IR 05000491/1979010

From kanterella
Jump to navigation Jump to search
IE Insp Repts 50-491/79-10,50-492/79-10 & 50-493/79-10 on 790612-13.Noncompliance Noted:Placement of Dam Filter Matl of Density Less than Specified
ML19207B536
Person / Time
Site: Cherokee  
Issue date: 06/27/1979
From: Conlon T, Lenahan J
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
To:
Shared Package
ML19207B521 List:
References
50-491-79-10, 50-492-79-10, 50-493-79-10, NUDOCS 7908300149
Download: ML19207B536 (3)


Text

>R Rf Cg

UNITED STATES

'

! j )", ff( 'g NUCLEAR REGULATORY COMMISSION

.

'//

c REGION 11 s/\\

o, Q' W...../

f*

101 MARIETTA sT., N.W., SUITE 3100 ATL ANT A, GEORGI A 30303 g

Report Nos. 50-491/79-10, 50-492/79-10, and 50-493/79-10 Licensee: Duke Power Company P. O. Box 33189 Charlotte, North Carolina 28242 Facility Name:

Cherokee Units 1, 2, and 3 License Nos. CPPR-167, CPPR-168, and CPPR-169 Inspection at:

Cherokee site near Gaffney, South Carolina C:"G 4/27/77 Inspector:

J. J. Lenahan Date Signed d-/27!7?

Approved by:M[

n w T. E. Conlon, Section Chief, RC&ES Branch Date signed SUMMARY Inspection on June 12-13, 1979 Areas Inspected This routine unannounced inspection involved 12 inspector-hours onsite in the areas of NSW dam construction work performance and quality records, licensee actions on previous inspection findings, and construction status.

Results:

Of the three areas inspected, no apparent items of noncompliance or deviation were identified in two areas; one apparent item of noncompliance was found in one area (Infraction - Placement of NSW dam filter materials of density less than specified paragraph 3)

852 \\6\\

/7 7908300

-

.

.

DETAILS 1.

Persons Contacted Licensee Employees

  • C. B. Aycock, Project Engineer, Construction
  • J. W. Willis, Senior QA Enigneer
  • K. W. Schmidt, QA Engineer B. R. Justice, QA Engineer
  • W. H. Linsey, Project Geotechnical Engineer Other Organizations Law Engineering Testing Company G. Weekly, Geotechnical Engineer
  • Attended exit interview 2.

Exit Interview The inspection scope and findings were summarized on June 13, 1979 with those persons indicated in Paragraph I above. The licensee acknowledged the noncompliance discussed in paragraph 3.

3.

Licensee Action on Previous Inspection Findings (Closed) Unresolved Item 491/79-09-02, 492/79-08-2 and 493/79-08-02: Relative Density Testing - NSW Dam. Cherokee Specification No. CKS-1114.00-00-0001 requires that filter materials be compacted to a minimum of 80 percent rela-tive density. The licensee has reviewed the test method (ASTM D 1556) used to verify that the filter materials are compacted to at least 80 percent relative density. This review disclosed that an error was made in performance of the quality control test which resulted in compaction of filter materials to less than the minimum specified density. This item is closed as Unresolved Item 491/492/493/79-09-02 and upgraded to Infraction Number 491/79-10-01, 492/79-10-01, and 493/79-10-01, " Placement of NSW Dam. Filter Materials at Densities Less than Specified."

4.

Unresolved Items Unresolved items were not identified during this inspection.

5.

Independent Inspection Effort The inspector examined the following areas:

162 a.

Construction status

.

-

.

s-2-b.

Concrete batch plant Partial placement of pour number CK-555 in the Unit 1 Reactor Building c.

shield wall.

No deviations or items of noncompliance were identified.

6.

I.akes Dans and Canals - Review of Quality Records, Units 1, 2, and 3 The inspector examined quality records for the fine, coarse and transition filter materials placed in the NSW dam. Acceptance criteria examined by the inspector include PSAR Section 2.5.5 and Appendix 2A, SER Section 2.5.5, SER Supplement No. 1 Section 2.5.3, Specification CKS 1114.00-00-0001, Procedure M-1, M-26, and CKB-21 and Drawing Numbers CK-0026-01 to CK-0026-06.

Records examined were:

Corrected results of field density tests (Sand Cone Method) performed a.

on coare, fine, and transition core materials which have been placed to date in the NSW dam.

b.

Logs of borings drilled at Stations 15 + 12, 15 + 22, and 15 + 72 in the fine filter portion of the chimney drain in the NSW dam.

As a result of questions raised by the inspector in Unresolved Item 491/492/493/79-09-02, the licensee made a review of laboratory and field test procedures to verify the accuracy of sand cone test results (ASTM D 1556). This review disclosed that an incorrect value was used for the bulk density of the standard sand used in the sand cone test.

The sand cone field density test results were recalculated using the correct value for the bulk density. Review of the revised density test results and discussions with responsible engineers disclosed that the revised QC test results indicate that approximately 30 percent of the fine filter material and 50 percent of the transition filter material were compacted to less than the required 80 percent relative density.

As discussed in paragraph 3, this was identified to the licensee as a noncompliance.

Due to the problem discussed above the licensee has under taken an investigation to determine the insita density of the filter materials which have been placed to date. This investigation includes additional in place density tests and drilling of borings and performance of standard penetration tests.

On June 9,1979, the license stopped fill placement in all areas of the NSW dam which contain filter materials. Other area of the dam are not affected since acceptance criteria for other types of fill is based on the drive cylinder method (ASTM D 2937). The licensee will notify NRC Region II prior to resuming work in areas where the filter materials are in place.

2 %3 No deviations were identified.