BVY 04-101, Technical Specification Proposed Change No. 263 - Supplement No. 16 Extended Power Uprate - Additional Information Related to Request for Additional Information EMEB-B-5

From kanterella
(Redirected from ML042820137)
Jump to navigation Jump to search

Technical Specification Proposed Change No. 263 - Supplement No. 16 Extended Power Uprate - Additional Information Related to Request for Additional Information EMEB-B-5
ML042820137
Person / Time
Site: Vermont Yankee File:NorthStar Vermont Yankee icon.png
Issue date: 09/30/2004
From: Wanczyk R
Entergy Nuclear Northeast
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
BVY 04-101, EMEB-B-5, TAC MC0761
Download: ML042820137 (4)


Text

Entergy Entergy Nuclear Northeast Entergy Nuclear Operations, Inc.

Vermont Yankee 185 Old Ferry Rd.

PO. Box 500 Brattleboro, Vr 05302 Tel 802-257-5271 September 30, 2004 Docket No. 50- 271 BVY 04-1 01 TAC MC0761 ATTN: Document Control Desk U.S. Nuclear Regulatory Commission Washington, DC 20555-0001

Subject:

Vermont Yankee Nuclear Power Station Technical Specification Proposed Change No. 263 - Supplement No. 16 Extended Power Uprate - Additional Information Related to Request for Additional Information EMEB-B-5

Reference:

1) Vermont Yankee Nuclear Power Station, "Technical Specification Proposed Change No. 263, Supplement 5 Extended Power Uprate - Response to Request for Additional Information," BVY 04-008, January 31, 2004
2) U.S. Nuclear Regulatory Commission letter to Vermony Yankee, "Vermont Yankee Nuclear Power Station-Safety Evaluation of Licensee's Response to Generic Letter 96-05 (TAC No. M97114)," December 14, 2000
3) BWR Owners' Group to U.S. Nuclear Regulatory Commission, "BWR Owners' Group DC Motor Program - BWR OG Project Number 691," BWR OG - 00083, October 2, 2002 This letter provides additional information in support of the application by Entergy Nuclear Vermont Yankee, LLC and Entergy Nuclear Operations, Inc. (Entergy) for a license amendment to increase the maximum authorized power level of the Vermont Yankee Nuclear Power Station (VYNPS) from 1593 megawatts thermal (MWt) to 1912 MWt.

Based on telecoms with NRC staff, additional information related to Vermont Yankee's (VY) response to EMEB-B-5, provided in Reference (1), is needed relative to VY's implementation of GL 96-05 "Periodic Verification of Design-Basis Capability of Safety-Related Motor-Operated Valves." Reference 3 provided NRC Staff acceptance of the VY's GL 96-05 response.

BVY 04-101 Page 2 of 3 The additional information is as follows:

Vermont Yankee (VY) will revise the Motor Operated Valve Periodic Verification Program (MOV PVP) to include periodic at-the-valve testing as a means to verify the effectiveness of the MCC testing methodology as discussed in Reference 2. The MOV PVP will also be revised to formalize the process for trending of DC motors.

The BWROG Direct Current Motor Methodology (DCM) (Reference 3) was implemented as a verification check for the existing VY analysis of line break" isolation valves stroke times. The stroke time estimates produced by both methods were comparable.

The DCM was not used to determine required forces for DC MOVs since the EPRI Performance Prediction Methodology (PPM) had already been performed for these valves. VY considered the PPM to be slightly more conservative, so there was no need to change the analysis method.

The DCM was not used to determine available motor torque for DC MOVs since the existing VY analysis for calculating available reduced voltage motor torque is comparable or slightly more conservative.

VY also has extensive DC motor dynamometer tests which can be used to validate or improve the standard motor curves.

VY's current use of the DCM is therefore limited to validation of current analysis.

This letter provides a commitment for revising the MOV PVP to include periodic at-the-valve testing and to formalize the trending process for DC motors.

This supplement to the license amendment request provides additional information to update Entergy's application for a license amendment and does not change the scope or conclusions in the original application, not does it change Entergy's determination of no significant hazards consideration.

If you have any questions or require additional information, please contact Mr. James M.

DeVincentis at (802) 258-4236.

I declare under penalty of perjury that the foregoing is true and correct.

Executed on September

3o, 2004.

Sincerely, 6&L 4. aLfiO Robert J. Vonizyk

(/a(

Director, Near Safety Assurance Vermont Yankee Nuclear Power Station

BVY 04-101 Page 3 of 3 cc:

Mr. Richard B. Ennis, Project Manager Project Directorate I Division of Licensing Project Management Office of Nuclear Reactor Regulation Mail Stop 0 8 B1 Washington, DC 20555 Mr. Samuel J. Collins Regional Administrator, Region 1 U.S. Nuclear Regulatory Commission 475 Allendale Road King of Prussia, PA 19406-1415 USNRC Resident Inspector Entergy Nuclear Vermont Yankee, LLC P.O. Box 157 Vernon, Vermont 05354 Mr. David O'Brien, Commissioner VT Department of Public Service 112 State Street - Drawer 20 Montpelier, Vermont 05620-2601

BVY 04-101 Licensee Identified Commitment Form This form identifies actions discussed in this letter for which Entergy Nuclear Operations, Inc.

(Entergy) commits to perform. Any other actions discussed in this submittal are described for the NRC's information and are not commitments.

TYPE (Check one)

SCHEDULED COMMITMENT COMPLETION

' °

.p&

DATE (If Required)

C:<

0 E 0

0 Revise the MOV Periodic Verification Program to X

12101/04 include periodic at-the-valve testing and formalize the process for DC motor trending I

-I

+

I