MONTHYEARL-2018-181, Revised Figure 3.a.1-1 for Turkey Point and Point Beach Updated Final Response to GL 2004-022018-10-18018 October 2018 Revised Figure 3.a.1-1 for Turkey Point and Point Beach Updated Final Response to GL 2004-02 L-2015-138, Updated Final Safety Analysis Report - Unit 4 Cycle 27 Update, Figures 9.3-1 Through 9.3-92015-04-22022 April 2015 Updated Final Safety Analysis Report - Unit 4 Cycle 27 Update, Figures 9.3-1 Through 9.3-9 L-2014-073, Inservice Inspection Plan Relief Request No. 142014-03-14014 March 2014 Inservice Inspection Plan Relief Request No. 14 L-2013-042, Response to NRC Request for Additional Information Regarding License Amendment Request No. 217 - Administrative Changes to Operating License Conditions and Technical Specifications2013-02-14014 February 2013 Response to NRC Request for Additional Information Regarding License Amendment Request No. 217 - Administrative Changes to Operating License Conditions and Technical Specifications ML18228A2001976-12-0101 December 1976 Figure, Nml Insurance Nuclear Area ML18227C7101976-08-25025 August 1976 08/25/1976 Letter Enclosure of Figure 1 - Sheet 3 in Proposed Amendment to Facility Operating License, Illustrating a Lifting Lug & Shim Plate of Proposed Temporary Storage Module Described in July 30, 1976 Submittal ML18228A4951976-04-29029 April 1976 Cask Transfer Path Study, Drawing No. 5177-69-SK-M-4 ML18228A4901976-04-19019 April 1976 Ptp - Units 3 & 4, Sampling System and Spent Fuel Pit Cooling System, Rev. 2 ML18228A4961976-04-16016 April 1976 P. & I. Diagram, Circulating Water, Salt Water & Chlorination System Unit No. 3 or 4, Drawing No. 5610-M-5 ML18228A4941976-04-16016 April 1976 FP&L Turkey Point Unit 3 Safety Injection System Engineering Flow Diagram, FP&L No. E-503185-7, SH.1 of 4 ML18228A4911975-10-0707 October 1975 Ptp - Units 3 & 4, Waste Disposal System - - Liquids, Rev. 1 ML18228A1851975-09-18018 September 1975 Figure, Turkey Point Plant and South Dade Properties, Property Plat, Dade County ML18228A1611975-06-10010 June 1975 Figure 8-1, Generalized Hydrogeologic Framework of the Floridan Aquifer in Southern Florida ML18228A4921975-05-30030 May 1975 Ptp - Units 3 & 4, Component Cooling System - SH.1, Outside Containment, Rev. 1 ML18228A4931975-05-20020 May 1975 Ptp - Units 3 & 4, Primary Water and Demineralized Water Systems, Rev. 1 2018-10-18
[Table view] Category:Letter type:L
MONTHYEARL-2024-010, Point Units 3 and 4, Seabrook, Duane Arnold, and Point Beach Units 1 and 2, Nuclear Property Insurance - 10 CFR 50.54(w)(3)2024-01-25025 January 2024 Point Units 3 and 4, Seabrook, Duane Arnold, and Point Beach Units 1 and 2, Nuclear Property Insurance - 10 CFR 50.54(w)(3) L-2024-007, Inservice Inspection Program Owner'S Activity Report (OAR-1)2024-01-18018 January 2024 Inservice Inspection Program Owner'S Activity Report (OAR-1) L-2023-173, Quality Assurance Topical Report (FPL-1) Revision 30 Update2023-12-15015 December 2023 Quality Assurance Topical Report (FPL-1) Revision 30 Update L-2023-166, Turkey Points Units 3 and 4, Correction to the 2022 Annual Radioactive Effluent Release Report2023-12-0606 December 2023 Turkey Points Units 3 and 4, Correction to the 2022 Annual Radioactive Effluent Release Report L-2023-172, Supplement to Exemption Request Regarding Enhanced Weapons. Firearms Background Checks. and Security Event Notifications Final Rule2023-11-29029 November 2023 Supplement to Exemption Request Regarding Enhanced Weapons. Firearms Background Checks. and Security Event Notifications Final Rule L-2023-155, Supplement to Response to Request for Additional Information, Revised NextEra Common Emergency Plan, and Revised Site-Specific Emergency Plan Annexes Regarding License Amendment Request for Common Emergency Plan Consistent with NUREG-06542023-11-28028 November 2023 Supplement to Response to Request for Additional Information, Revised NextEra Common Emergency Plan, and Revised Site-Specific Emergency Plan Annexes Regarding License Amendment Request for Common Emergency Plan Consistent with NUREG-0654, L-2023-146, Part 73 Exemption Request Regarding Enhanced Weapons, Firearms Background Checks, and Security Event Notifications Final Rule2023-11-16016 November 2023 Part 73 Exemption Request Regarding Enhanced Weapons, Firearms Background Checks, and Security Event Notifications Final Rule L-2023-078, License Amendment Request 278, Incorporate Advanced Fuel Products, Extend Surveillance Intervals and 10 CFR 50.46 Exemption Request to Facilitate Transition to 24-Month Fuel Cycles2023-11-15015 November 2023 License Amendment Request 278, Incorporate Advanced Fuel Products, Extend Surveillance Intervals and 10 CFR 50.46 Exemption Request to Facilitate Transition to 24-Month Fuel Cycles L-2023-077, License Amendment Request 277 Updated Spent Fuel Pool Criticality Analysis2023-10-11011 October 2023 License Amendment Request 277 Updated Spent Fuel Pool Criticality Analysis L-2023-110, Response to Requests for Additional Information Regarding License Amendment Request No. 276, Revise Fire Protection Program in Support of Reactor Coolant Pump Seal Replacement Project2023-08-25025 August 2023 Response to Requests for Additional Information Regarding License Amendment Request No. 276, Revise Fire Protection Program in Support of Reactor Coolant Pump Seal Replacement Project L-2023-115, Inservice Inspection Program Owner'S Activity Report (OAR-1)2023-08-21021 August 2023 Inservice Inspection Program Owner'S Activity Report (OAR-1) L-2023-114, Proposed Turkey Point Units 6 and 7; Seabrook Station; Point Beach Units 1 and 2 - Official Service List Update2023-08-17017 August 2023 Proposed Turkey Point Units 6 and 7; Seabrook Station; Point Beach Units 1 and 2 - Official Service List Update L-2023-098, and Point Beach Units 1 and 2 - Response to Request for Additional Information Regarding License Amendment Request for Common Emergency Plan Consistent with NUREG-0654, Revision 22023-08-0707 August 2023 and Point Beach Units 1 and 2 - Response to Request for Additional Information Regarding License Amendment Request for Common Emergency Plan Consistent with NUREG-0654, Revision 2 L-2023-094, Response to Requests for Additional Information Regarding License Amendment Request No. 276, Revise Fire Protection Program in Support of Reactor Coolant Pump Seal Replacement Project2023-07-27027 July 2023 Response to Requests for Additional Information Regarding License Amendment Request No. 276, Revise Fire Protection Program in Support of Reactor Coolant Pump Seal Replacement Project L-2023-087, Florida Power & Light/Nextera Energy, Results of the Safety Culture Program Effectiveness Review, March 20, 2023 (ADAMS Accession No. ML22340A452)2023-06-29029 June 2023 Florida Power & Light/Nextera Energy, Results of the Safety Culture Program Effectiveness Review, March 20, 2023 (ADAMS Accession No. ML22340A452) L-2023-086, Request Temporary Suspension of Turkey Point License Amendment Request 274, Reactor Protection System, Engineered Safety Features Actuation System, and Nuclear Instrumentation.2023-06-28028 June 2023 Request Temporary Suspension of Turkey Point License Amendment Request 274, Reactor Protection System, Engineered Safety Features Actuation System, and Nuclear Instrumentation. L-2023-074, Addendum to 2021 Decommissioning Funding Status Reports / Independent Spent Fuel Storage Installation Ctsfsi) Financial Assurance Update2023-06-0202 June 2023 Addendum to 2021 Decommissioning Funding Status Reports / Independent Spent Fuel Storage Installation Ctsfsi) Financial Assurance Update L-2023-069, Response to Requests for Additional Information Regarding License Amendment Request No. 276, Revise Fire Protection Program in Support of Reactor Coolant Pump Seal Replacement Project2023-05-31031 May 2023 Response to Requests for Additional Information Regarding License Amendment Request No. 276, Revise Fire Protection Program in Support of Reactor Coolant Pump Seal Replacement Project L-2023-072, Preparation and Scheduling of Operator Licensing Examinations2023-05-22022 May 2023 Preparation and Scheduling of Operator Licensing Examinations L-2023-071, NextEra Energy Quality Assurance Topical Report (FPL-1) Revision 29 and Florida Power and Light Company Quality Assurance Program Description for 10 CFR Part 52 Licenses (FPL-2) Revision 11, Annual Submittal2023-05-22022 May 2023 NextEra Energy Quality Assurance Topical Report (FPL-1) Revision 29 and Florida Power and Light Company Quality Assurance Program Description for 10 CFR Part 52 Licenses (FPL-2) Revision 11, Annual Submittal L-2023-061, 2022 Annual Radiological Environmental Operating Report2023-05-12012 May 2023 2022 Annual Radiological Environmental Operating Report L-2023-062, Cycle 33 Core Operating Limits Report2023-04-27027 April 2023 Cycle 33 Core Operating Limits Report L-2023-060, Radiological Emergency Plan, Revision 752023-04-26026 April 2023 Radiological Emergency Plan, Revision 75 L-2023-054, Submittal of Periodic Reports2023-04-12012 April 2023 Submittal of Periodic Reports L-2023-049, Correction to U4R33 Steam Generator Tube Inspection Report2023-03-30030 March 2023 Correction to U4R33 Steam Generator Tube Inspection Report L-2023-021, Units, 1 and 2, Turkey Point, Units 3 and 4, Seabrook Station and Point Beach, Units 1 and 2 - Decommissioning Funding Status Reports / Independent Spent Fuel Storage Installation (ISFSI) Financial Assurance Update2023-03-28028 March 2023 Units, 1 and 2, Turkey Point, Units 3 and 4, Seabrook Station and Point Beach, Units 1 and 2 - Decommissioning Funding Status Reports / Independent Spent Fuel Storage Installation (ISFSI) Financial Assurance Update L-2023-028, and Point Beach Units 1 and 2, 10 CFR 50.46 Annual Reporting of Changes to, or Errors in Emergency Core Cooling System Models or Applications2023-03-27027 March 2023 and Point Beach Units 1 and 2, 10 CFR 50.46 Annual Reporting of Changes to, or Errors in Emergency Core Cooling System Models or Applications L-2023-025, Fleet Relief Request (Frr) 23-01, Proposed Alternative to ASME Section XI Authorizing Implementation of ASME Code Case N-752-12023-03-15015 March 2023 Fleet Relief Request (Frr) 23-01, Proposed Alternative to ASME Section XI Authorizing Implementation of ASME Code Case N-752-1 L-2023-029, and Point Beach Units 1 and 2 Nuclear Property Insurance - 10 CFR 50.54(w)(3)2023-03-10010 March 2023 and Point Beach Units 1 and 2 Nuclear Property Insurance - 10 CFR 50.54(w)(3) L-2023-040, Response to Requests for Additional Information (Rals) and Requests for Confirmation of Information (Rc Ls) Following Regulatory Audit of Subsequent License Renewal Application2023-03-0303 March 2023 Response to Requests for Additional Information (Rals) and Requests for Confirmation of Information (Rc Ls) Following Regulatory Audit of Subsequent License Renewal Application L-2023-037, Annual Radioactive Effluent Release Report2023-03-0101 March 2023 Annual Radioactive Effluent Release Report L-2023-017, Radiological Emergency Plan Revision 73 and Revision 7 42023-02-17017 February 2023 Radiological Emergency Plan Revision 73 and Revision 7 4 L-2023-010, Supplemental Information Regarding License Amendment Request 274, Reactor Protection System, Engineered Safety Features Actuation System, and Nuclear Instrumentation System Replacement Project - Submittal of RPS / ESFAS / Nis2023-02-10010 February 2023 Supplemental Information Regarding License Amendment Request 274, Reactor Protection System, Engineered Safety Features Actuation System, and Nuclear Instrumentation System Replacement Project - Submittal of RPS / ESFAS / Nis L-2023-004, Supplemental Information Regarding License Amendment Request 274, Reactor Protection System, Engineered Safety Features Actuation System, and Nuclear Instrumentation System Replacement Project - Submittal of Huma Factors Results2023-01-17017 January 2023 Supplemental Information Regarding License Amendment Request 274, Reactor Protection System, Engineered Safety Features Actuation System, and Nuclear Instrumentation System Replacement Project - Submittal of Huma Factors Results L-2022-185, Turkey Points, Units 3 & 4; Seabrook Station; and Point Beach, Units 1 and 2 - Supplement to License Amendment Request for Common Emergency Plan Consistent with NUREG-0654, Revision 22022-12-0909 December 2022 Turkey Points, Units 3 & 4; Seabrook Station; and Point Beach, Units 1 and 2 - Supplement to License Amendment Request for Common Emergency Plan Consistent with NUREG-0654, Revision 2 L-2022-181, Response to Request for Additional Information Regarding License Amendment Request for the Technical Specifications Conversion to NUREG-1431, Revision 52022-12-0101 December 2022 Response to Request for Additional Information Regarding License Amendment Request for the Technical Specifications Conversion to NUREG-1431, Revision 5 L-2022-182, Emergency Response Data System (Eros) Changes2022-11-17017 November 2022 Emergency Response Data System (Eros) Changes L-2022-180, CFR 140.21 Licensee Guarantees of Payment of Deferred Premiums2022-11-0909 November 2022 CFR 140.21 Licensee Guarantees of Payment of Deferred Premiums L-2022-168, and Point Beach Units 1 and 2 - 10 CFR 50.46 - Emergency Core Cooling System LBLOCA 30-Day Report2022-10-26026 October 2022 and Point Beach Units 1 and 2 - 10 CFR 50.46 - Emergency Core Cooling System LBLOCA 30-Day Report L-2022-171, 10 CFR 50.59(d)(2) Summary Report2022-10-20020 October 2022 10 CFR 50.59(d)(2) Summary Report L-2022-167, Submittal of Periodic Reports2022-10-13013 October 2022 Submittal of Periodic Reports L-2022-166, Response to Request for Supplemental Information Regarding License Amendment Request 274, Reactor Protection System, Engineered Safety Features Actuation System, and Nuclear Instrumentation System Replacement2022-10-0505 October 2022 Response to Request for Supplemental Information Regarding License Amendment Request 274, Reactor Protection System, Engineered Safety Features Actuation System, and Nuclear Instrumentation System Replacement L-2022-149, U4R33 Steam Generator Tube Inspection Report2022-10-0404 October 2022 U4R33 Steam Generator Tube Inspection Report L-2022-160, Station,, Point Beach Units 1 and 2, License Amendment Request for Common Emergency Plan Consistent with NUREG-0654, Revision 22022-10-0404 October 2022 Station,, Point Beach Units 1 and 2, License Amendment Request for Common Emergency Plan Consistent with NUREG-0654, Revision 2 L-2022-148, Florida Power & Light Company, Comments on NRC Inspection Procedure (IP) 71111.21 N.03, Commercial Grade Dedication2022-09-16016 September 2022 Florida Power & Light Company, Comments on NRC Inspection Procedure (IP) 71111.21 N.03, Commercial Grade Dedication L-2022-151, Evacuation Time Estimate Study2022-09-15015 September 2022 Evacuation Time Estimate Study L-2022-142, Revised Diversity and Defense-In-Depth Evaluation (D3), Framatome Document No. 51-9324096-0042022-08-19019 August 2022 Revised Diversity and Defense-In-Depth Evaluation (D3), Framatome Document No. 51-9324096-004 L-2022-136, Response to Request for Additional Information Regarding Turkey Point Unit 3 Cycle 32 Steam Generator Tube Inspection Report2022-08-12012 August 2022 Response to Request for Additional Information Regarding Turkey Point Unit 3 Cycle 32 Steam Generator Tube Inspection Report L-2022-109, Inservice Inspection Program - Owner'S Activity Report (OAR-1)2022-06-27027 June 2022 Inservice Inspection Program - Owner'S Activity Report (OAR-1) L-2022-076, Subsequent License Renewal Application - Appendix E Environmental Report Supplement 22022-06-0909 June 2022 Subsequent License Renewal Application - Appendix E Environmental Report Supplement 2 2024-01-25
[Table view] |
Text
L-2013-042 010 FEBCFR1 450.90 2013 FPL.
U. S. Nuclear Regulatory Commission Attn.: Document Control Desk Washington, D.C. 20555-0001 Re: Turkey Point Units 3 and 4 Docket Nos. 50-250 and 50-251 Response to NRC Request for Additional Information Regarding License Amendment Request No. 217 - Administrative Changes to Operating License Conditions and Technical Specifications
References:
(1) M. Kiley (FPL) to U.S. Nuclear Regulatory Commission (L-2012-130), "Administrative License Amendment Request No. 217 Regarding Operating License Conditions and Technical Specifications," Accession No. ML12262A290, September 14, 2012.
(2) M. Kiley (FPL) to U.S. Nuclear Regulatory Commission (L-2013-019), "Supplement to Administrative License Amendment Request No. 217 Regarding Operating License Conditions and Technical Specifications," January 29, 2013.
(3) Email from Tracy Orf (NRC) to Olga Hanek (FPL), "Draft RAI on LAR 217, License Conditions and Technical Specifications," January 24, 2013.
By letter L-2012-130 dated September 14, 2012 [Reference 1], Florida Power & Light Company (FPL) requested to amend Renewed Facility Operating Licenses DPR-31 and DPR-41 and revise the Turkey Point Units 3 and 4 Technical Specifications (TS). The proposed amendments will (1) close and remove license conditions that have been fully satisfied, (2) revise TS 5.5.1 to remove related license conditions, (3) correct several inadvertent errors identified in the TS, and (4) update the reference to the Physical Security Plan (PSP) to the latest approved revision in the related license conditions. The license conditions that had been fully satisfied included 3.H on AST Modifications, 3.1 on Control Room Habitability, and 3.J on EPU Modifications for DPR-31 and license conditions 3.H on the Boraflex Remedy, 3.1.1 & 3.1.3 on AST Modifications, 3.J on Control Room Habitability, and 3.K on EPU Modifications for DPR-41.
By letter L-2013-019 dated January 29, 2013 [Reference 2], FPL submitted a supplement to License Amendment Request (LAR) No. 217 to (1) add 3.1.2 on AST Modifications for DPR-41 to the list of requested license conditions to be deleted, (2) add Control Room Envelope (CRE) to the Limiting Condition for Operation (LCO) listed system components, and (3) update the TS Index, delete TS pages that were no longer applicable and repaginate affected section pages.
By email from the U.S. Nuclear Regulatory Commission (NRC) Project Manager (PM) dated January 24, 2013 [Reference 3], additional information regarding the results of the completed tracer gas testing and pressurization testing was requested by the staff in NRC's Containment and Ventilation Branch (SCVB) to support its review of Administrative LAR No. 217. The RAI consisted of one question regarding the results of the completed tracer gas and pressurization testing and the associated test configuration. The RAI question and applicable FPL response are provided in the Attachment to this letter.
Florida Power & Light Company 9760 SW 344 St., Florida City, FL 33035
Turkey Point Units 3 and 4 L-2013-042 Docket Nos. 50-250 and 50-251 Page 2 of 2 This submittal does not alter the significant hazards consideration or environmental assessment previously submitted by FPL letter L-2012-130 [Reference 1].
This submittal contains no new commitments and no revisions to existing commitments.
In accordance with 10 CFR 50.91(b)(1), a copy of this letter is being forwarded to the State Designee of Florida.
Should you have any questions regarding this submittal, please contact Mr. Robert J. Tomonto, Licensing Manager, at (305) 246-7327.
I declare under penalty of perjury that the foregoing is true and correct.
Executed on February /I' , 2013.
Very truly yours, Michael Kiley Site Vice President Turkey Point Nuclear Plant Attachment cc: USNRC Regional Administrator, Region II USNRC Project Manager, Turkey Point Nuclear Plant USNRC Senior Resident Inspector, Turkey Point Nuclear Plant Ms. Cindy Becker, Florida Department of Health Florida Power & Light Company 9760 SW 344 St., Florida City, FL 33035
Turkey Point Units 3 and 4 L-2013-042 Docket Nos. 50-250 and 50-251 Attachment Page 1 of 6 Turkey Point Units 3 and 4 Response to NRC Request for Additional Information Regarding License Amendment Request No. 217 - Administrative Changes to Operating License Conditions and Technical Specifications ATTACHMENT
Turkey Point Units 3 and 4 L-2013-042 Docket Nos. 50-250 and 50-251 Attachment Page 2 of 6 Response to Request for Additional Information The following information is provided by Florida Power & Light Company (FPL) in response to the U. S. Nuclear Regulatory Commission's (NRC) Request for Additional Information (RAI). This information was requested to support License Amendment Request (LAR) No. 217 on Administrative Changes to Operating License Conditions and Technical Specifications, for Turkey Point Nuclear Plant (PTN) Units 3 and 4 that was submitted to the NRC by FPL letter L-2012-130 on September 14, 2012 [Reference 1] and supplemented by FPL letter L-2013-019 on January 29, 2013 [Reference 2].
In an email dated January 24, 2013 [Reference 3], the NRC staff requested additional information regarding FPL's request to implement proposed administrative changes to PTN's Operating Licenses and Technical Specification (TS) under LAR No. 217. The RAI consisted of one question from the NRC's Containment and Ventilation Branch (SCVB) regarding the results of the completed tracer gas and pressurization testing of the Control Room Envelope (CRE) and associated test configuration.
The RAI question and FPL's response are documented below.
SCVB-1 In the September 14, 2012 submittal, the licensee states that condition 3.1.(a) and (c) were satisfied with completion of the tracer gas testing and pressurization testing on July 25, 2012-no results are provided from the test. Please provide the test results and discuss how the Control Room test configuration is consistent with the AST assumptions.
On September 14, 2012, FPL requested via letter L-2012-130 [Reference 1] deletion of license conditions 3.1 for DPR-31 and 3.J for DPR-41 regarding (a) CRE unfiltered inleakage test (i.e., tracer gas test), (b) CRE habitability assessment, and (c) CRE differential pressure test. It was noted that license conditions 3.I.(a) & 3.I.(c) were satisfied with completion of the tracer gas testing and pressurization testing of the CRE using the normal control room emergency ventilation system (CREVS) filter train on July 18, 2012 and using the compensatory filtration unit on July 25, 2012 while license condition 3.I.(b) was satisfied with completion of the required CRE habitability assessment on September 13, 2012. These specific license conditions were established with the issuance of Amendments 248 and 244 for TSTF-448 on Control Room Habitability dated March 30, 2012 [Reference 4].
On July 18, 2012, the measured unfiltered CRE inleakage was approximately 37+/-5 scfm plus 10 scfm for CR ingress/egress using the normal CREVS filter train. On July 25, 2012, the measured unfiltered CRE inleakage was approximately 44+6 scfm plus 10 scfm for CR ingress/egress using the compensatory filtration train. The acceptance criterion for unfiltered CRE inleakage is < 90 scfm plus 10 scfm for CR ingress/egress based on Alternative Source Term (AST) and associated radiological dose consequence analyses which were approved by the NRC under Amendments 244 and 240 on June 23, 2011
[Reference 5]. Therefore, the measured unfiltered CRE inleakage was found acceptable.
On July 18, 2012, the CRE differential pressure for the normal filter train, using the "A" supply fan, was measured at 0.26 inch H 20 with regard to the battery room, 0.04 inch H 2 0 with regard to the cable spreading room, and 0.04 inch H 2 0 with regard to the outside environs. For the normal filter train using the "B" supply fan, the CRE differential pressure was measured at 0.28 inch H 20 with regard to the battery room, 0.04 inch H2 0 with regard to the cable spreading room, and 0.04 inch H2 0 with regard to the outside environs.
Turkey Point Units 3 and 4 L-2013-042 Docket Nos. 50-250 and 50-251 Attachment Page 3 of 6 On July 25, 2012, the CRE differential pressure for the compensatory filter train was measured at 0.40 inch H20 with regard to the battery room, 0.04 inch H20 with regard to the cable spreading room, and 0.07 inch H20 with regard to the outside environs.
Therefore, as all of the CRE differential pressure measurements were positive, the test results were found acceptable.
This testing followed two major plant modifications involving CREVS: one to relocate the CREVS emergency air intakes away from the Auxiliary Building and another to install a compensatory filtration unit to serve as a qualified backup to the normal filter train. Both of these modifications required temporary breaching of the CRE to implement the required design changes. In addition, the AST changes to CREVS TS 3/4.7.5 explicitly identified 1CREVS components required to be operable and corresponding surveillance requirements.
The LCO lists the two isolation dampers in the kitchen area exhaust duct and two isolation dampers in the toilet area exhaust duct with associated action statements and surveillance requirements. However, subsequent inspections revealed that these gravity backdraft dampers would require substantial corrective maintenance to be considered operable.
Therefore, the motor-operated dampers in the exhaust ducts were closed and the ducts were blanked off at the CRE boundary pending further design review by Engineering. In the interim, portable air filtration units have been installed in the control room kitchen and toilet areas. With an isolation damper inoperable in the kitchen area and toilet area exhaust dampers, TS 3/4.7.5 requires entry into Actions a.8 and a.9 that permit indefinite operation with the associated flow path isolated. This condition was documented in LAR No. 223 via FPL letter L-2012-313 on August 7, 2012 [Reference 6] where an additional footnote was proposed for Modes 5 and 6. The LAR was approved with the NRC's issuance of Amendments 253 and 249 on November 5, 2012 [Reference 7].
As a result of these actions, the CRE was tested with the exhaust ducts blanked off (See Figure 1 - CR Plan - Elev. 42 ft) and one of the two in-series normal air intake dampers (D-1A) failed open (See Figure 2 - CR Plan - Elev. 30 ft) as the worst single failure for the unfiltered inleakage and pressurization testing of both normal and compensatory filter trains. The measured unfiltered CRE inleakage and differential pressure results are as stated above for both the normal and compensatory filter trains. Figures 1 and 2 showing Control Room Boundary (CRB) plan views and applicable isolation dampers are attached.
Turkey Point Units 3 and 4 L-2013-042 Docket Nos. 50-250 and 50-251 Attachment Page 4 of 6 References
- 1. M. Kiley (FPL) to U.S. Nuclear Regulatory Commission (L-2012-130), "Administrative License Amendment Request No. 217 Regarding Operating License Conditions and Technical Specifications," Accession No. ML12262A290, September 14, 2012.
- 2. M. Kiley (FPL) to U.S. Nuclear Regulatory Commission (L-2013-019), "Supplement to Administrative License Amendment Request No. 217 Regarding Operating License Conditions and Technical Specifications," January 29, 2013.
- 3. Email from Tracy Off (NRC) to Olga Hanek (FPL), "Draft RAI on LAR 217, License Conditions and Technical Specifications," January 24, 2013.
- 4. J. Paige (NRC) to M. Nazar (FPL), "Turkey Point Units 3 and 4 - "Issuance of Amendments Regarding Control Room Habitability Technical Specification Task Force (TSTF)-448 (TAC Nos. ME4277 and ME4278)," Accession No. ML12067A176, March 30, 2012.
- 5. J. Paige (NRC) to M. Nazar (FPL), "Turkey Point Units 3 and 4 - "Issuance of Amendments Regarding Alternative Source Term (TAC Nos. ME1624 and ME 1625)," Accession No. ML110800666, June 23, 2011.
- 6. M. Kiley (FPL) to U.S. Nuclear Regulatory Commission (L-2012-313), "Administrative License Amendment Request No. 223 Regarding Control Room Emergency Ventilation System Technical Specification," Accession No. ML12221A392, August 7, 2012.
- 7. J. Paige (NRC) to M. Nazar (FPL), "Turkey Point Generating Station Unit Nos. 3 and 4 -
Issuance of Amendments Regarding Revision to Technical Specifications 3.7.5, "Control Room Emergency Ventilation System" (TAC Nos. ME9211 and ME9212), Accession No. ML12291A730, November 5, 2012.
Turkey Point Units 3 and 4 L-2013-042 Docket Nos. 50-250 and 50-251 Attachment Page 5 of 6 FIGURE 1 CONTROL ROOM BOUNDARY (CRB)
D-22 OS To Emergency Filter (V29)
Outside Air Intake and South Outside Air Control Room Plan - Elevation 42' Intake
Turkey Point Units 3 and 4 L-2013-042 Docket Nos. 50-250 and 50-251 Attachment Page 6 of 6 FIGURE 2 CONTROL ROOM BOU*TNDARY (CRE)
From D-31 CREVS Isolation Damper D-3 Mechanical Equipment Room Plan - Elevation 30' and I8'