From:
Alex Klein
To:
MARION, Alex
Date:
12/17/2007 8:04:10 AM
Subject:
Re: IN 2007-26
Alex,
Thank you for bringing this to our attention. We will take your comment under consideration.
After my staff has had a chance to look at your comment, we may propose to add/keep this as
part of the issues management protocol list (We are planning an issues management public
meeting for near the end of January 2008).
Alex
>>> "MARION, Alex" <am@nei.org> 12/13/2007 9:47 AM >>>
Alex,
There following statement appears on page 2, 4th paragraph: "ASTM E 84 is the standard test method required by NRC regulations and should be in
the licensing basis, unless..." The problem with this statement is
twofold.
1. ASTM E 84 is not required by NRC regulations. I have not been able
to find the citation.
2. Furthermore, this standard was originally intended for testing
ceiling and wall products - not flooring materials.
What is most troubling is that we submitted a paper 6/28/2004 on the
combustibility of epoxy coatings. It appears from the language in this
IN that our input was ignored. I can live with that but our paper was
developed with input from industry fire protection practitioners who I
have found to be correct when it comes to standards and other technical
point. I have attached a copy of that paper.
I bring this to your attention because the IN is factually incorrect.
Thank you for considering this.
Alex
This electronic message transmission contains information from the Nuclear Energy Institute, Inc. The information is intended solely for the use of the addressee and its use by any other
person is not authorized. If you are not the intended recipient, you have received this
communication in error, and any review, use, disclosure, copying or distribution of the contents
of this communication is strictly prohibited. If you have received this electronic transmission in
error, please notify the sender immediately by telephone or by electronic mail and permanently
delete the original message.
IRS Circular 230 disclosure: To ensure compliance with requirements imposed by the IRS and
other taxing authorities, we inform you that any tax advice contained in this communication
(including any attachments) is not intended or written to be used, and cannot be used, for the
purpose of (i) avoiding penalties that may be imposed on any taxpayer or (ii) promoting, marketing or recommending to another party any transaction or matter addressed herein.
CC:
Frumkin, Daniel; IQBAL, Naeem; Vettori, Robert
Mail Envelope Properties
(476673CA.968 : 7 : 8624)
Subject:
Re: IN 2007-26 Creation Date
12/17/2007 8:04:10 AM
From:
Alex Klein
Created By:
ARK1@nrc.gov
Recipients
nei.org
am (Alex MARION)
nrc.gov
OWGWPO02.HQGWDO01 DXF1 CC (Daniel Frumkin)
NXI CC (Naeem IQBAL)
nrc.gov
TWGWPO04.HQGWDO01 RXV1 CC (Robert Vettori)
Post Office
Route
nei.org
OWGWPO02.HQGWDO01
nrc.gov
TWGWPO04.HQGWDO01
nrc.gov
Files
Size
Date & Time
MESSAGE
3917
12/17/2007 8:04:10 AM
Options
Expiration Date:
None
Priority:
Standard
ReplyRequested:
No
Return Notification:
None
Concealed Subject:
No
Security:
Standard
|
|---|
|
| list | - Information Notice 2007-01, Recent Operating Experience Concerning Hydrostatic Barriers (31 January 2007, Topic: Hydrostatic)
- Information Notice 2007-02, Recent Operating Experience with Failure of the Male Coupling of the Lead Screw on the Control Rod Drive Mechanism (7 March 2007)
- Information Notice 2007-03, Reportable Medical Events Involving Patients Receiving Dosages of Sodium Iodide Iodine-131 Less Than the Prescribed Dosage Because of Capsules Remaining in Vials After Administration (2 February 2007, Topic: Tritium Exit Sign)
- Information Notice 2007-03, Reportable Medical Events Involving Patients Receiving Dosages of Sodium Iodide Iodine-131 Less than the Prescribed Dosage Because of Capsules Remaining in Vials After Administration (2 February 2007, Topic: Enforcement Discretion)
- Information Notice 2007-04, Construction Experience Related to the Assurance of Quality in the Construction of Nuclear Power Plants (5 February 2007)
- Information Notice 2007-05, Vertical Deep Draft Pump Shaft and Coupling Failures (9 February 2007, Topic: Ultimate heat sink)
- Information Notice 2007-06, Potential Common Cause Vulnerabilities in Essential Service Water Systems (9 February 2007, Topic: Ultimate heat sink, Probabilistic Risk Assessment, Coatings, Microbiologically influenced corrosion, Biofouling, Through-Wall Leak)
- Information Notice 2007-07, Potential Failure of All Control Rod Groups to Insert in a Boiling Water Reactor (BWR) Due to a Fire (15 February 2007, Topic: Hot Short, Safe Shutdown, Shutdown Margin, Fire Protection Program, Backfit)
- Information Notice 2007-08, Potential Vulnerabilities of Time-Reliant Computer-Based Systems Due to Change in Daylight Saving Time Dates (28 February 2007)
- Information Notice 2007-09, Equipment Operability Under Degraded Voltage Conditions (26 March 2007)
- Information Notice 2007-10, Yttritium-90 Theraspheres and Sirspheres Impurities (2 March 2007, Topic: Enforcement Discretion, TheraSphere)
- Information Notice 2007-10, Yttritium-90 TheraSpheres and SirSpheres Impurities (2 March 2007, 15 March 2007, Topic: Tritium Exit Sign, TheraSphere)
- Information Notice 2007-11, Recent Operator Performance Issues at Nuclear Power Plants (6 March 2007, Topic: Time of Discovery)
- Information Notice 2007-12, Tactical Communications Interoperability Between Nuclear Power Reactor Licensees and First Responders (15 March 2007)
- Information Notice 2007-14, Loss of Offsite Power and Dual-Unit Trip at Catawba Nuclear Generating Station (30 March 2007, Topic: Loss of Offsite Power)
- Information Notice 2007-15, Effects of Ethernet-based, Non-Safety Related Controls on the Safe and Continued Operation of Nuclear Power Stations (17 April 2007, Topic: Restart)
- Information Notice 2007-16, Common Violations of the Increased Controls Requirements and Related Guidance Documents (2 May 2007)
- Information Notice 2007-17, Fires at Nuclear Power Plants Involving Inadequate Fire Protection Administrative and Design Controls (3 May 2007, Topic: Safe Shutdown, Fire Barrier, Operator Manual Action, Continuous fire watch, Fire Protection Program, Fire Watch, Hourly Fire Watch)
- Information Notice 2007-18, Operating Experience Regarding Entrainment of Gas or Debris into Auxiliary Feedwater Systems (13 May 2007, Topic: Foreign Material Exclusion)
- Information Notice 2007-18, Operating Experience Regarding Entrainment of Gas or Debris Into Auxiliary Feedwater Systems (13 May 2007, Topic: Design basis earthquake)
- Information Notice 2007-19, Fire Protection Equipment Recalls and Counterfeit Notices (21 May 2007)
- Information Notice 2007-20, Use of Blank Ammunition (11 June 2007)
- Information Notice 2007-21, Pipe Wear Due to Interaction of Flow-Induced Vibration and Reflective Metal Insulation (11 December 2020, Topic: VT-2, Liquid penetrant)
- Information Notice 2007-22, Recent Hydrogen Fluoride Exposures at Fuel Cycle Facilities (19 June 2007, Topic: Uranium Hexafluoride, TheraSphere)
- Information Notice 2007-23, Inadvertent Discharge of Halon 1301 Fire Suppression System Due to Incorrect and/or Out of Date Procedures (8 August 2007, Topic: Fire Protection Program, TheraSphere)
- Information Notice 2007-23, Inadvertent Discharge of Halon 1301 Fire Suppression System Due to Incorrect And/Or Out of Date Procedures (8 August 2007, Topic: Fire Protection Program, TheraSphere)
- Information Notice 2007-24, Summary of Fitness-for-Duty Program Performance Reports for Calendar Year 2006 (19 July 2007, Topic: Fitness for Duty, Contraband)
- Information Notice 2007-25, Recommendations from the Advisory Committee on the Medical Use of Isotopes for Improved Compliance with 10 CFR 35.40 and 35.27 (19 July 2007, Topic: Enforcement Discretion)
- Information Notice 2007-25, Recommendations From the Advisory Committee on the Medical Use of Isotopes for Improved Compliance with 10 CFR 35.40 and 35.27 (19 July 2007, Topic: Tritium Exit Sign)
- Information Notice 2007-26, E-mail from Alex Klein to Alex Marion Regarding NRC Information Notice 2007-26 (17 December 2007, Topic: Coatings)
- Information Notice 2007-27, Recurring Events and Trends Involving Emergency Diesel Generator Operability (6 August 2007, Topic: Notice of Violation, Loss of Offsite Power, Preliminary White Finding)
- Information Notice 2007-28, Potential Common Cause Vulnerabilities in Essential Service Water Systems Due to Inadequate Chemistry Controls (19 September 2007, Topic: Probabilistic Risk Assessment, Frazil ice, Biofouling)
- Information Notice 2007-29, Temporary Scaffolding Affects Operability of Safety-Related Equipment (17 September 2007, Topic: High Energy Line Break, Fire Protection Program, Scaffolding)
- Information Notice 2007-30, Radiological Controls Create Criticality Safety Accident Scenario for Fissile Solution Container Transport at Fuel Cycle Facility (13 September 2007, Topic: Coatings, TheraSphere, Spill)
- Information Notice 2007-31, U.S. Food and Drug Administration Announcement Related to Sleep Disorder Drugs (13 November 2007, Topic: Fitness for Duty, Coatings, TheraSphere)
- Information Notice 2007-32, Out of Service Equipment Connected to in Service Process Line Results in Fissile Solution Spill at Fuel Cycle Facility (15 October 2007, Topic: Hydrostatic, Coatings, TheraSphere, Spill)
- Information Notice 2007-32, Out of Service Equipment Connected To In Service Process Line Results in Fissile Solution Spill at Fuel Cycle Facility (15 October 2007, Topic: Hydrostatic, Coatings, TheraSphere, Spill)
- Information Notice 2007-33, Exposure to Members of the Public Caused by Inadequate Controls Over Well Logging Sources (28 September 2007, Topic: Coatings, TheraSphere)
- Information Notice 2007-34, Operating Experience Regarding Electrical Circuit Breakers (22 October 2007, Topic: Loss of Offsite Power, Hardened grease)
- Information Notice 2007-35, Varian Medical Systems Varisource HDR Events: Iridium-192 Source Pulled from Shielded Position (17 October 2007, Topic: Coatings, TheraSphere)
- Information Notice 2007-36, Emergency Diesel Generator Voltage Regulator Problems (15 November 2007)
- Information Notice 2007-37, Buildup of Deposits in Steam Generators (23 November 2007, Topic: Eddy Current Test)
- Information Notice 2007-38, Ensuring Complete and Accurate Information in the Documentation of Training and Experience for Individuals Seeking Medical Authorization Under the Alternate Pathway (14 December 2007, Topic: TheraSphere)
- Information Notice 2007-40, Inadequate Implementation of 10 CFR Part 21 Requirements by Vendors Who Supply Basic Components to Nuclear Power Plant Licensees (21 December 2007, Topic: Basic Component)
|
|---|