UNITED STATES
NUCLEAR REGULATORY COMMISSION
OFFICE OF NUCLEAR REACTOR REGULATION
WASHINGTON, D.C. 20555 January 9, 1992 NRC INFORMATION NOTICE 92-07: RAPID FLOW-INDUCED EROSION/CORROSION
OF FEEDWATER PIPING
Addressees
All holders of operating licenses or construction permits for pressurized water
reactors.
Purpose
The U.S. Nuclear Regulatory Commission (NRC) is issuing this information notice
to alert addressees to problems discovered at the Catawba Nuclear Station, Unit
2, involving the rapid flow-induced erosion/corrosion of feedwater piping. The
problem discovered at Catawba affects the piping supplying the upper feedwater
nozzles and may apply to all Westinghouse units employing steam generator
models D-4, D-5, and E, in which a portion of main feedwater is diverted to the
upper feedwater nozzles when the unit is operating. It is expected that
recipients will review the information for applicability to their facilities
and consider actions, as appropriate, to avoid similar problems. However, suggestions contained in this information notice are not NRC requirements;
therefore, no specific action or written response is required.
Description of Circumstances
On November 4, 1991, while performing ultrasonic testing on a section of 4-inch
feedwater system piping on Catawba's Unit 2 A steam generator, the licensee, Duke Power Company, detected several locations that were at or near minimum
acceptable wall thickness. The licensee detected similar results on the other
three steam generators. The licensee was performing this testing as part of
its prescribed piping erosion/corrosion control program.
The licensee removed sections of the A106B carbon steel piping for analysis or
replacement. This analysis revealed that the piping had undergone significant, symmetric, flow-induced, single phase erosion/corrosion. In some areas, the
4-inch schedule 80 pipe (nominal thickness 0.337 inch) had been thinned to
0.185 inch in only four operating cycles. This implies an erosion/corrosion
rate of approximately 0.040 Inch per cycle. The licensee identified approxi- mately 90 feet of affected pipe for replacement.
It appears that the thinning is directly attributable to the design of the
steam generators (Model D5) on Catawba Unit 2, which requires a split-flow
feedwater delivery system. In this design, typically 10-20 percent of the
total feedwater flow is delivered to the upper feedwater nozzles to prevent
9201090188
IN 92-0i
January 9, 1992 flow-induced vibration damage to the steam generator feedwater preheater
section when full feedwater flow is delivered through the main nozzles.
The original Catawba feedwater system design did not employ split-flow delivery
at power. As a result, the piping was not sized to accommodate the operating
flow rates, resulting in flow velocities of 30-35 feet per second in sections
of 4-inch piping. This high flow rate has led to rapid erosion/corrosion.
In the case of Catawba, Unit 2, if the subject piping in the feedwater preheater
bypass line had ruptured, the break would not have been isolable and would have
resulted in the steam generator fluid being released outside containment.
This problem applies to Westinghouse units employing steam generator models
D-4, D-5, and E if the flow reaches a high velocity when a portion of
normal feedwater is diverted to the upper feedwater nozzles. In numerous
generic communications, the staff has previously stated that high velocity
flows may cause rapid flow-induced erosion/corrosion in carbon steel piping.
This information notice requires no specific action or written response. If
you have any questions about the information in this notice, please contact one
of the technical contacts listed below or the appropriate Office of Nuclear
Reactor Regulation (NRR) project manager.
hr oss ,frecto
Division of Operational Events Assessment
Office of Nuclear Reactor Regulation
Technical contacts: William Orders, RII
(803) 831-2963 John Zeiler, RII
(803) 831-2963 Krysztof I. Parczewski, NRR
(301) 504-2705 Attachment: List of Recently Issued NRC Information Notices
~'.'f 'a. cI men t
IN 92-07 January 9, 1992 LIST OF RECENTLY ISSUED
NRC INFORMATION NOTICES
Information Date of
Notice No. Subject Issuance Issued to
92-06 Reliability of ATWS Mitiga- 01/15/92 All holders of OLs or CPs
tion System and Other NRC for nuclear power reactors.
Required Equipment Not
Controlled by Plant Tech- nical Specifications
92-05 Potential Coil Insulation 01/08/92 All holders of OLs or CPs
Breakdown in ABB RXMH2 Relays for nuclear power reactors.
92-04 Potter & Brumfield Model 01/06/92 All holders of OLs or CPs
MDR Rotary Relay Failures for nuclear power reactors.
92-03 Remote Trip Function 01/06/92 All holders of OLs or CPs
Failures in General Electric for nuclear power reactors.
F-Frame Molded-Case Circuit
Breakers
92-02 Relap5/Mod3 Computer Code 01/03/92 All holders of OLs or CPs
Error Associated with the for nuclear power reactors.
Conservation of Energy
Equation
92-01 Cable Damage Caused by 01/03/92 All holders of OLs or CPs
Inadequate Cable Installa- for nuclear power reactors.
tion Procedures and Controls
91-87 Hydrogen Embrittlement of 12/27/91 All holders of OLs or CPs
Raychem Cryofit Couplings for nuclear power reactors.
91-86 New Reporting Requirements 12/27/91 All licensees authorized
for Contamination Events at to use byproduct materials
Medical Facilities for human use.
(10 CFR 30.50)
91-85 Potential Failures of 12/26/91 All holders of OLs or CPs
Thermostatic Control Valves for nuclear power reactors.
for Diesel Generator Jacket
Cooling Water
OL = Operating License
CP = Construction Permit
|
---|
|
list | - Information Notice 1992-01, Cable Damage Caused by Inadequate Cable Installation Procedures and Controls (3 January 1992)
- Information Notice 1992-02, Relap5/MOD3 Computer Code Error Associated with the Conservation of Energy Equation (3 January 1992)
- Information Notice 1992-02, Relap5/Mod3 Computer Code Error Associated with the Conservation of Energy Equation (3 January 1992)
- Information Notice 1992-03, Remote Trip Function Failures in General Electric F-Frame Molded-Case Circuit Breakers (6 January 1992)
- Information Notice 1992-04, Potter and Brumfield Model Mdr Rotary Relay Failures (6 January 1992, Topic: Probabilistic Risk Assessment)
- Information Notice 1992-04, Potter and Brumfield Model MDR Rotary Relay Failures (6 January 1992, Topic: Probabilistic Risk Assessment)
- Information Notice 1992-05, Potential Coil Insulations Breakdown in Abs RXMH2 Relays (8 January 1992)
- Information Notice 1992-05, Potential Coil Insulations Breakdown in Abs Rxmh2 Relays (8 January 1992)
- Information Notice 1992-05, Potential Coil Insulations Breakdown in ABS RXMH2 Relays (8 January 1992)
- Information Notice 1992-06, Reliability of ATWS Mitigation System and Other NRC Required Equipment Not Controlled by Plant Technical Specifications (15 January 1992)
- Information Notice 1992-06, Reliability of ATWS Mitigation System and Other NRC Required Equipment not Controlled by Plant Technical Specifications (15 January 1992)
- Information Notice 1992-07, Rapid Flow-induced Erosion/Corrosion of Feedwater Piping (9 January 1992)
- Information Notice 1992-08, Revised Protective Action Guidance for Nuclear Incidents (23 January 1992)
- Information Notice 1992-09, Overloading and Subsequent Lock Out of Electrical Buses During Accident Conditions (30 January 1992)
- Information Notice 1992-10, Brachytherapy Incidents Involving Iridium-192 Wire Used in Endobronchial Treatments (31 January 1992, Topic: Brachytherapy)
- Information Notice 1992-10, Brachytherapy Incidents Involving Iridium-192 Wire used in Endobronchial Treatments (31 January 1992, Topic: Brachytherapy)
- Information Notice 1992-11, Soil and Water Contamination at Fuel Cycle Facilities (5 February 1992, Topic: Brachytherapy)
- Information Notice 1992-12, Effects of Cable Leakage Currents on Instrument Settings and Indications (10 February 1992, Topic: Brachytherapy)
- Information Notice 1992-13, Inadequate Control Over Vehicular Traffic at Nuclear Power Plant Sites (18 February 1992, Topic: Brachytherapy)
- Information Notice 1992-14, Uranium Oxide Fires at Fuel Cycle Facilities (21 February 1992, Topic: Brachytherapy)
- Information Notice 1992-15, Failure of Primary Systems Compression Fitting (24 February 1992)
- Information Notice 1992-16, Loss of Flow from the Residual Heat Removal Pump During Refueling Cavity Draindown (25 February 1992, Topic: Reactor Vessel Water Level, Temporary Modification, Brachytherapy)
- Information Notice 1992-17, NRC Inspections of Programs Being Developed at Nuclear Power Plants in Response to Generic Letter 89-10 (26 February 1992, Topic: Stroke time)
- Information Notice 1992-18, Potential for Loss of Remote Shutdown Capability During a Control Room Fire (28 February 1992, Topic: Hot Short, Safe Shutdown)
- Information Notice 1992-19, Misapplication of Potter and Brumfield Mdr Rotary Relays (2 March 1992)
- Information Notice 1992-19, Misapplication of Potter and Brumfield MDR Rotary Relays (2 March 1992)
- Information Notice 1992-20, Inadequate Local Leak Rate Testing (3 March 1992)
- Information Notice 1992-21, Spent Fuel Pool Reactivity Calculations (24 March 1992)
- Information Notice 1992-23, Results of Validation Testing of Motor-Operated Valve Diagnostic Equipment (27 March 1992)
- Information Notice 1992-24, Distributor Modification to Certain Commercial-Grade Agastat Electrical Relays (30 March 1992)
- Information Notice 1992-25, Pressure Locking of Motor-Operated Flexible Wedge Gate Valves (2 April 1992, Topic: Stroke time, Hydrostatic)
- Information Notice 1992-27, Thermally Induced Accelerated Aging and Failure of ITE/Gould A.C. Relays used in Safety-Related Applications (3 April 1992)
- Information Notice 1992-27, Thermally Induced Accelerated Aging and Failure of Ite/Gould A.C. Relays Used in Safety-Related Applications (3 April 1992)
- Information Notice 1992-28, Inadequate Fire Suppression System Testing (8 April 1992, Topic: Safe Shutdown)
- Information Notice 1992-29, Potential Breaker Miscoordination Caused by Instantaneous Trip Circuitry (17 April 1992)
- Information Notice 1992-30, Falsification of Plant Records (23 April 1992)
- Information Notice 1992-31, Electrical Connection Problem in Johnson Yokogawa Corporation YS-80 Programmable Indicating Controllers (27 April 1992)
- Information Notice 1992-32, Problems Identified with Emergency Ventilation Systems for Near-Site (Within 10 Miles) Emergency Operations Facilities and Technical Support Centers (29 April 1992)
- Information Notice 1992-32, Problems Identified with Emergency Ventilation Systems for Near-Site (within 10 Miles) Emergency Operations Facilities and Technical Support Centers (29 April 1992)
- Information Notice 1992-33, Increased Instrument Response Time When Pressure Dampening Devices Are Installed (30 April 1992)
- Information Notice 1992-33, Increased Instrument Response Time When Pressure Dampening Devices are Installed (30 April 1992)
- Information Notice 1992-34, New Exposure Limits for Airborne Uranium and Thorium (6 May 1992)
- Information Notice 1992-35, Higher than Predicted Erosion/Corrosion in Unisolable Reactor Coolant Pressure Boundary Piping Inside Containment at a Boiling Water Reactor (6 May 1992)
- Information Notice 1992-35, Higher than Predicted Erosion/Corrosion in Unisolable Reactor Coolant Pressure Boundary Piping inside Containment at a Boiling Water Reactor (6 May 1992)
- Information Notice 1992-36, Intersystem LOCA Outside Containment (7 May 1992)
- Information Notice 1992-37, Implementation of the Deliberate Misconduct Rule (8 May 1992)
- Information Notice 1992-38, Implementation Date for the Revision to the EPA Manual of Protective Action Guides and Protective Actions for Nuclear Incidents (26 May 1992, Topic: Brachytherapy)
- Information Notice 1992-39, Unplanned Return to Criticality During Reactor Shutdown (13 May 1992, Topic: Fuel cladding)
- Information Notice 1992-40, Inadequate Testing of Emergency Bus Undervoltage Logic Circuitry (27 May 1992)
- Information Notice 1992-41, Consideration of Stem Rejection Load In Calculation of Required Valve Thrust (29 May 1992, Topic: Anchor Darling)
... further results |
---|