Information Notice 1992-28, Inadequate Fire Suppression System Testing
UNITED STATES
NUCLEAR REGULATORY COMMISSION
OFFICE OF NUCLEAR REACTOR REGULATION
WASHINGTON, D.C. 20555
April 8, 1992 NRC INFORMATION NOTICE 92-28:
INADEQUATE FIRE SUPPRESSION SYSTEM TESTING
Addressees
All holders of operating licenses or construction permits for nuclear power
reactors.
Purpose
The U.S. Nuclear Regulatory Commission (NRC) is issuing this information notice
to alert addressees to potential inadequate performance of carbon dioxide (CO2)
and Halon fire suppression systems caused by excessive leakage from the pro- tected enclosure or by deficient operation of the system's components. Limited
acceptance testing may not be adequate to identify these problems. It is
expected that recipients will review the information for applicability to their
facilities and consider actions, as appropriate, to avoid similar problems.
However, suggestions contained in this information notice are not NRC require- ments; therefore, no specific action or written response is required.
Background
In Section 50.48 of Title 10 of the Code of Federal Regulations, the NRC
established fire protection requirements for operating nuclear power plants.
This rule requires automatic and manual fire suppression systems to function so
that the capability to safely shut down the plant is ensured.
Many licensees
use total flooding CO2 and Halon fire suppression systems to protect systems
necessary for safe shutdown. In Branch Technical Position APCSB 9.5-1,
"Guidelines for Fire Protection for Nuclear Power Plants," the staff referenced
National Fire Protection Association (NFPA) standards, NFPA 12-1973, "Carbon
Dioxide Extinguishing Systems," and NFPA 12A-1973, "Halon 1301 Fire Extinguish- ing Systems." These standards emphasized the need to minimize leakage from the
enclosure in order to retain the fire suppressing agent for the required soak
time and the importance of thoroughly inspecting the fire suppression system to
ensure that it will operate properly. Licensees frequently use full discharge
tests to demonstrate that fire suppression systems perform properly and that
leakage from protected enclosures is acceptable.
Description of Circumstances
On February 23, 1988, the Connecticut Yankee Atomic Power Company, the licensee
for the Haddam Neck Power Plant, performed a full discharge test of the CO2 fire suppression system for the containment cable vault. The test results
indicated that the CO2 concentration within the cable vault failed to meet
NFPA 1242. "
ents.
Consequently, on February 27, the licensee declared the
M40201862O186
\\
IN 92-28 April 8, 1992 fire suppression system for the cable vault inoperable. The licensee deter- mined that the root cause of the failure was excessive leakage of CO from the
enclosure area through numerous unsealed electrical conduits in the lower level
of the cable vault.
These conduits were in the original plant design, but were
not considered in the design of the CO2 system.
While performing an inspection the week of April 3, 1989, at the Susquehanna
Steam Electric Station (Susquehanna), the NRC found a concern regarding the
adequacy of initial testing of the plant's CO2 fire suppression systems.
In 1982, the Pennsylvania Power and Light Company (PP&L), the licensee for
Susquehanna, had performed a full discharge test for one of seven areas pro- tected by automatic CO2 fire suppression systems. The test found that the
required concentration of CO2 was not maintained in the enclosure for the
required soak time. The test results may have been caused solely by the
failure of a temporary seal around an access door.
However, the licensee did
not perform additional testing to confirm the cause of the test failure. The
licensee then performed limited acceptance tests of the CO2 fire suppression
systems.
To address the NRC's concern, PP&L performed testing in the first quarter of
1990 using room pressurization to measure enclosure leakage and to determine a
projected agent retention time.
The licensee based the testing on the enclo- sure integrity procedure in Appendix B to NFPA 12A-1989. The test results
indicated that three of the seven areas included enclosures with leakage
greater than that which would ensure retention of the required CO2 concentrattogi-for-the-'requhtr-d-t-sbk tim6-.--T1eWfailure of these enclosures was
attributed to their small enclosed volume and the corresponding small allowable
leakage area.
In general, a smaller allowable leakage area should be expected
for small enclosures because of the higher ratio of boundary area to enclosed
volume.
On April 21, 1990, at the Catawba Nuclear Station (Catawba), an inadvertent
steam release actuated a CO2 fire suppression system. Although the fire
suppression system is designed to discharge to only one area at a time, the
three selector pilot valves installed in the system directed the CO2 discharge
to all three areas protected by the system. Duke Power Company, the licensee
for Catawba, investigated the incident and discovered that the solenoids
operating the three selector pilot valves were installed backwards. The
licensee determined that the required CO2 concentration could not be obtained
within the protected areas when the system discharged into more than one area
at a time. Therefore, the licensee declared the system inoperable. The
licensee attributed the improper solenoid installation, in part, to a
preoperational test procedure which did not adequately test the system for the
incorrectly installed components.
Discussion
Retaining an adequate concentration of fire suppressing agent for the required
soak time is important for enclosures containing equipment that could develop
"deep seated" fires.
In a study of deep seated cable fires, Sandia National
Laboratory determined that, for certain configurations of cables qualified to
Standard 383 of the Institute of Electrical and Electronic Engineers (IEEE), it
IN 92-28 April 8, 1992 was necessary to retain a 50X concentration of CO2 for a minimum soak time of
15 minutes to extinguish fully developed fires.
Sandia National Laboratory
documented the results of the study in NUREG/CR-3656, "Evaluation of Suppres- sion Methods for Electrical Cable Fires," dated October 1986.
Full discharge testing of CO2 fire suppression systems may present certain
hazards at operating nuclear power plants. These hazards include thermal shock
to safety-related components, uncontrolled electrostatic discharge, and hazards
to personnel from high concentrations of CO2.
Some licensees have used
alternative testing methods which avoid these hazards.
For example, the
licensee for the Vermont Yankee Atomic Power Station responded to the NRC's
concern regarding the adequacy of initial tests of the plant's fire suppression
systems by performing an alternative test that incorporated methodology from
the enclosure integrity procedure in Appendix B to NFPA 12A-1989.
That method- ology is conservative because the effects of the thermal expansion of the
mixture of CO2 and air are not included and a "worst case" distribution of
measured leakage area is assumed.
The licensee also performed a rigorous
engineering evaluation of the installed CO
system to verify that the system
would operate as designed to deliver a sufficient amount of Co2.
The testing described in Section 1-7.4 of NFPA 12A-1989 was developed to
alleviate concerns for both the cost and the environmental damage associated
with repeatedly performing full discharge tests of Halon fire suppression
systems.
The testing described in NFPA 12A provides an alternative method to
full discharge testing of Halon systems to demonstrate that the fire suppres- sion system and the enclosure function as designed.
This information notice requires no specific action or written response. If
you have any questions about the information in this notice, please contact the
technical contact listed below or the appropriate Office of Nuclear Reactor
Regulation (NRR) project manager.
Charles E. Rossi, Director
Division of Operational Events Assessment
Office of Nuclear Reactor Regulation
Technical contact:
S. R. Jones, NRR
(301) 504-2833 Attachment:
List of Recently Issued NRC Information Notices
Mz
--0
<n
0 0
-u r-
< a
CwU
Enl(A
a"n
z
C
0n
C} C Z.
ImC
in
a-4
0z
Attachment
April 8, 1992
Page I of I
LIST OF RECENTLY ISSUED
NRC INFORMATION NOTICES
Information
Date of
Notice No.
Subject
Issuance
Issued to
92-27 Thermally Induced Acceler-
04/03/92
All holders of OLs or CPs
ated Aging and Failure of
for nuclear power reactors.
ITE/GOULD A.C. Relays Used
in Safety-Related Applic- ations
92-26 Pressure Locking of Motor-
04/02/92
All holders of OLs or CPs
Operated Flexible Wedge
for nuclear power reactors.
Gate Valves
92-25 Potential Weakness in
03/31/92
All holders of OLs or CPs
Licensee Procedures for A
for nuclear power reactors.
Loss of the Refueling
Cavity Water
92-24 Distributor Modification to
03/30/92
All holders of OLs or CPs
Certain Commercial-Grade
for nuclear power reactors.
Agastat Electrical Relays
92-23 Results of Validation Test-
03/27/92
All holders of OLs or CPs
ing of Motor-Operated Valve
for nuclear power reactors
Diagnostic Equipment
and all vendors of motor- operated valve (MOV) diag- nostic equipment.
92-22 Criminal Prosecution and
03/24/92 All holders of OLs or CPs
K
Conviction of Wrongdoing
for nuclear power reactors.
Committed by A Commercial-
Grade Valve Supplier
92-21 Spent Fuel Pool Reactivity
03/24/92
All holders of OLs or CPs
Calculations
for nuclear power reactors.
92-20
Inadequate Local Leak Rate
03/03/92
All holders of OLs or CPs
Testing
for nuclear power reactors.
92-19 Misapplication of Potter L
03/02/92
All holders of OLs or CPs
Brumfield NOR Rotary Relays
for nuclear power reactors.
OL - Operating License
- Construction Permit
I
IN 92-28 April 8, 1992 was necessary to retain a 50% concentration of CO2 for a minimum soak time of
15 minutes to extinguish fully developed fires.
Sandia National Laboratory
documented the results of the study in NUREG/CR-3656, "Evaluation of Suppres- sion Methods for Electrical Cable Fires," dated October 1986.
Full discharge testing of CO2 fire suppression systems may present certain
hazards at operating nuclear power plants. These hazards include thermal shock
to safety-related components, uncontrolled electrostatic discharge, and hazards
to personnel from high concentrations of CO2.
Some licensees have used
alternative testing methods which avoid these hazards.
For example, the
licensee for the Vermont Yankee Atomic Power Station responded to the NRC's
concern regarding the adequacy of initial tests of the plant's fire suppression
systems by performing an alternative test that incorporated methodology from
the enclosure integrity procedure in Appendix B to NFPA 12A-1989. That method- ology is conservative because the effects of the thermal expansion of the
mixture of CO2 and air are not included and a "worst case" distribution of
measured leakage area is assumed.
The licensee also performed a rigorous
engineering evaluation of the installed CO system to verify that the system
would operate as designed to deliver a sufficient amount of CO2.
The testing described in Section 1-7.4 of NFPA 12A-1989 was developed to
alleviate concerns for both the cost and the environmental damage associated
with repeatedly performing full discharge tests of Halon fire suppression
systems. The testing described in NFPA 12A provides an alternative method to
full discharge testing of Halon systems to demonstrate that the fire suppres- sion system and the enclosure function as designed.
This information notice requires no specific action or written response. If
you have any questions about the information in this notice, please contact the
technical contact listed below or the appropriate Office of Nuclear Reactor
Regulation (NRR)
project manager.
Orginal Signed by
Charles E. oRsi
Charles E. Rossi, Director
Division of Operational Events Assessment
Office of Nuclear Reactor Regulation
Technical contact:
S. R. Jones, NRR
(301)
504-2833 Attachment:
List of Recently Issued NRC Information Notices
Document Name:
- SEE
PREVIOUS CONCURRENCES
D
- C/OGCB:DOEA:NRR
Ce
'
CHBerlinger
04/
\\ 03/30/92
- OGCB:DOEA:NRR*SPLB:DST:NRR
- C/SPLB:DST:NRR
- D/DST:NRR
- RPB:ADM
JLBirmingham
SRJones
CMcCracken
ACThadani
TechEd
02/21/92
02/24/92
03/02/92
03/26/92
02/21/92
IN 92-XX
March xx, 1992 15 minutes to extinguish fully developed fires.
Sandia National Laboratory
documented the results of the study in NUREG/CR-3656, "Evaluation of Suppres- sion Methods for Electrical Cable Fires," dated October 1986.
Full discharge testing of CO2 fire suppression systems may present certain
hazards at operating nuclear power plants. These hazards include thermal shock
to safety-related components, uncontrolled electrostatic discharge, and hazards
to personnel from high concentrations of CO2.
Some licensees have used
alternative testing methods which avoid these hazards.
For example, the
licensee for the Vermont Yankee Atomic Power Station responded to the NRC's
concern regarding the adequacy of initial tests of the plant's fire suppression
systems by performing an alternative test that incorporated methodology from
the enclosure integrity procedure in Appendix B to NFPA 12A-1989. That method- ology is conservative because the effects of the thermal expansion of the
mixture of CO2 and air are not included and a "worst case" distribution of
measured leakage area is assumed. The licensee also performed a rigorous
engineering evaluation of the installed CO system to verify that the system
would operate as designed to deliver a sufficient amount of CO2.
The testing described in Section 1-7.4 of NFPA 12A-1989 was developed to
alleviate concerns for both the cost and the environmental damage associated
with repeatedly performing full discharge tests of Halon fire suppression
systems. The testing described in NFPA 12A provides an alternative method to
full discharge testing of Halon systems to demonstrate that the fire suppres- sion system and the enclosure function as designed.
This information notice requires no specific action or written response. If
you have any questions about the information in this notice, please contact the
technical contact listed below or the appropriate Office of Nuclear Reactor
Regulation (NRR) project manager.
Charles E. Rossi, Director
Division of Operational Events Assessment
Office of Nuclear Reactor Regulation
Technical contact: S. R. Jones, NRR
(301) 504-2833 Attachment: List of Recently Issued NRC Information Notices
Document Name: FIRE INFO NOTE
- SEE PREVIOUS CONCURRENCES
060
D/DOEA:NRR
C/OGCB:DOEA:NRR
CERossi
CHBerlinger
02/ /92 t
0l/3s/92
- OGCB:DOEA:NRR*SPLB:DST:NRR *C/SPLB:DST:NRR
D/DST:NRR
- RPB:ADM
JLBirmingham SRJones
CMcCracken
ACThadani
TechEd
02/21/92
02/24/92
03/02/92
3/,21f92
02/21/92 a W~L
IN 92-XX
February xx, 1992 15 minutes to extinguish fully developed fires. Sandia National Laboratory
documented the results of the study in NUREG/CR-3656, "Evaluatio o- sion Methods for Electrical Cable Fires," dated October 1986.) Licensees may
ts which dem-ostratI
ed--
res can retain
the required concentration of fire suppressing agent for an appropriate minim
soak time and that the fire suppression system functions as designed.
Full discharge testing of CO2 fire suppression systems may present certain
hazards at operating nuclear power plants.
These hazards include thermal shock
to safety-related components, uncontrolled electrostatic discharge, and hazards
to personnel from high concentrations of CO2.
Some licensees have used
alternative testing methods which avoid these hazards.
For example, the
licensee for the Vermont Yankee Atomic Power Station responded to the NRC's
concern regarding the adequacy of initial tests of the plant's fire suppression
systems by performing an alternative test that incorporated methodology from
the enclosure integrity procedure in Appendix B to NFPA 12A-1989.
That method- ology is conservative because the effects of the thermal expansion of the
mixture of CO2 and air are not included and a "worst case" distribution of
measured leakage area is assumed. The licensee also performed a rigorous
engineering evaluation of the installed CO system to verify that the system
would operate as designed to deliver a sufficient amount of CO2.
The testing described in Section 1-7.4 of NFPA 12A-1989 was developed to
alleviate concerns for both the cost and the environmental damage associated
with repeatedly performing full discharge tests of Halon fire suppression
systems. The testing described in NFPA 12A provides an alternative method to
full discharge testing of Halon systems to demonstrate that the fire suppres- sion system and the enclosure function as designed.
This information notice requires no specific action or written response. If
you have ally questions about the information in this notice, please contact the
technical contact listed below or the appropriate Office of Nuclear Reactor
Regulation (NRR) project manager.
Charles E. Rossi, Director
Division of Operational Events Assessment
Office of Nuclear Reactor Regulation
Technical contact: S. R. Jones, NRR
(301) 504-2833 Attachment: List of Recently Issued NRC Information Notices
Document Name:
FIRE INFO NOTE
- SEE PREVIOUS CONCURRENCES
D/DOEA:NRR
C/OGCB:DOEA:NRR
CERossi
CHBerlinger
(11841
02/ /92
02/ /92
- OGCB:DOEA:NRR SPLB:DST: tR
C/SPLB:DST:NRR
D/DST:NR
- RPB:ADM
JLBirmingham SRJonesAbl
CMcCracken
ACTh dani
TechEd
02/21/92
02/2/92 (
03/o
492
4(
92
02/21/92
methodology is conservative because the effects of the thermal expansion of the
mixture of CO2 and air are not included and a "Worst case" distribution of
measured leakage area is assumed. The licensee also performed a rigorous
engineering evaluation of the installed CO2 system to verify that the system
would operate as designed to deliver a sufficient amount of CO2.
The testing described in Section 1-7.4 of NFPA 12A-1989 was developed to
alleviate concerns for both the cost and the environmental damage associated
with repeatedly performing full discharge tests of Halon fire suppression
systems. The testing described in NFPA 12A provides an alternative method to
full discharge testing of Halon systems to demonstrate that the fire suppres- sion system and the enclosure function as designed.
This information notice requires no specific action or written response. If
you have any questions about the information in this notice, please contact the
technical contact listed below or the appropriate Office of Nuclear Reactor
Regulation (NRR) project manager.
Charles E. Rossi, Director
Division of Operational Events Assessment
Office of Nuclear Reactor Regulation
Technical contact: S. R. Jones, NRR
(301) 504-2833 Attachment: List of Recently Issued NRC Information Notices
Document Name: FIRE INFO NOTE
D/DOEA:NRR
C/OGCB:DOEA:NRR
CERossi
CHBerlinger
02/ /92
02/ /92 OGCB:DOEA:NRR SPLB:DST:NRR
C/SPLB:DST:NRR
D/DST:NRR
RPB:ADM
JLBirmingha ,, SRJones
CMcCracken
ACThadani
TechEd UJHatp 0A
02/2j/920/2
02/ /92
02/
/92
02/
/92
02/a2/92
1