IR 05000373/1987003

From kanterella
Jump to navigation Jump to search
Forwards Rh Lasky Findings from Special Environ Qualification Insp on 870202-06 for Input to Insp Repts 50-373/87-03 & 50-374/87-04.Insp Checkoff Sheets Also Encl
ML20212J092
Person / Time
Site: LaSalle  
Issue date: 03/04/1987
From: Merschoff E
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE)
To: Harrison J
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
References
NUDOCS 8703060309
Download: ML20212J092 (20)


Text

.e UNITED STATES

'#

%,

NUCLEAR REGULATORY COMMISSION

,

o

s wasHmorow.o.c.coess

March 4, 1987

l'EMORANDUM FOR:

John J. Harrison, Chief Engineering Branch Division of Reactor Safety Region III FROM:

Ellis W. Merschoff, Acting Chief Vendor Program Branch Division of Quality Assurance, Vendor and Technical Training Center Programs Office of Inspection and Enforcement SUBJECT:

INPUT FOR THE LASALLE EQUIPMENT QUALIFICATION PEPORT (50-373/8703 AND 50-374/8704)

Enclosed are the findings of Mr. R. H. Lasky from the Special Environmental Qualification Team inspection conducted by Mr. A. S. Gautan, Region III, and other NRC representatives on February 2-6, 1987, at LaSalle Nuclear Power Station. The findings and comments are enclosed in Appendix A.

Inspection checkoff sheets are enclosed in Appendix B.

Should you have any cuestions concerning this correspondence, we will be pleased to discuss them with you.

Sincerely, W

}

Ellis W. Merschoff, Acting Chief Vendor Prooram Branch Division of Quality Assurance, Vendor and Technical Training Center Prograns Office of Inspection and Enforcement Enclosures:

1.

Appendix A-Report of Findings and Comments 2.

Appendix B-Inspection Checkoff Sheets (24 pages)

cc w/cnclosures:

A. S. Gautan, RIII 0703060309 B70304 PDR ADOCK 05000373 G

PDH

.

_ -

_

.

kI J

6t John.J. Harrison, Chief.

2-March 4, 1987

,

6 4s:(60-373/374) 'O PnO On 0-DISTRIBUTION:

VUB VPB Reading 00AVT Readir.g JTaylor BGrimes'

HMiller EMerschoff UPotapovs Plasky

!

..

f b

/

<f VV f 'V)B:DOAVT

-

~

'

rVPBESCAVT SC/VPB:DQAVT ABC/

RLasky:tt UPotapovs EMerschoff

'

j 3/$/87

}/3/87 3 /g /87

!

i

.o

...

APPENDIX A INSPECTION FINDINGS AND COMMENTS A.

Findings:

1.

EQ Master List did not list Rosemount transmitter 2B21-N4020 for Unit 2.

Licensee has initiated a chance to add transmitter 2821-N402D to the EQ Faster List.

2.

EQ Master List gives Environrental Zone H4 for some of the equipment.

The Environmental Zone should be H4A. Licensee has initiated a change to correct the EQ Master List.

-3.

File binder EQ-LS027 for Rosemount model 1153 series B transmitters did not properly address plant specific recuired transmitter accuracies. The licensee was able to establish usiag other documents that transmitter accuracies demonstrated during E0 testing were adequate for LaSalle. The licensee has committed to changing file EQ-L5027 to address plant specific accuracy requirements.

B.

Comments of Equipment Qualification Files:

1.

Binder EQ-LS027, Rosemount Model 1153 series B transmitters.

File was found deficient in that plant specific required transmitter accuracies were not addressed.

See finding A.3.

Supplemental information supplied by licensee showed adeouate cualification of transmitters.

2.

Binder EQ-LS027, GE pump notor, Model 5K6339XC109A File indicated that submergence of motors was not applicable but discussions with the licensee indicated that the motors could become submerged.

FSAR, Amendment 64, May 1984, Section 3.11.1.4.2c, states that the flooding threat of areas where the pumps are located is not directly connected to the accidents used to establish harsh environmental zones at the plant. Per the FSAR, flooding is not a E0 consideration.

3.

Binder E0-LS021 ITT General, Damper Actuator, model NH41. Adequate qualification was shown by this file.

4.

Binder EQ-LS069, Reliance Pump Motor, Model 184T.

Adequate qualification was shown by this file.

5.

Binder EQ-LS078, Reliance Pump Motor, Model 365T.

Adequate qualification was shown by this file.

6.

Binder E0-LS056, Westinghouse Motor, model 182T. Adecuate qualification was shown by this file.

i 7.

Binder EQ-LS059, Sierens Motor / Blower, rodel 2CH6 modified by GE. Adequate qualification was shown by this file.

.

.

-

.

_-.

.

.-..-

.

_

...

..

i

.

-2-8.

Binder EQ-L5035, Validyne Model P232 transmitter. Adequate

~ qualification was shown by this file.

C.

Comments on Plant Walkdown:

1.

_ The following items were examined during the plant walkdown:

a.

Rosemount-Transmitters:

1)

2B21-N4020 2)

2C11-N016B 3)

2PT-CM028 4)

2ER-N007A 5)

2CM-032,-Rosemount seal only 6)

2E21-N006A, Rcsemnunt seal only 7)

2E51-N003, Rosencunt seal only b.

Reliance Motors:

2EB51 C003

2C41 C001A c.

GE Motor, 1E12 C002A d.

Validyne transmitter, 2VG009FT e.

' Westinghouse motor, 2VG02C f.

Siemens Potor/ Blowers 1)

2E32-C001 2)

2E32-C002 All items examined during the plant walkdown appeared to be generally well naintained and in good condition. No deficient conditions were noted.

D.

General Inspection Comments:

1.

Files were auditable and appeared well maintained. The major concern with the files examined was the handling of the submergence issue.

Submergence was mentioned in most files but was not discussed in enough detail te give the inspector confidence that the issue was adequately considered by the licensee. See comment B.2.

2.

Master List findings A.1 and A.2 were not considered to be a generic concerns with respect to accuracy and adequacy of the lis O

.

-

APPENDIX B

-

CHECKLIST FOR REVIEW 0F LICENSEE EQ DOCUMENTATION FILES This chekkTist. is provided. for use in performing evaluations of the ade-Such reviews quacy of a qualification package for a piece of equipment.

will determine the adequacy of the EQ program for the device and will determine the adequacy of the licensee's review and approval process for the equipment.

Perform a complete review for one file.

For other files, items not reviewed should be marked "N/A" in Comments Column.

5'o-7 73/97 c 3 Plant / Docket No.:

So-3W/8)oy Reviewer:

Za.s dy

.

Component (s):

RosewouvY, Mode l /153 Senes "8 "

Equipment Documentation File:

b der A/e. Ed - /S O 2 7 Criteria: 10 CFR 50.49 i or 00R Guidelines or Other

_

puRES 0T/8 caf.T Covered in EQ Occumentation

.

'

EQ Issue Yes g

Comments 1.

Positive statement by the Y

licensee that the equipment is qualified for its application.

2.

Full description of the Z_

equipment.

'

.

3.

If qualification sample is X

not identical to. the instal-led devices, a similarity analysis has been provided.

4.

Allowed mounting methods and K

orientations.

l 5.

Interfaces - conduit, housing N

seal, etc.

6.

A qualified life has been

established based on accel-

erated aging-thermal,

radiation, cyclic, as appropriate.

,

7.

All type tests performed Y

on the same specimen (N/A 00R Guidelines).

l l

Appendix B, 2515 B-1 Issue Date:

03/27/86 I-

-

_ _ _ _

_ _. _ _ _ _.

_ _ __ ____ _ _

_

,

__

_

o

.

.

.

TRANSMITTER PHYSICAL INSPECTION CHECKLIST Component 10 No.:

(EE BElote.)

Reviewer:

/MtV

]

Installed Condition Acrees with Occumented Yes No Comments Documented Information 1.

Location

.

81dg.

Room Elev

,_Y_

2.

Nanutacturer Pesemov af A

_,,,,

3.a.

Model No.

//f ? reriks '8"

<

,

b.

Range / Type Coda

,,_,

_

c.

Serial No.

/A4 + f, /e

_

X 4.

Mounting Description

. ~ h d

.wR suaW h raale t 5.

Orientation A/

crAca/

P X

6.

Process Connection Type

-

m et Laweal

_

A 7.

Electrical Connection Type i

l 8.

Housing Seals in Good Condition, I

_

Covers in Place (If yes, review I

9.

Does Installed Device Experience

_

documentation to

_

a Significant Temperature Rise determine whether from Process?

considered)

(If ambient temp-i Ambient Normal Expected Temperature

'

10.

erature exceeds

__

Range normal expected, l

l verify that quali-l fied life evalu-ation considered)

General Comments on Physical Inspection:

p,y,(g,g pg]pg[

QM roS.7o)

2821 - Attfo g a. z y t

t15 ? &Bf

- D 014 8 - PT ps my usnc 2 Cll ne-pr e a, -

ac:aer p,,,,3 2 ea - um - er n...as, c 9515

--

l

.

. - ~

.

.

.

.

.

.

_ _ _ _

_

_ _ _ _.... _. _.. - _ _. _ _ _ _ _.. __

. _.. _ _. _ _

_

-

-

-

.

.

APPENDIX 8

-

'

-

CHECKLIST FOR REVIEW 0F LICENSEE EQ DOCUMENTATION FILES This chetiffst. is provided. for use in performing evaluations of the ade-quacy of a cualification package for a piece of equipment.

Such reviews will determine the adequacy of the EQ program for the device and will determine the adequacy of the licensee's review and approval process for the equipment.

Perform a complete review for one file.

For other files, items not reviewed should be marked "N/A" in Comments Column.

S~o ~ 3 73/ $702 Plant / Docket No.:

50 - 3'7W 6?oV Reviewer:

Z A ~Ey

,

Component (s):

6E Pu. w p /fo /o r

'

Equipment Documentation File:

L der No.

Go - 25 aog Criteria:

10 CFR 50.49 X

or D0R Guidelines or Other

~

NARC 6 orge cd 1~.

Covered in EQ Documentation

.

'

EQ Issue Yes No Comments

!

1.

Positive statement by the X

licensee that the equipment is qualified for its application.

,

l 2.

Full description of the L

equipment.

l l

3.

If qualification sample is

not identical to.the instal-led devices, a similarity analysis has been provided.

4.

Allowed mounting methods and X"

_

orientations.

5.

Interfaces - conduit, housing JC seal, etc.

<

6.

A qualified life has been

_

established based on accel-l

!

erated aging-thermal,

radiation, cyclic, as I

appropriate.

7.

All type tests performed

[_

on the same specimen (N/A 00R Guidelines).

Appendix B, 2515 B-1 Issue Date: 03/21<86

- -. - - -

_ - -.

-

- - - -. -

-

-.

-

. - -

-..

-

-

___

ELECTRIC MOTOR PHYSICAL INSPECTION CHECKLIST

]

Component ID:

2 H/0 - E/2 c oc 2A Reviewer:

'"

Installed Condition

'

Aarees with Documented Yes No'

Comments Documented Information

.

1.

Location Bldg Room Elev

%

_

'

2.

Nanufacturer GE X

3.a.

Nodel No.

SG339/Clo?A

'K

,

b.

Serial No.

_

c.

Voltage vooo HP 600 L

_

4.

Mounting and Orientation d

tier h eal

.

5.

Accessories

.

Coolers

_

Lubricant Reservoirs o e '/

Heaters IAtM

_

s X

6.

Housing Seals and Covers _

in Place and Tight 7.

Area Surrounding Motor is

%

Clean and Dry 8.

Ambient Normal Expected

~_

Temperature Range 9.a.

Junction Box Type 2$

b.

Orainage Method d

General Comments on Physical Inspection:

Issue Date: 03/27/86 C-6 Apcendix C, 2515

--. - -.-...

-. -.

-

-

...-

.

-

_ __ _. _ - _ -

-

-

._

,

APPENDIX B

-

CHECKLIST FOR REVIEW OF LICENSEE EQ DOCUMENTATION FILES This chetkTist. is provided. for use in performing evaluations of the ade-quacy of a qualification package for a piece of equipment.

Such reviews will oetermine the adequacy of the EQ program for the device and will

' determine the adequacy of the licensee's review and approval process for the equipment.

Perform a complete review for one file.

For other files, items not reviewed should be marked "N/A" in Comments Column.

C0-???/97o2 Plant / Docket No.:

90 ?7y/e7o y Reviewer:

z'A LF v'

Component (s):

TTT Geeerol Dwper AeGh<

'

Equipment Documentation File:

E der A/o.

Ed -4502 /

Criteria:

10 CFR 50.49

'/

or 00R Guidelines or Other

_

pvRE& O::8R ca1. I Covered in EQ Documentation EQ Issue Yes No Comments

~

\\

1.

Positive statement by the

'<

l licensee that the equipment

-

is qualified for its application.

2.

Full description of the X

_

equipment.

3.

If qualification sample is

_M not identical to the instal-I led devices, a similarity analysis has been provided.

4.

Allowed mounting methods and M

orientations.

5.

Interfaces - conduit, housing

_

seal, etc.

6.

A qualified life has been

_Y established based on accel-

,

erated aging-thermal, radiation, cyclic, as appropriate.

,

7.

All type tests performed on the same specimen (N/A 00R Guidelines).

Appendix B, 2515 8-1 Issue Date: 0,1/27/86

-.

. _ _.

.__ -

. _. - - - _ _ _. _ _ _ -

-

-

.

-

-

-

.

.

'

EQUIPMENT DESCRIPTION

'

-

Component ID:

2F1-VGoo3 Revfewer:

Installed Condition

.-

,,-

-

Aareas with Documented Documented Information Yes No Comments 1.

Location Bldg Room _ Elev

'

2.

Manufacturer ITT 6emea/

{

3.a.

Model No.

Mll 9 /

~ ~ ~

p(ikfX/4 8 J

..

-

-

b.

Serial No.

4.

Mounting Description

-

be>lled 5.

Orientation aleelncal

~

cowarL-ed (sees up sc h kr ce-kr^~e ee oe.neoe por,z 4 1 6.

Process Connection Type 7.

Electrical Connection Type m

8.

Housing Seals in Good Condition,

.

Covers in Place 9.

Does Installed Device Experience (If yes, document-a Significant Temperature Rise ation must be from Process?

reviewed to deter-mine if the temper-ature rise was

'

considered)

(

10. Ambient Normal Expected (If ambient temp-l Temperature Range erature exceeds normal expected i

conditions, verify that licensee has considered the

,

elevated tempera-

'

-

ture in the qualified

,

'

life evaluation)

General Comments on Physical Inspection:

l Issue Date:

03/27/86 C-8 Appendix C, 2515 I

.. _.

__

,_.,____

.._.__ -

_

_,_ _,____.. -,- -.- _ -. -.

. -..

.

. _ _ -

-.

, - _

_

_ _ _ _ _ _ _ _ _ _ _

i

'

-

APPENDIX 8

-

CHECKLIST FOR REVIEW 0F LICENSEE EQ DOCUMENTATION FILES This chekk7fst. is provided. for use in performing evaluations of the ade-quacy of a qualification package for a piece of equipment.

Such reviews will determine the adequacy of the EQ program for the device and will determine the adequacy of the licensee's review and approval process for the equipment.

Perform a complete review for one file.

For other files, items not reviewed should be marked "N/A" in Comments Column.

So - r7W 9702 Plant /Occket No.:

re 3 N / sp o a/

Reviewer:

2 4 ff y'

,

Component (s):

Re/due. L a Mobr

Equipment Documentation File:

Bsdar Ed-250(9 Criteria: 10 CFR 50.49

)(

or 00R Guidelines or Other DtrRE6 Of88 Cod I Covered in EQ Documentation

.

'

Yes M

Comments EQ Issue 1.

Positive statement by the g

licensee that the equipment is qualified for its application.

2.

Full description of the

$

equipment.

A 3.

If qualification sample is

_

not identical to the instal-led devices, a similarity analysis has been provided.

X 4.

Allowed mounting methods and orientations.

5.

Interfaces - conduit, housing d

seal, etc.

Y 6.

A qualified life has been

_

established based on accel-erated aging-thermal,

,

radiation, cyclic, as approprictc.

,

7.

All type tests performed

_

on the same specimen (N/A 00R Guidelines).

Appendix 8, 2515 8-1 Issue Date:

03/27/86

._.

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _.

_ _ - - -

.

,

-

' ELECTRIC MOTOR PHYSICAL INSPECTION CHECKLIST

MNV

]

Component 10:

2 E8 sl C003 - #10 Reviewer:

Installed Condition Agrees with Documented Yes No Comments Documented Information

.

1.

Location 81dg Room _ Elev K

i I

2.

Manufacturer d e /li n e-A 3.a.

Model No.

/ 8 4 T, SP, Ph

'N

_

,

_

b.

Scrial No.

_

Voltage %'d HP 7,$~

I c.

.

4.

Mounting and Orientation d

Nor/ 20 h$k l 5.

Accessories

,

_

-

-

Coolers

_

_

,

Lubricant Reservoirs J

i

_

-

^

Heaters

_

K l

6.

Housing Seals and Covers

_

in Place and Tight

,

I Y

i 7.

Area Surrounding Motor is Clean and Dry

8.

Ambient Normal Expected

_

Temperature Range

,

9.a.

Junction Box Type

_

_

b.

Orainage Method

_

General Comments on Physical Inspection:

l l

l Issue Date: 03/27/66 C-6 Apoendix C, 2515

.

.

.

,

A

'

.

<

~

'

APPENDIX B

-

-

'

-

CHECKLIST FOR REVIEW OF LICENSEE EQ DOCUMENTATION FILES

'

This chetkTTrt. is provided. fer use in performing evaluations of the ade-quacy of.s qualification package for a piece of equipment.

Such reviews will detectine the adequacy of tne EQ program for the device and will

' determine tae adequacy of the licensee's review and approval process for the equipse.nt.

Perform a complete review for one file.

For other filss, items not ruviewed should be marked "N/A" in Comments Column.

CD - 773/9?o!

Plant /Dockr.t No.:

ro-nv/270v Reviewer:

los/y Component (s):

$bb b,bu,J do J ro l Pa a.o No6

y Equipment Cocumentation File:

Ede. A'c.

Ed -2507#

'

Criteria:

10 CFR 50.49 1 or 00R Guidelines or Other i

!

nueE(, ossa ggf. T l

_

,

Covered in EQ Occumentation,

-

,

'

D) Issue Yes g

Comments 1.

Positive statement by the V

licensee that the equipment is qualified for its application.

'

'

l 2.

Full description of the I

-

'.

l equipment.

,;

/

3.

If qualification sample is I

not identic*.1 to.the instal-l led devides, a similarity analysis has been provide.d.

4.

Allowed mounting methods and K

orientations.

5.

Interfaces - conduit, housing d

seal, etc.

,

N

>

6.

A qualifigo life has been

_

establishtd based on accel-erated aging-thermal,

,;

radiation, cyclic, as appropriate _

l 7.

All type tests performed X

i on the same specimen (N/A 00R Guidelines).

l s

.

l Appendix 8, 2515 B-1 Issue Oata p3/th86

,

,. - -

- -,-

-

..n.

-n,- - - - -. -. -. - -

,,n.,

, - - -,,,.

-,-,.,._,..-._.-

, - _ - - - -., -, - - -... - - - - - - - -

,

,

___

.

-

ELECTRIC MOTOR PHYSICAL INSPECTION CHECKLIST

'

/CIy

)

Component 10:

2 cV/ coo /A Reviewer:

Installed Condition Agrees with Documented Yes g

Comments Documented Information o

.

1.

Location

<

B1dg Room _ Elev _,,_

'

2.

Manufacturer Pelaw t, f

3.a.

Model No. ?u~ 744n he-F

'I

,

Terc-xt b.

Serial No.

c.

Voltage y_f0,, HP NO

/

.

4.

Mounting and Orientation X

__

Grozok Go4 ff w h d 5.

Accessories

_ _ _

_

Coolers

__,

Lubricant Reservoirs

~_,,_

d

,_,_,

-

Heaters

-~

-

6.

Housing Seals and Covers

_,__.

in Place and Tight I

7.

Area Serrounding Motor is clean and Dry 8.

Ambient Mormal Expected Temperature Range 9 a.

Junction Box Type

_

_,,_.

b.

Orainage Method

_,

General Comments on Physical Inspection:

.

Issue Date: 03/27/86 C-6 Apoendix C, 2515

-

_

. _ _ _, _ _ _.

. _.. _, _.

- _.

_.... _ _ _ _. _ _

.

.

APPENDIX B

-

-

CHECKLIST FOR REVIEW 0F LICENSEE EQ DOCUMENTATION FILES This chetkTfst. is provided. for use in performing evaluations of the ade-quacy of a cualification package for a piece of equipment.

Such reviews will detemine the adequacy of the EQ program for the device and will

,

' determine the adequacy of the licensee's review and approval process for the equipment.

Perform a complete review for one file.

For other files, items not reviewed should be marked "N/A" in Comments Column.

To- ?? r/9103 Plant / Docket No.:

ro- ? W/ &;o Y Reviewer:

/N#f Component (s):

blesf ae, lie u se Cee/, y 5u w der

Equipment Documentation File:

&J/e.- t/o. F4 - 45056 Criteria:

10 CFR 50.49 1 or 00R Guidelines or Other Wu 2 ECr ofeo Ca.f. Z Covered in EQ Documentation

.

'

EQ Issue Yes g

Comments 1.

Positive statement by the

~X licensee that the equipment is qualified for its application.

2.

Full description of the X

_

equipment.

3.

If qualification sample is K

_

not identical to.the instal-

,

l 1ed devices, a similarity analysis has been provided.

I 4.

Allowed mounting methods and X

j orientations.

5.

Interfaces - conduit, housing

&

seal, etc.

6.

A qualified life has been N

established based on accel-

'

erated aging-thermal,

radiation, cyclic, as appropriate.

,

7.

All type tests performed

on the same specimen (N/A 00R Guidelines).

Appendix B, 2515 B-1 Issue Date-03/27/86

,

- - -

- - - - ~ -, -, - - -..

__

.

.

-

.-

ELECTRIC MOTOR PHYSICAL INSPECTION CHECKLIST Reviewer:

2MIY/

]

Component ID:

2,">:

V', cir 2tik.) ~ V6 c2c Installed Condition Agrees with Documented Documented Information Yes No'

Ccaments

.

1.

Location 81dg _ Room _ Elev

'

d kles/9 ous c.

A 2.

Manufacturer i;;,7;

.- ':.

182 Tl TBK,;~H K

3.a.

Nodel No.

.

b.

Serial No.

_

-+to--

-ce-c.

Voltage 440 HP l. 4~

d

.

4.

Mounting and Or,iegtation A

-

Henzia%/

5.

Accessories

_

_

__

-

Coolers

-

^

Lubricant Reservoirs J

~

._

Heaters

_

s A

6.

Housing Seals and Covers _

in Place and Tight A

7.

Area Surrounding Motor is Clean and Dry 8.

Ambient Normal Expected d

Temperature Range X'

9.a.

Junction Box Type

.

b.

Orainage Method A

l l

General Comments on Physical Inspection:

t

!

l l

l Issue Date: 03/27/86 C-6 Apoendix C, 2515 l

l

_-

._

-

.

-

.

-.

.-- -.

..-

.

.

_

_

_

.

-

APPENDIX B

-

.

CHECKLIST FOR REVIEW 0F LICENSEE EQ DOCUMENTATION FILES This chaut7firt. is provided. for use in performing evaluations of the ade-Such reviews quacy of a qualification package for a piece of equipment.EQ program for the

will detemine the adequacy of the

' detemine the adequacy of the licensee's review and approval process for Perform a complete review for one file.

For other files, the equipment.

items not reviewed should be marked "N/A" in Comments Column.

Eb-27.W 9763

.

Plant / Docket No.:

56-3 7 Y /9 7 W,

Reviewer:

ddSA'y Component (s):

SEENSU 5 Ho76rfffgu)gg

Equipment Documentation File:

FC L /e < /Uo. Ed-4Soff Criteria:

10 CFR 50.49 X'

or 00R Guidelines or Other

_

uu2Efr 0S88 Cd. i Covered in EQ Documentation

.

'

Yes

]!o, Comments EQ Issue 1.

Positive statement by the g_

licensee that the equipment is qualified for its application.

2.

Full description of the X

equipoent.

!

3.

If qualification sample is X

_

not identical to.the instal-

,

led devices, a similarity

'

analysis has been provided.

!

4.

Allowed mounting methods and g

orientations.

5.

Interfaces - conduit, housing

>(

seal, etc.

6.

A qualified life has been d

established based on accel-

'

erated aging-thersal,

'

radiation, cyclic, as appropriate.

,

7.

All type tests performed d

on the same specimen (N/A 00R Guidelines).

S-1 Issue Date: 03/27/86 f

Appendix 8, 2515

,

- _,

, _ - _.. - _. - _

.

- -

__

.

.. - -

-

.

..

. -.

.

. - -.

. - -

-

,-

.

.

EQdIPMENTDESCRIPTION

'

'-

-

Component ID:

2EJF - (oo /

Reviewer:

/ASA'M j

~O Installed Condition

.-

Agrees with Documented

,,,

Documented Information Yes No Comments 1.

Location 81dg Room Elev X

'

2.

Nanufacturer GIGt1FMS m),iid by GE X

3.a.

Nodel No.

2CGC,2.7oo Y

y.7Ap

,

b.

Serial No.

_

4.

Mounting Description d

~

20Hed Fee'l 5.

Orientation Aorlzo da /

X 6.

Process Connection Type

_,

WA 7.

Electrical Connection Type

><.

gey g

-

8.

Housing Seals in Good Condition,

&

-

Covers in Place 9.

Does Installed Device Experience (If yes, document-a Significant Temperature Rise ation must be from Process?

reviewed to deter-mine if the temper-ature rise was considered)

10. Ambient Normal Expected (If ambient temp-

!

Temperature Range erature exceeds normal expected

,

l conditions, verify that licensee has (

considered the

'

elevated tempera-ture in the qualified

,

'

life evaluation)

,

General Comments on Physical Inspection:

l Issue Date:

03/27/86 C-8 Appendix C, 2515

_ - -.

.

_.

-_ -

...

.

'

APPENDIX B

CHECKLIST FOR REVIEW 0F LICENSEE EQ 00CUMENTATION FILES This chetkTYst. is provided. for use in performing evaluations of the ade-quacy of a qualification package for a piece of equipment.

Such reviews will determine the adequacy of the EQ program for the device and will

~ determine the adequacy of the licensee's review and approval process for the equipment.

Perform a complete review for one file.

For other files, items not reviewed should.be marked "N/A" in Comments Column.

5D-777/ B7o?

Plant / Docket No.:

So -17 v/ 8 ?o v Reviewer:

4 A f N '/

,

Component (s):

%),J u F/w fews defer

/fede/ Pifa

y Equipment Documentation File:

3r a /er-No.

R-Z SCR Criteria: 10 CFR 50.49 y

or 00R Guidelines or other h REG 0396 cof.Z'

Covered in EQ Documentation

'

EQ Issue Yes g

Comments 1.

Positive statement by the X

licensee that the equipment is qualified for its application.

2.

Full description of the

/

_

l equipment.

'YA 3.

If qualification sample is not identical to.the instal-led devices, a similarity analysis has been provided.

4.

Allowed mounting methods and I

orientations.

!

5.

Interfaces - conduit, housing X

seal, etc.

6.

A qualified life has been A'

established based on accel-

erated aging-thermal, radiation, cyclic, as appropriate.

,

7.

All type tests performed 1_

on the same specimen (N/A 00R Guidelines).

Appendix 8, 2515 B-1 Issue Date: 03/27/86 i

._

. _ _

__ -

.

._. _ _

_

_

.. - -

e

  • '

.

.

TRANSMITTER PHYSICAL INSPECTION CHECKLIST Component 10 No.:

2 FT-VGoog Reviewer:

2AM/

Flow Trans ter Installed Condition Aarees with Occumented Yes No Comments Documented Information 1.

Location 81dg.

Room Elev h

/

2.

Manufacturer t/ah J vn g_

_

Ng

-

3.a.

Model No.

9232.

r

_

b.

Range / Type Code

,

_

c.

Serial No.

Bot

~

4.

Mounting Description

_

e rwel iVO l 5.

Orientation uaf crde ka /

gXAMIR0

~

6.

Process Connection Type

~

rne e len,e o e a. /

d 7.

Electrical Connection Type

_

a dw.f

-.

8.

Housing Seals in Good Condition,

_

Covers in Place 9.

Does Installed Device Experience (If yes, review documentation to

-

-

a Significant Temperature Rise determine whether from Process?

considered)

l 10.

Ambient Normal Expected Temperature (If ambient temp-erature exceeds

_ _

Range normal expected, verify that quali-fied life evalu-ation considered)

General Comments on Physical Inspection:

.

l l

l

.--

a. e esis

--

_ _ - -.

-

-_

.

- - _.

.

..

.

.

.

.

-

.

.

-