L-2017-006, Supplement to License Amendment Request 236, Revision to the Technical Specifications to Adopt Risk Informed Completion Times TSTF-505, Revision 1, Provide Risk-Informed Extended Completion Times RITSTF Initiative 4b

From kanterella
(Redirected from L-2017-006)
Jump to navigation Jump to search

Supplement to License Amendment Request 236, Revision to the Technical Specifications to Adopt Risk Informed Completion Times TSTF-505, Revision 1, Provide Risk-Informed Extended Completion Times RITSTF Initiative 4b
ML17060A249
Person / Time
Site: Turkey Point  
Issue date: 02/09/2017
From: Summers T
Florida Power & Light Co
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
L-2017-006
Download: ML17060A249 (85)


Text

U.S. Nuclear Regulatory Commission Attn: Document Control Desk Washington, D.C. 20555-0001 Re:

Turkey Point Nuclear Plant, Units 3 and 4 Docket Nos. 50-250 and 50-251 February 9, 2017 L-2017-006 10 CFR 50.90 Supplement to License Amendment Request 236, Revision to the Technical Specifications to Ad?pt Risk Informed Completion Times TSTF-505, Revision 1, Provide Risk-Informed Extended Completion Times - RITSTF Initiative 4b"

References:

1. Florida Power & Light Company letter L-2014'-369, License Amendment Request No. 236 Revision to the Technical Specifications to Adopt Risk Informed Completion Times TSTF-505, Revision 1, 'Provide Risk-Informed Extended Completion Times - RITSTF Initiative 4B'.," December 23, 2014 (ML15029A297)
2. NRC E-mail "Request for Additional Information re. Turkey Point 3 & 4 LAR-236 (CACs MFS455 & MF5456)," April 14, 2016 (ML16105A459)
3. NRC E-mail "Request for Additional Information - Turkey Point 3 & 4 LAR-236 (CACs MF5455 & MF5456)," April 18, 2016 (ML16110A004)
4. NRC E-mail "Request for Additional Information ~e. Turkey Point 3 & 4 LAR-236 (CACs _

MF54555 & MFS456)," June 1, 2016 (ML16154A339)

5. Florida Power & Light Company letter L-2016-116, Response to Request for Additional Information Regarding License Amendment Request 236, Revision to the Technical Specifications to Adopt Risk Informed Completion Times TSTF-505, Revision 1, 'Provide Risk-Informed Extended Completion Times-RITSTF Initiative 4b'," June 16, 2016 (ML16180A178)
6. Florida Power & Light Company letter L-2016-136, "Second Response to Request for Additional Information Regarding License Amendment Request 236, Revision to the Technical Specifications to Adopt Risk Informed Completion Times TSTF-505, Revision 1,

'Provide Risk-Informed Extended Completion Times - RITSTF Initiative 4b'," August 11, 2016 (ML16243A104)

In Reference 1,,as supplemented by References 5 and 6, Florida Power & Light Company (FPL) submitted license amendment request (LAR) 236 for Turkey Point Units 3 and 4. The proposed Florida Power & Light Company 9760 SW 344 St., Homestead, FL 33035

Florida Power & Light Company L-2017-006 Page 2 of 3 amendment would revise the Technical Specifications (TS) to implement TSTF-505, Revision 1, "Provide Risk-Informed Extended Completion Times RITSTF [Risk Informed TSTF] Initiative 4b."

This letter provides a supplement to LAR 236 to address NRC staff concerns with TSTF-505 to support approval of the requested license amendment.

Consistent with TSTF-505, LAR 236 added new TS Actions for configurations that currently would require entry into TS 3.0.3. These Actions provide one hour or a time determined in accordance with the Risk Informed Completion Time (RICT) Program to restore at least one train of the inoperable system. TSTF-505 allows applying a RICT under emergent conditions that result in loss of a specified safety function or inoperability of all required trains of a system required to be operable provided one or more of the trains is probabilistic risk assessment (PRA) functional.

The current Turkey Point TS also include Actions for conditions that represent a loss of function, and the LAR proposed adding a RICT to these Actions.

In a letter to the Technical Specifications Task Force on November 15, 2016, and during a public meeting on December 13, 2016, the NRC staff discussed its concerns with TSTF-505. The staff determined that reductions in safety margin and defense-in-depth have not been adequately evaluated for the loss of function conditions permitted in TSTF-505. As a result, the NRC has suspended approval of TSTF-505 until the staffs concerns are resolved. At the same time, the staff stated that it intef!.dS to continue its review of in-house applications requesting adoption of RICT programs.

One of the industry-proposed options to address the staffs concerns in future LARs is to exclude the use of the loss of function provisions currently provided in TSTF-505. FPL is using this approach in its supplement to the LAR by removing the loss of function provisions. This supplement revises the LAR to remove the new TS Actions for configurations that currently would require entry into TS 3.0.3. Similarly, the supplement removes the application of RICTs to existing Actions that represent a loss of function. In addition, the new Risk Informed Completion Time Program added to the administrative section of the TS is modified to exclude use of a RICT for any configuration that represents loss of a specified safety function or inoperability of all required trains of a system required to be operable. For the reasons discussed above, this supplement removes the proposed RICTs for which there is no consensus between staff and industry. This change is intended to allow the staff to move forward with a timely review and approval of the requested amendment. to this letter provides a table that displays the relevant TS changes previously proposed in References 1 and 6 and the modifications to the proposed changes. Attachment 2 provides a complete markup of the TS for LAR 236, including the modifications to the proposed changes presented in Attachment 1, and supersedes the TS markups provided in Attachment 2 to Reference 1 and Attachment 1 to Reference 6.

Revised TS pages are provided in Attachment 3 and supersede the corresponding pages provided in to Reference 1 and Attachment 2 to Reference 6. Attachment 4 provides proposed changes to the TS Bases and supersedes the corresponding Bases changes provided in Attachment 4 to Reference 1 and Attachment 3 to Reference 6.

Florida Power & Light Company L-2017-006 Page 3 of 3 This supplement does not alter the conclusions in Reference 1 that the changes do not involve a significant hazards consideration pursuant to 10 CFR 50.92, and there are no significant environmental impacts associated with the changes.

No new or revised commitments are included in this letter.

Should you have any questions regarding this submittal, please contact Mr. Mitch Guth, Licensing Manager, at (305) 246-6698.

I declare under penalty of perjury that the foregoit_!_g is true and correct.

Executed on February 9, 2017 Sincerely,

~~~r--:

Thomas Summers Regional Vice President - Southern Region Florida Power & Light Company Enclosure cc:

NRC Regional Administrator, Region II NRC Senior Resident Inspector NRC Project Manager Ms. Cindy Becker, Florida Department of Health

Florida Power & Light Company ATTACHMENT 1 L-2017-006 Summary of Modifications to the Proposed Changes to the Technical Specifications

Florida Power & Light Company Page 1of6 Pre.Vfov~IyP,~?p6s~d::~,i:iat)g~

~-**

Technical * * * * ' * **

Table 3.3-1 ESFAS

  • ~

~~

-~.. - -

Add new Action 1A with a risk informed completion time (RlCT) for the condition that two manual reactor trip channels are inoperable Add new Action 10A with a RICT for the condition that one diverse trip feature on two or more reactor trip breakers is inoperable Add new Action 18A with a RICT for the condition that both required instrument channels are inoperable Add new Action 27 with a RICT for the condition that two or more required instrument channels are inoperable Add new Action 29 with a RICT for the condition that both required instrument channels are inoperable Revise Action b to apply risk informed completion time (RlCT):

L-2017-006

  • *Modification io Proposed *

..... *... **. Chan*e..

Proposed change is deleted.

Proposed change is deleted.

Propo.sed change is deleted.

Proposed change is deleted.

Proposed change is deleted.

b. With one accumulator inoperable due to the boron concentration not being within the limits, restore boron concentration back to the required limits within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> or in Proposed change is deleted.

TS 3.5.1 accordance with the Risk Infr>rmed Completion Time Program, or be in at least Accumulators HOT STANDBY within 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and reduce pressurizer pressure to less than 1000 psig within the following 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />.

Add new Action c with a RICT for two or more accumulators inoperable Proposed change is deleted.

Revise Action h to apply RICT:

With the suction flow path from the refueling water storage tank inoperable, restore the Proposed change is deleted.

TS 3.5.2 suction flow path to OPERABLE status within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> or in accordance with the Risk ECCS Subsystems Infr>rmed Completion Time Program, or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in HOT SHUTDOWN within the following 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />.

Add new Actions i, j, k, 1, and m with a RICT for the conditions that redundant ECCS Proposed changes are components are inoperable deleted.

Florida Power & Light Company Page 2 of 6

'.. Techiifoal

'*~:, :.t*:

1

,, ' *.. ':~i~0ous.I~ *:~~op9s~¢(Cha~ge

~***'

-* ~. '

,, ' s edficaiion Revise Action to apply RICT:

TS 3.5.4 With less than the required number of RWST(s) OPERABLE, restore the tank(s) to Refueling Water OPERABLE status within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> or i.n accordance with the Risk In!Ormed Storage Tank Completion Time Program, or be in at least HOT STANDBY within 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

Revise Action b to apply RICTs:

With two Containment Spray Systems inoperable restore at least one Spray System to TS 3.. 6.2.1 OPERABLE status within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> or in accordance with the Risk In!Ormed Containment Spray Completion Time Program, or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> System and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />. Restore both Spray Systems to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> of initial loss or i.n accordance with the Risk In!Ormed Completion Time Program, or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

Revise Action b to apply RICTs:

(

With two or more of the above required emergency containment cooling units TS 3.6.2.2 inoperable, restore at least two cooling units to OPERABLE status within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> or i.n Emergency accordance with the Risk In!Ormed Completion Time Program, or be in at least Containment HOT STANDBY within the next 6.hours and in COLD SHUTDOWN within the Cooling System following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />. Restore all of the above required cooling units to OPERABLE status

/

within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> of initial loss or i.n accordance with the Risk In!O.tmed Completion Time Program, or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

L-2017-006 Modi.fication to Propose.Cl. *

  • * ***, :than e, Proposed change is deleted.

Delete the RICT from the first statement in the Action.

Delete the RICT from the first statement in the Action.

Florida Power & Light Company Page 3 of 6 TS 3.7.1.2 Auxiliary Feedwater System TS 3.7.1.3 Condensate Storage Tank Revise Action 2 to apply RICT:

With both required auxiliary feedwater trains inoperable, within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> or in accordance with the Risk InfO.aned Completion Time Program, either restore both trains to an OPERABLE status, or restore one train to an OPERABLE status and follow ACTION statement 1 above for the other train. If neither train can be restored to an OPERABLE status within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> or in accordance with the Risk InfO.aned Completion Time Program, verify the OPERABILITY of both standby feed-water pumps and place the affected unit(s) in at least HOT STANDBY within the next 6 hour6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />s* and in HOT SHUTDOWN within the following 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> Revise Actions to apply RICT:

Opposite Unit in MODES 4. 5 or 6 With the CST system inoperable, within 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> or in accordance with the Risk InfO.aned Completion Time Program, restore the CST system to OPERABLE status or be in at least HOT STANDBY in the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in HOT SHUTDOWN within the following 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />.

Opposite Unit in MODES 1. 2 or 3

1) With the CST system inoperable due to indicating less than 420,000 gallons, but greater than or equal to 210,000 gallons indicated, within 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> or in accordance with the Risk InfO.aned Completion Time Program, restore the inoperable CST system to OPERABLE status or place one unit in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in HOT SHUTDOWN within the following 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />.
2) With the CST system inoperable with les's than 210,000 gallons indicated, within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> or in accordance with the Risk InfO.aned Completion Time Program, restore the CST system to OPERABLE status or be in at least HOT STANDBY within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and in HOT SHUTDOWN within the following 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />.

This ACTION applies to both units simultaneously.

L-2017-006

  • M_odification to ~roposed.

..... Chall. e Delete the RICT from the condition that both required auxiliary feedwater trains are inoperable.

Proposed changes are deleted.

Florida Power & Light Company Page 4 of 6

  • *T~chtiical *.,. *
  • S ecificatipn ;,. ;\\t '

TS 3.7.1.5 Main Steam Add new Action b with a RICT for the condition that two or more MSIVs are inoperable in Isolation Valves Mode 1 (MSIV)

Revise Action c to apply RICT:

TS 3.7.2

c. With less than two CCW heat exchangers OPERABLE, restore two heat exchangers to Component OPERABLE status within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> or in accordance with the Risk Informed Cooling Water Completion time Program, or be in HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in (CCW)

COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

Add new Action d with a RICT for the condition that*three CCW pumps are inop~rable TS 3.7.3 Add new Action d with a RICT for the condition that three ICW pumps are inoperable Intake Cooling Add new Action e with a RICT for the condition that two ICW headers are inoperable Water (ICW)

L-2017-006 Modification to Proposed Chan e Proposed change is deleted.

Proposed change is deleted.

Proposed change is deleted.

Proposed change is deleted.

Proposed change is deleted.

Florida Power_& Light Company Page 5 of 6

_ - Techillcaf

-s ecification ' :

TS 3.8.1.1 AC Sources TS 3.8.2.1 DC Sources TS 3.8.3.1 Onsite Power Distribution

~'*'!." - '( *: _.\\.

..<Y

'j

.'i-"<

--.. **: *.. Pr~yi9~s_ly ~t()pO_S~~hChange,; c<

'-'?.-'

~--

Revise Action e to apply RICT:

With two of the above required startup transformers or their associated circuits

' *'~

inoperable notify the NRC within 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br />; restore at least one of the inoperable startup transformers to OPERABLE status within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> or in accordance with the Risk Inf.Ormed Completion time Program, or be in at least HOT STANDBY within the next 6 hour6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />s* and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

Revise Action f to apply RICT:

With two of the above required diesel generators inoperable, demonstrate the OPERABILITY of two startup transformers and their associated circuits by performing the requirements of Specification 4.8.1:1.la. within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> and at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter; restore at least one of the inoperable diesel generators to OPERABLE status within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> or in accordance with the Risk I.nf.Ormed Completion time Program, or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

Add new Action i with a RICT for the condition that three or more AC sources are inoperable Add new Action c with a RICT for the condition that two or more battery banks or battery chargers are inoperable Replace Action d with a new Action with a RICT for the condition that two or more A.C.

vital panels are not energized from their associated inverters or inverters are not connected to their associated D.C. buses L-2017-006

~Modification to Proposed Chan e Proposed change is deleted.

Proposed change is deleted.

Proposed change is deleted.

Proposed change is deleted.

Proposed change is deleted.

Florida Power & Llght Company Page 6 of 6

  • : - Techliic~I : "
  • S edfi~ati'an'

TS 6.8.4.m

m.

<~

Risk Informed C ompletlon lune Program This program provides controls to calculate a Risk Informed Completion Time (RICT) and must be implemented in accordance with NEI 06-09, "Risk-Informed Technical Specification Initiative 4b: Risk-Managed Technical Specifications (RMTS) Guidelines, Revision 0-A, November 2006. The program shall include the following:

a. The RICT may not exceed 30 days;
b. A RICT may only be utilized in MODES 1 and 2;
c. When a RICT is being used, any plant configuration change within the scope of the Risk Informed Completion Time Program must be considered for the effect on the RICT.
1. For planned changes, the revised RICT must be determined prior to implementation of the change in configuration.
2. For emergent conditions, the revised RICT must be determined within the time limits of the Required Action Completion Time (i.e., not the

. RICT) or 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> after the plant configuration change, whichever is less.

3. Revisin~ the RICT is not required if the plant configuration change would ower plant risk and would result in a longer RICT.
d. Use of a RICT is not permitted for voluntary entry into a configuration which represents a loss 'of a specified safety function or inoperability of all required trains of a system required to be OPERABLE.
e. Use of a RICT, not to exceed 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />, is permitted for emergent conditions which represent a loss of a specified safety function or inoperability of all required trains of a system required to be OPERABLE if one or more of the trains are considered "PRA functional" as defined in Section 2.3.1 of NEI 06-09.

L-2017-006

-Modification to Proposed ::

  • Chan e -

Item d is revised to remove the term "voluntary."

Item e is deleted.

Florida Power & Light Company ATTACHMENT 2 Markup of the Technical Specifications (30 pages follow)

L-2017-006

INSERTt J

or in accordance with the Risk Informed Completion Time Program, INSERT 2

m.

Risk Informed Completion Time Program This program provides controls to calculate a Risk Informed Completion Time (RICT) and must be implemented in accordance with NEI 06-09, "Risk-Informed Technical Specifications' Initiative 4b: Risk-Managed Technical Specifications (RMTS) Guidelines," Revision 0-A, November 2006. The program shall include the following:

a.

The RICT may not exceed 30 days;

b. A RICT may only be utilized in MODES 1 and 2;
c. When a RICT is being used, any plant configuration change within the scope of the Risk Informed Completion Time Program must be considered for the effect on the RICT.
1. For planned changes, the revised RICT must be determined prior to implementation of the change in configuration.
2. For emergent conditions, the revised RICT must be determined within the time limits of the Required Action Completion Time (i.e:, not the RICT) or 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> after the plant configuration change, whichever is less.
3. Revising the RICT is not required If the plant configuration change would lower plant risk and would result in a longer RICT.
d. Use of_a RICT is not permitted for entry into a configuration which represents a loss of a specified safety function or inoperability of all requir~d trains of a system required to be OPERABLE.

TABLE 3.3-1 (Continued)

TABLE NOTATION When the Reactor Trip System breakers are in the closed position and the Control Rod Drive System is capable of rod withdrawal.

When the Reactor Trip System breakers are in the open position, one or both of the backup NIS instrumentation channels may be used to satisfy this requirement. For backup NIS testing requirements, see Specification 3/4.3.3.3, ACCIDENT MONITORING.

Reactor Coolant Pump breaker A is tripped by underfrequency sensor UF-3A1(UF-4A1) or UF-3B1 (UF-4B1 ). Reactor Coolant Pump breakers Band Care tripped by underfrequency sensor UF-3A2(UF-4A2) or UF-3B2(UF-4B2).

Below the P-6 (Intermediate Range Neutron Flux Interlock) Setpoint.

Below the P-10 (Low Setpoint Power Range Neutron Flux Interlock) Setpoint.

ACTION STATEMENTS ACTION 1 - With the number of OPERABLE channels one less than the Minimum Channels OPERABLE requirement, restore the inoperable channel to OPERABLE status within 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> or be in HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />.

~

ACTION 2 -With the number of OPERABLE channels one less than the Total Number of Channels, STARTUP and/or POWER OPERATION may proceed provided the following conditions are satisfied:

a.
b.
c.

The inoperable channel is placed in the tripped condition within 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />,

}-

The Minimum Channels OPERABLE requirement is met; however, the inoperable I ~

channel may be bypassed for up to 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> for surveillance testing of other channels per f Specification 4.3.1.1, and Either, THERMAL POWER is restricted to less than or equal to 75% of RATED THERMAL POWER and the Power Range Neutron Flux Trip Setpoint is reduced to less than or equal to 85% of RA TED THERMAL POWER within 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br />; or, the QUADRANT POWER TILT RATIO is monitored per Specification 4.2.4.2.

TURKEY POINT - UNITS 3 & 4 3/4 3-5 AMENDMENT NOS. ~ AND ++J

TABLE 3.3-1 (Continued)

ACTION STATEMENTS (Continued)

ACTION 3 - With the number of channels OPERABLE one less than the Minimum Channels OPERABLE requirement and with the THERMAL POWER level:

a. Below the P-6 (Intermediate Range Neutron Flux Interlock) Setpoint, restore the inoperable channel to OPERABLE status prior to increasing THERMAL POWER above the P-6 Setpoint, and
b. Above P-6 (Intermediate Range Neutron Flux Interlock) Setpoint but below 10% of RATED THERMAL POWER, restore the inoperable channel to OPERABLE status prior to increasing THERMAL POWER above 10% of RATED THERMAL POWER.

ACTION 4 - With the number of OPERABLE channels one less than the Minimum Channels OPERABLE requirement, suspend all operations involving positive reactivity changes.

ACTION 5 - With the number of OPERABLE channels one less than the Minimum Channels OPERABLE requirement, suspend all operations involving positive reactivity changes and verify compliance with the SHUTDOWN MARGIN requirements of Specification 3.1.1.1 or 3.1.1.2, as applicable, within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> and at least once per 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> thereafter.

ACTION 6 - With the number of OPERABLE channels one less than the Total Number of Channels, STARTUP and/or POWER OPERATION may proceed until performance of the next required ANALOG CHANNEL OPERATIONAL TEST provided the inoperable channel is placed in the tripped condition within 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />.

)

ACTION 7 - With less than the Minimum Number of Channels OPERABLE, within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> determine by observation of the associated permissive annunciator window(s) that the interlock is in its required state for the existing plant condition, or apply Specification 3.0.3.

ACTION 8 - With the number of OPERABLE channels one less than the Minimum Channels OPERABLE requirement, be in at least HOT STANDBY within 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />; however, one channel may be bypassed for up to 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> for surveillance testing per Specification 4.3.1.1, provided the other channel is OPERABLE.

ACTION 9 - With the number of OPERABLE channels one less than the Minimum Channels OPERABLE requirement, restore the inoperable channel to OPERABLE status within 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> or open the Reactor Trip System breakers within the next hour.

Insert 1 ACTION 10- With one of the diverse trip features (undervolt or shunt trip attachment) inoperable, restore it to OPERABLE status within 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> or declare the breaker inoperable and apply ACTION 8. The breaker shall not be bypassed while one of the diverse trip features is inoperable, except for the time required for performing maintenance to restore the breaker to OPERABLE status.

TURKEY POINT - UNITS 3 & 4 3/4 3-6 AMENDMENT NOS..:i-+-9 AND ~

--l c

0

/\\

m

"'U 0 z

--l I c z

=i

(/)

w Qo

)>

s::

m z

0 s::

m z

--l z 0

(/)

t

)> z 0

~

TABLE 3.3-2 ENGINEERED SAFETY FEATURES ACTUATION SYSTEM INSTRUMENTATION FUNCTIONAL UNIT

1.

Safety Injection

a. Manual Initiation
b. Automatic Actuation Logic and Actuation Relays
c. Containment Pressure - High
d.

Pressurizer Pressure - Low

e. High Differential Pressure Between the Steam Line Header and any Steam Line TOTAL NO.

CHANNELS OF CHANNELS TO TRIP 2

2 1

3 2

3 2

3/steam line 2/steam line in any steam line MINIMUM CHANNELS OPERABLE 2

2 2

2 2/steam line APPLICABLE MODES 1 2, 3, 4 1 2, 3, 4 1 2, 3 1 2, 3#

1 2, 3#

ACTION 14

TABLE 3.3-2 {Continued)

-I c

ENGINEERED SAFETY FEATURES ACTUATION SYSTEM INSTRUMENTATION

a m

MINIMUM

-0 TOTAL NO.

CHANNELS CHANNELS APPLICABLE 0

FUNCTIONAL UNIT OF CHANNELS TO TRIP OPERABLE MODES ACTION z

-I I

f.

Steam Line flow--High 2/steam line 1 /steam line 1/steam line 1, 2, 3*

~~

c Coincident with:

in any two in any two z

=i steam lines steam lines

(/)

(,.)

Steam Generator QI>

~

Pressure--Low 1/steam 1/steam 1/steam 1, 2. 3*

~ r generator generator generator in any two in any two steam lines steam lines or

(,.)

Tav9--Low 1/loop 1 /loop in any 1 /loop in any 1, 2, 3*

25

~

two loops two loops

(,.)

I.....

(.11

2.

Containment Spray

a. Automatic Actuation 2

2 1, 2, 3, 4 14 Logic and Actuation

)>

Relays s::

m

b.

Containment Pressure--

3 2

2 1, 2, 3

~

z 0

High-High s::

Coincident with:

m z

Containment Pressure--

-I z

High 3

2 2

1, 2, 3

~

0

(/)

3.

Containment Isolation

~Y t

Phase "A" Isolation

)>

a.

z

1) Manual Initiation 2

2 1, 2, 3, 4 0

t

2) Automatic Actuation 2

2 1, 2, 3, 4 14 Logic and Actuation Relays

-l c

0
"\\

m "1J 0 z

-l I c z

=l

(/)

v.>

QC>

~

)>

s::

m z

0 s::

m z

-l z

0

(/)

~

)> z 0

~

TABLE 3.3-2 (Continued)

ENGINEERED SAFETY FEATURES ACTUATION SYSTEM INSTRUMENTATION FUNCTIONAL UNIT

3.

Containment Isolation (Continued)

3)

Safety Injection

b.

Phase "B" Isolation

1) Manual Initiation
2) Automatic Actuation Logic and Actuation Relays
3)

Containment Pressure--High-High Coincident with:

Containment Pressure--

High

c. Containment Ventilation Isolation
1) Containment Isolation Manual Phase A or Manual Phase B TOTAL NO.

CHANNELS OF CHANNELS TO TRIP MINIMUM CHANNELS OPERABLE APPLICABLE MODES See Item 1. above for all Safety Injection initiating functions and (Manual S.I. initiation will not initiate Phase A Isolation).

2 2

3 3

2 (Both buttons must be pushed simultaneously to actuate) 2 2

2 1, 2, 3,4 2

1, 2, 3, 4 2

1, 2, 3 2

1, 2, 3 ACTION requirements.

47J 14 15 15 See Items 3.a.1 and 3.b.1 above for all Manual Containment Ventilation functions and requirements.

--i c

0
ii
::

m

-0 0 z

--i I c z

=i Cf)

(,)

QO

.i::.

)>

s::

m z

0 s::

m z

--i z 0

Cf)

~

)> z 0

£ TABLE 3.3-2 (Continued)

ENGINEERED SAFETY FEATURES ACTUATION SYSTEM INSTRUMENTATION FUNCTIONAL UNIT

6.

Auxiliary Feedwater### (Continued)

b. Stm. Gen. Water Level--

Low-Low

c. Safety Injection
d. Bus Stripping
e. Trip of all Main Feed-water Pumps Breakers
7.

Loss of Power

a.

4.16 kV Susses A and B (Loss of Voltage)

b.

480 V Load Centers 3A, 38, 3C, 3D and 4A, 48, 4C, 4D Undervoltage Coincident with:

Safety Injection TOTAL NO.

CHANNELS OF CHANNELS TO TRIP 3/steam 2/steam generator generator in any steam generator MINIMUM CHANNELS OPERABLE 2/steam generator APPLICABLE MODES 1, 2, 3 ACTION See Item 1. above for all Safety Injection initiating functions and requirements.

1/bus 1/breaker 2/bus 2 per load center 1/bus (1/breaker)

/operating pump 2/bus 2 on any load center 1/bus (1 /breaker)

/operating pump 2/bus 2 per load center 1, 2, 3 23 1, 2 23 1, 2, 3, 4 18 1, 2, 3, 4 18 See Item 1. above for all Safety Injection initiating functions and requirements.

t

ACTION 18 -

ACTION 19 -

ACTION 20-ACTION 21 -

ACTION 22 -

ACTION 23-ACTION 24 -

ACTION 25 -

or in accordance with the Risk Informed Completion Time Program.

TABLE 3.3-2 (Continued)

TABLE NOTATION (Continued)

With the number of OPERABLE channels one les han the Total Number of Channels, STARTUP and/or POWER OPERATION maY.

ceed provided the inoperable channel is +

placed in the tripped condition within 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> oth channels of any one load center may be taken out of service for up to 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> in order to perform surveillance testing per Specification 4.3.2.1.

With less than the Minimum Number of Channels OPERABLE, within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> determine by observation of the associated permissive annunciator window(s) that the interlock is in its required state for the existing plant condition, or apply Specification 3.0.3.

With the number of OPERABLE channels one less than the Minimum Channels OPERABLE requirement, be in at least HOT STANDBY within 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in at least HOT SHUTDOWN within the following 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />; however, one channel may be bypassed for up to 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> for surveillance testing per Specification 4.3.2.1 provided the other channel is OPERABLE.

With the number of OPERABLE channels one less than the Total Number of Channels, restore the inoperable channel to OPERABLE status within 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> or declare the associated valve inoperable and take the ACTION required by Specification 3.7.1.5.

With the number of OPERABLE channels one less than the Minimum Channels OPERABLE requirement, be in at least HOT STANDBY within 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />; however, one channel may be bypassed for up to 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> for surveillance testing per Specification 4.3.2.1 provided the other channel is OPERABLE.

With the number of OPERABLE channels one less than the Minimum Channels OPERABLE requirement, comply with Specification 3.0.3.

Control Room With the number of OPERABLE channels on ess than the Minimum Channels OPERABLE requirement, within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> isolate the GORtrol room Emergency Ventilation System and initiate operation of the Control Room Emergency Ventilation System in the recirculation mode.

With number of OPERABLE channels one less than the Total number of channels, STARTUP and/or POWER OPERATION may proceed provided the inoperable channel is placed in the tripped condition within 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> or subsequent required DIGITAL CHANNEL OPERATIONAL TESTS the inoperable chann ay be placed in bypass status for up to 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br />.

or in accordance with the Risk Informed Completion Time Program.

ACTION 26 - With one channel inoperable, operation may proceed until performance of the next required ANALOG CHANNEL OPERATIONAL TEST or TRIP ACTUATING DEVICE OPERATIONAL TEST provided the inoperable channel is placed in the tripped condition within 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> or in accordance with the Risk Informed Completion Time Program.

ACTION 27-With one channel inoperable, restore the inoperable channel to OPERABLE status within 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> or in accordance with the Risk Informed Completion Time Program, or be in HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

TURKEY POINT - UNITS 3 & 4 3/4 3-22 AMENDMENT NOS. ~ AND ~

REACTOR COOLANT SYSTEM OPERATING LIMITING CONDITION FOR OPERATION 3.4.2.2 All pressurizer Code safety valves shall be OPERABLE with a lift setting of 2465 psig + 2%, -3%.* ** APPLICABILITY:

MODES 1, 2 and 3.

ACTION:

With one pressurizer Code safety valve inoperable, either restore the inoperable valve to OPERABLE status within 15 minutes~

or be in at least HOT STANDBY within 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in at least HOT SHUTDOWN within the following 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />.

INSERT 1 SURVEILLANCE REQUIREMENTS 4.4.2.2 No additional requirements other than those required by Specification 4.0.5.

  • The lift setting pressure shall correspond to ambient conditions of the valve at nominal operating temperature and pressure.
    • All valves tested must have "as left" lift setpoints that are within +/- 1 % of the lift setting value.

TURKEY POINT - UNITS 3 & 4 3/4 4-8 AMENDMENT NOS. ~ AND ~

3/4.5 EMERGENCY CORE COOLING SYSTEMS 3/4.5.1 ACCUMULATORS LIMITING CONDITION FOR OPERATION 3.5.1 Each Reactor Coolant System (RCS) accumulator shall be OPERABLE.

APPLICABILITY:

MODES 1, 2, and 3*.

INSERT 1 ACTION :

a.

With one accumulator inoperable, except as a result of boron concentration being within limits, restore the inoperable accumulator to OPERABLE status within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and reduce pressurizer pressure to less than 1000 psig within the following 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />.

b.

With one accumulator inoperable due to the boron concentration not being within the limits, restore boron concentration back to the required limits within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br />, or be in at least HOT STANDBY within 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and reduce pressurizer pressure to less than 1000 psig within the following 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />.

SURVEILLANCE REQUIREMENTS 4.5.1.1 Each accumulator shall be demonstrated OPERABLE:

a.

In accordance with the Surveillance Frequency Control Program by:

1)

Verifying the borated water volume in each accumulator is between 6520 and 6820 gallons, and

2)

Verifying that the nitrogen cover pressure in each accumulator is between 600 and 675 psig, and

3)

Verifying that each accumulator isolation valve is open by control room indication (power may be restored to the valve operator to perform this surveillance if redundant indicator is inoperable).

  • Pressurizer pressure above 1000 psig.

TURKEY POINT - UNITS 3 & 4 3/4 5-1 AMENDMENT NOS. ~ AND ~

EMERGENCY CORE COOLING SYSTEMS 3/4.5.2 ECCS SUBSYSTEMS - Tavg GREATER THAN OR EQUAL TO 350°F LIMITING CONDITION FOR OPERATION 3.5.2 The following Emergency Core Cooling System (ECCS) equipment and flow paths shall be OPERABLE:

a.

Four Safety Injection (SI) pumps, each capable of being powered from its associated OPERABLE diesel generator#, with discharge flow paths aligned to the RCS cold legs,*

b.

Two RHR heat exchangers,

c.

Two RHR pumps with discharge flow paths aligned to the RCS cold legs,

d.

A flow path capable of taking suction from the refueling water storage tank as defined in Specification 3.5.4, and

e.

Two flow paths capable of taking suction from the containment sump.

APPLICABILITY: MODES 1, 2, and 3**.

ACTION:

a.
b.
c.

INSERT 1 With one RHR heat exc anger or suction flow path from the containment sump inoperable, restore the inoperable RHR h t exchanger or suction flow path from the containment sump to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in HOT SHUTDOWN within the following 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />.

In the event the ECCS is actuated and injects water in the Reactor Coolant System, a Special Report shall be prepared and submitted to the Commission pursuant to Specification 6.9.2 within 90 days describing the circumstances of the actuation and the total accumulated actuation cycles to date since January 1, 1990.

With one of the four required Safety Injection pumps or its associated discharge flow path inoperable v and the opposite unit in MODE 1, 2, or 3, restore the pump or flow path to OPERABLE status within 1

30 days or be in at least HOT STANDBY within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and in HOT SHUTDOWN within the following 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />.***

  • only three Safety Injection (SI) pumps (two associated with the unit and one from the opposite unit), each y

capable of being powered from its associated OPERABLE diesel generator#, with discharge flow paths aligned "I to the RCS cold leg are required if the opposite unit is in MODE 4, 5, or 6.

    • The provisions of Specifications 3.0.4 and 4.0.4 are not applicable for entry into MODE 3 for the Safety Injection flow paths isolated pursuant to Specification 3.4.9.3 provided that the Safety Injection flow paths are restored to OPERABLE status prior to Tavg exceeding 380°F. Safety Injection flow paths may be isolated when Tavg is less than 380°F.
      • The provisions of Specifications 3.0.4 and 4.0.4 are not applicable.
  1. lnoperability of the required diesel generators does not constitute inoperability of the associated Safety Injection I,,,

pumps.

f TURKEY POINT - UNITS 3 & 4 3/4 5-3 AMENDMENT NOS. ~AND ~

EMERGENCY CORE COOLING SYSTEMS 3/4.5.2 ECCS SUBSYSTEMS - Tavg GREATER THAN OR EQUAL TO 350°F

d.
e.
f.
g.
h.

INSERT 1 With two of the four required Safety lnjectio pumps or their associated discharge flow paths f

inoperable and the opposite unit in MODE 2, or 3, restore one of the two inoperable pumps or flow paths to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> or be in at least HOT STANDBY within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and in HOT SHUTDOWN within the following 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />. This ACTION applies to both units simultaneously.

INSERT 1 With one of e three required Safety Injection pumps or its associated discharge flow path inoperable v and the o osite unit in MODE 4, 5, or 6, restore the pump or flow path to OPERABLE status within 1 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> r be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in HOT SHUTDOWN within the following 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />.

INSERT 1 With a required Safety Injection pump OPERABLE but not capab of being powered from its associated diesel generator, restore the capability within 14 days or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in HOT SHUTDO within the following 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />.

at With an ECCS subsystem inoperable due o an RHR pump or its associated discharge flow path t being inoperable, restore the inoperable R pump or its associated discharge flow path to OPERABLE status within 7 days~

or be in as-least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in HOT SHUTDOWN within the following our INSERT 1 With the suction flow path from the refueling water storage tank inoperable, restore the suction flow 1 path to OPERABLE status within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in HOT SHUTDOWN within the following 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />.

TURKEY POINT - UNITS 3 & 4 3/4 5-4 AMENDMENT NOS. ~ AND ~

CONTAINMENT SYSTEMS CONTAINMENT AIR LOCKS LIMITING CONDITION FOR OPERATION 3.6.1. 3 Each containment air lock shall be OPERABLE with:

a.

Both doors closed except when the air lock is being used for normal transit entry and exit through the containment, or during the performance of containment air lock surveillance and/or testing requirements, then at least one air lock door shall be closed, and

b.

An overall air lock leakage rate in accordance with the Containment Leakage Rate Testing Program.

APPLICABILITY: MODES 1, 2, 3, and 4.

ACTION:

a.

With one containment air lock door inoperable:

1.

Maintain at least the OPERABLE air lock door closed and either restore the inoperable air lock door to OPERABLE status within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> or lock the OPERABLE air lock door closed;

2.

Operation may then continue until performance of the next required overall air lock leakage test provided that the OPERABLE air lock door is verified to be locked closed at least once per 31 days;

3.

Otherwise, be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

b.

With the containment air lock inoperable, except as the result of an inoperable air lock door, maintain at least one air lock door closed; restore the inoperable air lock to OPERABLE status within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN in the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

INSERT 1 TURKEY POINT - UNITS 3 & 4 3/4 6-3 AMENDMENT NOS. 200 AND 2-65 ~

CONTAINMENT SYSTEMS CONTAINMENT VENTILATION SYSTEM LIMITING CONDITION FOR OPERATION 3.6.1.7 Each containment purge supply and exhaust isolation valve shall be OPERABLE and:

a.

The containment purge supply and exhaust isolation valves shall be sealed closed to the maximum extent practicable but may be open for purge system operation for pressure control, for environmental conditions control, for ALARA and respirable air quality considerations for personnel entry and for surveillance tests that require the valve to be open.

b.

The purge supply and exhaust isolation valves shall not be opened wider than 33 or 30 degrees, respectively (90 degrees is fully open).

APPLICABILITY:

MODES 1, 2, 3, AND 4.

ACTION:

INSERT 1

a.

With a containment purge supply and/or exhaust isolation valve(s) open for reasons other t n

given in 3.6.1.7.a above, close the open valve(s) or isolate the penetration(s) within 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br />, otherwise be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

b.

With a containment purge supply and/or exhaust isolation valve(s) having a measured leakage rate exceeding the limits of Specification 4.6.1.7.2, restore the inoperable valve(s) to OPERABLE status or isolate the penetrations such that the measured leakage rate does not exceed the limits of Specification 4.6.1. 7.2 within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> otherwise be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN withi he following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

SURVEILLANCE REQUIREMENTS INSERT 1 4.6.1.7.1 Each containment purge supply and exhaust isolation valve shall be verified to be sealed closed or

)'

open in accordance with Specification 3.6.1.7.a in accordance with the Surveillance Frequency Control Program.

  • 1 4.6.1.7.2 In accordance with the Surveillance Frequency Control Program, each containment purge supply and exhaust isolation valve shall be demonstrated OPERABLE by verifying that the measured leakage rate is less than or equal to 0.05 La when pressurized to Pa.

f 4.6.1. 7.3 In accordance with the Surveillance Frequency Control Program, the mechanical stop on each

{

containment purge supply and exhaust isolation valve shall be verified to be in place and that the valves will open no more than 33 or 30 degrees, respectively.

TURKEY POINT - UNITS 3 & 4 3/4 6-11 AMENDMENT NOS. ~ AND ~

CONTAINMENT SYSTEMS 3/4.6.2 DEPRESSURIZATION AND COOLING SYSTEMS CONTAINMENT SPRAY SYSTEM LIMITING CONDITION FOR OPERATION 3.6.2.1 Two independent Containment Spray Systems shall be OPERABLE with each Spray System capable of taking suction from the RWST and manually transferring suction to the containment sump via the RHR System.

APPLICABILITY:

MODES 1, 2, 3, and 4.

ACTION:

INSERT 1

a.

With one Containment Spray Syst inoperable restore the inoperable Spray System to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

b.

With two Containment Spray Systems inoperable restore at least one Spray System to OPERABLE status within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />. Restore both Spray Systems to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> of initial loss or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the foll ing 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

4.6.2.1 Each Containment Spray System shall be demonstrated OPERABLE:

a.

In accordance with the Surveillance Frequency Control Program by verifying that each valve (manual, power-operated, or automatic) in the flow path that is not locked, sealed, or otherwise secured in position, is in its correct position* and that power is available to flow path components.{

that require power for operation;

b.

By verifying that on recirculation flow, each pump develops the indicated differential pressure, when tested pursuant to Specification 4.0.5:

c.

Containment Spray Pump ~241

. 6 psid while aligned in recirculation mode.

In accordance with the Surveillance Frequency Control Program by verifying containment spray locations susceptible to gas accumulation are sufficiently filled with water.

  • Not required to be met for system vent flow paths opened under administrative control.

TURKEY POINT - UNITS 3 & 4 3/4 6-12 AMENDMENT NOS. ~ AND 2a9

CONTAINMENT SYSTEMS EMERGENCY CONTAINMENT COOLING SYSTEM LIMITING CONDITION FOR OPERATION 3.6.2.2 Three emergency containment cooling units shall be OPERABLE.

APPLICABILITY:

MODES 1, 2, 3, and 4.

INSERT 1

a.

With one of the above required emergency containment co g units inoperable restore the inoperable cooling unit to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

b.

With two or more of the above required emergency containment cooling units inoperable, restore at least two cooling units to OPERABLE status within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />. Restore all of the above required cooling units to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> of initial loss or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the f.

owing 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

INSERT 1 SURVEILLANCE REQUIREMENTS 4.6.2.2 Each emergency containment cooling unit shall be demonstrated OPERABLE:

a.

In accordance with the Surveillance Frequency Control Program by starting each cooler unit from {

the control room and verifying that each unit motor reaches the nominal operating current for the test conditions and operates for at least 15 minutes.

b.

In accordance with the Surveillance Frequency Control Program by:

1)

Verifying that two emergency containment cooling units start automatically on a safety injection (SI) test signal, and

2)

Verifying a cooling water flow rate of greater than or equal to 2000 gpm to each cooler.

TURKEY POINT - UNITS 3 & 4 3/4 6-14 AMENDMENT NOS.~

AND ~

CONTAINMENT SYSTEMS 3/4.6.4 CONTAINMENT ISOLATION VALVES LIMITING CONDITION FOR OPERATION 3.6.4 Each containment isolation valve shall be OPERABLE with isolation times less than or equal to required isolation times.

APPLICABILITY:

MODES 1, 2, 3, and 4.

ACTION:

  • With one or more isolation valves inoperable, maintain at least one isolation valve OPERABLE in each affected penetration that is open and either.

~INSERT 1 I

a.

Restore the inoperable valve(s) to OPERABLE status within 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br />, or

b.

Isolate each affected penetration within 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> use of at least one deactivated automatic containment isolation valve secured in the isolat10 ositi1yu.....u.1.------.

c.

Isolate each affected penetration within 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> y use of a eas one cosed manual valve or blind flange, or

d.

Be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

SURVEILLANCE REQUIREMENTS 4.6.4.1 The isolation valves shall be demonstrated OPERABLE prior to returning the valve to service after maintenance, repair or replacement work is performed on the valve or its associated actuator, control or power circuit by performance of a cycling test, and verification of isolation time.

  • CAUTION: The inoperable isolation valve(s) may be part of a system(s). Isolating the affected penetration(s) may affect the use of the system(s). Consider the technical specification requirements on the affected system(s) and act accordingly.

TURKEY POINT - UNITS 3 & 4 3/4 6-16 AMENDMENT NOS. ~ AND 2§§ t

PLANT SYSTEMS AUXILIARY FEEDWATER SYSTEM LIMITING CONDITION FOR OPERATION 3.7.1.2 Two independent auxiliary feedwater trains including 3 pumps as specified in Table 3.7-3 and associated flowpaths shall be OPERABLE.

APPLICABILITY:

MODES 1, 2 and 3 INSERT 1 ACTION:

1)

With one of the two required independent auxiliary feed ter trains inoperable, either restore the inoperable train to an OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br />, or place the affected unit(s) in at least HOT STANDBY within the next 6 hour6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />s* and in HOT SHUTDOWN within the following 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />.

2)

With both required auxiliary feedwater trains inoperable, within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> either restore both trains to an OPERABLE status, or restore one train to an OPERABLE status and follow ACTION statement 1 above for the other train. If neither train can be restored to an OPERABLE status within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br />, verify the OPERABILITY of both standby feed-water pumps and place the affected unit(s) in at least HOT STANDBY within the next 6 hour6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />s* and in HOT SHUTDOWN within the following 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />. Otherwise, initiate corrective action to restore at least one auxiliary feedwater train to an OPERABLE status as soon as possible and follow ACTION statement 1 above for the other train.

3)

With a single auxiliary feedwater pump inoperable, within 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br />, verify OPERABILITY of two independent auxiliary feedwater trains, or follow ACTION statements 1 or 2 above as applicable.

Upon verification of the OPERABILITY of two independent auxiliary feedwater trains, restore the inoperable auxiliary feedwater pump to an OPERABLE status within 30 days, or place the operating unit(s) in at least HOT STANDBY within 6 hour6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />s* and in HOT SHUTDOWN within the following 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />. The provisions of Specification 3.0.4 are not applicable during the 30 day period for the inoperable auxiliary feedwater pump.

SURVEILLANCE REQUIREMENTS 4.7.1.2.1 The required independent auxiliary feedwater trains shall be demonstrated OPERABLE:

a.

In accordance with the Surveillance Frequency Control Program by:

1)

Verifying by control panel indication and visual observation of equipment that each steam turbine-driven pump operates for 15 minutes or greater and develops a flow of greater than or

  • If this ACTION applies to both units simultaneously, be in at least HOT STANDBY within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and in HOT SHUTDOWN within the following 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />.

TURKEY POINT - UNITS 3 & 4 3/4 7-3 AMENDMENT NOS. ~ AND ~

PLANT SYSTEMS MAIN STEAM LINE ISOLATION VALVES LIMITING CONDITION FOR OPERATION 3.7.1.5 Each main steam line isolation valve (MSIV) shall be OPERABLE.

APPLICABILITY:

MODES 1, 2, and 3.

ACTION:

INSERT 1 MODE 1:

With one MSIV inoperable but open, POWER RATION may continue provided the inoperable valve is restored to OPERABLE status within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />; otherwise be in 1

~oT r NDBIY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in HOT SHUTDOWN within the fellowing 6 ho~rs.

MODES 2 and 3:

MODE 2 SURVEI LLANCE REQUIREMENTS 4.7.1.5 Each MSIV shall be demonstrated OPERABLE by verifying full closure within 5 seconds when tested pursuant to Specification 4.0.5. The provisions of Specification 4.0.4 are not applicable for entry into MODE 3.

With one or more MSIVs inoperable, subsequent operation in MODE 2 or 3 may continue provided:

1. The inoperable MSIVs are closed within 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br />, and
2. The inoperable MSIVs are verified closed once per 7 days.

Otherwise, be in HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in HOT SHUTDOWN within the following 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />.

TURKEY POINT - UNITS 3 & 4 3/4 7-10 AMENDMENT NOS. ~AND ~

PLANT SYSTEMS 3/4.7.2 COMPONENT COOLING WATER SYSTEM LIMITING CONDITION FOR OPERATION 3.7.2 The Component Cooling Water System (CCW) shall be OPERABLE with:

a.

Three CCW pumps, and

b.

Two CCW heat exchangers.

APPLICABILITY:

MODES 1, 2, 3, and 4.

ACTION:

a.

With only two CCW pumps with independent power supplies OPERABLE, restore the inoperable _,....

CCW pump to OPERABLE status within 30 days or be in HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />. The provisions of Specification 3.0.4 are not applicable.

b.

With only one CCW pump OPERABLE or with two CCW pumps OPERABLE but not from independent power supplies, restore two pumps from independent power supplies to OPERABLE status within 72 hour8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br />s~in H~

within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hour~

c.

With less than two CCW heat exchangers OPERABLE, restore two heat exchangers to OPERABLE status within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> or be in HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

SURVEILLANCE REQUIREMENTS 4.7.2 The Component Cooling Water System (CCW) shall be demonstrated OPERABLE:

a.

In accordance with the Surveillance Frequency Control Program, by verifying that two heat exchangers and one pump are capable of removing design basis heat loads.

TURKEY POINT - UNITS 3 & 4 3/4 7-14 AMENDMENT NOS. ~ AND ~

PLANT SYSTEMS 3/4.7.3 INTAKE COOLING WATER SYSTEM LIMITING CONDITION FOR OPERATION 3.7.3 The Intake Cooling Water System (ICW) shall be OPERABLE with:

a.

Three ICW pumps, and

b.

Two ICW headers.

APPLICABILITY:

MODES 1, 2, 3, and 4.

ACTION:

INSERT 1

a.

With only two ICW pumps with independent po r supplies OPERABLE, restore the inoperable ICW pump to OPERABLE status within 14 days or be in HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />. The provisions of Specification 3.0.4 are not applicable.

b.

With only one ICW pump OPERABLE or with two ICW pumps OPERABLE but not from independent power supplies, restore two pumps from independent power supplies to OPERABLE status within 72 hour~r be in HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 3I ours. jlNSERT 1 I

c.

With onl~ne ICW header OPERABLE, restore two headers to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> or be in HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

SURVEILLANCE REQUIREMENTS 4.7.3 The Intake Cooling Water System (ICW) shall be demonstrated OPERABLE:

a.
b.

In accordance with the Surveillance Frequency Control Program by verifying that each valve (manual, power-operated, or automatic) servicing safety-related equipment that is not locked, sealed, or otherwise secured in position is in its correct position; and In accordance with the Surveillance Frequency Control Program during shutdown, by verifying that:

1)

Each automatic valve servicing safety-related equipment actuates to its correct position on a SI test signal, and

2)

Each Intake Cooling Water System pump starts automatically on a SI test signal.

3)

Interlocks required for system operability are OPERABLE.

TURKEY POINT-UNITS 3 & 4 3/4 7-16 AMENDMENT NOS. ~AND ~

ELECTRICAL POWER SYSTEMS LIMITING CONDITION FOR OPERATION <Continued)

APPLICABILITY: MODES 1, 2, 3, and 4.

ACTION:

INSERT 1

a.

With one of two startup transformers or an as ociated circuit inoperable, demonstrate the OPERABILITY of the other startup transform rand its associated circuits by performing Surveillance Requirement 4.8.1.1.1.a within hour and at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter. If the inoperable startup transformer is the ass ciated startup transformer and became inoperable

/

while the unit is in MODE 1, reduce THERM L POWER to ::::30% RA TED THERMAL POWER within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />, or restore the inoperable s up transformer and associated circuits to OPERABLE status within the next 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />. If THERMAL POWER is reduced to ::::30% RA TED THERMAL POWER within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> or if the inoperable startup transformer is associated with the opposite unit restore the startup transformer and its associated circuits to OPERABLE status within 30 days of the loss of OPERABILITY, or be in at least HOT STANDBY within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />. If the inoperable startup transformer is the associated startup transformer and became inoperable while the unit was in MODE 2, 3, or 4 restore the startup transformer and its associated circuits to OPERABLE status within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> in at least HOT STANDBY within 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br /> This ACTION applies to both units simultaneously.

INSERT 1

b.

With one of the required diesel g perable, demonstrate the OPERABILITY of the above required startup transformers and their associated circuits by performing Surveillance Requirement 4.8.1.1.1.a within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> and at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter. If the diesel generator became inoperable due to any cause other than an inoperable support system, an independently testable component, or preplanned preventative maintenance or testing, demonstrate the OPERABILITY of the remaining required diesel generators by performing Surveillance Requirement 4.8.1.1.2.a.4 within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />, unless the absence of any potential common mode failure for the remaining diesel generators is determined. If testing of remaining required diesel generators is required, this testing must be performed regardless of when the inoperable diesel generator is restored to OPERABILITY. Restore the inoperable diesel generator to OPERABLE status within 14 days** r be in at least HOT STANDBY within the

+

next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within th llowin 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

INSERT 1

c.

With one startup transformer and one of the required diesel generators inoperable, demonstrate the OPERABILITY of the remaining A.C. sources by performing Surveillance Requirement 4.8.1.1.1.a on the remaining 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> if inoperability is associated with Action Statement 3.8.1.1.c.

-+

TURKEY POINT - UNITS 3 & 4 3/4 8-2 AMENDMENT NOS. ~ AND ~

ELECTRICAL POWER SYSTEMS LIMITING CONDITION FOR OPERATION <Continued)

ACTION (Continued)

f.

SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />. This ACTION applies to both units simultaneously.

With only one startup transformer and associated circuits restored, perform Surveillance Requirement 4.8.1.1.1 a on the OPERABLE Startup transformer at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br />, and restore the other startup transformer and its associated circuits to OPERABLE status or shutdown in accordance with the provisions of Action Statement 3.8.1.1 a with time requirements of that Action Statement based on the time of initial loss of a startup transformer. This ACTION applies to both units simultaneously.

With two of the above required diesel generators inoperable, demonstrate the OPERABILITY of two startup transformers and their associated circuits by performing the requirements of Specification 4.8.1.1.1 a. within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> and at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter; restore at least one of the inoperable diesel generators to OPERABLE status within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

Restore all required diesel generators to OPERABLE status within 14 days from time of initial loss or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

INSERT 1

g.

Following the addition of the new fuel oil* to the Diesel Fuel Oil Storage Tanks, with one or more diesel generators with new fuel oil properties outside the required Diesel Fuel Oil Testing Program limits, restore the stored fuel oil properties to within the required limits within 30 days.

h.

With one or more diesel generators with stored fuel oil total particulates outside the required Diesel Fuel Oil Testing Program limits, restore the fuel oil total particulates to within the required limits within 7 days.

The properties of API Gravity, specific gravity or an absolute specific gravity; kinematic viscosity; clear and bright appearance; and flash point shall be confirmed to be within the Diesel Fuel Oil Testing Program limits, prior to the addition of the new fuel oil to the Diesel Fuel Oil Storage Tanks.

TURKEY POINT - UNITS 3 & 4 3/4 8-4 AMENDMENT NOS. ~ AND ~

t

3/4.8.2 D.C. SOURCES OPERATING LIMITING CONDITION FOR OPERATION 3.8.2.1 The following D.C. electrical sources shall be OPERABLE:*#

a. 125-volt D.C. Battery Bank 3A or spare battery bank D-52 and associated full capacity charger(s)
1) 3A 1 powered by motor control center (MCC) 3C with EOG 3A OPERABLE, or
2) 3A2 powered by MCC 40 with EOG 4A and 4B OPERABLE, or
3) 3A 1 powered by MCC 3C with EOG 3A OPERABLE and 3A2 powered by MCC 40 with EOG 4A and 4B OPERABLE,
b. 125-volt D.C. Battery Bank 3B or spare battery bank D-52 and associated full capacity charger(s)
1) 3B1 powered by MCC 3B with EOG 3B OPERABLE, or
2) 3B2 powered by MCC 40 with EOG 4A and 4B OPERABLE, or
3) 3B1 powered by MCC 3B with EOG 3B OPERABLE and 3B2 powered by MCC 40 with EOG 4A and 4B OPERABLE,
c. 125-volt D.C. Battery Bank 4A or spare battery bank D-52 and associated full capacity charger(s)
1) 4A 1 powered by MCC 4C with EOG 4A OPERABLE, or
2) 4A2 powered by MCC 30 with EOG 3A and 3B OPERABLE, or
3) 4A 1 powered by MCC 4C with EOG 4A OPERABLE and 4A2 powered by MCC 30 with EOG 3A and 3B OPERABLE,
d. 125-volt D.C. Battery Bank 4B or spare battery bank D-52 and associated full capacity charger(s)
1) 4B1 powered by MCC 4B with EOG 4B OPERABLE, or
2) 4B2 powered by MCC 30 with EOG 3A and 3B OPERABLE, or
3) 4B1 powered by MCC 4B with EOG 4B OPERABLE and 4B2 powered by MCC 30 with EOG 3A and 3B OPERABLE.

APPLICABILITY:

MODES 1, 2, 3, and 4.

ACTION:

INSERT 1

a. With one or more of the required battery chargers OPERABLE but not capable o eing powered from its associated OPERABLE diesel generator(s), restore the capability within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> or be in at least HOT STANDBY within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />. This ACTION applies to both units simultaneously.
  • All battery chargers required to satisfy the LCO shall be powered from separate MCCs.
  1. lnoperability of the required EDG's specified in the LCO requirements below does not constitute inoperability of the associated battery chargers or battery banks.

TURKEY POINT - UNITS 3 & 4 3/4 8-13 AMENDMENT NOS. ~

AND ~

D.C. SOURCES LIMITING CONDITION FOR OPERATION ACTION:

(Continued)

INSERT 1

b.

With one of the required battery banks inoperable, or with none of the full-capacity chargers associated with a battery bank OPERABLE, restore all battery banks to OPERABLE status a at least one charger associated with each battery bank to OPERABLE status within two hours* r be in at least HOT STANDBY within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />. This ACTION applies to both units simultaneously.

SURVEILLANCE REQUIREMENTS 4.8.2.1 Each 125-volt battery bank and its associated full capacity charger(s) shall be demonstrated OPERABLE:

a.

In accordance with the Surveillance Frequency Control Program by verifying that:

1)

The parameters in Table 4.8-2 meet the Category A limits, and

2)

The total battery terminal voltage is greater than or equal to 129 volts on float charge and the battery charger(s) output voltage is ~ 129 volts, and

3)

If two battery chargers are connected to the battery bank, verify each battery charger is supplying a minimum of 10 amperes, or demonstrate that the battery charger supplying less than 10 amperes will accept and supply the D.C. bus load independent of its associated battery charger.

b.

In accordance with the Surveillance Frequency Control Program and within 7 days after a battery {'

discharge with battery terminal voltage below 105 volts (108.6 volts for spare battery D-52), or battery overcharge with battery terminal voltage above 143 volts, by verifying that:

1)

The parameters in Table 4.8-2 meet the Category B limits,

2)

The average electrolyte temperature of every sixth cell is above 60°F, and

3)

There is no visible corrosion at either terminals or connectors, or verify battery connection resistance is:

Battery Connection Limit (Micro-Ohms) 3B, 4A inter-cell I termination

~29 inter-cell (brace locations)

~30 transition cables

~ 125 or total battery connections

~ 1958 Battery Connection Limit (Micro-Ohms) 3A, 4B, D-52 inter-cell I termination

~35 inter-cell (brace locations)

~40 transition cables

~ 125 or total battery connections

< 2463

c.

In accordance with the Surveillance Frequency Control Program by verifying that:

1)

The cells, cell plates, and battery racks show no visual indication of physical damage or abnormal deterioration, 0

  • can be extended to 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> if the opp 1te unit 1s in MODE 5 or 6 and each of the remaining required battery chargers is capable of being powered from its associated diesel generator(s).

TURKEY POINT - UNITS 3 & 4 3/4 8-14 AMENDMENT NOS. ~ AND ~

ONSITE POWER DISTRIBUTION LIMITING CONDITION FOR OPERATION <Continued)

j.

120 Volt AC Vital Panel 3P09 and 3P24 energized from its associated inverter connected to D.C.

Bus 4A.****

k.

120 Volt AC Vital Panel 4P09 and 4P24 energized from its associated inverter connected to D.C.

Bus 4A.****

I.

125 Volt D.C. Bus 3D01 energized from an associated battery charger and from Battery Bank 3A or spare battery bank D-52,

m.

125 Volt D.C. Bus 3D23 energized from an associated battery charger and from Battery Bank 3B or spare battery bank D-52,

n.

125 Volt D.C. Bus 4D01 energized from an associated battery charger and from Battery Bank 4B or spare battery bank D-52, and

o.

125 Volt D.C. Bus 4D23 energized from an associated battery charger and from Battery Bank 4A or spare battery bank D-52 APPLICABILITY:

MODES 1, 2, 3, and 4.

ACTION:

a.

With one of the required trains (3.8.3.1 a., b., and c) of A.C. emergency busses not fully energized (except for the required LC's and MCC's associated with the opposite unit), reenergize the train within 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the follo in hours. INSERT 1

b.

With any of the required LC's and/or MCC's associated with the opposite unit inoperable, restore the inoperable LC or MCC to OPERABLE status in accordance with Table 3.8-1 or Table 3.8-2 as applicable or place the unit in at least HOT STANDBY within 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

INSERT 1

c.

With one A.C. vital panel either not energized from its associated inverter, or with the i rter not connected to its associated D.C. bus: (1) Reenergize the A.C. vital panel within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> or be in at least HOT STANDBY within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />; and (2) reenergize the A.C. vital panel from an inverter connected to its associated D.C.

bus

        • A back-up inverter may be used to replace the normal inverter, provided the normal inverter on the same DC bus for the opposite unit is not replaced at the same time.

TURKEY POINT - UNITS 3 & 4 3/4 8-19 AMENDMENT NOS. ~ AND ~

ONSITE POWER DISTRIBUTION LIMITING CONDITION FOR OPERATION <Continued)

ACTION :

d.

(Continued) f INSERT 1 I within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> or be in at least HOT STANDBY within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />. This ACTION applies to both units simultaneously.

With one D.C. bus not energized from its associated battery bank or associated charger, reenergize the D.C. bus from its associated battery bank within 2 hour2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br />s* or be in at least HOT STANDBY within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and in COLD SHUTDOWN within th following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />. This ACTION applies to both units simultaneously.

INSERT 1 SURVEILLANCE REQUIREMENTS 4.8.3.1 The specified busses shall be determined energized and aligned in the required manner by verifying t correct breaker alignment and indicated voltage on the buses in accordance with the Surveillance Frequency Control Program.

  • Can be extended to 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> if the opposite unit is in MODE 5 or 6 and each of the remaining required battery chargers is capable of being powered from its associated diesel generator(s).

TURKEY POINT - UNITS 3 & 4 3/4 8-20 AMENDMENT NOS. ~ AND ~

Unit 4 Load Centers and Motor Control Centers Inoperable (Any MODE)

LC4A MCC4A LC 4C and/or MCC 4C LC 4H and/or MCC 40 LC 4B and/or MCC 4B LC4D TABLE 3.8-1 APPLICABLE TO UNIT 3 BASED ON UNIT 4 LOAD CENTERS AND MOTOR CONTROL CENTERS INOPERABLE ALLOWABLE OUTAGE TIMES Allowable Outage Times (hours)

Unit 3 - MODES 1, 2, 3 and 4 With AC With AC Trains 3A, 3B, Trains 3A, 4A, & 4B 3B, & 4A OPERABLE OPERABLE N/A 72 N/A 2*

2*

2*

N/A N/A N/A With AC Trains 3A, 3B, & 4B OPERABLE N/A N/A N/A 2*

72

  • If the battery charger powered from the out-of-service LC and/or MCC is not required by LCO 3.8.2.1, the out-of-service time is not applicable (N/A).
    • If neither of the battery chargers powered from the out-of-service LC and/or MCC is required by LCO 3.8.2.1, the out-of-service time is 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br />.~

a or in accordance with the Risk Informed Completion Time Program TURKEY POINT - UNITS 3 & 4 3/4 8-21 AMENDMENT NOS. 446 AND ~

+

Unit 3 Load Centers and Motor Control Centers Inoperable (Any MODE)

LC 3A LC 3C and/or MCC 3C LC 3H and/or MCC 3D LC 3B and/or MCC 3B LC 3D TABLE 3.8-2 APPLICABLE TO UNIT 4 BASED ON UNIT 3 LOAD CENTERS AND MOTOR CONTROL CENTERS INOPERABLE ALLOWABLE OUTAGE TIMES With AC Trains 4A, 4B, 3A, & 3B OPERABLE N/A N/A Allowable Outage Times (hours)

Unit 4 - MODES 1, 2, 3 and 4 With AC Trains 4A, 4B, & 3A OPERABLE N/A N/A With AC Trains 4A, 4B, & 3B OPERABLE N/A N/A

  • If the battery charger powered from the out-of-service LC and/or MCC is not required by LCO 3.8.2.1, the out-

{

of-service time is not applicable (N/A).

    • If neither of the battery chargers powere~ ut-of-service LC and/or MCC is required by LCO 3.8.2.1, the out-of-service time is 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br />.~

a or in accordance with the Risk Informed Completion Time Program TURKEY POINT - UNITS 3 & 4 3/4 8-22 AMENDMENT NOS. 44& AND 44G

ADMINISTRATIVE CONTROLS PROCEDURES AND PROGRAMS (Continued)

I.

Surveillance Frequency Control Program This program provides controls for Surveillance Frequencies. The program shall ensure that Surveillance Requirements specified in the Technical Specifications are performed at intervals sufficient to assure the associated Limiting Conditions for Operations are met:

a.

The Surveillance Frequency Control Program shall contain a list of frequencies of those Surveillance Requirements for which the frequency is controlled by the program.

b.
c.

6.8.5 DELETED Changes to the frequencies listed in the Surveillance Frequency Control Program shall be made in accordance with NEI 04-10, " Risk-Informed Method for Control of Surveillance Frequencies," Revision 1.

The provisions of Surveillance Requirements 4.0.2 and 4.0.3 are applicable to the frequencies established in the Surveillance Frequency Control Program.

TURKEY POINT - UNITS 3 & 4 6-14 AMENDMENT NOS. ~ AND ~

Florida Power & Light Company ATTACHMENT 3 Revised Technical Sp~cification Pages (29 pages follow)

L-2017-006

TABLE 3.3-1 (Continued)

TABLE NOTATION When the Reactor Trip System breakers are in the closed position and the Control Rod Drive.

System is capable of rod withdrawal.

When the Reactor Trip System breakers are in the open position, one or both of the backup NIS instrumentation channels may be used to satisfy this requirement. For backup NIS testing requirements, see Specification 3/4.3.3.3, ACCIDENT MONITORING.

Reactor Coolant Pump breaker A is tripped by underfrequency sensor UF-3A 1(UF-4A1) or UF-3B1(UF-4B1). Reactor Coolant Pump breakers Band Care tripped by underfrequency sensor UF-3A2(UF-4A2) or UF-3B2(UF-4B2).

Below the P-6 (Intermediate Range Neutron Flux Interlock) Setpoint.

Below the P-10 (Low Setpoint Power Range Neutron Flux Interlock) Setpoint.

ACTION STATEMENTS ACTION 1 -With the number of OPERABLE channels one less than the Minimum Channels OPERABLE requirement, restore the inoperable channel to OPERABLE status within 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> or in accordance with the Risk Informed Completion Time Program, or be in HOT STANDE;w within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />.

ACTION 2 -With the number of OPERABLE channels one less than the Total Number of *channels, STARTUP and/or POWER OPERATION may proceed provided the following conditions are satisfied:

a.

The inoperable channel is placed in the tripped condition within 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />,

b.

The Minimum Channels OPERABLE requirement is met; however, the inoperable channel may be bypassed for up to 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> for surveillance testing of other channels per Specification 4.3.1.1, and

c.

Either, THERMAL POWER is restricted to less than or equal to 75% of RATED THERMAL POWER and the Power Range Neutron Flux Trip Setpoint is reduced to less than or equal to 85% of RA TED THERMAL POWER within 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br />; or, the QUADRANT POWER TILT RATIO is monitored per Specification 4.2.4.2.

TURKEY POINT - UNITS 3 & 4 3/4 3-5 AMENDMENTNOS.

AND

TABLE 3.3-1 (Continued)

ACTION STATEMENTS (Continued)

ACTION 3 - With the number of channels OPERABLE one less than the Minimum Channels OPERABLE requirement and with the THERMAL POWER level:

a.

Below the P-6 (Intermediate Range Neutron Flux Interlock) Setpoint, restore the inoperable channel to OPERABLE status prior to increasing THERMAL POWER above the P-6 Setpoint, and

b.

Above P-6 (Intermediate Range Neutron Flux Interlock) Setpoint but below 10% of RA TED THERMAL POWER, restore the inoperable channel to OPERABLE status prior to increasing THERMAL POWER above 10% of RA TED THERMAL POWER.

ACTION 4 - With the number of OPERABLE channels one less than the Minimum Channels OPERABLE requirement, suspend all operations involving positive reactivity changes.

ACTION 5 - With the number of OPERABLE channels one less than the Minimum Channels OPERABLE requirement, suspend all operations involving positive reactivity changes and verify compliance with the SHUTDOWN MARGIN requirements of Specification 3.1.1.1 or 3.1.1.2, as applicable, within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> and at least once per 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> thereafter.

ACTION 6 - With the number of OPERABLE channels one less than the Total Number of Channels, STARTUP and/or POWER OPERATION may proceed until performance of the next required ANALOG CHANNEL OPERATIONAL TEST provided the inoperable channel is placed in the tripped condition within 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />.

ACTION 7 - With less than the Minimum Number of Channels OPERABLE, within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> determine by observation of the associated permissive annunciator window(s) that the interlock is in its required_ state for the existing plant condition, or apply Specification 3.0.3.

ACTION 8 - With the number of OPERABLE channels one less than the Minimum Channels OPERABLE requirement, be in at least HOT STANDBY within 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />; however, one channel may be bypassed for up to 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> for surveillance testing per Specification 4.3.1.1, provided the other channel is OPERABLE.

ACTION 9 - With the number of OPERABLE channels one less than the Minimum Channels OPERABLE requirement, restore the inoperable channel to OPERABLE status within 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> or open the Reactor Trip System breakers within the next hour.

ACTION 10- With one of the diverse trip features (undervoltage or shunt trip attachment) inoperable, restore it to OPERABLE status within 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> or in accordance with the Risk Informed Completion Time Program, or declare the breaker inoperable and apply ACTION 8. The breaker shall not be bypassed while one of the diverse trip features is inoperable, except for the time required for performing maintenance to restore the breaker to OPERABLE status.

/

TURKEY POINT - UNITS 3 & 4 3/4 3-6 AMENDMENTNOS.

AND

-I c

o
ii
:: m

"'U 0 z

-I I c z

=l

(/)

w QO

~

w

~

w I......

~

)>

s::

m z

0 s::

m z

. -I z

0

(/)

)> z 0

TABLE 3.3-2

  • ENGINEERED SAFETY FEATURES ACTUATION SYSTEM INSTRUMENTATION.

FUNCTIONAL UNIT

1.

Safety Injection

a.

Manual Initiation

b.

Automatic Actuation Logic and Actuation Relays

c.

Containment Pressure - High

d.

Pressurizer Pressure - Low

e.

High Differential Pressure Between the Steam Line Header and any Steam Line TOTAL NO.

CHANNELS OF CHANNELS TO TRIP 2

1 2

3 2

3 2

3/steam line 2/steam line in any steam line MINIMUM CHANNELS OPERABLE 2

2 2

2 2/steam line APPLICABLE MODES 1 2, 3, 4 1 2, 3, 4 1 2, 3 1 2, 3#

1 2, 3#

ACTION 27 14 26 26 26

TABLE 3.3-2 (Continued}

-I c

ENGINEERED SAFETY FEATURES ACTUATION SYSTEM INSTRUMENTATION

0
i
::

m MINIMUM "U

TOTAL NO.

CHANNELS CHANNELS APPLICABLE 0

FUNCTIONAL UNIT OF CHANNELS TO TRIP OPERABLE MODES ACTION z

-I I

f.

Steam Line flow--High 2/steam line

  • 1/steam line 1/steam line 1, 2, 3*

26 c

Coincident with:

in any two in any two z

=i steam lines steam lines CJ)

Vl Steam Generator QC>

Pressure--Low 1/steam 1/steam 1/steam 1, 2. 3*

26 generator generator generator in any two in any two steam lines steam lines or Vl Tavg--Low 1/loop 1/loop in any 1 /loop in any 1, 2, 3*

25

~

two loops two loops Vl I......

0"1

2.

Containment Spray

a.

Automatic Actuation 2

  • 1 2

1, 2, 3, 4 14 Logic and Actuation

)>

Relays s::

m

b.

Containment Pressure--

3 2

2 1, 2, 3.

26 z

0 High-High s::

Coincident with:

m z

Containment Pressure--

-I z

High 3

2 2

1, 2, 3 26 0

CJ)

3.

Containment Isolation

)> z

a.

Phase "A" Isolation 0

1) Manual Initiation 2

1 2

1, 2, 3, 4 27

2) Automatic Actuation 2

1 2

1, 2, 3, 4 14 Logic and Actuation Relays

-I c

0
ii
:: m

"'U 0 z

-I I c z

=i

(/')

w Qo

)>

s::

m z

0 s::

m z

-I z

0

(/')

)> z 0

TABLE 3.3-2 (Continued)

ENGINEERED SAFETY FEATURES ACTUATION SYSTEM INSTRUMENTATION FUNCTIONAL UNIT

3.

Containment Isolation (Continued)

3) Safety Injection
b.

Phase "B" Isolation

1) Manual Initiation
2) Automatic Actuation Logic and Actuation Relays
3) Containment Pressure--High-High Coincident with:

Containment Pressure--

High

c.

Containment Ventilation Isolation

1) Containment Isolation Manual Phase A or Manual Phase B TOTAL NO.

CHANNELS OF CHANNELS TO TRIP MINIMUM CHANNELS OPERABLE APPLICABLE MODES ACTION See Item 1. above for all Safety Injection initiating functions and requirements.

(Manual S.I. initiation will not initiate Phase A Isolation).

2 2

3 3

2 (Both buttons must be pushed simultaneously to actuate) 2 2

2 2

2 2

1, 2, 3, 4 27 1,2,3,4 14 1, 2, 3 15 1, 2, 3 15 See Items 3.a.1 and 3.b.1 above for all Manual Containment Ventilation functions and requirements.

-I c

0
ii;;

m

""O Q

z

-I I c z

=i CJ) w QC>

~

w

~

w I......

CD

)>

s::

m z

0 s::

m z

-I z

0 CJ)

)> z 0

TABLE 3.3-2 (Continued)

ENGINEERED SAFETY FEATURES ACTUATION SYSTEM INSTRUMENTATION FUNCTIONAL UNIT

6.

Auxiliary Feedwater### (Continued)

b.

Stm. Gen. Water Level--

Low-Low

c.

Safety Injection

d.

Bus Stripping

e.

Trip of all Main Feed-water Pumps Breakers

7.

Loss of Power

a.

4.16 kV Susses A and B (Loss of Voltage)

b.

480 V Load Centers 3A, 38, 3C, 3D and 4A, 48, 4C, 4D Undervoltage Coincident with:

Safety Injection TOTAL NO.

CHANNELS OF CHANNELS TO TRIP 3/steam 2/steam generator generator in any steam generator MINIMUM CHANNELS OPERABLE 2/steam generator APPLICABLE MODES 1, 2, 3 ACTION 26 See Item 1. above for all Safety Injection initiating functions and requirements.

1/bus 1/breaker 2/bus 2 per load center 1/bus

( 1 /breaker)

/operating pump 2/bus 2 on any load center 1/bus

( 1 /breaker)

/operating pump 2/bus 2 per load center 1,2, 3 1, 2 1, 2, 3, 4 1, 2, 3, 4 23 23 18 18 See Item 1. above for all Safety Injection initiating functions and requirements.

ACTION 18-ACTION 19 -

ACTION 20-ACTION 21 -

ACTION 22-ACTION 23-ACTION 24-ACTION 25-ACTION 26-ACTION 27-TABLE 3.3-2 (Continued)

TABLE NOTATION (Continued)

With the number of OPERABLE channels one less than the Total Number of Channels, STARTUP and/or POWER OPERATION may proceed provided the inoperable channel is placed in the tripped condition within 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> or in accordance with the Risk Informed Completion Time Program. Both channels of any one load center may be taken out of service for up to 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> in order to perform surveillance testing per Specification 4.3.2.1.

With less than the Minimum Number of Channels OPERABLE, within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> determine by observation of the associated permissive annunciator window(s) that the interlock is in.its required state for the existing plant condition, or apply Specification 3.0.3.

With the number"of OPERABLE channels one less than the Minimum Channels OPERABLE requirement, be in at least HOT STANDBY within 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in at least HOT SHUTDOWN within the following 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />; however, one channel may be bypassed for up to 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> for surveillance testing per Specification 4.3.2.1 provided the other channel is OPERABLE.

With the number of OPERABLE channels one less than the Total Number of Channels, restore the inoperable channel to OPERABLE status within 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> or declare the associated valve inoperable and take the ACTION required by Specification 3.7.1.5.

With the number of OPERABLE channels one less than the Minimum Channels OPERABLE requirement, be in at least HOT STANDBY within 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />; however, one channel may be bypassed for up to 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> for surveillance testing per Specification 4.3.2.1 provided the other channel is OPERABLE.

With the number of OPERABLE channels one less than the Minimum Channels OPERABLE requirement, comply with Specification 3.0.3.

1 With the n.umber of OPERABLE channels one less than the Minimum Channels OPERABLE requirement, within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> isolate the Control Room Emergency Ventilation System and initiate operation of the Control Room Emergency Ventilation System in the recirculation mode.

With number of OPERABLE channels one less than the Total number of channels, STARTUP and/or POWER OPERATION may proceed provided the inoperable channel is placed in the tripped condition within 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> or in accordance with the Risk Informed Completion Time Program. For subsequent required DIGITAL CHANNEL OPERATIONAL TESTS the inoperable channel may be placed in bypass status for up to 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br />.

With one channel inoperable, operation may proceed until performance of the next required ANALOG CHANNEL OPERATIONAL TEST or TRIP ACTUATING DEVICE OPERATIONAL TEST provided the inoperable channel is placed in the tripped condition within 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> or in accordance with the Risk Informed Completion Time Program.

With one channel inoperable, restore the inoperable channel to OPERABLE status within 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> or in accordance with the Risk Informed Completion Time Program, or be in HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

TURKEY POINT - UNITS 3 & 4 3/4 3-22 AMENDMENTNOS.

AND

REACTOR COOLANT SYSTEM OPERATING LIMITING CONDITION FOR OPERATION 3.4.2.2 All pressurizer Code safety valves shall be OPERABLE with a lift setting of 2465 psig + 2%, -3%.* **

APPLICABILITY:

MODES 1, 2 and 3.

ACTION:

With one pressurizer Code safety valve inoperable, either restore the inoperable valve to OPERABLE status within 15 minutes or in accordance with the Risk Informed Completion Time Program, or be in at least HOT STANDBY within 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in at least HOT SHUTDOWN within the following 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />.

SURVEILLANCE REQUIREMENTS 4.4.2.2 No additional requirements other than those required by Specification 4.0.5.

  • The lift setting pressure shall correspond to ambient conditions of the valve at nominal operating temperature and pressure.
    • All valves tested must have "as left" lift setpoints that are within +/- 1 % of the lift setting value.

TURKEY POINT - UNITS 3 & 4 3/4 4-8 AMENDMENTNOS.

AND

3/4.5 EMERGENCY CORE COOLING SYSTEMS 3/4.5.1 ACCUMULATORS LIMITING CONDITION FOR OPERATION

. 3.5.1 Each Reactor Coolant System (RCS) accumulator shall be OPERABLE.

APPLICABILITY:

MODES 1, 2, and 3*.

ACTION:

a.

With one accumulator inoperable, except as a result of boron concentration not being within limits, restore the inoperable accumulator to OPERABLE status within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> or in I

accordance with the Risk Informed Completion Time Program, or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and reduce pressurizer pressure to less than 1000 psig within the following 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />.

b.

With one accumulator inoperable due to the boron concentration not being within the limits, restore boron concentration back to the required limits within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br />, or be in at least

,HOT STANDBY within 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and reduce pressurizer pressure to less than 1000 psig within the following 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />.

SURVEILLANCE REQUIREMENTS 4.5.1.1 Each accumulator*shall be demonstrated OPERABLE:

a.

In accordance with the Surveillance Frequency Control Program by:

1) 1 Verifying the borated water volume in each accumulator is between 6520 and 6820 gallons, and
2)

Verifying that the nitrogen cover pressure in each accumulator is between 600 and 675 psig, and

3)

Verifying that each accumulator isolation valve is open by control room indication (power may be restored to the valve operator to perform this surveillance if redundant indicator is inoperable).

  • Pressurizer pressure above 1000 psig.

TURKEY POINT - UNITS 3 & 4 3/4 5-1 AMENDMENTNOS.

AND

EMERGENCY CORE COOLING SYSTEMS 3/4.5.2 ECCS SUBSYSTEMS - Tavg GREATER THAN OR EQUAL TO 350°F LIMITING CONDITION FOR OPERATION 3.5.2 The following Emergency Core Cooling System (ECCS) equipment and flow paths shall be OPERABLE:

a.

Four Safety Injection (SI) pumps, each capable of being powered from its associated OPERABLE diesel generator#, with discharge flow paths aligned to the RCS cold legs,*

b.

Two RHR heat exchangers,

c.

Two RHR pumps with discharge flow paths aligned to the RCS cold legs,

d.

A flow path capable of taking suction from the refueling.water storage tank as defined in Specification 3.. 5.4, and

e.

Two flow paths capable of taking suction from the containment sump.

APPLICABILITY: MODES 1, 2, and 3**.

ACTION:

a.

With one RHR heat exchanger or suction flow path from the containment sump inoperable, restore the inoperable RHR heat exchanger or suction flow path from the containment sump to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> or in accordance with the Risi< Informed Completion Time Program, or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in HOT SHUTDOWN within the following 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />.

b.

In the event the ECCS is actuated and injects water in the Reactor Coolant System; a Special Report shall be prepared and submitted to the Commission pursuant to Specification 6.9.2 within 90 days describing the circumstances of the.actuation and the total accumulated actuation cycles to date since January 1, 1990.

c.

With one of the four required Safety Injection pumps or its associated discharge flow path inoperable and the opposite unit in MODE 1, 2, or 3, restore the pump or flow path to OPERABLE status within 30 days or be in at least HOT STANDBY within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and in HOT SHUTDOWN within the following 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />.***

  • Only three Safety Injection (SI) pumps (two associated with the unit and one from the opposite unit), each capable of being powered from its associated OPERABLE diesel generatol, with discharge flow paths aligned to the RCS cold leg are required if the opposite unit is in MODE 4, 5, or 6.
    • The provisions of Specifications 3.0.4 and 4.0.4 are not applicable for entry into MODE 3 for the Safety Injection flow paths isolated pursuant to Specification 3.4.9.3 provided that the Safety Injection flow paths are restored to OPERABLE status prior to Tavg exceeding 380°F. Safety Injection flow paths may be isolated when Tavg is less than 380°F.
      • The provisions of Specifications 3.0.4 and 4.0.4 are not applicable.
  1. lnoperability of the required diesel generators does not constitute inoperability of the associated Safety Injection pumps.

TURKEY POINT - UNITS 3 & 4 3/4 5-3 AMENDMENTNOS.

AND

EMERGENCY CORE COOLING SYSTEMS 3/4.5.2 ECCS SUBSYSTEMS - Tavg GREATER THAN OR EQUAL TO 350°F LIMITING CONDITION FOR OPERATION

d.

With two of the four required Safety Injection pumps or their associated discharge flow paths inoperable and the opposite unit in MODE 1, 2, or 3, restore one of the two inoperable pumps or flow paths to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> or in accordance with the Risk Informed Completion Time Program, or be in at least HOT STANDBY within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and in HOT SHUTDOWN within the following 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />. This ACTION applies to both units simultaneously.

e.

With one of the three required Safety Injection pumps or its associated discharge flow path inoperable and the opposite unit in MODE 4, 5, or 6, restore the pump or flow path to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> or in accordance with the Risk Informed Completion Time Program, or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in HOT SHUTDOWN within the following 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />.

f.

With a required Safety Injection pump OPERABLE but not capable of being powered from its associated diesel generator, restore the capability within 14 days or in accordance with the Risk Informed Completion Time Program, or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in HOT SHUTDOWN within the following 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />.

g.

With an ECCS subsystem inoperable due to an RHR pump or its associated discharge flow path being inoperable, restore the inoperable RHR pump or its associated discharge flow path to OPERABLE status within 7 days or in accordance with the Risk Informed Completion Time Program, or be in at least HOT STANDBY within the.next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in HOT SHUTDOWN within the following 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />..

h.

With the suction flow path from the refueling water storage tank inoperable, restore the suction flow path to OPERABLE status within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in HOT SHUTDOWN within the following 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />.

TURKEY POINT - UNITS 3 & 4 3/4 5-4 AMENDMENTNOS.

AND

CONTAINMENT SYSTEMS CONTAINMENT AIR LOCKS LIMITING CONDITION FOR OPERATION 3.6.1.3 Each containment air lock shall be OPERABLE with:

a.

Both-doors closed except when the air lock is being used for normal transit entry and exit through the containment, or during the performance of containment air lock surveillapce and/or testing requirements, then at least one air lock door shall be closed, and

b.

An overall air lock leakage rate in accordance with the Containment Leakage Rate Testing Program.

APPLICABILITY: MODES 1, 2, 3, and 4.

ACTION:

a.

With one containment air lock door inoperable:

1.

Maintain at least the OPERABLE air lock door closed and either restore the inoperable air lock door to OPERABLE status within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> or lock the OPERABLE air lock door closed;

2.

Operation may then continue until performance of the next required overall air lock leakage test provided that the OPERABLE air lock door is verified to be locked closed at least once per 31 days;

3.

Otherwise; be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

b.

With the containment air lock inoperable, except as the result of an inoperable air lock door, maintain at least one air lock door closed; restore the inoperable air lock to OPERABLE status within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> or in accordance with the Risk Informed Completion Time Program, or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

TURKEY POINT - UNITS 3 & 4 3/4 6-3 AMENDMENTNOS.

AND

CONTAINMENT SYSTEMS CONTAINMENT VENTILATION SYSTEM LIMITING CONDITION FOR OPERATION 3.6.1.7 Each containment purge supply and exhaust isolation valve shall be OPERABLE and:

a.

The containment purge supply and exhaust isolation valves shall be sealed closed to the maximum extent practicable but may be open for purge system operation for pressure control, for environmental conditions control, for ALARA and respirable air quality considerations for personnel entry and for surveillance tests that require the valve to be open.

b.

The purge supply and exhaust isolation valves shall not be opened wider than 33 or 30 degrees, respectively (90 degrees is fully open).,

APPLICABILITY:

MODES 1, 2, 3, AND 4.

ACTION:

a.

With a containment purge supply and/or exhaust isolation valve(s) open for reasons other than given in 3.6.1.7.a above, close the open valve(s) or isolate the penetration(s) within 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br />, or in accordance with the Risk Informed Completion Time Program, otherwise be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

b.

With a containment purge supply and/or exhaust isolation valve(s) having a measured leakage rate exceeding the limits of Specification 4.6.1.7.2, restore the inoperable valve(s) to OPERABLE status or isolate the penetrations such that the measured leakage rate does not exceed the limits of Specification 4.6.1.7.2 within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />, or in accordance with the Risk Informed Completion Time Program, otherwise be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

SURVEILLANCE REQUIREMENTS 4.6.1. 7.1 Each containment purge supply and exhaust isolation valve shall be verified to be sealed closed or open in accordance with Specification 3.6.1.7.a in accordance with the Surveillance Frequency Control Program.

4.6.1.7.2 In accordance with the Surveillance Frequency Control Program, each containment purge supply and exhaust isolation valve shall be demonstrated OPERABLE by verifying that the measured.leakage rate is less than or equal to 0.05 La when pressurized to Pa.

4.6.1. 7. 3 In accordance with the Surveillance Frequency Control Program, the mechanical stop on each containment purge supply and exhaust isolation valve shall be verified to be in place and that the valves will open no more than 33 or 30 degrees, respectively.

TURKEY POINT - UNITS 3 & 4 3/4 6-11 AMENDMENTNOS.

AND

CONTAINMENT SYSTEMS 3/4.6.2 DEPRESSURIZATION AND COOLING SYSTEMS CONTAINMENT SPRAY SYSTEM LIMITING CONDITION FOR OPERATION 3.6.2.1 Two independent Containment Spray Systems shall be OPERABLE with each Spray System capable of taking suction from the RWST and manually transferring suction to the containment sump via the RHR System.

APPLICABILITY:

MODES 1, 2, 3, and 4.

ACTION:

a.

With one Containment Spray System inoperable restore the inoperable Spray System to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> or in accordance with the Risk Informed Completion Time Program, or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

b.

With two Containment Spray Systems inoperable restore at least one Spray System to OPERABLE status within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />. Restore both Spray Systems to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> of initial loss or in accordance with the Risk Informed Completion Time Program, or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

SURVEILLANCE REQUIREMENTS 4.6.2.1 Each Containment Spray System shall be demonstrated OPERABLE:

a.

In accordance with the Surveillance Frequency Control Program by verifying that each valve (manual, power-operated, or automatic) in the flow path that is not locked, sealed, or otherwise secured in position, is in its correct position* and that power is available to flow path components that require power for operation;

b.

By verifying that on recirculation flow, each pump develops the indicated differential pressure, when tested pursuant to Specification 4.0.5:

Containment Spray Pump ~241.6 psid while aligned in recirculation mode.

c.

In accordance with the Surveillance Frequency Control Program by verifying containment spray locations susceptible to gas accumulation are sufficiently filled with water.

  • Not required to be met for system vent flow paths opened under administrative control.

TURKEY POINT - UNITS 3 & 4 3/4 6-12 AMENDMENTNOS.

AND

CONTAINMENT SYSTEMS EMERGENCY CONTAINMENT COOLING SYSTEM LIMITING CONDITION FOR OPERATION 3.6.2.2 Three emergency containment cooling units shall be OPERABLE.

APPLICABILITY:

MODES 1, 2, 3,,and 4.

a.

With one of the above required emergency containment cooling units inoperable restore the inoperable cooling unit to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> or in accordance with the Risk Informed Completion Time Program, or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

b.

With two or more of the above required emergency containment cooling units inoperable, restore at leasttwo cooling units to OPERABLE status within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />. Restore all oft.he above required cooling units to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> of initial loss or in accordance I with the Risk Informed Completion Time Program, or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

SURVEILLANCE REQUIREMENTS 4.6.2.2 Each emergency containment cooling unit shall be demonstrated OPERABLE:

a.

In accordance with the Surveillance Frequency Control Program by starting each cooler unit from the control room and verifying that each unit motor reaches the nominal operating current for the test conditions and operates for at least 15 minutes.

b.

In accordance with the Surveillance Frequency Control Program by:

1)

Verifying that two emergency containment cooling units start automatically on a safety injection (SI) test signal, and

2)

Verifying a cooling water flow rate of great~r than or equal to 2000 gpm to each cooler.

TURKEY POINT - UNITS 3 & 4 3/4 6-14 AMENDMENTNOS.

AND

CONTAINMENT SYSTEMS 3/4.6.4 CONTAINMENT ISOLATION VALVES LIMITING CONDITION FOR OPERATION 3.6.4 Each containment isolation valve shall be OPERABLE with isolation times less than or equal to required isolation times.

APPLICABILITY:

MODES 1, 2, 3, and 4.

ACTION:

  • With one or more isolation valves inoperable, maintain at least one isolation valve OPERABLE in each affected penetration that is open and either:
a.

Restore the inoperable valve(s) to OPERABLE status within 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br />, or in accordance with the Risk Informed Completion Time Program, or*

b.

Isolate each affected penetration within 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> or in accordance with the Risk Informed Completion Time Program, by use of at least one deactivated automatic containment isolation valve secured in the isolation position, or

c.

Isolate each affected penetration within 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> or in accordance with the Risk Informed Completion Time Program, by use of at least one closed manual valve or blind flange, or

d.

Be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the follow_ing 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

SURVEILLANCE REQUIREMENTS 4.6.4.1 The isolation valves shall be demonstrated OPERABLE Wior to returning the valve to service after maintenance, repair or replacement work is performed on the valve or its associated actuator, control or power circuit by performance of a cycling test, and verification of isolation time.

  • CAUTION: The inoperable isolation valve(s) may be part of a system(s). Isolating the affected penetration(s) may affect the use of the system(s). Consider the technical specification requirements on the affected system(s) and act accordingly.

TURKEY POINT - UNITS 3 & 4 3/4 6-16 AMENDMENT NOS.

AND

PLANT SYSTEMS AUXILIARY FEEDWATER SYSTEM LIMITING CONDITION FOR OPERATION 3.7.1.2 Two independent auxiliary feedwater trains including 3 pumps as specified in Table 3.7-3 and associated flowpaths shall be OPERABLE.

APPLICABILITY:

MODES 1, 2 and 3 ACTION:

1)

With one of the two required independent auxiliary feedwater trains inoperable, either restore the inoperable train to an OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br />, or in accordance with the Risk Informed I Completion Time Program, or place the affected unit(s) in at least HOT STANDBY within the next 6 hour6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />s* and in HOT SHUTDOWN within the following 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />.

2)

With both required auxiliary feedwater trains inoperable, within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> either restore both trains to an OPERABLE status, or restore one train to an OPERABLE status and follow ACTION statement 1 above for the other train. If neither train can be restored to an OPERABLE status within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br />, verify the OPERABILITY of both standby feed-water pumps and place the affected unit(s) in at least HOT STANDBY within the next 6 hour6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />s* and in HOT SHUTDOWN within the following 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />. Otherwise, initiate corrective action to restore at least one auxiliary feedwater train to an OPERABLE status as soon as possible and follow ACTION statement 1 above for the other train.

3)

With a single auxiliary feedwater pump inoperable, within 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br />, verify OPERABILITY of two independent auxiliary feedwater trains, or follow ACTION statements 1 or 2 above as applicable.

'Upon verification of the OPERABILITY of tw*o independent auxiliary feedwater trains, restore the1 inoperable auxiliary feedwater pump to an OPERABLE status within 30 days, or place the operating unit(s) in at least HOT STANDBY within 6 hour6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />s* and in HOT SHUTDOWN within the following 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />. The provisions of Specification 3.0.4 are not applicable during the 30 day period for the inoperable auxiliary feedwater pump.

SURVEILLANCE REQUIREMENTS 4.7.1.2.1 The required independent auxiliary feedwater trains shall be demonstrated OPERABLE:

a.

In accordance with the Surveillance Frequency Control Program by:

1)

Verifying by control panel indication and visual observation of equipment that each steam turbine-driven pump operates for 15 minutes or greater and develops a flow of greater than or

  • If this ACTION applies to both units simultaneously, be in at least HOT STANDBY within *the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and in HOT SHUTDOWN within the following 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />.

TURKEY POINT - UNITS 3 & 4 3/4 7-3 AMENDMENTNOS.

AND

PLANT SYSTEMS MAIN STEAM LINE ISOLATION VALVES LIMITING CONDITION FOR OPERATION 3.7.1.5 Each main steam line isolation valve (MSIV) shall be OPERABLE.

APPLICABILITY:

MODES 1, 2, and 3.

ACTION:

MODE 1:

With one MSIV inoperable but open, POWER OPERATION may continue provided the inoperable valve is restored to OPERABLE status within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> or in accordance with the Risk Informed Completion Time Program; otherwise be in MODE 2 within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />.

MODES 2 and 3:

With one or more MS IVs inoperable, subsequent operation in MODE 2 or 3 may continue provided:

1.

The inoperable MSIVs are closed within 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br />, and

2.

The inoperable MSIVs are verified closed once per 7 days.

Otherwise, be in HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in HOT SHUTDOWN within the.following 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />.

SURVEI LLANCE REQUIREMENTS 4.7.1.5 Each MSIV shall be demonstrated OPERABLE by verifying full closure within 5 seconds when tested

. pursuant to Specification 4.0.5. The provisions of Specification 4.0.4 are not applicable for entry Into MODE 3.

TURKEY POINT - UNITS 3 & 4 3/4 7-10 AMENDMENTNOS.

AND

I PLANT SYSTEMS 3/4.7.2 COMPONENT COOLING WATER SYSTEM LIMITING CONDITION FOR OPERATION 3.7.2 The Component Cooling Water System (CCW) shall be OPERABLE with:

a.

Three CCW pumps, and

b.

Two CCW heat exchangers.

APPLICABILITY:

MODES 1, 2, 3, and 4.

ACTION:

a.

With only two CCW pumps with independent power supplies OPERABLE, restore the inoperable CCW pump to OPERABLE status within 30 days or be in HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />. The provisions of Specification 3.0.4 are not applicable.

b.

With only one CCW pump OPERABLE or-with two CCW pumps OPERABLE but not from independent power supplies, restore two pumps from 'independent power supplies to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> or in accordance with the Risk Informed Completion Time Program, or be in HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

c.

, With less than two CCW heat exchangers OPERABLE, restore two heat exchangers to OPERABLE status within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> or be in HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

SURVEILLANCE REQUIREMENTS 4.7.2 The Component Cooling Water System (CCW) shall be demonstrated OPERABLE:.

a.

In accordance with the Surveillance Frequency Control Program, by verifying that two heat exchangers and one pump are capable of removing design basis heat loads.

TURKEY POINT - UNITS 3 & 4 3/4 7-14 AMENDMENTNOS.

AND

PLANT SYSTEMS 3/4.7.3 INTAKE COOLING WATER SYSTEM

., LIMITING CONDITION FOR OPERATION 3.7.3 The Intake Cooling Water System (ICW) shall be OPERABLE with:

a.

Three ICW pumps, and

b.

Two ICW headers.

APPLICABILITY:

MODES 1, 2, 3, and 4.

ACTION:

a.

With only two ICW pumps with independent power supplies OPERABLE, restore the inoperable ICW pump to OPERABLE status within 14 days or in accordance with the Risk Informed Completion Time Program, or be in HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />. The provisions of Specification 3.0.4 are not applicable.

b.

With only one ICW pump OPERABLE or with two ICW pumps OPERABLE but not from independent power supplies, restore two pumps from independent power supplies to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> or in accordance with the Risk Informed Completion Time Program, or be in HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

c.

With only one ICW header OPERABLE, restore two headers to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> or in accordance with the Risk Informed Completion Time Program, or be in HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

SURVEILLANCE REQUIREMENTS 4.7.3 The Intake Cooling Water System (ICW)'shall be demonstrated OPERABLE:

a.

In accordance with the Surveillance Frequency Control Program by verifying that each valve (manual, power-operated, or automatic) servicing safety-related equipment that is not locked, sealed, or otherwise secured in position is in its correct position; and

b.

In accordance with the Surveillance Frequency Control Program during shutdown, by verifying that:

1)

Each automatic valve servicing safety-related equipment actuates to its correct position on a SI test signal, and

  • 2)

Each Intake Cooling Water System pump starts automatically on a SI test signal.

3)

Interlocks required for system operability are OPERABLE.

TURKEY POINT - UNITS 3 & 4 3/4 7-16 AMENDMENTNOS.

AND

ELECTRICAL POWER SYSTEMS LIMITING CONDITION FOR OPERATION <Continued)

APPLICABILITY: MODES 1, 2, 3, and 4.

ACTION:

a.

With one of two startup transformers or an associated circuit inoperable, demonstrate the OPERABILITY of the other startup transformer and its associated circuits by performing Surveillance Requirement 4.8.1.1.1.a within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> and at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter. If the inoperable startup transformer is the associated startup transformer and became inoperable while the unit is in MODE 1, reduce THERMAL POWER to ::;30% RA TED THERMAL POWER within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />, or restore the inoperable startup transformer and associated circuits to OPERABLE status within the next 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> or in accordance with the Risk Informed Completion Time Program, or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />. If THERMAL POWER is reduced to ::;30% RATED THERMAL POWER within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> or if the inoperable startup transformer is associated with the opposite unit restore the startup transformer and its associated circuits to OPERABLE status within 30 days of the loss of OPERABILITY, or be in at least HOT STANDBY within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />. If the inoperable startup transformer is the associated startup transformer and became inoperable while the unit was in MODE 2, 3, or 4 restore the startup transformer and its associated circuits to OPERABLE status within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> or in accordance with the Risk Informed Completion Time Program, or be in at least HOT STANDBY within 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

This ACTION applies to both units simultaneously.

b.

With one of the required diesel generators inoperable, demonstrate the OPERABILITY of the above required startup transformers and their associated circuits by performing Surveillance Requirement 4.8.1.1.1.a within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> and at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter. If the diesel generator became inoperable due to any cause other than an inoperable support system, an independently testable component, 6r preplanned preventative maintenance or testing, demonstrate the OPERABILITY of the remaining required diesel generators by performing Surveillance Requirement 4.8.1.1.2.a.4 within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />, unless the absence of any potential common mode failure for the remaining diesel generators is determined. If testing of remaining required diesel generators is required, this testing must be performed regardless of when the inoperable diesel generator is restored to OPERABILITY. Restore the inoperable diesel generator to OPERABLE status within 14 days** or in accordance with the Risk Informed 1

  • Completion Time Program, or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.
c.

With one startup transformer and one of the required diesel generators inoperable, demonstrate the OPERABILITY of the remaining A.C. sources by performing Surveillance Requirement 4.8.1.1.1.a on the remaining 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> if inoperability is associated with Action Statement 3.8.1.1.c.

TURKEY POINT - UNITS 3 & 4 3/4 8-2 AMENDMENTNOS.

AND

ELECTRICAL POWER SYSTEMS LIMITING CONDITION FOR OPERATION <Continued)

ACTION (Continued)

\\_

SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />. This ACTION applies to both units simultaneously.

With only one startup transformer and associated circuits restored, perform Surveillance Requirement 4.8.1.1.1 a on the OPERABLE Startup transformer at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br />, and restore the other startup transformer and its associated circuits to OPERABLE status or shutdown in accordance with the provisions of Action Statement 3.8.1.1 a with time requirements of that Action Statement based on the time of initial loss* of a startup transformer. This ACTION applies

  • to both units simultaneously.
f.

With two of the above required diesel generators inoperable, demonstrate the OPERABILITY ol_

two startup transformers and their associated circuits by performing the requirements of Specification 4.8.1.1.1 a. within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> and at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter; restore at least one of the inoperable diesel generators to OPERABLE status within 2 ~ours or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

Restore all required diesel generators to OPERABLE status within 14 days from time of initial loss or in accordance with the Risk Informed Completion Time Program, or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

g.

Following the addition of the new fuel oil* to the Diesel Fuel Oil Storage Tanks, with one or more diesel generators with new fuel oil properties outside the required Diesel Fuel Oil Testing Program limits, restore the stored fuel oil properties to within the required limits within 30 days.

h.

With one or more diesel generators with stored fuel oil total particulates outside the required Diesel Fuel Oil Testing Program limits, restore the fuel oil total particulates to within the required limits within 7 days.

The properties of API Gravity, specific gravity or an absolute specific gravity; kinematic viscosity; clear and bright appearance; and flash point shall be confirmed to be within the Diesel Fuel. Oil Testing Program limits, prior to the addition of the new fuel oil to the Diesel Fuel Oil Storage Tanks.

TURKEY POINT - UNITS 3 & 4 3/4 8-4 AMENDMENT NOS.

AND

3/4.8.2 D.C. SOURCES OPERATING LIMITING CONDITION FOR OPERATION 3.8.2.1 The following D.C. electrical sources shall be OPERABLE:*#

a. 125-volt D.C. Battery Bank 3A or spare battery bank D-52 and associated full capacity charger(s)
1) 3A1 powered by motor control center (MCC) 3C with EOG 3A OPERABLE, or
2) 3A2 powered by MCC 40 with EOG 4A and 4B OPERABLE, or
3) 3A 1 powered by MCC 3C with EDG 3A OPERABLE and 3A2 powered by MCC 40 with EOG 4A and 4B OPERABLE,
b. 125-volt D.C. Battery Bank 3B or spare battery bank D-52 and associated full capacity charger(s)
1) 3B1 powered by MCC 3B with EOG 3B OPERABLE, or
2) 3B2 powered by MCC 40 with EOG 4A and 4B OPERABLE, or
3) 3B1 powered by MCC 3B with EOG 3B OPERABLE and 3B2 powered by MCC 40 with EOG 4A and 4B OPERABLE,
c.

125-volt D.C. Battery Bank 4A or spare battery bank D-52 and a~sociated full capacity charger(s)

1) 4A 1 powered by MCC 4C with EOG 4A OPERABLE, or
2) 4A2 powered by MCC 30 with EOG 3A and 3B OPERABLE, or
3) 4A 1 powered by MCC 4C with EOG 4A OPERABLE and 4A2 powered by MCC 30 with EOG 3A and 3B OPERABLE,
d. 125-volt D.C. Battery Bank 4B or spare battery bank D-52 and associated full capacity charger(s)
1) 4B1 powered by MCC 4B with EDG 4B OPERABLE, or
2) 4B2 powered by MCC 30 with EOG 3A and 3B OPERABLE, or
3) 4B1 powered by MCC 4B with EOG 4B OPERABLE and 4B2 powered by MCC 30 with EOG 3A and 3B OPERABLE.

APPLICABILITY:

MODES 1, 2, 3, and 4.

ACTION:

a. With one or more of the required battery chargers OPERABLE but not capable of being powered from its associated OPERABLE diesel generator(s), restore the capability within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> or in accordance with the Risk Informed Completion Time Program, or be in at least HOT STANDBY within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />. This ACTION applies to both units simultaneously.
  • All battery chargers required to satisfy the LCO shall be powered from separate MCCs.
  1. lnoperability of the required EDG's specified in the LCO requirements below does not constitute inoperability of the associated battery chargers or battery banks.

TURKEY POINT - UNITS 3 & 4 3/4 8-13 AMENDMENTNOS.

AND

D.C. SOURCES LIMITING CONDITION FOR OPERATION ACTION:

b.

(Continued)

With one of the required battery banks inoperable, or with none of the full-capacity chargers associated with a battery bank OPERABLE, restore all battery banks to OPERABLE status and at least one charger associated with each battery bank to OPERABLE status within two hours* or in accordance with the Risk Informed Completion Time Program, or be in at least HOT STANDBY within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />. This ACTION applies to both units simultaneously.

SURVEILLANCE REQUIREMENTS 4.8.2.1 Each 125-volt battery bank and its associated full capacity charger(s) shall be demonstrated OPERABLE:

a.

In accordance with the Surveillance Frequency Control Program by verifying that:

1)

The parameters in Table 4.8-2 meet the Category A limits, and

2)

The total battery terminal voltage is greater than or equal to 129 volts on float charge and the battery charger(s) output voltage is~ 129 volts, and

3)

If two battery chargers are connected to the battery bank, verify each battery charger is supplying a minimum of 10 amperes, or demonstrate that the battery charger supplying less than 10 amperes will accept and supply the D.C. bus load independent of its associated battery charger.

b.

In accordance with the Surveillance Frequency Control Program and within 7 days after a battery discharge with battery terminal voltage below 105 volts (108.6 volts for spare battery D-52), or battery overcharge with battery terminal voltage above 143 volts, by verifying that:

1)

The parameters in Table 4.8-2 meet the Category B limits,

2)

The average electrolyte temperature of every sixth cell is above 60°F, and

3)

There is no visible corrosion at either terminals or connectors, or verify battery connection resistance is:

Battery Connection Limit (Micro-Ohms) 3B,4A inter-cell /termination

.:: 29 inter-cell (brace locations)

.:: 30 transition cables

.:: 125 or total battery connections

.:: 1958 Battery Connection I

Limit (Micro-Ohms) 3A, 4B, D-52 inter-cell/ termination

.:: 35 inter-cell (brace locations)

.:: 40 transition cables

.:: 125 or total battery connections

< 2463

c.

In accordance with the Surveillance Frequency Control Program by verifying that:

1)

The cells, cell plates, and battery racks show no visual indication of physical damage or abnormal deterioration,

  • can be extended to 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> if the opposite unit is in MODE 5 or 6 and each of the remaining required battery chargers is capable of being powered from its associated diesel generator(s).

TURKEY POINT - UNITS 3 & 4 3/4 8-14 AMENDMENTNOS.

AND

ONSITE POWER DISTRIBUTION LIMITING CONDITION FOR OPERATION (Continued)

j.

120 Volt AC Vital Panel 3P09 and 3P24 energized from its associated inverter connected to D.C.

Bus 4A.****

k.

120 Volt AC Vital Panel 4P09 and 4P24 energized from its associated inverter connected to D.C.

Bus 4A.****

I.

125 Volt D.C. Bus 3D01 energized from an associated battery charger and from Battery 13ank 3A or spare battery bank D-52,

m.

125 Volt D.C. Bus 3D23 energized from an associated battery charger and from Battery Bank 3B or spare battery bank D-52,

n.

125 Volt D.C. Bus 4D01 energized from an associated battery charger and from Battery Bank 4B or spare battery bank D-52, and

o.

125 Volt D.C. Bus 4D23 energized from an associated battery charger and from Battery Bank 4A or spare battery bank D-52 APPLICABILITY:

MODES 1, 2, 3, and 4.

ACTION:

a.

With one of the required trains (3.8.3.1 a., b., and c) of A.C. emergency busses not fully energized (except for the required LC's and MCC's associated with the opposite unit). reenergize the train within 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> or in accordance with the Risk Informed Completion Time Program, or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

b.

With any of the required LC's and/or MCC's associated with the opposite unit inoperable, restore the inoperable LC or MCC to OPERABLE status in accordance with Table 3.8-1 or Table 3.8-2 as applicable or place the unit in at least HOT STANDBY within 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

c.

With one A.C. vital panel either not energized from its associated inverter, or with the inverter not connected to its associated D.C. bus: (1) Reenergize the A.C. vital panel within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> or in accordance with the Risk Informed Completion Time Program, or be in at least HOT STANDBY within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />; and (2) reenergize the A.C. vital panel from an inverter connected to its associated D.C. bus

        • A back-up inverter may be used to replace the normal inverter, provided the normal inverter on the same DC bus for the opposite unit is not replaced at the same time.

TURKEY POINT - UNITS 3 & 4 3/4 8-19 AMENDMENTNOS.

AND

ONSITE POWER DISTRIBUTION LIMITING CONDITION FOR OPERATION (Continued)

ACTION:

(Continued) within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> or in accordance with the Risk Informed Completion Time Program, or be in at least HOT STANDBY within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />. This ACTION applies to both units simultaneously.

d.

With one D.C. bus not energized from its associated battery bank or associated charger, reenergize the D.C. bus from its associated battery bank within 2 hour2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br />s* or in accordance with the Risk Informed Completion Time Program, or be in at least HOT STANDBY within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />. This ACTION applies to both units simultaneously.

SURVEILLANCE REQUIREMENTS 4.8.3.1 The specified busses shall be determined energized and aligned in the required manner by verifying correct breaker alignment and indicated voltage on the buses in accordance with the Surveillance Frequency Control Program.

  • Can be extended to 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> if the opposite unit is in MODE 5 or 6 and each of the remaining required battery chargers is capable of being powered from its associated diesel generator(s).

TURKEY POINT - UNITS 3 & 4 3/4 8-20 AMENDMENTNOS.

AND

/

Unit4 Load Centers and Motor Control Centers Inoperable (Any MODE)

LC4A MCC4A LC 4C and/or MCC 4C LC 4H and/or MCC 4D LC 4B and/or MCC 4B LC4D TABLE 3.8-1 APPLICABLE TO UNIT 3 BASED ON UNIT 4 LOAD CENTERS AND MOTOR CONTROL CENTERS INOPERABLE ALLOWABLE OUTAGE TIMES Allowable Outage Times (hours)

Unit 3 - MODES 1, 2, 3 and 4 With AC With AC Trains 3A, 3B, Trains 3A, 4A, & 4B 3B, & 4A OPERABLE OPERABLE N/A 72a N/A N/A 2*a 2*a 2**a 2**a 2*a N/A N/A N/A With AC Trains 3A, 3B, & 4B OPERABLE N/A N/A N/A 2**a 2*a 72a

  • If the battery charger powered from the out-of-service LC and/or MCC is not required by LCO 3.8.2.1, the out-of-service time is not applicable (N/A).
    • If neither of the battery chargers powered from the out-of-service LC and/or MCC is required by LCO 3.8.2.1, the out-of-service time is 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br />, or in accordance with the Risk Informed Completion Time Program.

a or in accordance with the Risk Informed Completion Time Program.

TURKEY POINT - UNITS 3 & 4 3/4 8-21 AMENDMENTNOS.

AND

Unit 3 Load Centers and Motor Control Centers Inoperable (Any MODE)

LC 3A LC 3C and/or MCC 3C LC 3H and/or MCC 3D LC 3B and/or MCC 3B LC 3D TABLE 3.8-2 APPLICABLE TO UNIT 4 BASED ON UNIT 3 LOAD CENTERS AND MOTOR CONTROL CENTERS INOPERABLE ALLOWABLE OUTAGE TIMES Allowable Outage Times (hours)

Unit 4 - MODES 1, 2, 3 and 4 With AC With AC Trains 4A, 4B, Trains 4A, 3A, & 3B 4B, & 3A OPERABLE OPERABLE NIA 72a 2*a 2*a 2**a 2**a 2*a N/A N/A N/A With AC Trains 4A, 4B, & 3B OPERABLE N/A N/A 2**a 2*a 72a

  • If the battery charger powered from the out-of-service LC and/or MCC is not required by LCO 3.8.2.1, the out-of-service time is not applicable (N/A).
    • If neither of the battery chargers powered from the out-of-service LC and/or MCC is required by LCO 3.8.2.1, the out-of-service time is 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br />, or in accordance with the Risk Informed Completion Time Program.

a or in accordance with the Risk Informed Completion Time Program TURKEY POINT - UNITS 3 & 4 3/4 8-22 AMENDMENTNOS.

AND

ADMINISTRATIVE CONTROLS PROCEDURES AND PROGRAMS (Continued)

I.

Surveillance Frequency Control Program This program provides controls for Surveillance Frequencies. The program shall ensure that Surveillance Requirements specified in the Technical Specifications are performed at intervals sufficient to assure the associated Limiting Conditions for Operations are met:

a.

The Surveillance Frequency Control Program shall contain a list of frequencies of those Surveillance Requirements for which the frequency is controlled by the program.

b.

Changes to the frequencies listed in the Surveillance Frequency Control Program shall be made in accordance with NEI 04-10, " Risk-Informed Method for Control of Surveillance Frequencies," Revision 1.

c.

The provisions of Surveillance Requirements 4.0.2 and 4.0.3 are applicable to the frequencies established in the Surveillance Frequency Control Program.

m.

Risk Informed Completion Time Program This program provides controls to calculate a Risk Informed Completion Time (RICI) and must be implemented in accordance with NEI 06-09, "Risk-Informed Technical Specification Initiative 4b: Risk-Managed Technical Specifications (RMTS) Guidelines," Revision 0-A, November 2006.

The program shall include the following:

a.

The RICI may not exceed 30 days;

b.

A RICI may only be utilized in MODES 1 and 2;

c.

When a RICI is being used, any plant configuration change within the scope of the Risk,

Informed Completion Time Program must be considered for the effect on the RICI.

1.

For planned changes, the revised RICI must be determined prior to implementation of the change in configuration.

2.

For emergent conditions, the revised RICI must be determined within the time limits of the Required Action Completion Time (i.e., not the RICI) or 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> after the plant configuration change, whichever is less.

3.

Revising the RICI is not required if the plant configuration change would lower plant risk and would result in a longer RICI.

d.

Use of a.RICI is not permitted for entry into a configuration which represents a loss of a specified safety function or inoperability of all required trains of a system required to be OPERABLE.

6.8.5 DELETED TURKEY POINT - UNITS 3 & 4 6-14 AMENDMENT NOS.

AND

Florida Power & Light Company ATTACHMENT 4 Proposed Bases Changes (Information Only)

(13 pages follow)

L-2017-006

INSERT BASES 1 Actions Action 1 With one Manual Reactor Trip channel inoperable, the inoperable channel must be restored to OPERABLE status within 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> or in accordance with the Risk Informed Completion Time Program.

Action 1 O With one of the reactor trip breakers (RTB) diverse trip features (undervoltage or shunt trip) inoperable, it must be restored to an OPERABLE status within 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> or in accordance with the Risk Informed Completion Time Program.

Action 18 With the number of OPERABLE channels for loss of power instrumentation (functional units 7.a, 7.b, 7.c) pne less than the Total Number of Channels, the Action requires placing the inoperable channel in the tripped condition within 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> or in accordance with the Risk Informed Completion Time Program.

Acton 25 With one less than the total number of channels OPERABLE, the Action requires placing the inoperable channel in the tripped condition within 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> or in accordance with the Risk Informed Completion Time Program.

Action 26 With one channel inoperable, the Action requires placing the inoperable channel in the tripped condition within 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> or in accordance with the Risk Informed Completion Time Program.

Acton 27 With one channel of Manual Initiation inoperable, the Action requires restoring the inoperable channel to OPERABLE status within 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> or in accordance with the Risk Informed Completion Time Program.

REVISION NO.:

19 PROCEDURE NO.:

O-ADM-536 PROCEDURE TITLE:

TECHNICAL SPECIFICATION BASES CONTROL PROGRAM TURKEY POINT PLANT ATTACHMENT 2 Technical Specification Bases (Page 59 of 194)

PAGE:

76of211 3/4.3.1 & 3/4.3.2 (Continued)

!INSERT BASES 1 The Engineered Safety Features Actuation System interlocks perform the following functions:

HIGH STEAM FLOW SAFETY INJECTION BLOCK - This permissive is used to block the safety injection (SI) signal generated by High Steam Line Flow coincident with Low Steam Line Pressure or Low Tavg. The permissive is generated when two out of three Low Tavg channels drop below their setpoints and the manual SI Block/Unblock switch is momentarily placed in the block position.

This switch is a spring return to the normal position type. The permissive will automatically be defeated if two out of three Low Tavg channels rise above their setpoints. The permissive may be manually defeated when two out of three Low Tavg channels are below their setpoints and the manual SI Block/Unblock switch is momentarily placed in the unblock position.

LOW PRESSURIZER PRESSURE SAFETY INJECTION BLOCK -

This permissive is used to block the safety injection signals generated by Low Pressurizer Pressure and High Differential Pressure between the Steam Line Header and any Steam Line. The permissive is generated when two out of three pressurizer pressure permissive channels drop below their setpoints and the manual SI Block/Unblock switch is momentarily placed in the block position.

This is the same switch that is used to manually block the High Steam Flow Safety Injection signals mentioned above. This permissive will automatically be defeated if two out of three pressurizer pressure permissive channels rise above their setpoints.

The permissive may be manually defeated when two out of three pressurizer pressure permissive channels are below their setpoints and the manual SI Block/Unblock switch momentarily placed in the Unblock position.

REVISION NO.:

PROCEDURE TITLE:

PAGE:

86 of 211 19 TECHNICAL SPECIFICATION BASES CONTROL PROGRAM PROCEDURE NO.:

O-ADM-536 TURKEY POINT PLANT 3/4.4.2 (Continued)

ATTACHMENT 2 Technical Specification Bases (Page 69 of 194)

During operation, all Pressurizer Code Safety Valves must be OPERABLE to prevent the RCS from being pressurized above its Safety Limit of 2735 psig. The combined relief capacity of all of these valves is greater than the maximum surge rate resulting from a complete loss-of-load assuming NO Reactor trip until the first Reactor Trip System Trip Setpoint is reached (i.e., NO credit is taken for a direct Reactor trip on the loss-of-load) and also assuming NO operation of the power-operated relief valves or steam dump valves. /\\

The pressurizer safety valves are set to open at an RCS pressure of 2465 psig +2% and -3% to avoid exceeding the maximum design pressure safety limit and to maintain accident assumptions. The pressurizer safety valve lift setting is needed to assure acceptable results for the Loss of Load/ Turbine Trip analysis. The upper and lower pressure tolerance limits are based on the tolerance requirements assumed in the safety analyses.

With one pressurizer safety valve inoperable, restoration must take place within 15 minutes or in accordance with the Risk Informed Completion Time Program.

REVISION NO.:

19 PROCEDURE NO.:

O-ADM-536 PROCEDURE TITLE:

TECHNICAL SPECIFICATION BASES CONTROL PROGRAM TURKEY POINT PLANT ATTACHMENT 2 Technical Specification Bases (Page 111 of 194)

PAGE:

128of211 3/4.5.1 (Continued)

For an Accumulator to be considered OPERABLE, the isolation valve must be fully open, power removed above 1000 psig, and the limits established in the surveillance requirements for contained volume, boron concentration, and nitrogen cover pressure must be met.

Operability of the accumulators does NOT depend on the Operability of the water level and pressure channel instruments, therefore, Accumulator volume and nitrogen cover pressure surveillance may be verified by any valid means, NOT just by instrumentation.

If the boron concentration of one Accumulator is NOT within limits, it must be returned to within the limits within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br />. In this condition, ability to maintain subcriticality or minimum boron precipitation time may be reduced. The boron in the Accumulators contributes to the assumption that the combined ECCS water in the partially recovered core during the early reflooding phase of a large break Loss of Coolant Accident (LOCA) is sufficient to keep that portion of the core subcritical.

One Accumulator below the minimum boron concentration limit, however, will have NO effect on available ECCS water and an insignificant effect on core subcriticality during reflood. In addition, current Turkey Point analysis demonstrates that the Accumulators discharge only a small amount following a large main steam line break.

Their impact is minor since the use of the Accumulator volume compensates for Reactor Coolant System shrinkage and the change in boron concentration is insignificant. Thus, 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> is allowed to return the boron concentration to within limits.

If one Accumulator is inoperable for a reason other than boron concentration, the Accumulator must be returned to OPERABLE status within 1 hour1\\ In this condition, the required contents of three Accumulators cannot be assumed to reach the core during a LOCA.

Due to the s ~verity of the consequences should a LOCA occur in these conditions, 11e 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> completion time to open the valve, remove power to the valve or restore the proper water volume or nitrogen cover pressure er sures that prompt action will be taken to return the inoperable accumulator to OPERABLE status. The completion time minimizes he potential for exposure of the plant to a LOCA under these conditions.

or in accordance with the Risk Informed Completion Time Program.

I

REVISION NO.:

19 PROCEDURE NO.:

O-ADM-536 PROCEDURE TITLE:

TECHNICAL SPECIFICATION BASES CONTROL PROGRAM TURKEY POINT PLANT ATTACHMENT 2 Technical Specification Bases (Page 113 of 194)

PAGE:

130of211 3/4.5.2 & 3/4.5.3 (Continued) rior in accordance with the Risk Informed completion r ITime Program TS 3.5.2, Action g. pr~ y ides an allowed outage/action completion time (AOT) of up to 7 days to restore an inoperable RHR Pump to OPERABLE status, provided the affected ECCS Subsystem is inoperable only because its associated RHR pump is inoperable. This 7 day AOT is based on the results of a deterministic and probabilistic safety assessment, and is referred to as a Risk-Informed AOT Extension. Planned entry into this AOT requires that a Risk Assessment be performed in accordance with the Configuration Risk Management Program (CRMP), which is described in the administrative procedure that implements the Maintenance Rule pursuant to 10 CFR 50.65. If an RHR pump suction isolation valve (3/4-752A or B) is CLOSED, then one of the two required flow paths from the containment sump becomes INOPERABLE and TS LCO 3.5.2.e is NOT met. In this case, TS 3.5.2, Action a, is entered and the AOT for the inoperable flow path is 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br />. ~

TS 3.5.2, Action h. limits the allowed outage time for an inoperable RWST flow path from the RWST(s) required by TS 3.5.4 to 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> consistent with the allowed outage time for a required RWST.

REVISION NO.:

19 PROCEDURE NO.:

O-ADM-536 PROCEDURE TITLE:

TECHNICAL SPECIFICATION BASES CONTROL PROGRAM TURKEY POINT PLANT ATTACHMENT 2 Technical Specification Bases (Page 125 of 194)

PAGE:

142of211 3/4.6.2.1 (Continued)

Alternatively, a completion time can be determined in accordance with the Risk Informed Completion Time Program.

The allowable out-of-service time requirements r the Containment Spray System have been maintained cons*

nt with that assigned other inoperable ESF equipment and OT reflect the additional redundancy in cooling capabili vided by the Emergency Containment Cooling System.

ump performance requirements are obtained from the accidents analysis assumptions.

Motor Operated Valves (MOVs) 862A, 8628, 863A, 8638 are required to take suction from the Containment Sump via the RHR system.

PC-600 supplies controlling signals to valves MOVs 8628 and 8638, to prevent opening these valves if RHR pump B discharge pressure is above 210 psig. PC-601 provides similar functions to valves MOVs 862A and 863A. Although all four valves are normally locked in position, with power removed, the capability to power up and stroke the valves must be maintained in order to satisfy the requirements for OPERABLE flow paths (capable of taking suction from the containment sump).

When PC-600/-601 are calibrated, a test signal is supplied to each circuit to check operation of the relays and annunciators operated by subject controllers. This test signal will prevent MOVs 862A, 8628, 863A, 8638 from opening. Therefore, it is appropriate to tag out the MOV breakers, and enter Technical Specification Action Statement 3.5.2.a. and 3.6.2.1 when calibrating PC-600/-601.

Containment Spray System piping and components have the potential to develop voids and pockets of entrained gases.

Preventing and managing gas intrusion and accumulation is necessary for proper operation of the containment spray trains and may also prevent a water hammer and pump cavitation.

REVISION NO.:

19 PROCEDURE NO.:

O-ADM-536 PROCEDURE TITLE:

TECHNICAL SPECIFICATION BASES CONTROL PROGRAM TURKEY POINT PLANT ATTACHMENT 2 Technical Specification Bases (Page 128of194)

PAGE:

145 of 211 3/4.6.2.2 Emergency Containment Cooling System The OPERABILITY of the Emergency Containment Cooling (ECC)

System ensures that the heat removal capacity is maintained within acceptable ranges following postulated design basis accidents. To support both containment integrity safety analyses and component cooling water thermal analysis, two ECCs must start and run within 60 seconds of receipt of a safety injection (SI) signal (one ECC receives an A train SI signal and another ECC receives a B train SI signal). The third (swing) ECC is required to automatically start upon failure of either of the other two ECCs to start.

The allowable out-of-service time requirements for the Containment Cooling System have been maintained consistent with that assigned other inoperable ESF equipment and do NOT reflect the additional redundancy in cooling capability provided by the Containment Spray System.

I\\

The surve llance requirement for ECC flow is verified by correlating the test confi~ uration value with the design basis assumptions for system configurat on and flow. The surveillance interval is based on the use of water from the CCW system, which results in a low risk of heat exchange tube fouling. The surveillance frequency is controlled under the Survei lance Frequency Control Program.

Alternatively, a completion time can be determined in accordance with the Risk Informed Completion Time Program.

REVISION NO.:

19 PROCEDURE NO.:

O-ADM-536 PROCEDURE TITLE:

TECHNICAL SPECIFICATION BASES CONTROL PROGRAM TURKEY POINT PLANT ATTACHMENT 2 Technical Specification Bases (Page 141 of 194)

PAGE:

158 of 211 3/4. 7.1.4 (Continued)

XIQ = atmospheric dispersion parameter = 1.54 x 1 o-4 sec/m3 0.1 = equivalent fraction of activity released

...---~~~~~~~~~~~

With one MSIV inoperable in MODE 1, action must be taken to restore OPERABLE DCF = dose conversion factor, Rem/Ci status within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> or in The resultant thyroid dose is less than 1.5 Rem accordance with the Risk Informed Completion Time 3/4.7.1.5 Main Steam Line Isolation Valves Program.

The OPERABILITY of the Main Steam Line Isolation Valves (MSIV) ensures that NO more than one Steam Genorator will blow down in the event of a steam line rupture. This restrictio h is required to:

(1) Minimize the positive reactivity effects of the Reactor Coolant System cooldown associated with the blowc own, and (2) Limit the pressure rise within Containment in the eve 1t a Main Steam Line or Feedwater Line rupture occurs within Containment. The OPERABILITY of the Main Steam Isolation Valves within the closure times of the Surveillance Requirements are consistent with the assumptions used in the Safety Analyses. \\ f he 24 hour2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> ACTION time provides a reasonable amount of time to troubleshoot and repair the system.

The Main Steam Bypass Valves (MSBV) are motor operated valves that provide the capability to warm the main steam lines and to equalize the steam pressure across the associated MSIV during unit startup. The MSBVs are normally closed during power operation and close on a Main Steam Isolation signal if open. The MSIVs and their associated MSBVs are NOT Containment Isolation Valves. The Main Steam Check Valves (MSCV) automatically close on reverse flow for a main steam line break upstream of the MS IVs.

While the MSBVs and MSCVs support the Main Steam Isolation function, no Technical Specification Limiting Condition for Operation or Action applies to them.

REVISION NO.:

19 PROCEDURE NO.:

O-ADM-536 PROCEDURE TITLE:

TECHNICAL SPECIFICATION BASES CONTROL PROGRAM TURKEY POINT PLANT ATTACHMENT 2 Technical Specification Bases (Page 175 of 194)

PAGE:

192 of 211 3/4.8.1, 3/4.8.2 & 3/4.8.3 (Continued)

The frequency for performing surveillance on stored fuel oil is based on stored fuel oil degradation trends which indicate that particulate concentration is unlikely to change significantly between surveillances.

The OPERABILITY of the minimum specified A.C. and D.C. Power Sources and associated distribution systems during shutdown and refueling ensures that (1) The facility can be maintained in the shutdown or refueling condition for extended time periods, and (2) Sufficient instrumentation and control capability is available for monitoring and maintaining the unit status.

During a unit shutdown, the one required circuit between the offsite transmission network and the onsite Class 1 E Distribution System can consist of at least the associated unit startup transformer feeding one 4160 volt Bus A or B, or the opposite unit's startup transformer feeding the associated unit's 4160 volt Bus A, or the associated unit's 4160 volt Bus A or B backfed through its auxiliary transformers with the main generator isolated.

Alternatively, a completion time can be determined in accordance with the Risk Informed Completion Time Program.

As in opera bi I ity of n u\\.-rn::ITT'n.....,.-=M'"'TTn"'":l,......,'TFTIT'TTTrTD"l,..,....,....,.......n::rnr::rrn::ri'-.....,-TTTC.------'=.----'

operation of the opposite unit, the applicability for the shutdown LIMITING CONDITION FOR OPERATION (LCO) fa A.C. Sources, D.C.

Sources and Onsite Power Distribution all contain tatements to ensure the LCOs of the opposite unit are considered.

The allowable out-of-service time for the D.C. usses is 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> with one unit shutdown in order to allow for requir ti battery maintenance without requiring both units to be shutdown.

revisions to substitute the spare battery for any one of the four station batteries have been included to allow for battery maintenance without requiring both units to be shutdown. The requirement to have only one OPERABLE battery charger associated with a required battery bank permits maintenance to be conducted on the redundant battery charger.

A battery charger may be considered acceptable when supplying less than 10 amperes provided:

1) The battery charger's ability to independently accept and supply the D.C. bus has been verified within the previous 7 days and,
2) D.C. output voltage is ~ 129 volts.

REVISION NO.:

19 PROCEDURE NO.:

O-ADM-536 PROCEDURE TITLE:

TECHNICAL SPECIFICATION BASES CONTROL PROGRAM TURKEY POINT PLANT ATTACHMENT 2 Technical Specification Bases (Page 176 of 194)

PAGE:

193of211 3/4.8.1, 3/4.8.2 & 3/4.8.3 (Continued)

The minimum number of battery chargers required to be OPERABLE is based on the following criteria:

1)

A minimum of one battery charger per bus with each powered from a separate 480 volt MCC is required to satisfy the single failure criteria when assuming the failure of a MCC. This restriction prohibits the use of two chargers powered from the same bus for meeting the minimum requirements.

2)

To satisfy the single failure criteria, when assuming a Loss-Of-Offsite Power with the loss of an EOG, an additional restriction is stipulated which requires each battery charger to have its associated diesel generators OPERABLE. This requires both EDGs associated with a swing bus battery charger to be OPERABLE.

Provisions for requiring the OPERABILITY of the EOG associated with the battery charger is explicitly specified in the LCO. This is because conditions exist where the affected unit would NOT enter the applicable ACTION statement in the LCO without this provision. For example, with Unit 3 in MODE 1 and Unit 4 in MODE 5, the operability of both EOG 4A and 4B is NOT required. One could postulate conditions where battery chargers 4A 1, 3A2, 3B2, or 4B1 could be used to satisfy the LCO without having an associated OPERABLE EOG, unless specific provisions were made to preclude these conditions.

An out-of-service limit of 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> is applied when the required EOG is NOT OPERABLE. With less than the required battery chargers OPERABLE, an allowable out-of-service time of 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> is applied, which can be extended to 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> if the opposite unit is in MODES 5 or 6 and each of the remaining required battery chargers is capable of being powered from its associated diesel generators.

Verifying average electrolyte temperature above the minimum for which the battery was sized, total battery terminal voltage on float charge, connection resistance values, and the performance of battery service and discharge tests ensure the effectiveness of the charging system, the ability to handle high discharge rates, and verifies the battery capability to supply its required load.

Alternatively, completion times can be determined in


1accordance with the Risk Informed Completion Time Program.

REVISION NO.:

19 PROCEDURE NO.:

O-ADM-536 PROCEDURE TITLE:

TECHNICAL SPECIFICATION BASES CONTROL PROGRAM TURKEY POINT PLANT ATTACHMENT 2 Technical Specification Bases (Page 178 of 194)

PAGE:

195of211 3/4.8.1, 3/4.8.2 & 3/4.8.3 (Continued)

The ACTION requirements specified for the inoperability of certain Motor Control Centers (MCCs), Load Centers (LCs) and the 4160-Volt Susses provide restrictions upon continued facility operation commensurate with the level of degradation on each unit and the amount of time one could reasonably diagnose and correct a minor problem. The level of degradation is based upon the types of equipment powered and the out-of-service limit imposed on that equipment by the associated ACTION statement. If this degradation affects the associated unit only, then NO restriction is placed on the opposite unit and an out-of-service limit of 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> (except for MCCs 3A, 3K, 4J and 4K) is applied to the associated unit. Since MCCs 3A, 3K, 4J and 4K are used to power EOG auxiliaries, an out-of-service limit of 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> is applied as required by 3.8.1.1. If the degradation impacts both units (i.e., required shared systems or cross-unit loads), then an out-of-service limit of 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> is applied to the associated unit and an out-of-service limit based on the most restrictive ACTION requirement for the applicable shared or cross-unit load is applied to the opposite unit.

For example, if being used to satisfy 3.8.2.

the Battery Chargers 3A2, 382, 4A2, and 482 are cross-unit loads and ve out-of-service limits of 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br />. This is the most restrictive limit oft e applicable equipment powered from MCC 30 and 40. Therefore, an o t of service limit of 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> is applied if the battery charger is require o be OPERABLE.

The ACTION requirements specified when an AC. vi I panel is NOT energized from an inverter connected to its associated

.C. bus provides for two phases of restoration. Expedient restor ion of an AC.

panel is required due to the degradation of the Reactor Pro ection System and vital instrumentation. The first phase requires re-energization of the AC. vital panel within two hours. Durin this phase the panel may be powered by a Class 1 E constant voltag transformer (CVT) fed from a vital MCC. However, the condition i permissible for only 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> as the second phase of the ACTION requires re-energization of the AC. vital panel from an inverter connected to its associated D.C. bus within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />. Failure to satisfy these ACTIONS results in a dual unit shutdown.

Alternatively, completion times can be determined in accordance with the Risk Informed Completion Time Program.

REVISION NO.:

19 PROCEDURE NO.:

O-ADM-536 PROCEDURE TITLE:

TECHNICAL SPECIFICATION BASES CONTROL PROGRAM TURKEY POINT PLANT ATTACHMENT 2 Technical Specification Bases (Page 180of194)

PAGE:

197of211 3/4.8.1, 3/4.8.2 & 3/4.8.3 (Continued) or a completion time determined in accordance with the Risk Informed Completion Time Program The swing load centers are used to supply shared system and cross-unit loads, and other Technical Specification ACTION statemen may be invoked for loss of swing capability. As discussed above, t Unit 3 DC battery chargers 3A2 and 3B2 are powered from Unit via swing MCC 40, and the Unit 4 DC battery chargers 4A2 and 2 are powered from Unit 3 via swing MCC 30. lnoperability oft swing capability could impact both units if any of the swing b ery chargers is credited for satisfying Technical Specification 3.8.2.. Both EDGs are required to be OPERABLE for a swing battery c rger. An inoperable swing function prevents one EOG from supp mg that battery charger, and a dual-unit 72 hour8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> ACTION statement applies in accordance with TS 3.8.2.1 ACTION statement a.

With a unit shutdown one 4160-volt bus on the associated unit can be deenergized for periodic refueling outage maintenance. The associated 480-volt Load Centers can then be cross-tied upon issuance of an engineering evaluation.

For the shutdown unit, the swing load center does NOT have to be powered from a diesel backed source, since:

a)

Technical Specification 3.8.3.2 only requires that the swing load center be energized. NO operability requirements are specified for the swing function (as opposed to the requirements for an operating unit) and b)

The only accident postulated to occur in Modes 5 and 6 is a fuel handling accident. Loss of offsite power is NOT assumed to occur concurrently with these events. Additionally, there is NO causal relationship between a fuel handling event and a loss of offsite power. Thus, from a design basis standpoint, all of the Control Room HVAC safety functions can be accomplished with the swing load center energized from an offsite source.

REVISION NO.:

19 PROCEDURE NO.:

O-ADM-536 PROCEDURE TITLE:

TECHNICAL SPECIFICATION BASES CONTROL PROGRAM TURKEY POINT PLANT ATTACHMENT 2 Technical Specification Bases (Page 181 of 194)

PAGE:

198 of 211 3/4.8.1, 3/4.8.2 & 3/4.8.3 (Continued)

Operating units on the other hand are subject to accidents that can both affect the grid, and release radioactivity to the outside environment, e.g., LOCA, MSLB. Thus, to satisfy the design basis requirements for the Control Room HVAC system when a unit is in MODES 1 - 4, the swing load center must be powered from a diesel-backed source.

For an operating unit, the swing load center also has to be powered from a diesel-backed source to be considered OPERABLE. The swing load center is considered to be powered from a diesel-backed source if:

a)

It is connected to an electrical power train that has an OPERABLE diesel generator, or b)

It can automatically transfer to a bus that has an OPERABLE diesel generator.

If Load Center H is energized from a load center (either C or D) that does NOT have an OPERABLE Emergency Diesel Generator aligned to it and the swing function is also inoperable, then a 2-hour or a 72 hour8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> LC would have to be entered, depending on the battery charger re 1rements (Technical specification Tables 3.8-1 and 3.8-2).

he swing load center will momentarily de-energize any time it transfers between supply busses (manual, automatic, or test conditions). Since this is the specified manner of operation, the momentary load center de-energization does NOT require entry into the Technical Specification 3/4.8.3.2 action statement.

or a completion time determined in accordance with the Risk Informed Completion Time Program