C SR 3.3.5.2.5 NA CLINTON 3.3-47 Amendment No. 169
Primary Containment and Drywell Isolation Instrumentation 3.3.6.1 SURVEILLANCE REQUIREMENTS
NOTES-------------------------------------
- 1. Refer to Table 3.3.6.1-1 to determine which SRs apply for each Primary Containment and Drywell Isolation Function.
- 2. When a channel is placed in an inoperable status solely for performance of required Surveillances, entry into associated Conditions and Required Actions may be delayed for up to 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />, provided the associated Function maintains isolation capability.
SURVEILLANCE FREQUENCY SR 3.3.6.1.1 Perform CHANNEL CHECK.
12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> SR 3.3.6.1.2 Perform CHANNEL FUNCTIONAL TEST.
92 days SR 3.3.6.1.3 Calibrate the analog trip module.
92 days SR 3.3.6.1.4 Perform CHANNEL CALIBRATION.
92 days SR 3.3.6.1.5 Perform CHANNEL CALIBRATION.
24 months SR 3.3.6.1.6 Perform LOGIC SYSTEM FUNCTIONAL TEST.
24 months SR 3.3.6.1.7
NOTE---------------------
- 1. Channel sensors are excluded.
- 2. The STAGGERED TEST BASIS Frequency for each Function shall be determined on a per channel basis.
Verify the ISOLATION SYSTEM RESPONSE TIME 24 months on a for the main steam isolation valves is STAGGERED TEST within limits.
BASIS SR 3.3.6.1.8 Perform CHANNEL CALIBRATION.
18 months CLINTON 3.3 -54 Amendment No.169
Primary Containment and Drywell Isolation Instrumentation 3.3.6.1 Table 3.3.6.1-1 (page 1 of 6)
Primary Containment and Drywell Isolation Instrumentation APPLICABLE CONDITIONS MODES OR REQUIRED REFERENCED OTHER CHANNELS FROM SPECIFIED PER REQUIRED SURVEILLANCE ALLOWABLE FUNCTION CONDITIONS FUNCTION ACTION F.1 REQUIREMENTS VALUE
- 1.
Main Steam Line Isolation
- a. Reactor Vessel Water 1,2,3 4
G SR 3.3.6.1.1 2 -148.1 Level-Low Low Low, SR 3.3.6.1.2 inches Level 1 SR 3.3.6.1.3 SR 3.3.6.1.6 SR 3.3.6.1.7 SR 3.3.6.1.8
- b. Main Steam Line 1
4 H
SR 3.3.6.1.1 2 841 psig Pressure-Low SR 3.3.6.1.2 SR 3.3.6.1.3 SR 3.3.6.1.5 SR 3.3.6.1.6 SR 3.3.6.1.7
- c. Main Steam Line 1,2,3 4
G SR 3.3.6.1.1 S 284 psid Flow-High SR 3.3.6.1.2 SR 3.3.6.1.3 SR 3.3.6.1.5 SR 3.3.6.1.6 SR 3.3.6.1.7
- d. Condenser Vacuum-Low 1,21, 4
Ž 7.6 inches SR 3.3.6.1.2 Hg vacuum SR 3.3.6.1.3 SR 3.3.6.1.5 SR 3.3.6.1.6
- e. Main Steam Tunnel 1.2,3 4
G SR 3.3.6.1.1 S 171*F Temperature-High SR 3.3.6.1.2 SR 3.3.6.1.5 SR 3.3.6.1.6
- f.
Main Steam Line Turbine 1,2.3 4
G SR 3.3.6.1.1 Modules 1-4 Building SR 3.3.6.1.2 S 1426F, Temperature-High SR 3.3.6.1.5 Module 5 SR 3.3.6.1.6 5 150F
- g. Manual Initiation 1,2,3 4
J SR 3.3.6.1.6 NA (continued)
I (a) With any turbine stop valve not closed.
CLINTON 3.3 -55 Amendment No.169
Primary Containment and Drywell Isolation Instrumentation 3.3.6.1 Table 3.3.6.1-1 (page 2 of 6)
Primary Containment and Drywell Isolation Instrumentation APPLICABLE CONDITIONS MODES OR REQUIRED REFERENCED OTHER CHANNELS FROM SPECIFIED PER REQUIRED SURVEILLANCE ALLOWABLE FUNCTION CONDITIONS FUNCTION ACTION F.1 REQUIREMENTS VALUE
- 2.
Primary Containment and Drywell Isolation
- a. Reactor Vessel Water Level-Low Low, Level 2 1,2,3 4 b)
K SR SR SR SR SR 3.3.6.1.1 3.3.6.1.2 3.3.6.1.3 3.3.6.1.6 3.3.6.1.8 a -48.1 inches I
IC) 4 4 (b) 0 SR SR SR SR SR K
SR SR SR SR SR 3.3.6.1.1 3.3.6.1.2 3.3.6.1.3 3.3.6.1.6 3.3.6.1.8 3.3. 6.1.1 3.3.6.1.2
- 3. 3. 6. 1.3 3.3.6.1.5 3.3.6.1.6 2 -48.1 inches I
- b. Drywell Pressure-High 1,2,3 5 1.88 psig
- c. Deleted
- d. Drywell Pressure-High MECCS Divisions 1 and 21 1,2,3
- e. Reactor Vessel Water Level-Low Low, Level 2 (HPCS NSPS Div 3 and 4)
- f. Drywell Pressure-High (HPCS NSPS Div 3 and 4) 1,2.3 1.2,3 4
4 I
SR SR SR SR SR I
SR SR SR SR SR I
SR SR SR SR SR 3.3. 6. 1.1 3.3.6.1.2 3.3.6.1.3 3.3.6. 1.5 3.3.6.1.6 3.3.6.1.1 3.3.6.1.2 3.3.6.1.3 3.3.6.1.6 3.3.6.1.8 3.3.6.1.1
- 3. 3.6. 1.2 3.3.6.1.3 3.3.6.1.5 3.3.6. 1.6 S 1.88 psig 2 -48.1 inches I
S 1.88 psig (continued)
(b) Also required to initiate the associated drywell isolation function.
Cc) During operations with a potential for draining the reactor vessel.
CLINTON 3.3-56 Amendment No.169
Primary Containment and Drywell Isolation Instrumentation 3.3.6.1 Table 3.3.6.1-1 (page 3 of 6)
Primary Containment and Drywell Isolation Instrumentation APPLICABLE CONDITIONS MODES OR REQUIRED REFERENCED OTHER CHANNELS FROM SPECIFIED PER REQUIRED SURVEILLANCE ALLOWABLE FUNCTION CONDITIONS FUNCTION ACTION F.1 REQUIREMENTS VALUE j
- 2. Primary Containment and Drywell Isolation (continued)
- g. Containment Building Fuel Transfer Pool Ventilation Plenum Radiation-High
- h. Containment Building Exhaust Radiation-High le). (dl 1,2,3 W.* Id)
- i. Containment Building Continuous Containment Purge tCCP) Exhaust Radiation-High J. Reactor Vessel Water Level-Low Low Low, Level 1
- k. Containment Pressure-High
- 1. Manual Initiation 1,2,3 WC)
. (dl 1,2,3 (CI 1,2,3 ICl. Id) 4 4 1b" 4
4 Ib 4
4 1b) 4 2
2 (b) 2 U
SR SR SR SR I
SR SR SR SR N
SR SR SR SR I
SR SR SR SR N
SR SR SR SR I
SR SR SR SR SR 0
SR SR SR SR SR I
SR SR SR SR J
SR N
SR 3.3.6.1.1 3.3.6.1.2 3.3.6.1.5 3.3.6.1.6 3.3.6.1.1 3.3.6.1.2 3.3.6.1.5 3.3.6.1.6 3.3.6.1.1 3.3.6.1.2 3.3. 6.1.5 3.3.6.1.6 3.3.6.1.1 3.3.6.1.2 3.3.6. 1.5 3.3. 6.1.6 3.3.6. 1.1 3.3. 6.1.2 3.3.6.1.5 3.3.6.1.6 3.3.6.1.1 3.3.6.1.2 3.3.6.1.3 3.3.6.1.6 3.3.6. 1.8 3.3.6.1.1 3.3.6. 1.2 3.3.6. 1.3 3.3.6.1.6 3.3.6.1.8 3.3.6.1.1 3.3.6.1.2 3.3.6.1.5 3.3.6.1.6 3.3.6. 1.6 3.3.6.1.6 S 500 mR/hr S 400 mR/hr S 400 mR/hr S 400 mR/hr
- 400 mR/hr 2 -148.1 inches I
2 -148.1 inches 3.0 psid NA 11A (continued)
(b)
Also required to initiate the associated drywell isolation function.
(c) During operations with a potential for draining the reactor vessel.
(d)
(e)
During movement of recently irradiated fuel assemblies in the primary or secondary containment.
MODES 1, 2, and 3 with the associated PCIVs not closed.
CLINTON
- 3. 3 -57 Amendment No.169
Primary Containment and Drywell Isolation Instrumentation 3.3.6.1 Table 3.3.6.1-1 (page 4 of 6)
Primary Containment and Drywell Isolation Instrumentation APPLICABLE CONDITIONS MODES OR REQUIRED REFERENCED OTHER CHANNELS FROM SPECIFIED PER REOUIRED SURVEILLA1CE ALLOWABLE FUNCTION CONDITIONS FUNCTION ACTION F.1 REQUIREMENTS VALUE
- 3. Reactor Core Isolation Cooling (RCIC) System Isolation
- a. Auxiliary Building RCIC Steam Line Flow-High 1,2,3 SR SR SR SR SR 3.3.6.1.1 3.3.6.1.2 3.3.6.1.3 3.3.6.1.5 3.3.6.1.6 5 118.5 inches water
- b. RCIC Steam Line Flow-High, Time Delay
- c. RCIC Steam Supply Line Pressure-Low
- e. RCIC Equipment Room Ambient Temperature-High
- f. Main Steam Line Tunnel Ambient Temperature-High 1,2,3 SR 3.3.6.1.2 SR 3.3.6.1.5 SR 3.3.6.1.6 S 13 seconds 1,2,3 1,2,3 1,2,3 1,2,3 2
4 2
2 I
SR SR SR SR SR I
SR SR SR SR SR I
SR SR SR SR I
SR SR SR SR 3.3.6.1.1 3.3.6.1.2 3.3.6.1.3 3.3.6.1.5 3.3.6.1.6 3.3.6.1.1 3.3.6.1.2 3.3.6.1.3 3.3.6.1.5 3.3.6.1.6 3.3.6.1.1 3.3.6.1.2 3.3.6. 1.5 3.3.6.1.6 3.3.6.1.1 3.3.6.1.2 3.3.6.1.5 3.3.6.1.6 2 52 psig S 20 psig S 207'F S 171OF
- g. Main Steam Line Tunnel Temperature Timer 1,2,3 2
I SR 3.3.6.1.2 SR 3.3.6.1.5 SR 3.3.6.1.6 S 28 minutes
- h. Reactor Vessel Water Level-Low Low, Level 2
- i. Drywell RCIC Steam Line Flow - High 1.2,3 I
SR SR SR SR SR 3.3.6.1.1 3.3.6. 1.2 3.3.6.1.3 3.3.6.1.6 3.3. 6.1.8 3.3.6. 1.1 3.3.6.1.2 3.3.6.1.3 3.3.6.1.5 3.3.6.1.6 2 -48.1 inches I
1,2,3 I
SR SR SR SR SR 5 188 inches water (continued)
CLINTON 3.3 -58 Amendment No.169
Primary Containment and Drywell Isolation Instrumentation 3.3.6.1 Table 3.3.6.1-1 (page 5 of 6)
Primary Containment and Drywell Isolation Instrumentation APPLICABLE CONDITIONS MODES OR REQUIRED REFERENCED OTHER CHANNELS FROM SPECIFIED PER REQUIRED SURVEILLANCE ALLOWABLE FUNCTION CONDITIONS FUNCTION ACTION F.1 REQUIREMENTS VALUE
- 3.
RCIC System Isolation (continued)
- j. Drywell Pressure - High 1.2,3 2
I SR SR SR SR SR 3.3.6.1.1 3.3.6.1.2 3.3.6.1.3 3.3.6.1.5 3.3.6.1.6 S 1.88 psig
- k. Manual Initiation
- 4. Reactor Water Cleanup (RWCU) System Isolation
- a. Differential Flow -
High 1,2,3 1
J SR 3.3.6.1.6 NA 1,2,3 2
I SR SR SR SR 3.3.6.1.1 3.3.6.1.2 3.3.6.1.6 3.3.6.1.8 5 66.1 gpm I
- b. Differential Flow-Timer 1,2,3 2
I SR 3.3.6.1.2 SR 3.3.6.1.4 SR 3.3.6.1.6 S 47 seconds
- c.
RWCU Heat Exchanger Equipment Room Temperature-High
- d. RWCU Pump Rooms Temperature-High
- e. Main Steam Line Tunnel Ambient Temperature-High 1,2,3 2 per room 1,2,3 2 per room I
SR SR SR SR I
SR SR SR SR I
SR SR SR SR 3.3.6.1.1 3.3.6.1.2 3.3.6.1.5 3.3.6.1.6 3.3.6.1.1 3.3.6.1.2 3.3.6.1.5 3.3. 6.1.6 3.3.6.1.1 3.3.6.1.2 3.3.6.1.5 3.3.6.1.6 5205OF
- 5 202OF
- 5 171OF 1,2,3 2
- f. Reactor Vessel Water Level-Low Low, Level 2 1,2,3 4
I SR SR SR SR SR 3.3.6.1.1 3.3.6.1.2 3.3.6.1.3 3.3.6.1.6 3.3.6.1.8 3.3.6.1.1 3.3.6.1.2 3.3.6.1.3 3.3.6.1.6 3.3.6.1.8 2 -48.1 inches I
ICe 4
0 SR SR SR SR SR 2 -48.1 inches I
- g. Standby Liquid Control System Initiation
- h. Manual Initiation 1,2,3 1,2,3 (cl. Id}
2 2
2 L
SR 3.3.6.1.6 NA J
SR 3.3.6.1.6 NA N
SR 3.3.6.1.6 NA (continued)
(c) During operations with a potential for (d) During movement of recently irradiated draining the reactor vessel.
fuel assemblies in the primary or secondary containment.
CLINTON
- 3. 3-59 Amendment No. 169
Primary Containment and Drywell Isolation Instrumentation 3.3.6.1 Table 3.3.6.1-1 (page 6 of 6)
Primary Containment and Drywell Isolation Instrumentation APPLICABLE CONDITIONS MODES OR REFERENCED OTHER REQUIRED FROM SPECIFIED CHANNELS PER REQUIRED SURVEILLANCE ALLOWABLE FUNCTION CONDITIONS FUNCTION ACTION F.1 REQUIREMENTS VALUE
- 5.
RHR System Isolation
- a. RHR Heat Exchanger 1,2,3 2 per room I
SR 3.3.6.1.1 5 1600 F Ambient SR 3.3.6.1.2 Temperature-High SR 3.3.6.1.5 SR 3.3.6.1.6
- b. Reactor Vessel Water 1,2,3"t 4
I SR 3.3.6.1.1 2 8.3 inches Level -
Low, Level 3 SR 3.3.6.1.2 SR 3.3.6.1.3 SR 3.3.6.1.5 SR 3.3.6.1.6
- c. Reactor Vessel Water 3 'g", 4, 5 4 1h M
SR 3.3.6.1.1 2 8.3 inches Level -
Low, Level 3 SR 3.3.6.1.2 SR 3.3.6.1.3 SR 3.3.6.1.5 SR 3.3.6.1.6
- d. Reactor Vessel Water 1,2,3 4
I SR 3.3.6.1.1 2 -148.1 Level - Low Low Low, SR 3.3.6.1.2 inches Level 1 SR 3.3.6.1.3 SR 3.3.6.1.6 SR 3.3.6.1.8
- e. Reactor Vessel 1,2,3 4
I SR 3.3.6.1.1 5 113 psig Pressure-High SR 3.3.6.1.2 SR 3.3.6.1.3 SR 3.3.6.1.5 SR 3.3.6.1.6
- f. Drywell Pressure-High 1,2,3 8
I SR 3.3.6.1.1 S 1.88 psig SR 3.3.6.1.2 SR 3.3.6.1.3 SR 3.3.6.1.5 SR 3.3.6.1.6
- g. Manual Initiation 1,2,3 2
3 SR 3.3.6.1.6 NA I
Mf)
(g)
(h)
With reactor steam dome pressure greater than or equal to the RHR cut in permissive pressure.
With reactor steam dome pressure less than the RUR cut in permissive pressure.
Only one trip system required in MODES 4 and 5 with RHR Shutdown Cooling System integrity maintained.
CLINTON 3.3 -60 Amendment No. 169
Secondary Containment Isolation Instrumentation 3.3.6.2 SURVEILLANCE REQUIREMENTS
NOTES------------------------------------
- 1. Refer to Table 3.3.6.2-1 to determine which SRs apply for each Secondary Containment Isolation Function.
- 2. When a channel is placed in an inoperable status solely for performance of required Surveillances, entry into associated Conditions and Required Actions may be delayed for up to 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />, provided the associated Function maintains secondary containment isolation capability.
SURVEILLANCE FREQUENCY SR 3.3.6.2.1 Perform CHANNEL CHECK.
12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> SR 3.3.6.2.2 Perform CHANNEL FUNCTIONAL TEST.
92 days SR 3.3.6.2.3 Calibrate the analog trip module.
92 days SR 3.3.6.2.4 Perform CHANNEL CALIBRATION.
24 months SR 3.3.6.2.5 Perform LOGIC SYSTEM FUNCTIONAL TEST.
24 months SR 3.3.6.2.6 Perform CHANNEL CALIBRATION.
18 months I
I I
CLINTON 3.3 -63 Amendment No. 1t9
Secondary Containment Isolation Instrumentation 3.3.6.2 Table 3.3.6.2-1 (page 1 of 1)
Secondary Containment Isolation Instrumentation APPLICABLE MODES OR OTHER SPECIFIED CONDITIONS 1,2,3,(a)
REQUIRED CHANNELS PER TRIP SYSTEM 2
SURVEILLANCE REQUIREMENTS ALLOWABLE VALUE FUNCTION
- 1.
Reactor Vessel Water Level-Low Low, Level 2 SR SR SR SR SR 3.3.6.2.1 3.3.6.2.2 3.3.6.2.3 3.3.6.2.5 3.3.6.2.6 2 -48.1 inches I
- 2.
Drywell Pressure-High
- 3.
Containment Building Fuel Transfer Pool Ventilation Plenum Exhaust Radiation-High
- 4.
Containment Building Exhaust Radiation-High
- 5.
Containment Building Continuous Containment Purge (CCP) Exhaust Radiation-High
- 6.
Fuel Building Exhaust Radiation-High
- 7.
Manual Initiation 1,2,3 (a), (b) 1,2,3, (a), (b) 1,2,3, (a), (b) 1,2,3, (c) 1,2,3, (a), (b) 2 SR SR SR SR SR 2
SR SR SR SR 2
SR SR SR SR 2
SR SR SR SR 2
SR SR SR SR 1
SR 3.3.6.2. 1 3.3.6. 2. 2 3.3.6.2.3 3.3.6.2.4 3.3.6.2.5 3.3.6.2.1 3.3.6.2.2 3.3.6.2.4 3.3.6.2.5 3.3.6.2.1 3.3.6.2.2 3.3.6.2.4 3.3.6.2.5 3.3.6.2.1 3.3.6.2.2 3.3.6.2.4 3.3.6.2.5 3.3.6.2.1 3.3.6.2.2 3.3.6.2.4 3.3.6.2.5 3.3.6.2.5 5 1.88 psig S 500 mR/hr S 400 mR/hr 5 400 mR/hr S 17 mR/hr NA (a) During operations with a potential for draining the reactor vessel.
(b) During movement of recently irradiated fuel assemblies in the primary or secondary containment.
(c) During movement of recently irradiated fuel assemblies in the fuel building.
CLINTON 3.3 -64 Amendment No.i69
RHR Containment Spray System Instrumentation 3.3.6.3 SURVEILLANCE REQUIREMENTS
NOTES------------------------------------
- 1. Refer to Table 3.3.6.3-1 to determine which SRs apply for each RHR Containment Spray System Function.
- 2. When a channel is placed in an inoperable status solely for performance of required Surveillances, entry into associated Conditions and Required Actions may be delayed for up to 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />, provided the associated Function maintains RHR containment spray initiation capability.
SURVEILLANCE FREQUENCY SR 3.3.6.3.1 Perform CHANNEL CHECK.
12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> SR 3.3.6.3.2 Perform CHANNEL FUNCTIONAL TEST.
92 days SR 3.3.6.3.3 Calibrate the analog trip module.
92 days SR 3.3.6.3.4 Perform CHANNEL CALIBRATION.
24 months SR 3.3.6.3.5 Perform LOGIC SYSTEM FUNCTIONAL TEST.
24 months SR 3.3.6.3.6 Perform CHANNEL CALIBRATION.
18 months I
I I
CLINTON 3.3 -67 Amendment No.169
RHR Containment Spray System Instrumentation 3.3.6.3 Table 3.3.6.3-1 (page 1 of 1)
RHR Containment Spray System Instrumentation CONDITIONS REQUIRED REFERENCED CHANNELS FROM PER TRIP REQUIRED SURVEILLANCE ALLOWABLE FUNCTION SYSTEM ACTION A.1 REQUIREMENTS VALUE
- 1. Drywell Pressure-High 2
B SR 3.3.6.3.1 S 1.88 psig SR 3.3.6.3.2 SR 3.3.6.3.3 SR 3.3.6.3.4 SR 3.3.6.3.5
- 2.
Containment Pressure-High 2
B SR 3.3.6.3.1 S 22.4 psia SR 3.3.6.3.2 SR 3.3.6.3.3 SR 3.3.6.3.4 SR 3.3.6.3.5
- 3.
Reactor Vessel Water 2
B SR 3.3.6.3.1 2 -148.1 inches Level-LOw Low Low, SR 3.3.6.3.2 Level 1 SR 3.3.6.3.3 SR 3.3.6.3.5 SR 3.3.6.3.6
- 4. Timers, System A 1
C SR 3.3.6.3.2 2 606 seconds and and System B SR 3.3.6.3.4 45 614 seconds SR 3.3.6.3.5 S. Timer, System B Only 1
C SR 3.3.6.3.2 S 90.6 seconds SR 3.3.6.3.4 SR 3.3.6.3.5
- 6. Manual Initiation 1
C SR 3.3.6.3.5 NA I
CLINTON 3.3 -68 Amendment No.169
SPMU System Instrumentation 3.3.6.4 SURVEILLANCE REQUIREMENTS
NOTES------------------------------------
- 1. Refer to Table 3.3.6.4-1 to determine which SRs apply for each SPMU Function.
- 2. When a channel is placed in an inoperable status solely for performance of required Surveillances, entry into associated Conditions and Required Actions may be delayed for up to 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />, provided the associated Function maintains SPMU initiation capability.
SURVEILLANCE FREQUENCY SR 3.3.6.4.1 Perform CHANNEL CHECK.
12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> SR 3.3.6.4.2 Perform CHANNEL FUNCTIONAL TEST.
92 days SR 3.3.6.4.3 Calibrate the analog trip module.
92 days SR 3.3.6.4.4 Calibrate the analog comparator unit.
92 days SR 3.3.6.4.5 Perform CHANNEL CALIBRATION.
92 days SR 3.3.6.4.6 Perform CHANNEL CALIBRATION.
24 months SR 3.3.6.4.7 Perform LOGIC SYSTEM FUNCTIONAL TEST.
24 months SR 3.3.6.4.8 Perform CHANNEL CALIBRATION.
18 months I
I I
CLINTON 3.3 -71 Amendment No. 169
SPMU System Instrumentation 3.3.6.4 Table 3.3.6.4-1 (page 1 of 1)
Suppression Pool Makeup System Instrumentation REQUIRED CONDITIONS CHANNELS REFERENCED PER FROM TRIP REQUIRED SURVEILLANCE ALLOWABLE FUNCTION SYSTEM ACTION A.1 REQUIREMENTS VALUE
- 1.
Drywell Pressure-High 2
B SR 3.3.6.4.1 S 1.88 psig SR 3.3.6.4.2 SR 3.3.6.4.3 SR 3.3.6.4.6 SR 3.3.6.4.7
- 2. Reactor Vessel Water 2
B SR 3.3.6.4.1 2 -148.1 inches Level-Low Low Low, SR 3.3.6.4.2 Level 1 SR 3.3.6.4.3 SR 3.3.6.4.7 SR 3.3.6.4.8
- 3.
Suppression Pool Water 2
B SR 3.3.6.4.1 2 29 inches Level-Low Low SR 3.3.6.4.2 SR 3.3.6.4.4 SR 3.3.6.4.6 SR 3.3.6.4.7
- 4. Timer 1
- 30 minutes SR 3.3.6.4.5 SR 3.3.6.4.7 S.
Manual Initiation 2
C SR 3.3.6.4.7 NA I
CLINTON
- 3. 3-72 Amendment No. 16 9
Relief and LLS Instrumentation 3.3.6.5 SURVEILLANCE REQUIREMENTS
NOTE-------------------------------------
When a channel is placed in an inoperable status solely for performance of required Surveillances, entry into associated Conditions and Required Actions may be delayed for up to 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />, provided the associated Function maintains LLS or relief initiation capability, as applicable.
SURVEILLANCE FREQUENCY SR 3.3.6.5.1 Perform CHANNEL FUNCTIONAL TEST.
92 days
NOTE---------------------------------
- 1. If the as-found channel setpoint is conservative with respect to the Allowable Value but outside its predefined As-Found Tolerance band, then the channel shall be evaluated to verify that it is functioning as required before returning the channel to service.
If the as-found instrument channel setpoint is not conservative with respect to the Allowable Value, the channel shall be declared inoperable.
- 2. The instrument channel setpoint shall be reset to a value within the As-Left Tolerance of the Actual Trip Setpoint; otherwise, the channel shall be declared inoperable.
- 3. The Nominal Trip Setpoint and the methodology used to determine the Nominal Trip Setpoint, the predefined As-Found Tolerance and As-Left Tolerance bands shall be specified in the ORM.
SR 3.3.6.5.2 Calibrate the analog trip module.
92 days
NOTE------------------------------------
- 1. If the as-found channel setpoint is conservative with respect to the Allowable Value but outside its predefined As-Found Tolerance band, then the channel shall be evaluated to verify that it is functioning as required before returning the channel to service.
If the as-found instrument channel setpoint is not conservative with respect to the Allowable Value, the channel shall be declared inoperable.
- 2. The instrument channel setpoint shall be reset to a value within the As-Left Tolerance of the Actual Trip Setpoint; otherwise, the channel shall be declared inoperable.
- 3. The Nominal Trip Setpoint and the methodology used to determine the Nominal Trip Setpoint, the predefined As-Found Tolerance and As-Left Tolerance bands shall be specified in the ORM.
SR 3.3.6.5.3 Perform CHANNEL CALIBRATION.
The Allowable Values 24 months shall be:
- a. Relief Function Low:
< 1118 psig Medium:
< 1128 psig High:
c 1138 psig
- b. LLS Function Low open: < 1044 psig close:< 937 psig Medium open: c 1084 psig close:Z 947 psig High open: c 1124 psig close:<
957 psig SR 3.3.6.5.4 Perform LOGIC SYSTEM FUNCTIONAL TEST.
24 months CLINTON
- 3. 3-74 Amendment No. 169
Control Room Ventilation System Instrumentation 3.3.7.1 ACTIONS (continued)
CONDITION REQUIRED ACTION COMPLETION TIME B.
Required Action and B.1 Place one Control 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> associated Completion Room Ventilation Time not met.
subsystem in the high radiation mode of operation.
OR B.2 Declare associated 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> Control Room Ventilation subsystem inoperable.
SURVEILLANCE REQUIREMENTS
NOTES------------------------------------
- 1. Refer to Table 3.3.7.1-1 to determine which SRs apply for each Function.
- 2. When a channel is placed in an inoperable status solely for performance of required Surveillances, entry into associated Conditions and Required Actions may be delayed for up to 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />.provided the associated Function maintains Control Room Ventilation initiation capability.
SURVEILLANCE FREQUENCY SR 3.3.7.1.1 Perform CHANNEL CHECK.
12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> SR 3.3.7.1.2 Perform CHANNEL FUNCTIONAL TEST.
92 days SR 3.3.7.1.3 Perform CHANNEL CALIBRATION.
24 months I
CLINTON 3.3-76 Amendment No.169
LOP Instrumentation 3.3.8.1 SURVEILLANCE REQUIREMENTS
NOTES------------------------------------
- 1. Refer to Table 3.3.8.1-1 to determine which SRs apply for each LOP Function.
- 2. When a channel is placed in an inoperable status solely for performance of required Surveillances, entry into associated Conditions and Required Actions may be delayed for up to 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> provided the associated Function maintains DG initiation capability.
SURVEILLANCE FREQUENCY SR 3.3.8.1.1 Deleted SR 3.3.8.1.2 Perform CHANNEL FUNCTIONAL TEST.
31 days SR 3.3.8.1.3 Perform CHANNEL CALIBRATION.
24 months SR 3.3.8.1.4 Perform LOGIC SYSTEM FUNCTIONAL TEST.
24 months I
I CLINTON 3.3-79 Amendment No. 169
LOP Instrumentation 3.3.8.1 Table 3.3.8.1-1 (page 1 of 1)
Loss of Power Instrumentation REQUIRED CHANNELS PER SURVEILLANCE ALLOWABLE FUNCTION DIVISION REQUIREMENTS VALUE
- 1. Divisions 1 and 2 - 4.16 kV Emergency Bus Undervoltage
- a. Loss of Voltage -
4.16 kV 6
SR 3.3.8.1.3 2 2345 V and S 3395 V basis SR 3.3.8.1.4
- b. Loss of Voltage - Time 6
SR 3.3.8.1.3 S 5.0 seconds Delay SR 3.3.8.1.4
- c. Degraded Voltage 2
SR 3.3.8.1.2 2 4102.2 V and S 4109.3 V Reset - 4.16 kV basis SR 3.3.8.1.3 SR 3.3.8.1.4
- d.
Degraded Voltage 2
SR 3.3.8.1.2 2 4051 V Drop-out -
4.16 kV basis SR 3.3.8.1.3 SR 3.3.8.1.4
- e. Degraded Voltage-Time 1
SR 3.3.8.1.2 2 14 seconds and S 16 seconds Delay SR 3.3.8.1.3 SR 3.3.8.1.4
- 2. Division 3 -
4.16 kV Emergency Bus Undervoltage
- a. Loss of Voltage -
4.16 kV 4
SR 3.3.8.1.3 2 2345 V and S 2730 V basis SR 3.3.8.1.4
- b. Loss of Voltage -
Time 1
3.0 seconds Delay SR 3.3.8.1.4
- c. Degraded Voltage 2
SR 3.3.8.1.2 2 4102.2 V and S 4109.3 V Reset - 4.16 kV basis SR 3.3.8.1.3 SR 3.3.8.1.4
- d. Degraded Voltage 2
SR 3.3.8.1.2 2 4051 V Drop-out - 4.16 kV basis SR 3.3.8.1.3 SR 3.3.8.1.4
- e. Degraded Voltage - Time 1
SR 3.3.8.1.2 2 13.2 seconds and S 16.8 Delay SR 3.3.8.1.3 seconds SR 3.3.8.1.4 I
I I
I I
I CLINTON 3.3 -80 Amendment No.169
RPS Electric Power Monitoring 3.3.8.2 SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.3.8.2.1 NOTE------------------
Only required to be performed prior to entering MODE 2 or 3 from MODE 4, when in MODE 4 for Z 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.
Perform CHANNEL FUNCTIONAL TEST.
184 days SR 3.3.8.2.2 Perform CHANNEL CALIBRATION.
The 24 months Allowable Values shall be:
- a. Overvoltage Bus A s 127.3 V Bus B s 126.7 V
- b. Undervoltage Bus A a 115.0 V Bus B 2 114.7 V
- c. Underfrequency (with time delay < 4.0 seconds)
Bus A 2 57 Hz Bus B 2 57 Hz SR 3.3.8.2.3 Perform a system functional test.
24 months CLINTON 3.3 -82 Amendment No.169
FCVs 3.4.2 3.4 REACTOR COOLANT SYSTEM (RCS) 3.4.2 Flow Control Valves (FCVS)
LCJ 3.4.2 A recirculation loop FCV shall be OPERABLE in each operating recirculation loop.
APPLICABILITY:
MODES 1 and 2.
ACTIONS
NOTE-----------------------------------
Separate Condition entry is allowed for each FCV.
CONDITION REQUIRED ACTION COMPLETION TIME A. One or two required A.1 Lock up the FCV.
4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> FCVs inoperable.
B. Required Action and B.1 Be in MODE 3.
12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> associated Completion Time not met.
SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.4.2.1 Verify each FCV fails "as is" on loss of 24 months hydraulic pressure at the hydraulic unit.
I CLINTON 3.4 -6 Amendment No.169
S/RVs 3.4.4 SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.4.4.1 Verify the safety function lift setpoints of the required S/RVs are as follows:
In accordance with the Inservice Testing Program Number of S/RVs 7
5 4
Setpoint (psig) 1165 +/- 34.9 1180 +/- 35.4 1190 +/- 35.7 Following testing, lift settings shall be within +/- 1t.
NOTE-------------------
Valve actuation may be excluded.
Verify each required relief function S/RV 24 months actuates on an actual or simulated automatic initiation signal.
NOTE-------------------
Not required to be performed until 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> after reactor steam pressure and flow are adequate to perform the test.
Verify each required S/RV actuator strokes 24 months when manually actuated.
I.
CLINTON 3.4 -11 Amendment No.169
RCS Leakage Detection Instrumentation 3.4.7 SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.4.7.1 Perform CHANNEL CHECK of required drywell 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> atmospheric monitoring system.
SR 3.4.7.2 Perform CHANNEL FUNCTIONAL TEST of required 31 days leakage detection instrumentation.
SR 3.4.7.3 Perform CHANNEL CALIBRATION of required 24 months leakage detection instrumentation.
I CLINTON 3.4-19 Amendment No.169
ECCS-Operating 3.5.1 SURVEILLANCE REQUIREMENTS (continued)
SURVEILLANCE FREQUENCY SR 3.5.1.5-NOTE--------------------
Vessel injection/spray may be excluded.
Verify each ECCS injection/spray subsystem 24 months actuates on an actual or simulated automatic initiation signal.
NOTE-------------------
Valve actuation may be excluded.
Verify the ADS actuates on an actual or 24 months simulated automatic initiation signal.
NOTE--------------------
Not required to be performed until 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> after reactor steam pressure and flow are adequate to perform the test.
Verify each ADS valve actuator strokes when 24 months manually actuated.
NOTE--------------------
ECCS actuation instrumentation is excluded.
Verify the ECCS RESPONSE TIME for each ECCS injection/spray subsystem is within limits.
24 months CLINTON 3.5-5 Amendment No.169
ECCS -
Shutdown 3.5.2 SURVEILLANCE REQUIREMENTS (continued)
SURVEILLANCE FREQUENCY SR 3.5.2.5 Verify each required ECCS pump develops the specified flow rate with the specified pump differential pressure.
In accordance with the Inservice Testing Program SYSTEM LPCS LPCI HPCS FLOW RATE 2 5010 gpm 2 5050 gpm 2 5010 gpm PUMP DIFFERENTIAL PRESSURE 2 290 psid 2 113 psid 2 363 psid SR 3.5.2.6
NOTE--------------------
Vessel injection/spray may be excluded.
Verify each required ECCS injection/spray 24 months subsystem actuates on an actual or simulated automatic initiation signal.
I CLINTON 3.5-9 Amendment No.169
RCIC System 3.5.3 SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.5.3.1 Verify the RCIC System piping is filled 31 days with water from the pump discharge valve to the injection valve.
SR 3.5.3.2 Verify each RCIC System manual, power 31 days operated, and automatic valve in the flow path, that is not locked, sealed, or otherwise secured in position, is in the correct position.
NOTE--------------------
Not required to be performed until 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> after reactor steam pressure and flow are adequate to perform the test.
Verify, with RCIC steam supply pressure 92 days
- 1020 psig and 2 920 psig, the RCIC pump can develop a flow rate 2 600 gpm against a system head corresponding to reactor pressure.
NOTE--------------------
Not required to be performed until 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> after reactor steam pressure and flow are adequate to perform the test.
Verify, with RCIC steam supply pressure 24 months
< 150 psig and 2 135 psig, the RCIC pump can develop a flow rate 2 600 gpm against a system head corresponding to reactor pressure.
(continued)
CLINTON 3.5-11 Amendment No. 169
RCIC System 3.5.3 SURVEILLANCE REQUIREMENTS (continued)
SURVEILLANCE FREQUENCY SR 3.5.3.5
NOTE--------------------
Vessel injection may be excluded.
Verify the RCIC System actuates on an 24 months actual or simulated automatic initiation signal.
I CLINTON 3.5-12 Amendment No.169
PCIVs 3.6.1.3 SURVEILLANCE REQUIREMENTS (continued)
SURVEILLANCE FREQUENCY SR 3.6.1.3.4 Verify the isolation time of each power In accordance operated and each automatic PCIV, except with the MSIVs, is within limits.
Inservice Testing Program SR 3.6.1.3.5 NOTE------------------
Only required to be met in MODES 1, 2, and 3.
Perform leakage rate testing for each Once within 92 primary containment purge valve with days after resilient seals.
opening the valve AND In accordance with the Primary Containment Leakage Rate Testing Program SR 3.6.1.3.6 Verify the isolation time of each MSIV In accordance is 2 3 seconds and < 5 seconds.
with the Inservice Testing Program SR 3.6.1.3.7 Verify each automatic PCIV actuates to 24 months the isolation position on an actual or simulated isolation signal.
(continued)
I CLINTON 3.6 -18 Amendment No.169
PCIVs 3.6.1.3 SURVEILLANCE FREQUENCY SR 3.6.1.3.11
NOTE--------------------
In accordance Only required to be met in MODES 1, 2, with the and 3.
Primary Containment Leakage Rate Verify that the combined leakage rate Testing for both primary containment feedwater Program.
penetrations is < 2 gpm when pressurized to Ž 1.31 Pa.
SR 3.6.1.3.12 Verify each instrumentation line excess 24 months flow check primary containment isolation valve actuates within the required range.
I CLINTON 3.6-19a Amendment No. 169
LLS Valves 3.6.1.6 SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.6.1.6.1
NOTE-------------------
Not required to be performed until 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> after reactor steam pressure and flow are adequate to perform the test.
Verify each LLS valve actuator strokes 24 months when manually actuated.
NOTE-------------------
Valve actuation may be excluded.
Verify the LLS System actuates on an 24 months actual or simulated automatic initiation signal.
CLINTON 3.6 -23 Amendment No.169
RHR Containment Spray System 3.6.1.7 SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.6.1.7.1
NOTE-------------------
RHR containment spray subsystems may be considered OPERABLE during alignment and operation for decay heat removal when below the RHR cut in permissive pressure in MODE 3 if capable of being manually realigned and not otherwise inoperable.
Verify each RHR containment spray 31 days subsystem manual, power operated, and automatic valve in the flow path that is not locked, sealed, or otherwise secured in position is in the correct position.
SR 3.6.1.7.2 Verify each RHR pump develops a flow rate In accordance of 2 3800 gpm on recirculation flow with the through the associated heat exchanger to Inservice the suppression pool.
Testing Program SR 3.6.1.7.3 Verify each RHR containment spray 24 months subsystem automatic valve in the flow path actuates to its correct position on an actual or simulated automatic initiation signal.
SR 3.6.1.7.4 Verify each spray nozzle is unobstructed.
Following activities that could result in nozzle blockage I
CLINTON 3.6-25 Amendment No.169
FVILCS 3.6.1. 9 3.6 CONTAINMENT SYSTEMS 3.6.1.9 Feedwater Leakage Control System (FWLCS)
LCO 3.6.1.9 APPLICABILITY:
Two FWLCS subsystems shall be OPERABLE.
MODES 1, 2, and 3.
ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A.
One FWLCS subsystem A.1 Restore FWLCS 30 days inoperable.
subsystem to OPERABLE status.
B.
Two FWLCS subsystems B.1 Restore one FWLCS 7 days inoperable.
subsystem to OPERABLE status.
C.
Required Action and C.1 Be in MODE 3.
12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> associated Completion Time not met.
AND C.2 Be in MODE 4.
36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br /> SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.6.1.9.1 Perform a system functional test of each 24 months FWLCS subsystem.
I CLINTON 3.6-27a Amendment No. 169
SPMU System 3.6.2.4 SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.6.2.4.1 Verify upper containment pool water level is:
- a. 2 el. 825 ft 6 inches;
- b. 2 el. 825 ft 10 inches when the inclined fuel transfer pool to steam dryer storage pool gate is not open; 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> and
- c. 2 el. 827 ft 1 inch when the reactor cavity to steam dryer storage pool gate is not open.
- d. Reactor cavity pool level 2 el. 824 ft 7 inches in MODE 3 with reactor pressure less than 235 psig.
- e. Suppression pool water level 2 19 ft 9 inches in MODE 3 with reactor pressure less than 235 psig.
SR 3.6.2.4.2 Verify upper containment pool water 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> temperature is < 1200F.
SR 3.6.2.4.3 Verify each SPMU subsystem manual, power 31 days operated, and automatic valve that is not locked, sealed, or otherwise secured in position is in the correct position.
NOTE-------------------
Actual makeup to the suppression pool may be excluded.
Verify each SPMU subsystem automatic 24 months valve actuates to the correct position on an actual or simulated automatic initiation signal.
I CLINTON 3.6 -35 Amendment No.169
Primary Containment and Drywell Hydrogen Igniters 3.6.3.2 ACTIONS (continued)
CONDITION REQUIRED ACTION COMPLETION TIME i
C.
Required Action and C.1 Be in MODE 3.
12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> associated Completion Time not met.
SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.6.3.2.1 Energize each primary containment and 184 days drywell hydrogen igniter division and perform current versus voltage measurements to verify required igniters in service.
SR 3.6.3.2.2 NOTE-------------------
Not required to be performed until 92 days after discovery of four or more igniters in the division inoperable.
Energize each primary containment and 92 days drywell hydrogen igniter division and perform current versus voltage measurements to verify required igniters in service.
SR 3.6.3.2.3 Verify each required igniter in 24 months inaccessible areas develops sufficient current draw for a 2 1700OF surface temperature.
I (continued)
CLINTON 3.6 -3 9 Amendment No.169
Primary Containment and Drywell Hydrogen Igniters 3.6.3.2 SURVEILLANCE REQUIREMENTS (continued)
SURVEILLAICE FREQUENCY SR 3.6.3.2.4 Verify each required igniter in 24 months accessible areas develops a surface temperature of Z 17000F.
I CLINTON
- 3. 6-40 Amendment No.1 69
Containment/Drywell Hydrogen Mixing Systems 3.6.3.3 SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.6.3.3.1 Operate each Containment/Drywell Hydrogen 92 days Mixing System.
SR 3.6.3.3.2 Verify each Containment/Drywell Hydrogen 24 months Mixing System flow rate is 2 800 scfm.
I CLINTON 3.6-42 Amendment No. 169
Secondary Containment 3.6.4.1 SURVEILLANCE REQUIREMENTS (continued)
SURVEILLANCE FREQUENCY SR 3.6.4.1.3 Verify one door in each access to 31 days secondary containment is closed, except during normal entry and exit.
SR 3.6.4.1.4 Verify each standby gas treatment (SGT) 24 months on subsystem will draw down the secondary a STAGGERED containment to 2 0.25 inch of vacuum TEST BASIS water gauge within the time required.
SR 3.6.4.1.5 Verify each SGT subsystem can maintain 24 months on a 2 0.25 inch of vacuum water gauge in the STAGGERED TEST secondary containment for 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> at a BASIS flow rate < 4400 cfm.
I I
CLINTON 3.6-45 Amendment No. 169
SCIDs 3.6.4.2 SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY
+
NOTES------------------
- 1. Valves, dampers, and blind flanges in high radiation areas may be verified by use of administrative means.
- 2. Not required to be met for SCIDs that are open under administrative controls.
Verify each secondary containment isolation manual valve, damper, and blind flange that is required to be closed during accident conditions is closed.
31 days SR 3.6.4.2.2 Verify the isolation time of each power 92 days operated and each automatic SCID is within limits.
SR 3.6.4.2.3 Verify each automatic SCID actuates to 24 months the isolation position on an actual or simulated automatic isolation signal.
I CLINTON 3.6 -50 Amendment No.169
SGT System 3.6.4.3 ACTIONS (continued)
CONDITION REQUIRED ACTION COMPLETION TIME E. Two SGT subsystems E.1 Suspend movement of Immediately inoperable during recently irradiated movement of recently fuel assemblies in the irradiated fuel primary and secondary assemblies in the containment.
primary or secondary containment, or during AND OPDRVs.
E.2 Initiate action to Immediately suspend OPDRVs.
SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.6.4.3.1 Operate each SGT subsystem for 31 days 2 10 continuous hours with heaters operating.
SR 3.6.4.3.2 Perform required SGT filter testing in In accordance accordance with the Ventilation Filter with the VFTP Testing Program (VFTP).
SR 3.6.4.3.3 Verify each SGT subsystem actuates on an 24 months actual or simulated initiation signal.
SR 3.6.4.3.4 Verify each SGT filter cooling bypass 24 months damper can be opened and the fan started.
I I
CLINTON 3.6-53 Amendment No.169
Drywell Isolation Valves 3.6.5.3 SURVEILLANCE REQUIREMENTS (continued)
SURVEILLANCE FREQUENCY SR 3.6.5.3.3
NOTES------------------
- 1. Valves and blind flanges in high radiation areas may be verified by use of administrative means.
- 2. Not required to be met for drywell isolation valves that are open under administrative controls.
Verify each required drywell isolation manual valve and blind flange that is required to be closed during accident conditions is closed.
Prior to entering MODE 2 or 3 from MODE 4, if not performed in the previous 92 days SR 3.6.5.3.4 Verify the isolation time of each In accordance required power operated and each required with the automatic drywell isolation valve is inservice within limits.
Testing Program SR 3.6.5.3.5 Verify each required automatic drywell 24 months isolation valve actuates to the isolation position on an actual or simulated isolation signal.
I CLINTON 3.6-65 Amendment No.169
Drywell Post-LOCA Vacuum Relief System 3.6.5.6 SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.6.5.6.1
NOTES-------------------
- 1. Not required to be met for drywell post-LOCA vacuum relief valves open during Surveillances.
- 2. Not required to be met for drywell post-LOCA vacuum relief valves open when performing their intended function.
Verify each drywell post-LOCA vacuum relief valve is closed.
l 7 days SR 3.6.5.6.2 Perform a functional test of each drywell 31 days post-LOCA vacuum relief valve.
SR 3.6.5.6.3 Verify the opening pressure differential 24 months of each drywell post-LOCA vacuum relief valve is < 0.2 psid.
I CLINTON 3.6 -70 Amendment No. 169
Division 1 and 2 SX Subsystems and UHS 3.7.1 Actions (continued)
CONDITION REQUIRED ACTION COMPLETION TIME C. Required Action and C.1 Be in MODE 3.
12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> associated Completion Time of Condition A AND or B not met.
C.2 Be in MODE 4.
36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br /> OR Division 1 and 2 SX subsystems inoperable.
SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.7.1.1 Verify UHS water volume is 2 593 acre-ft.
In accordance with UHS
- Erosion, Sediment Monitoring, and Dredging Program SR 3.7.1.2 Verify each required SX subsystem manual, 31 days power operated, and automatic valve in the flow path servicing safety related systems or components, that is not locked, sealed, or otherwise secured in position, is in the correct position.
SR 3.7.1.3 Verify each SX subsystem actuates on an 24 months actual or simulated initiation signal.
I CLINTON 3.7-2 Amendment No. 169
Division 3 SX Subsystem 3.7.2 3.7 PLANT SYSTEMS 3.7.2 Division 3 Shutdown Service Water (SX) Subsystem LCO 3.7.2 APPLICABILITY:
The Division 3 SX subsystem shall be OPERABLE.
MODES 1, 2, and 3.
ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. Division 3 SX A.1 Declare High Pressure Immediately subsystem inoperable.
Core Spray System inoperable.
SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.7.2.1 Verify each required Division 3 SX 31 days subsystem manual, power operated, and automatic valve in the flow path servicing safety related systems or components, that is not locked, sealed, or otherwise secured in position, is in the correct position.
SR 3.7.2.2 Verify the Division 3 SX subsystem actuates 24 months on an actual or simulated initiation signal.
I CLINTON 3.7-3 Amendment No. 169
Control Room Ventilation System 3.7.3 SURVEILLANCE REQUIREMENTS (continued)
SURVEILLANCE FREQUENCY SR 3.7.3.4 Verify each Control Room Ventilation 24 months subsystem actuates on an actual or simulated initiation signal.
SR 3.7.3.5 Verify the air inleakage rate of the 24 months negative pressure portions of the Control Room Ventilation System is
- 650 cfm.
SR 3.7.3.6 Verify each Control Room Ventilation 24 months on a subsystem can maintain a positive pressure STAGGERED TEST of 2 1/8 inch water gauge relative to BASIS adjacent areas during the high radiation mode of operation at a flow rate of
- 3000 cfm.
I I
I CLINTON 3.7-7 Amendment No. 169
Control Room AC System 3.7.4 ACTIONS (continued)
CONDITION REQUIRED ACTION COMPLETION TIME E.
Required Action and NOTE-------------
associated Completion LCO 3.0.3 is not applicable.
Time of Condition B not met during movement of irradiated E.1 Suspend movement of Immediately fuel assemblies in the irradiated fuel primary or secondary assemblies in the containment, during primary and secondary CORE ALTERATIONS, or containment.
during OPDRVs.
AND E.2 Suspend CORE Immediately ALTERATIONS.
AND E.3 Initiate action to Immediately suspend OPDRVs.
SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.7.4.1 Verify each control room AC subsystem has 24 months the capability to remove the assumed heat load.
I CLINTON 3.7-10 Amendment No.169
Main Turbine Bypass 3.7.6 3.7 PLANT SYSTEMS 3.7.6 Main Turbine Bypass System LCO 3.7.6 The Main Turbine Bypass System shall be OPERABLE.
APPLICABILITY:
THERMAL POWER 2 21.6% RTP.
ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. Main Turbine Bypass A.1 Restore Main Turbine 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> System inoperable.
Bypass System to OPERABLE status.
B. Required Action and B.1 Reduce THERMAL POWER 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> associated Completion to < 21.6% RTP.
Time not met.
SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.7.6.1 Verify one complete cycle of each main 31 days turbine bypass valve.
SR 3.7.6.2 Perform a system functional test.
24 months SR 3.7.6.3 Verify the TURBINE BYPASS SYSTEM RESPONSE 24 months TIME is within limits.
I CLINTON 3.7-13 Amendment No.169
AC Sources-Operating 3.8.1 SURVEILLANCE REQUIREMENTS (continued)
SURVEILLANCE FREQUENCY SR 3.8.1.7
NOTE------------------
All DG starts may be preceded by an engine prelube period.
Verify each DG starts from standby condition and achieves:
- a.
In
- 12 seconds, voltage 2 4084 V and frequency 2 58.8 Hz; and
- b. Steady state voltage 2 4084 V and 5 4580 V and frequency 2 58.8 Hz and 5 61.2 Hz.
184 days SR 3.8.1.8
NOTE--------------------
This Surveillance shall not be performed in MODE 1 or 2. However, credit may be taken for unplanned events that satisfy this SR.
Verify automatic and manual transfer of 24 months unit power supply from the normal offsite circuit to the alternate offsite circuit.
(continued)
I CLINTON 3.8 -6 Amendment No.169
AC Sources-Operating 3.8.1 SURVEILLANCE REQUIREMENTS (continued)
SURVEILLANCE FREQUENCY SR 3.8.1.9
NOTE--------------------
- 1.
Credit may be taken for unplanned events that satisfy this SR.
- 2.
If performed with DG synchronized with offsite power, it shall be performed at a power factor < 0.9.
Verify each DG rejects a load greater than or equal to its associated single largest post accident load and following load 24 months rejection, the engine speed is maintained less than nominal plus 75% of the difference between nominal speed and the overspeed trip setpoint or 15% above nominal, whichever is lower.
(continued)
I CLINTON 3.8-6a Amendment No.169
AC Sources-Operating 3.8.1 SURVEILLANCE REQUIREMENTS (continued)
SURVEILLANCE FREQUENCY SR 3.8.1.10
NOTE--------------------
Credit may be taken for unplanned events that satisfy this SR.
Verify each DG operating at a power factor 5 0.9 does not trip and voltage is 24 months maintained S 5000 V for DG IA and DG lB and 5 5824 V for DG IC during and following a load rejection of a load 2 3482 kW for DG 1A, 2 3488 kW for DG 1B, and 2 1980 kW for DG IC.
(continued)
I CLINTON 3.8 -7 Amendment No. 169
AC Sources-Operating 3.8.1 SURVEILLANCE REQUIREMENTS (continued)
SURVEILLANCE FREQUENCY l-SR 3.8.1.11
NOTES-------------------
- 1.
All DG starts may be preceded by an engine prelube period.
- 2.
This Surveillance shall not be performed in MODE 1, 2, or 3.
However, credit may be taken for unplanned events that satisfy this SR.
Verify on an actual or simulated loss of offsite power signal:
- a.
De-energization of emergency buses;
- b.
Load shedding from emergency buses for Divisions 1 and 2; and
- c.
DG auto-starts from standby condition and:
- 1. energizes permanently connected loads in <12 seconds,
- 2. energizes auto-connected shutdown
- loads,
- 3. maintains steady state voltage 2 4084 V and
- 4580 V,
- 4. maintains steady state frequency 2 58.8 Hz and < 61.2 Hz, and
- 5. supplies permanently connected and auto-connected shutdown loads for 2 5 minutes.
24 months I
(continued)
CLINTON
- 3. 8-8 Amendment No.169
AC Sources-Operating 3.8.1 SURVEILLANCE REQUIREMENTS (continued)
SURVEILLANCE FREQUENCY SR 3.8.1.12
NOTES-------------------
- 1.
All DG starts may be preceded by an engine prelube period.
- 2.
This Surveillance shall not be performed in MODE 1 or 2. However, credit may be taken for unplanned events that satisfy this SR.
Verify on an actual or simulated Emergency Core Cooling System (ECCS) initiation signal each DG auto-starts from standby condition and:
- a.
In < 12 seconds after auto-start and during tests, achieves voltage 2 4084 V and frequency 258.8 Hz;
- b.
Achieves steady state voltage 2 4084 V and < 4580 V and frequency 2 58.8 Hz and
- 61.2 Hz; and
- c.
Operates for 2 5 minutes.
24 months SR 3.8.1.13
NOTE--------------------
Credit may be taken for unplanned events that satisfy this SR.
Verify each DG's automatic trips are bypassed on an actual or simulated ECCS initiation signal except:
- a.
Engine overspeed;
- b.
Generator differential current; and
- c.
Overcrank for DG 1A and DG 1B.
24 months (continued)
CLINTON 3.8-9 Amendment No. 1i6
AC Sources-Operating 3.8.1 SURVEILLANCE REQUIREMENTS (continued)
SURVEILLANCE FREQUENCY SR 3.8.1.14
NOTES-------------------
- 1.
Momentary transients outside the load and power factor ranges do not invalidate this test.
- 2.
Credit may be taken for unplanned events that satisfy this SR.
Verify each DG operating at a power factor
< 0.9 operates for 2 24 hour2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />s:
24 months
- a.
For 2 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> loaded 2 4062 kW for DG 1A, 2 4069 kW for DG 1B, and 2 2310 kW for DG IC; and
- b.
For the remaining hours of the test loaded 2 3482 kW for DG 1A, 2 3486 kW for DG 1B, and 2 1980 kW for DG IC.
(continued)
I CLINTON 3.8-10 Amendment No. 169
AC Sources-Operating 3.8.1 SURVEILLANCE REQUIREMENTS (continued)
SURVEILLANCE FREQUENCY SR 3.8.1.15
NOTE----------------
- 1.
This Surveillance shall be performed within 5 minutes of shutting down the DG after the DG has operated 2 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> loaded 2 3482 kW for DG 1A, a 3488 kW for DG 1B, and 2 1980 kW for DG IC.
Momentary transients outside of the load range do not invalidate this test.
- 2.
All DG starts may be preceded by an engine prelube period.
Verify each DG starts and achieves:
24 months
- a.
In S 12 seconds, voltage 2 4084 V and frequency 2 58.8 Hz and
- b.
Steady state voltage 2 4084 V and 5 4580 V and frequency 2 58.8 Hz and S 61.2 Hz.
(continued)
I CLINTON 3.8-10a Amendment No. 169
AC Sources-Operating 3.8.1 SURVEILLANCE REQUIREMENTS (continued)
SURVEILLANCE FREQUENCY SR 3.8.1.16
NOTE--------------------
This Surveillance shall not be performed in MODE 1, 2, or 3. However, credit may be taken for unplanned events that satisfy this SR.
Verify each DG:
- a.
Synchronizes with offsite power source while loaded with emergency loads upon a simulated restoration of offsite power;
- b.
Transfers loads to offsite power source; and
- c.
Returns to ready-to-load operation.
24 months 4
SR 3.8.1.17
NOTE-------------------
Credit may be taken for unplanned events that satisfy this SR.
Verify, with a DG operating in test mode and connected to its bus, an actual or simulated ECCS initiation signal overrides the test mode by:
- a.
Returning DG to ready-to-load operation; and
- b.
Automatically energizing the emergency loads from offsite power.
24 months (continued)
CLINTON 3.8 -11 Amendment No. 169
AC Sources-Operating 3.8.1 SURVEILLANCE REQUIREMENTS (continued)
SURVEILLANCE FREQUENCY SR 3.8.1.18
NOTE----------------
This Surveillance shall not be performed in MODE 1, 2, or 3. However, credit may be taken for unplanned events that satisfy this SR.
Verify the sequence time is within A 106 of 24 months design for each load sequence timer.
(continued)
I CLINTON 3.8-12 Amendment No.l69
AC Sources-Operating 3.8.1 SURVEILLANCE REQUIREMENTS (continued)
SURVEILLANCE I
FREQUENCY SR 3.8.1.19
NOTES-------------------
- 1.
All DG starts may be preceded by an engine prelube period.
- 2.
This Surveillance shall not be performed in MODE 1, 2, or 3.
However, credit may be taken for unplanned events that satisfy this SR.
Verify, on an actual or simulated loss of offsite power signal in conjunction with an actual or simulated ECCS initiation signal:
- a.
De-energization of emergency buses;
- b.
Load shedding from emergency buses for Divisions 1 and 2; and
- c.
DG auto-starts from standby condition and:
- 1. energizes permanently connected loads in 5 12 seconds,
- 2. energizes auto-connected emergency
- loads,
- 3. achieves steady state voltage 2 4084 V and
- 4580 V,
- 4. achieves steady state frequency 2 58.8 Hz and S 61.2 Hz, and
- 5. supplies permanently connected and auto-connected emergency loads for 2 5 minutes.
24 months I
(continued)
CLINTON 3.8-13 Amendment No. 169
DC Sources-Operating 3.8.4 SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.8.4.1 Verify battery terminal voltage is greater 7 days than or equal to the minimum established float voltage.
SR 3.8.4.2 Verify each Division 1 and 2 battery charger 24 months supplies 2 300 amps at greater than or equal to the minimum established float voltage for 2 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> and each Division 3 and 4 battery charger supplies 2 100 amps at greater than or equal to the minimum established float voltage for a 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br />.
OR Verify each battery charger can recharge the battery to the fully charged state within 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> while supplying the largest combined demands of the various continuous steady state loads, after a battery discharge to the bounding design basis event discharge state.
SR 3.8.4.3 NOTES-------------------
- 1.
The modified performance discharge test in SR 3.8.6.6 may be performed in lieu of SR 3.8.4.3.
- 2.
This Surveillance shall not be performed in MODE 1, 2, or 3. However, credit may be taken for unplanned events that satisfy this SR.
Verify battery capacity is adequate to 24 months supply, and maintain in OPERABLE status, the required emergency loads for the design duty cycle when subjected to a battery service test.
CLINTON 3.8 -25 Amendment No. 169
SVC Protection Systems 3.8.11 SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.8.11.1 For each required SVC Protection System, 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> perform a local, visual check of the SVC system control and status panel to confirm satisfactory operation.
SR 3.8.11.2 Perform a system functional test of each 24 months SVC protection subsystem, including breaker actuation.
I CLINTON 3.8 -45 Amendment No.169
Programs and Manuals 5.5 5.5 Programs and Manuals (continued) 5.5.7 Ventilation Filter Testing Program (VFTP)
A program shall be established to implement the following required testing of Engineered Safety Feature (ESF) filter ventilation systems at the frequencies specified in Regulatory Guide 1.52, Revision 2, except that testing specified at a frequency of 18 months is required at a frequency of 24 months.
- a.
Demonstrate for each of the ESF systems that an inplace test of the high efficiency particulate air (HEPA) filters shows a penetration and system bypass < 0.05% when tested in accordance with Regulatory Guide 1.52, Revision 2, and ANSI N510-1980 at the system flowrate specified below +/- 10%:
ESF Ventilation System Flowrate SGTS 4,000 cfm Control Room Ventilation (CRV) Makeup Filter 3,000 cfm
- b.
Demonstrate for each of the ESF systems that an inplace test of the charcoal adsorber shows a penetration and system bypass less than specified below when tested in accordance with Regulatory Guide 1.52, Revision 2, and ANSI N510-1980 at the system flowrate specified below +/- 10%:
Penetration ESF Ventilation System Flowrate and Bypass SGTS 4,000 cfm 0.05%
CRV Makeup Filter 3,000 cfm 0.05%
CRV Recirculation Filter 64,000 cfm 2%
- c.
Demonstrate for each of the ESF systems that a laboratory test of a sample of the charcoal adsorber, when obtained as described in Regulatory Guide 1.52, Revision 2, shows the methyl iodide penetration less than the value specified below when tested in accordance with ASTM D3803-1989 at a temperature of 30 "C and a relative humidity of 70%:
ESF Ventilation System Penetration SGTS 0.175%
CRV Makeup Filter 0.175%
CRV Recirculation Filter 6%
(continued)
CLINTON 5.0-12 Amendment No. 169