IR 05000482/2020012

From kanterella
Jump to navigation Jump to search
Triennial Fire Protection Inspection Report 05000482/2020012
ML20324A078
Person / Time
Site: Wolf Creek 
Issue date: 11/19/2020
From: Nick Taylor
NRC/RGN-IV/DRS/EB-2
To: Reasoner C
Wolf Creek
References
IR 2020012
Download: ML20324A078 (11)


Text

November 19, 2020

SUBJECT:

WOLF CREEK GENERATING STATION - TRIENNIAL FIRE PROTECTION INSPECTION REPORT 05000482/2020012

Dear Mr. Reasoner:

On November 5, 2020, the U.S. Nuclear Regulatory Commission (NRC) completed an inspection at Wolf Creek Generating Station. On November 5, 2020, the NRC inspectors discussed the results of this inspection with Mr. J. McCoy, Site Vice-President, and other members of your staff. The results of this inspection are documented in the enclosed report.

No findings or violations of more than minor significance were identified during this inspection.

This letter, its enclosure, and your response (if any) will be made available for public inspection and copying at http://www.nrc.gov/reading-rm/adams.html and at the NRC Public Document Room in accordance with Title 10 of the Code of Federal Regulations 2.390, Public Inspections, Exemptions, Requests for Withholding.

Sincerely, Nicholas H. Taylor, Chief Engineering Branch 2 Division of Reactor Safety

Docket No. 05000482 License No. NPF-42

Enclosure:

As stated

Inspection Report

Docket Number:

05000482

License Number:

NPF-42

Report Number:

05000482/2020012

Enterprise Identifier: I-2020-012-0018

Licensee:

Wolf Creek Nuclear Operating Company

Facility:

Wolf Creek Generating Station

Location:

Burlington, Kansas

Inspection Dates:

October 19, 2020 to November 5, 2020

Inspectors:

S. Alferink, Reactor Inspector

S. Graves, Senior Reactor Inspector

J. Mateychick, Senior Reactor Inspector

Approved By:

Nicholas H. Taylor, Chief

Engineering Branch 2

Division of Reactor Safety

SUMMARY

The U.S. Nuclear Regulatory Commission (NRC) continued monitoring the licensees performance by conducting a triennial fire protection inspection at Wolf Creek Generating Station, in accordance with the Reactor Oversight Process. The Reactor Oversight Process is the NRCs program for overseeing the safe operation of commercial nuclear power reactors.

Refer to https://www.nrc.gov/reactors/operating/oversight.html for more information.

List of Findings and Violations

No findings or violations of more than minor significance were identified.

Additional Tracking Items

None.

INSPECTION SCOPES

Inspections were conducted using the appropriate portions of the inspection procedures (IPs) in effect at the beginning of the inspection unless otherwise noted. Currently approved IPs with their attached revision histories are located on the public website at http://www.nrc.gov/reading-rm/doc-collections/insp-manual/inspection-procedure/index.html. Samples were declared complete when the IP requirements most appropriate to the inspection activity were met consistent with Inspection Manual Chapter (IMC) 2515, Light-Water Reactor Inspection Program - Operations Phase. The inspectors reviewed selected procedures and records, observed activities, and interviewed personnel to assess licensee performance and compliance with Commission rules and regulations, license conditions, site procedures, and standards.

Starting on March 20, 2020, in response to the National Emergency declared by the President of the United States on the public health risks of the coronavirus (COVID-19), inspectors were directed to begin telework. In addition, regional baseline inspections were evaluated to determine if all or a portion of the objectives and requirements stated in the IP could be performed remotely. If the inspections could be performed remotely, they were conducted per the applicable IP. In some cases, portions of an IP were completed remotely and on site. The inspections documented below met the objectives and requirements for completion of the IP.

REACTOR SAFETY

71111.21N.05 - Fire Protection Team Inspection (FPTI) Structures, Systems, and Components (SSCs) Credited for Fire Prevention, Detection, Suppression, or Post-Fire Safe Shutdown Review (IP Section 03.01)

The inspectors verified that the following systems credited in the approved fire protection program could perform their licensing basis function:

(1) Auxiliary feedwater system and the steam generator power operated relief valves
(2) Fire water system including the fire pumps and the yard loop distribution piping
(3) Fire protection features including fire detection system and Halon suppression system in Fire Area C-10, ESF Switchgear Room (South)
(4) Fire protection features including fire detection system and Halon suppression system in Fire Area A-18, Auxiliary Building - 2026' Elevation, Electrical Penetration Room (North)

Fire Protection Program Administrative Controls (IP Section 03.02) (2 Samples)

The inspectors verified that the following fire protection program administrative controls were implemented in accordance with the current licensing basis:

(1) The licensees administrative controls of hot work, transient combustibles, fire impairments, control of modifications, and control of procedure revisions
(2) The licensees fire brigade training program

Fire Protection Program Changes/Modifications (IP Section 03.03) (2 Samples)

The inspectors reviewed the following changes to ensure that they did not constitute an adverse effect on the ability to safely shutdown post-fire and to verify that fire protection program documents and procedures affected by the changes were updated:

(1) Revisions to Procedures OFN RP-17, Control Room Evacuation, and OFN RP-17A, Hot Standby to Cold Shutdown from Outside the Control Room due to Fire, including corrective actions for NCV 05000482/2017008-01, Inadequate Evaluation of Spurious Valve Operation, (Agencywide Documents Access and Management System (ADAMS) Accession No. ML17325A098)
(2) Modification of control circuits for the pressurizer power operated relief valves isolation valves (BBHV8000A and BBHV8000B) as a corrective action for NCV 05000482/2017008-01, Inadequate Evaluation of Spurious Valve Operation, (ADAMS Accession No. ML17325A098)

INSPECTION RESULTS

No findings were identified.

EXIT MEETINGS AND DEBRIEFS

The inspectors verified no proprietary information was retained or documented in this report.

  • On November 5, 2020, the inspectors presented the triennial fire protection inspection results to Mr. J. McCoy, Site Vice-President, and other members of the licensee staff.

DOCUMENTS REVIEWED

Inspection

Procedure

Type

Designation

Description or Title

Revision or

Date

71111.21N.05 Calculations

AN 98-023

WCGS Fire Risk Evaluation Re-Analysis

E-1F9900

Post-Fire Safe Shutdown Operator Manual Actions

E-1F9910

Post-Fire Safe Shutdown Area Analysis

E-1F9915

Design Basis Document for OFN RP-017

KC-M-0006

Water-Based Fire Protection System and Standpipe System

Hydraulic Calculation

SA-08-006

RETRAN-3D Post-Fire Safe Shutdown (PFSSD)

Consequence Evaluation for a Postulated Control Room

Fire

WCNOC-CP-002

Wolf Creek Fire Protection Transient Analysis with

RETRAN-3D

XX-E-013

Post-Fire Safe Shutdown (PFSSD) Analysis

Corrective Action

Documents

Condition

Reports

116489, 116786, 116831, 143808, 116410, 116786,

116829, 116831, 126394, 125836, 012907, 135530, 132829

Corrective Action

Documents

Resulting from

Inspection

Condition

Reports

145789, 145801, 145802, 145803, 145816

Drawings

771661

Schematic & Interconnection Diagram 2 Zone Halon

A888-M153

F

25-M-0CFF01,

Sheet 1

Site Fire Protection Yard Loop

E-1F1401

Fire Detection/Protection System - Auxiliary Building

El. 20206' - 0"

E-1F3301

Fire Detection/Protection System Control Building and

Communications Corridor - El. 2000' - 0" & El. 2016' - 0"

M-0023, Sheet 1

P&ID Fire Protection System (FP)

M-0023, Sheet 2

P&ID Fire Protection System (FP)

M-12KC01

Piping & Instrumentation Diagram Fire Protection Turbine

Building

M-12KC02

Piping & Instrumentation Diagram Fire Protection System

M-12KC04

Piping and Instrumentation Diagram Fire Protection Halon

Inspection

Procedure

Type

Designation

Description or Title

Revision or

Date

System

M-12KCO7

Piping and Instrumentation Diagram Fire Protection Halon

System

M0-0023, Sheet 7 P&ID Fire Protection System (FP) Temporary Fire Pump

Installation & Operation Requirement

M650A

Standardized Nuclear Unit Power Plant System SNUPPS

WCNOC-102

OFN RP-017 Emergency Lighting Path Drawing

Level 1974'-0"

WCNOC-102A

OFN RP-017 Emergency Lighting Drawing Level 1984'-0"

and 1988'-0"

WCNOC-102B

OFN RP-017 Emergency Lighting Path Drawing

Level 2000'-0"

WCNOC-102C

OFN RP-017 Emergency Lighting Path Drawing

Level 2015'-0" and 2016'-0"

WCNOC-102D

OFN RP-017 Emergency Lighting Path Dearing Level 2026',

2032' and 2033'

WCNOC-102E

OFN RP-017 Emergency Lighting Path Drawing

Level 2047'-6"

Engineering

Changes

20035

PORV Block Valve and Other Procedural Changes for

PFSSD

20191

BBHV8000A-B PFSSD Modification to Address IN 92-18

Engineering

Evaluations

20178

Fire Protection Underground Pipe Coating Requirements

20416

MOV Pressure Boundary Extent of Condition Evaluation for

PFSSD Control Room Fire (Ref. CD 116831)

E-1F9905

Fire Hazards Analysis

Miscellaneous

Fire Protection Program Regulatory Bases

Fire Protection Program Health Report

08/25/2020

Fire Brigade Training Drill Performance Log 2017 - 2020

Summary of Drill Performance Issues

10/19/2020

Fire Protection Impairment Approved/Posted Permits

10/19/2020

IRIS Operating Experience List

10/19/2020

Fire Protection Program Health Report

01/27/2020

AIF 10-001-01

Fire Brigade Equipment Inventory and Inspection

09/23/2020

Inspection

Procedure

Type

Designation

Description or Title

Revision or

Date

AIF 10-001-02

SCBA Inspection

08/31/2020

APF 10-105-02

Fire Drill Scenario and Critique Report

08/05/2020

APF 10-105-02

Fire Drill Scenario and Critique Report

07/24/2020

APF 28D-001-02

WCNOC Committed NFPA Codes

NA

FB 1231400

Initial Fire Brigade Training Manual

M-10KC

System Description Fire Protection Systems (KC & FP)

TCMP-20-0030

Transient Combustible Materials Permit

08/12/2020

TCMP-20-0033

Transient Combustible Materials Permit

08/21/2020

TISP-20-0067

Transient Ignition Source Permit

09/16/2020

TISP-20-0070

Transient Ignition Source Permit

09/28/2020

Updated Safety

Analysis Report,

Section 9.5.1

Fire Protection Systems

WCLR-14

Fire Water System B2.1.13 NUREG-1891 Program XI.M27

Aging Management Program

WCLR-15

Fire Protection B2.1.12 NUREG-1801 Program XI.M26

Aging Management Program

WCLR-34

Buried Piping and Tanks Inspection B2.1.18 NUREG 18-1

Program XI.M34 Aging Management Program

WCLR-35

Selective Leaching of Materials B2.1.17 NUREG 1801

Program XI.M33 Aging Management Program

Procedures

AI 10-001

Fire Brigade Equipment Inventory, Maintenance And

Cleaning

13A

AI 10-001

Fire Brigade Equipment Inventory, Maintenance And

Cleaning

13A

AI 21-017

Timed Fire Protection Actions Validation

AP 05-005

Design, Implementation, and Configuration Control of

Modifications

AP 05-008

Fire Protection Review

AP 10-002

Fire Protection Quality Program Requirements

9A

AP 10-100

Fire Protection Program

AP 10-101

Control of Transient Ignition Sources

AP 10-102

Control of Combustible Materials

Inspection

Procedure

Type

Designation

Description or Title

Revision or

Date

AP 10-103

Fire Protection Impairment Control

AP 10-104

Breach Authorization

AP 10-106

Fire Preplans

AP 10-109

Fire Protection Inspections

AP 15C-004

Preparation, Review and Approval of Procedures,

Instructions and Forms

53A

AP 22C-003

On-Line Nuclear Safety and Generation Risk Assessment

AP 23I-003

License Renewal Implementation

0A

FB 1231400

Initial Fire Brigade Training Manual

FB1231421

Fire Brigade Orientation, Fire Prevention Policies, Thermal

Protective Clothing and Fire Behavior

01/22/2020

INC AL-0010

Turbine Driven Auxiliary Feedwater Pump to Steam

Generator B Flow Loop AL LPF-0010

IP-ENG-001

Standard Design Process

MGE LT-008

Routine Electrical Limitorque Operator Maintenance

8A

MPM LT-001

Limitorque Operator Minor Maintenance, Lubrication, and

Inspection

OFN KC-016

Fire Response

OFN RP-17

Control Room Evacuation

OFN RP-17A

Hot Standby to Cold Shutdown from Outside the Control

Room Due to Fire

STN FP-202

Yard Loop & Hydrant Flush & Hydrant Inspection

STN FP-204

Fire Protection System C-Factor Test

STN FP-209

Fire Pump Performance and Sequential Start Test

31, 33

STN FP-211

Diesel Fire Pump 1FP01PB Monthly Operation and Fuel

Level Check

STN FP-212

Electric Motor Driven Fire Pump 1FP01PA Monthly

Operation

STN FP-401B

Halon System/ESF Switchgear Room 2 (KC-222)

5, 6

STN FP-404A

Halon Main Bank Tank Weight and Pressure Checks

11A

STN FP-404B

Halon Reserve Bank Tank Weight and Pressure Checks

11A

STN FP-405A

Halon System North Electrical Penetration Room (KC-224)

0A

STN FP-450

Fire Damper Inspection and Drop Test

Inspection

Procedure

Type

Designation

Description or Title

Revision or

Date

STN FP-452

Fire Barrier Penetration Seals Inspection

STN FP-817A

Trip Act. Device Oper. Test for Bechtel Zones 100, 103,

104, 105, 106, 107, 112, 113 and114

11B

STN FP-817F

Trip Act. Device Oper. Test for Bechtel Zones 306, 307, and

314-317

8B

STS IC-507C

Steam Generator Steam Line Pressure Balance of Plant

Channel Calibration

STS IC-565

Auxiliary Feedwater Pump Suction Pressure Indication for

Remote Shutdown Pressure Channel Calibration

Work Orders

03-248394-000, 10-323339-011, 10-323339-014, 10-

27878-000, 10-327887-000, 10-327888-000, 10-327899-

000, 15-396705-000, 15-396706-000, 15-396709-000, 15-

396748-000, 15-396749-000, 15-396753-000, 16-414781-

144, 17-422881-000, 17-427606-000, 18-435133-000, 18-

435653-000, 18-442172-000, 18-443690-084, 18-444963-

000, 18-445340-000, 18-446390-083, 18-446395-000, 18-

447279-000, 19-448738-000, 19-448843-000, 19-448878-

000, 19-448879-000, 19-448882-000, 19-450628-000, 19-

2962-000, 19-453068-000, 19-454695-000, 19-454737-

000, 19-454807-000, 19-454812-000, 20-457462-000, 20-

457796-000, 20-458199-000, 20-458286-000