IR 05000259/2014003

From kanterella
(Redirected from IR 05000296/2014003)
Jump to navigation Jump to search
IR 05000259-14-003, 05000260-14-003 & 05000296-14-003, on 04/01/2014 - 06/30/2014, Browns Ferry Nuclear Plant, Units 1, 2 and 3; Flood Protection Measures
ML14212A112
Person / Time
Site: Browns Ferry  
Issue date: 07/30/2014
From: Bartley J
Reactor Projects Region 2 Branch 6
To: James Shea
Tennessee Valley Authority
References
IR-14-003
Download: ML14212A112 (46)


Text

UNITED STATES NUCLEAR REGULATORY COMMISSION uly 30, 2014

SUBJECT:

BROWNS FERRY NUCLEAR PLANT - NRC INTEGRATED INSPECTION REPORT 05000259/2014003, 05000260/2014003, AND 05000296/2014003

Dear Mr. Shea:

On June 30, 2014, the U.S. Nuclear Regulatory Commission (NRC) completed an inspection at your Browns Ferry Nuclear Plant, Units 1, 2, and 3. On July 11, 2014, the NRC inspectors discussed the results of this inspection with Mr. K. Polson and other members of your staff.

Inspectors documented the results of this inspection in the enclosed inspection report.

NRC inspectors documented one NRC identified finding which was determined to be of very low safety significance (Green) in this report. This finding did not involve a violation of NRC requirements.

Further, inspectors documented one licensee-identified violation which was determined to be of very low safety significance in this report. The NRC is treating this violation as a non-cited Violation (NCV) consistent with Section 2.3.2.a of the Enforcement Policy.

If you contest the violation or significance of the NCV, you should provide a response within 30 days of the date of this inspection report, with the basis for your denial, to the U.S. Nuclear Regulatory Commission, ATTN: Document Control Desk, Washington DC 20555-0001; with copies to the Regional Administrator, Region II; the Director, Office of Enforcement, U.S.

Nuclear Regulatory Commission, Washington, DC 20555-0001; and the NRC resident inspector at the Browns Ferry Nuclear Plant.

In addition, if you disagree with a cross-cutting aspect assignment or a finding not associated with a regulatory requirement in this report, you should provide a response within 30 days of the date of this inspection report, with the basis for your disagreement, to the Regional Administrator, Region II, and the NRC resident inspector at the Browns Ferry Nuclear Plant. In accordance with Title 10 of the Code of Federal Regulations 2.390, Public Inspections, Exemptions, Requests for Withholding, of the NRCs Rules of Practice, a copy of this letter, its enclosure, and your response (if any), will be available electronically for public inspection in the NRCs Public Document Room or from the Publicly Available Records (PARS) component of the NRCs Agencywide Documents Access and Management System (ADAMS). ADAMS is accessible from the NRC Web site at http://www.nrc.gov/reading-rm/adams.html (the Public Electronic Reading Room).

Sincerely,

/RA/

Jonathan H. Bartley, Chief Reactor Projects Branch 6 Division of Reactor Projects Docket Nos.: 50-259, 50-260, 50-296 License Nos.: DPR-33, DPR-52, DPR-68

Enclosure:

NRC Integrated Inspection Report 05000259/2014003, 05000260/2014003 and 05000296/2014003

REGION II==

Docket Nos.: 50-259, 50-260, 50-296 License Nos.: DPR-33, DPR-52, DPR-68 Report No.: 05000259/2014003, 05000260/2014003, 05000296/2014003 Licensee: Tennessee Valley Authority (TVA)

Facility: Browns Ferry Nuclear Plant, Units 1, 2, and 3 Location: Corner of Shaw and Nuclear Plant Road Athens, AL 35611 Dates: April 1, 2014, through June 30, 2014 Inspectors: D. Dumbacher, Senior Resident Inspector L. Pressley, Resident Inspector T. Stephen, Resident Inspector C. Kontz, Senior Project Engineer S. Sanchez, Senior Emergency Preparedness Inspector C. Fontana, Emergency Preparedness Inspector A. Nielsen, Senior Health Physicist R. Kellner, Health Physicist Approved by: Jonathan H. Bartley, Chief Reactor Projects Branch 6 Division of Reactor Projects Enclosure

SUMMARY

IR 05000259/2014003, 05000260/2014003, 05000296/2014003; 04/01/2014-06/30/2014;

Browns Ferry Nuclear Plant, Units 1, 2 and 3; Flood Protection Measures.

The report covered a three month period of inspection by the resident inspectors, three regional inspectors and two emergency preparedness inspectors. One NRC identified finding was identified. The significance of most findings is identified by their color (Green, White, Yellow, and Red) using Inspection Manual Chapter (IMC) 0609, Significance Determination Process (SDP); and, the cross-cutting aspects were determined using IMC 0310, Components Within the Cross-Cutting Areas. Findings for which the SDP does not apply may be Green or be assigned a severity level after NRC management review. The NRCs program for overseeing the safe operation of commercial nuclear power reactors is described in NUREG-1649, Reactor Oversight Process Revision 5, dated February 201

NRC Identified and Self-Revealing Findings

Cornerstone: Mitigating Systems

Green.

An NRC-identified finding was identified for the licensees failure to adhere to TVA General Specification 40 (G-40) for Installation, Modification, and Maintenance of Electrical Systems, section 3.5.7, which required standing water in Handholes be kept below any safety related cables. Hand hole numbers 15 and 26 were discovered to have had standing water above several of the Residual Heat Removal (RHR) service water (safety related) power cables from January to May 2014.

The licensees failure to adhere to TVA General Specification 40 (G-40) for Installation,

Modification, and Maintenance of Electrical Systems, section 3.5.7, which required standing water in hand holes be kept below any safety related cables was a performance deficiency. Specifically, the licensee allowed hand hole numbers 15 and 26 to have standing water above several of the RHR service water (safety related)power cables. The performance deficiency was more than minor because if left uncorrected, it had the potential to lead to a more significant safety concern including cable degradation and increased likelihood of cable failure. This issue screened as having very low safety significance, Green, using IMC 0609 Appendix A, Exhibit 2,

Mitigating Systems Screening Questions issued on June 19, 2012, because it affected the design or qualification of a mitigating SSC but the mitigating SSC maintained its operability. The finding had a cross cutting aspect of Problem Identification and Resolution: Resolution because the licensee failed to ensure that corrective actions addressed the cause of the power cable wetting and failure in 2007. (P.3) (Section 1R06.2)

Licensee Identified Violations

  • One violation of very low safety significance that was identified by the licensee has been reviewed by the NRC. Corrective actions taken or planned by the licensee have been entered into the licensees corrective action program (CAP). The violation and corrective action tracking number are listed in Section 4OA7 of this report.

REPORT DETAILS

Summary of Plant Status

Unit 1 operated at 100 percent of rated thermal power (RTP) except for one unplanned and two planned downpowers. The planned downpowers, each for rod sequence exchange and main condenser water box cleaning, occurred on May 9, 2014, and June 7, 2014. The unplanned downpower to 98 percent for four hours occurred on June 17, 2014, when the inoperability of both trains of the Control Room air conditioning system resulted in beginning preparations for a Technical Specifications required shutdown. The shutdown was averted when one train of the Control Room air conditioning system was restored prior to the expiration of the required action time (Event Number50207). Power remained at 100 percent for the remainder of the quarter.

Unit 2 operated at 100 percent RTP except for two unplanned and three planned downpowers.

The unplanned downpowers to 98 and 87 percent power occurred on May 10, 2014, (three days) and on June 15, 2014, due to lowering vacuum in the main condenser. The vacuum was affected by lower river flow, higher river temperature, and a partially stuck closed main condenser water box outlet valve. During the June 15 time period the unit also was impacted by the inoperability of two trains of Control Room air conditioning system (EN 50207). The unit returned to 100 percent power on June 26, 2014. The planned downpowers occurred on May 30, 2014, for repairs to the 2B Recirculation Pump Variable Frequency Drive (VFD),

June 2, 2014, for rod sequence exchange, and June 27. 2014, for main condenser water box outlet valve repair. Power remained at 100 percent for the remainder of the quarter.

Unit 3 operated at 100 percent RTP except for two unplanned downpowers, an unplanned scram, and one planned downpower. On April 9, 2014, an unplanned downpower to 78 percent occurred to remove water from the 3A Condensate Booster Pumps oil system. Power was restored to 100 percent the next day. On May 6, 2014, an unplanned scram occurred while performing ATWS-RPT Analog Trip Unit testing. A failed power supply coupled with the test signal caused both recirculation pumps to trip and ATWS - ARI logic to insert all control rods.

The resulting transient caused the unit to scram on low reactor water level. The unit returned to 100 percent power on May 12, 2014. The planned downpower occurred on June 6, 2014, for a rod sequence exchange and condenser water box cleaning. An unplanned downpower to 98 percent for four hours occurred on June 17, 2014, when the inoperability of both trains of the Control Room air conditioning system resulted in beginning preparations for a Technical Specifications required shutdown. The shutdown was averted when one train of the Control Room air conditioning system was restored prior to the expiration of the required action time.

(EN 50207). Power remained at 100 percent RTP for the remainder of the quarter.

REACTOR SAFETY

Cornerstones: Initiating Events, Mitigating Systems, Barrier Integrity

1R01 Adverse Weather Protection

.1 Actual Weather Event

a. Inspection Scope

On April 28, 2014, a tornado watch and then a warning was declared for Limestone County. The inspectors reviewed the licensees overall preparations, personnel and equipment protection for the unexpected onset of severe weather conditions associated with the tornado watch that the plant was under. The inspectors reviewed and discussed the implementation of licensee Abnormal Operating Instruction 0-AOI-100-7, Severe Weather, with the responsible Unit Supervisors, Nuclear Security Supervisors, and the Shift Manager. The inspectors witnessed the licensees suspension of higher risk activities and were informed of the relocation of personnel from vulnerable areas.

The Inspectors toured the plant grounds for loose debris, which could become missiles during a tornado, and reviewed operator staffing and their accessibility to controls and indications required for safe control of the plant. This activity constituted one Adverse Weather Protection inspection sample.

b. Findings

No findings were identified.

.2 Readiness for Seasonal Extreme Weather Conditions

a. Inspection Scope

Prior to and during the onset of hot weather conditions, the inspectors reviewed the licensees implementation of 0-GOI-200-3, Hot Weather Inspection, and the TVA procedure for determination of grid qualification, (TRO-EA-SOP 30.405). The inspectors discussed implementation of 0-GOI-200-3 with responsible Operations personnel and management. The inspectors walked down the licensees switchyard to verify the physical condition of offsite power sources and reviewed the status of several work orders for offsite power sources. The inspectors monitored the status of risk significant equipment to cool the Unit 1, 2, and 3 control rooms and the status of the 7 cooling towers on site. This activity constituted one Readiness for Seasonal Extreme Weather inspection sample.

b. Findings

No findings were identified.

.3 Offsite and Alternate AC Power System Requirement

a. Inspection Scope

Prior to the summer season, inspectors reviewed electrical power design features, and onsite risk and work management procedures to verify appropriate operational oversight and assurance of continued availability of offsite and alternate AC power systems.

Inspectors verified that communications protocols existed between the transmission system operator and Browns Ferry Nuclear Plant for coordination of off-normal and emergency events affecting the plant, event details, estimates of return-to-service times, and notifications of grid status changes. The inspectors verified that the changes made since June 2013 to the licensees procedures addressing offsite AC power and onsite alternate AC power did not affect their availability and reliability. The inspectors walked down the licensees switchyard to verify the physical condition of offsite power sources and reviewed the status of several work orders for offsite power sources. This activity constituted one Offsite and Alternate AC Power System inspection sample.

b. Findings

No findings were identified.

1R04 Equipment Alignment

.1 Partial Walkdown

a. Inspection Scope

The inspectors conducted partial equipment alignment walkdowns to evaluate the operability of selected redundant trains or backup systems, listed below, while the other train or subsystem was inoperable or out of service. The inspectors reviewed the functional systems descriptions, Updated Final Safety Analysis Report (UFSAR), system operating procedures, and Technical Specifications (TS) to determine correct system lineups for the current plant conditions. The inspectors performed walkdowns of the systems to verify that critical components were properly aligned and to identify any discrepancies which could affect operability of the redundant train or backup system.

This activity constituted three Equipment Alignment Partial Walkdown inspection samples.

b. Findings

No findings were identified.

1R05 Fire Protection

.1 Fire Protection Tours

a. Inspection Scope

The inspectors reviewed licensee procedures for transient combustibles and fire protection impairments, and conducted a walkdown of the fire areas (FA) and fire zones (FZ) listed below. Selected FAs/FZs were examined in order to verify licensee control of transient combustibles and ignition sources; the material condition of fire protection equipment and fire barriers; and operational lineup and operational condition of fire protection features or measures. The inspectors verified that selected fire protection impairments were identified and controlled in accordance with procedures. The inspectors reviewed applicable portions of the Fire Protection Report, Volumes 1 and 2, including the applicable Fire Hazards Analysis, and Pre-Fire Plan drawings, to verify that the necessary firefighting equipment, such as fire extinguishers, hose stations, ladders, and communications equipment, was in place. This activity constituted six Fire Protection Walkdown inspection samples.

  • Intake Pumping Station, (Fire Area 25-1)
  • Unit 1, Control Building, EL 593 Battery and Battery Board Room (Fire Area 17)
  • Unit 2, Control Building, EL 593 Battery and Battery Board Room (Fire Area 18)
  • Unit 2, Reactor Building, EL 593 North of Column Line R (Fire Zone 2-3)
  • Unit 2, Reactor Building, EL 593 South of Column Line Q (Fire Zone 2-4)
  • Unit 2, Reactor Building, EL 621 and EL 639 (Fire Zone 2-5)

b. Findings

No findings were identified.

.2 Observe Fire Brigade

a. Inspection Scope

The inspectors witnessed a fire brigade response in the area between the Unit 2 and 3 cable spreading rooms on elevation 606 feet. The response was due to the smell of smoke that was coming from a failed power supply for a security system remote repeater. No actual fire occurred. The failed power supply was de-energized and replaced as documented in the licensees CAP as Problem Evaluation Report (PER)874890. The inspectors assessed fire alarm effectiveness; response time for notifying and assembling the fire brigade; the readiness of firefighting equipment; use of personnel fire protective clothing and equipment (e.g., turnout gear, self-contained breathing apparatus); communications; incident command and control; teamwork; and firefighting strategies. The inspectors also attended the post-event critique to assess the licensees ability to review fire brigade performance and identify areas for improvement.

Following the critique, the inspectors compared their observations with the requirements specified in the licensees Fire Protection report. This activity constituted one Fire Brigade response inspection sample.

b. Findings

No findings were identified.

1R06 Flood Protection Measures

.1 Internal Flood Protection

a. Inspection Scope

The inspectors reviewed a sampling of the licensees corrective action documents with an actual flood-related item affecting the standby gas treatment building and Unit 1, 2 emergency diesel areas to verify that impact of a broken demineralized water line was being identified and corrected. The inspectors reviewed selected completed preventive maintenance procedures, work orders, and surveillance procedures to verify that actions were completed within the specified frequency and in accordance with design basis documents. This activity constituted one Internal Flood Protection inspection sample.

b. Findings

No findings were identified.

.2 Cables Located in Underground Bunkers/Manholes

a. Inspection Scope

During the inspection period covered by Browns Ferry Inspection Report 05000259, 260, 296/2014-002, the inspectors conducted an inspection of underground manholes subject to flooding. As a result of the inspection, two Unresolved Items were opened. URI 2014-002-01, RHRSW pump power cables submerged in water in hand hole 26 contrary to TVA General Specification G-40, and URI 2014-002-02, Inadequate Corrective Action for sump pump in hand hole 15 allowing RHRSW pump power cables to be submerged in water without the pump operating. Their disposition is discussed below. No additional inspection samples were counted.

b. Finding

Introduction:

An NRC-identified Green Finding (FIN) was documented for the licensees failure to adhere to TVA General Specification 40 (G-40) for Installation, Modification, and Maintenance of Electrical Systems section 3.5.7 which required standing water in hand holes be kept below all safety related cables and electrical devices. Specifically, inspectors identified hand hole numbers 15 and 26 had standing water above several of the RHR service water (safety related) power cables.

Description:

Browns Ferry had RHR service water pump power cables routed underground for protection from potential hazards. There are two divisions of RHR service water pumps. One division has power cables routed through hand hole numbers 15 and 26. A hand hole is an underground cable vault that is accessible from above ground by removing an access cover. TVAs guidance for electrical cable installation, modification, and maintenance in General Specification G-40 section 3.5.7 states, in part, that hand holes shall be maintained free of standing water to the extent practical.

Standing water is acceptable as long as the water level in the hand holes containing safety related cables is below all cables and electrical devices.

The RHR service water power cables that are routed through these hand holes were discovered to be covered in water in 2001. As part of the licensee corrective actions, a sump pump was installed in hand hole 15 to remove standing water prior to the power cables becoming wetted. In 2007, the power cables in hand hole numbers 15 and 26 failed, in part due to being wetted. The licensee replaced these failed power cables in 2007 with a water impervious design built to the draft IEEE 1142-2009 standards. Also, as part of the extent of cause review, the licensee determined that the installed sump pump suction was not low enough in the hand hole to prevent the power cables from being wetted. As part their corrective actions for PER 119954, the licensee installed a new sump pump and a warning light to provide a visual alert to rising water levels prior to power cables becoming wetted. The pump suction depth was lowered to try to prevent power cable wetting. However, the pump was not lowered enough.

During an inspection of hand hole numbers 15 and 26 on January 17, 2014, standing water was discovered covering several of the RHR service water power (safety related)cables. The licensee verified all water from the hand hole was removed on May 29, 2014. The licensee provided sufficient test results to demonstrate operability for one year but could not provide analysis that the cables were rated for continuous submergence. The inspector determined that the period of time that the cable was wetted was less than the as tested maximum allowed time.

The issue identified in Unresolved Item (URI) 05000259, 260, 296/2014-002-01, RHRSW pump power cables submerged in water in hand hole 26 contrary to TVA General Specification G-40, was determined to be a performance deficiency and is being closed out as a finding.

URI 05000259, 260, 296/2014-002-02, Inadequate Corrective Action for sump pump in hand hole 15 allowing RHRSW pump power cables to be submerged in water without the pump operating, was determined to not be a performance deficiency because the inspectors determined that the corrective actions to install the new sump pump and alarm were not actions necessary to restore compliance with General Specification G-40. Compliance was restored when the water was removed from the hand hole.

Therefore, URI 05000259, 260, 296/2014-002-02 is being closed because no finding or violations of NRC requirements was identified.

Analysis:

The licensees failure to adhere to TVA General Specification 40 (G-40) for Installation, Modification, and Maintenance of Electrical Systems, section 3.5.7, which required standing water in hand holes be kept below any safety related cables, was a performance deficiency. Specifically, the licensee allowed hand hole number 15 and 26 to have standing water above several of the RHR service water (safety related) power cables. The performance deficiency was more than minor because if left uncorrected, it had the potential to lead to a more significant safety concern including cable degradation and increased likelihood of cable failure. This issue screened as having very low safety significance, Green, using IMC 0609 Appendix A, Exhibit 2, Mitigating Systems Screening Questions issued on June 19, 2012, because it affected the design or qualification of a mitigating SSC but the mitigating SSC maintained its operability. The finding had a cross cutting aspect of Problem Identification and Resolution: Resolution because the licensee failed to ensure that corrective actions addressed the cause of the power cable wetting and failure in 2007. (P.3)

Enforcement:

This finding does not involve enforcement action because no violation of a regulatory requirement was identified. Because this finding does not involve a violation and is of very low safety significance, it is identified as a FIN 259, 260, 296/2014-003-01, RHRSW Pump Power Cables Submerged in Water. This Green finding closes URI 05000259, 260, 296/2014-002-01.

1R07 Heat Sink Performance

a. Inspection Scope

Unit 3 EDG 3B Heat Exchanger:

The inspectors examined activities associated with Unit 3 EDG 3B Heat Exchanger. The inspectors reviewed procedures used for testing flow rates; and reviewed design basis documents, calculations, test procedures, and results to evaluate the licensees program for maintaining heat sinks in accordance with the licensing basis. The inspectors reviewed PERs and corrective actions to verify that the licensee was identifying issues and correcting them.

The inspectors performed walkdowns of key components of EECW systems to verify material conditions were acceptable and physical arrangement matched procedures and drawings. The inspectors reviewed the paperwork for the cleaning and inspection activities associated with the Unit 3 3B EDG heat exchanger. Inspectors reviewed licensee compliance to commitments made based on their response to the NRC Generic Letter 89-13 for service water system problems that could affect heat exchanger performance. Licensee corrosion and mollusk control chemical addition processes for heat exchangers were also reviewed. This activity constituted one Heat Sink Performance Inspection sample.

b. Findings

No findings were identified.

1R11 Licensed Operator Requalification and Performance

.1 Licensed Operator Requalification

a. Inspection Scope

On May 12, 2014, the inspectors observed a licensed operator training session for an operating crew according to Unit 2 Simulator Exercise Guide (SEG) OPL173S342, Power Reduction, Loss of the Reactor Protection System, Loss of a Steam Jet Air Ejector, and Anticipated Transient without Scram (ATWS).

The inspectors specifically evaluated the following attributes related to the operating crews performance:

  • Clarity and formality of communication
  • Ability to take timely action to safely control the unit
  • Prioritization, interpretation, and verification of alarms
  • Correct use and implementation of procedures including Abnormal Operating Instructions (AOIs), Emergency Operating Instructions (EOIs) and Safe Shutdown Instructions (SSI)
  • Timely control board operation and manipulation, including high-risk operator actions
  • Timely oversight and direction provided by the shift supervisor, including ability to identify and implement appropriate technical specifications actions such as reporting and emergency plan actions and notifications
  • Group dynamics involved in crew performance The inspectors assessed the licensees ability to administer testing and assess the performance of their licensed operators. The inspectors attended the post-examination critique performed by the licensee evaluators, and verified that licensee-identified issues were comparable to issues identified by the inspector. The inspectors reviewed simulator physical fidelity (i.e., the degree of similarity between the simulator and the reference plant control room, such as physical location of panels, equipment, instruments, controls, labels, and related form and function). This activity constituted one Observation of Requalification Activity inspection sample.

b. Findings

No findings were identified.

.2 Control Room Observations

a. Inspection Scope

Inspectors observed and assessed licensed operator performance in the plant and main control room, particularly during periods of heightened activity or risk and where the activities could affect plant safety. Inspectors reviewed various licensee policies and procedures covering Conduct of Operations, Plant Operations and Power Maneuvering.

Inspectors utilized activities such as post maintenance testing, surveillance testing and other activities to focus on the following conduct of operations as appropriate;

  • Operator compliance and use of procedures.
  • Control board manipulations.
  • Communication between crew members.
  • Use and interpretation of plant instruments, indications and alarms.
  • Use of human error prevention techniques.
  • Documentation of activities, including initials and sign-offs in procedures.
  • Supervision of activities, including risk and reactivity management.
  • Pre-job briefs.

This activity constituted one Control Room Observation inspection sample.

b. Findings

No findings were identified.

1R12 Maintenance Effectiveness

.1 Routine

a. Inspection Scope

The inspectors reviewed the specific structures, systems and components (SSC) within the scope of the Maintenance Rule (MR) (10CFR50.65) with regard to some or all of the following attributes, as applicable: 1) Appropriate work practices; 2) Identifying and addressing common cause failures; 3) Scoping in accordance with 10 CFR 50.65(b) of the MR;(4) Characterizing reliability issues for performance monitoring; 5) Tracking unavailability for performance monitoring; 6) Balancing reliability and unavailability; 7) Trending key parameters for condition monitoring; 8) System classification and reclassification in accordance with 10 CFR 50.65(a)(1) or (a)(2); 9) Appropriateness of performance criteria in accordance with 10 CFR 50.65(a)(2); and 10) Appropriateness and adequacy of 10 CFR 50.65 (a)(1) goals, monitoring and corrective actions. The inspectors compared the licensees performance against site procedures. The inspectors reviewed, as applicable, work orders, surveillance records, PERs, system health reports, engineering evaluations, and MR expert panel minutes; and attended MR expert panel meetings to verify that regulatory and procedural requirements were met.

This activity constituted four Maintenance Effectiveness inspection samples.

  • High Pressure Fire Pump maintenance rule scoping
  • Liquid Radwaste system maintenance rule scoping

b. Findings

No findings were identified.

1R13 Maintenance Risk Assessments and Emergent Work Evaluation

a. Inspection Scope

For planned online work and/or emergent work that affected the combinations of risk significant systems listed below, the inspectors examined on-line maintenance risk assessments, and actions taken to plan and/or control work activities to effectively manage and minimize risk. The inspectors verified that risk assessments and applicable risk management actions (RMA) were conducted as required by 10 CFR 50.65(a)(4)applicable plant procedures. As applicable, the inspectors verified the actual in-plant configurations to ensure accuracy of the licensees risk assessments and adequacy of RMA implementations. This activity constituted five Maintenance Risk Assessment inspection samples.

  • April 28, 2014, Unit 1, 2 and 3 risk and delay of associated maintenance on B Emergency Diesel Generator (EDG) and B Shutdown Board Battery due to impending adverse weather
  • May 01, 2014, Heavy lift of 3C Circulating Water pump over RHRSW pumps while B EDG was out of service for maintenance
  • May 08, 2014, Unit 1 Yellow Risk due to RHRSW and RHR Loop I out of service for scheduled maintenance
  • May 14, 2014, Unit 1 Yellow Risk due to RHRSW and RHR Loop II out of service for scheduled maintenance
  • May 20, 2014, Unit 3 Yellow Risk due to RHRSW and RHR Loop II out of service for scheduled maintenance

b. Findings

No findings were identified.

1R15 Operability Determinations and Functionality Assessment

a. Inspection Scope

The inspectors reviewed the operability/functional evaluations listed below to verify technical adequacy and ensure that the licensee had adequately assessed TS operability. The inspectors reviewed applicable sections of the UFSAR to verify that the system or component remained available to perform its intended function. In addition, where appropriate, the inspectors reviewed licensee procedures to ensure that the licensees evaluation met procedure requirements. Where applicable, inspectors examined the implementation of compensatory measures to verify that they achieved the intended purpose and that the measures were adequately controlled. The inspectors reviewed PERs on a daily basis to verify that the licensee was identifying and correcting any deficiencies associated with operability evaluations. This activity constituted seven Operability Evaluation inspection samples.

  • Standing Order OS-195, Technical Requirements Manual 3.7.6, Electric Board room air conditioning system not consistent with Technical Specifications
  • Past Operability Evaluation of 3A 480V Load Shed Logic Function Failure During EDG 3A Load Acceptance Test (PER 847155)
  • 3B EDG Heat Exchanger exceeded its acceptance criteria for fouling (PER 867001)
  • Leak under RHRSW D Room door (PER 878297)
  • Gas release identified on Unit 2 RHR spray loop I discharge piping in excess of the acceptance criteria (PER 892052)
  • Jet Pump Mismatch (PER 884538)

b. Findings

During the inspection of the Standing Order 0S-195, the inspectors identified the below Unresolved Item (URI).

Introduction:

The inspectors identified an URI for Technical Requirements Manual (TRM) allowances that conflict with the supported system requirements to maintain equipment operability as described in technical specifications (TS).

Description:

On July 14, 1998, Browns Ferry received approval to use the Improved Technical Specifications (NUREG-1433) and develop a TRM by license amendment number 232 (Unit 1), 253 (Unit 2), and 212 (Unit 3) (ML020040291). The Browns Ferry Technical Specifications, Section 1.0, "Definitions," stated, in part, A system, subsystem, division, component, or device shall be operable when all necessary attendant instrumentation, controls, cooling, and other auxiliary equipment required for the component to perform its specified safety function are also capable of performing their related support function(s). The TRM is a licensee controlled document to control safety related equipment not covered by technical specifications (10CFR50.36) including:

Reactor Zone Isolation Timers (TRM 3.3.2.2); Refuel Zone Isolation Timers (TRM 3.3.2.3); Low Pressure ECCS Area Cooler Instrumentation (TRM 3.3.3.2); EECW Pump Timers (TRM 3.3.3.7); Drywell Control Air System (TRM 3.6.3); and Electric Board Room Air Conditioning System (TRM 3.7.6). These TRMs, as written, potentially allowed the aforementioned attendant systems to become non-functional without causing the supported TS equipment to be declared inoperable. The licensee initiated PERs 846040 and 877729 to investigate and analyze these issues of concern. URI 05000259, 260, 296/2014-003-02, TRM Allowances Conflicting with Technical Specifications, is opened pending completion of licensee analysis and NRC inspection of this issue of concern to determine if a more than minor performance deficiency or violation exists.

1R18 Plant Modifications

.1 Permanent Plant Modifications

a. Inspection Scope

The inspectors reviewed the Design Change Notice (DCN) and completed work package (WO 114173563) for DCN 70835. DCN 70835 was a modification to the low pressure coolant injection function of the RHR system to allow a manual override of the 450 psig interlock should that interlock not be cleared due to a circuit failure. The inspectors reviewed licensee procedures NPG-SPP-09.3, Plant Modifications and Engineering Change Control, and NPG-SPP-06.9.3, Post-Modification Testing, post-maintenance testing package (PMTI-70835-005) for the implementation of this modification to loop 1 of the Unit 3 RHR system. The inspectors reviewed the associated 10 CFR 50.59 screening against the RHR system design bases documentation to verify that the modifications had not affected system operability/availability. The inspectors reviewed selected ongoing and completed work activities to verify that installation was consistent with the design control documents. This activity constitutes one Permanent Plant Modification sample.

b. Findings

No findings were identified.

1R19 Post Maintenance Testing

a. Inspection Scope

The inspectors witnessed and reviewed post-maintenance tests (PMT) listed below to verify that procedures and test activities confirmed Structure, System, or Component (SSC) operability and functional capability following the described maintenance. The inspectors reviewed the licensees completed test procedures to ensure any of the SSC safety function(s) that may have been affected were adequately tested, that the acceptance criteria were consistent with information in the applicable licensing basis and/or design basis documents. The inspectors witnessed and/or reviewed the test data, to verify that test results adequately demonstrated restoration of the affected safety function(s). The inspectors verified that problems associated with PMTs were identified and entered into the CAP. This activity constituted six Post Maintenance Test inspection samples.

  • Replacement and post maintenance testing of 4KV Shutdown Board 3EB time delay relays, (WO 114709767)
  • Replacement and post maintenance testing of Analog Trip Unit A following Unit 3 Scram, (WO 115771962)
  • Post maintenance testing of C2 RHRSW pump following impeller gap adjustment, (WO 115823524)

b. Findings

No findings were identified.

1R20 Refueling and Other Outage Activities

a. Inspection Scope

Unit 3 Forced Outage From May 6, 2014, through May 8, 2014, the inspectors examined the Unit 3 forced outage activities to verify that they were conducted in accordance with Technical Specifications (TS), applicable plant procedures, and the licensees outage risk assessment and management plans. The inspectors monitored critical plant parameters and observed operator control of plant conditions through Hot Shutdown (Mode 3).

Some of the significant outage activities specifically reviewed and/or witnessed by the inspectors were as follows:

Shutdown and Cooldown Process The inspectors witnessed the shutdown and cooldown of Unit 3 in accordance with licensee procedures OPDP-1, Conduct of Operations; 3-GOI-100-12A, Unit Shutdown from Power Operations to Cold Shutdown and Reduction in Power During Power Operations; and 3-SR-3.4.9.1(1), Reactor Heatup or Cooldown Rate Monitoring.

Restart Activities The inspectors specifically observed the following:

  • Unit 3 approach to criticality and power ascension per 3-GOI-100-1A, Unit Startup, and 3-GOI-100-12, Power Maneuvering
  • Reactor Coolant Heatup/Pressurization to Rated Temperature and Pressure per 3-SR-3.4.9.1, Reactor Heatup and Cooldown Rate Monitoring Corrective Action Program The inspectors reviewed PERs generated during the forced outage and attended management review meetings to verify that initiation thresholds, priorities, mode holds, operability concerns and significance levels were adequately addressed. Resolution and implementation of corrective actions of several PERs were reviewed for completeness.

This activity constituted one Forced Outage Activity sample.

b. Findings

No findings were identified

1R22 Surveillance Testing

a. Inspection Scope

The inspectors witnessed portions of, and/or reviewed completed test data for the following surveillance tests of risk-significant and/or safety-related systems to verify that the tests met technical specification surveillance requirements, UFSAR commitments, and in-service testing and licensee procedure requirements. The inspectors review confirmed whether the testing effectively demonstrated that the SSCs were operationally capable of performing their intended safety functions and fulfilled the intent of the associated surveillance requirement. This activity constituted four Surveillance Testing inspection samples: one in-service, one reactor coolant system leakage detection, and two routine tests.

In-Service Tests:

Reactor Coolant System Leakage Detection Tests:

  • 2-SR-3.4.4.1, Manual Calculation of Unidentified, Identified, and Total Leakage, (WO 115683930)

Routine Surveillance Tests:

b. Findings

No findings were identified.

Cornerstone: Emergency Preparedness (EP)

1EP2 Alert and Notification System Evaluation

a. Inspection Scope

The inspectors evaluated the adequacy of the licensees methods for testing the alert and notification system in accordance with NRC Inspection Procedure 71114, 02, Alert and Notification System (ANS) Testing. The applicable planning standard, 10 CFR Part 50.47(b)(5) and its related 10 CFR Part 50, Appendix E,Section IV.D requirements were used as reference criteria. The criteria contained in NUREG-0654, Criteria for Preparation and Evaluation of Radiological Emergency Response Plans and Preparedness in Support of Nuclear Power Plants, Revision 1, were also used as a reference.

The inspectors reviewed various documents which are listed in the Attachment.

Inspectors interviewed personnel involved with siren system maintenance and observed annual siren maintenance field activities. This inspection activity satisfied one inspection sample for the alert and notification system on a biennial basis.

b. Findings

No findings were identified.

1EP3 Emergency Preparedness Organization Staffing and Augmentation System

a. Inspection Scope

The inspectors reviewed the licensees Emergency Response Organization (ERO)augmentation staffing requirements and process for notifying the ERO to ensure the readiness of key staff for responding to an event and timely facility activation. The qualification records of key position ERO personnel were reviewed to ensure all ERO qualifications were current. A sample of problems identified from augmentation drills or system tests performed since the last inspection was reviewed to assess the effectiveness of corrective actions.

The inspection was conducted in accordance with NRC Inspection Procedure 71114, 03, Emergency Preparedness Organization Staffing and Augmentation System. The applicable planning standard, 10 CFR 50.47(b)(2), and its related 10 CFR 50, Appendix E requirements were used as reference criteria.

The inspectors reviewed various documents which are listed in the Attachment. This inspection activity satisfied one inspection sample for the ERO staffing and augmentation system on a biennial basis.

b. Findings

No findings were identified.

1EP4 Emergency Action Level and Emergency Plan Changes

a. Inspection Scope

Since the last NRC inspection of this program area, no changes have been made to the Emergency Action Levels. The licensee did make several changes to the Radiological Emergency Plan and emergency plan implementing procedures, and determined that, in accordance with 10 CFR 50.54(q), the changes made in these revisions resulted in no reduction in the effectiveness of the Plan, and that the Plan continued to meet the requirements of 10 CFR 50.47(b) and Appendix E to 10 CFR Part 50. The inspectors conducted a sampling of the implementing procedure changes made between June 2013, and January 2014, to evaluate for potential reductions in the effectiveness of the Plan. However, this review was not documented in a Safety Evaluation Report and does not constitute formal NRC approval of the changes. Therefore, these changes remain subject to future NRC inspection in their entirety.

The inspection was conducted in accordance with NRC Inspection Procedure 71114, 04, Emergency Action Level and Emergency Plan Changes. The applicable planning standards of 10 CFR 50.47(b), and its related requirements in 10 CFR 50, Appendix E, were used as reference criteria.

The inspectors reviewed various documents that are listed in the Attachment to this report. This inspection activity satisfied one inspection sample for the emergency action level and emergency plan changes on an annual basis.

b. Findings

No findings were identified.

1EP5 Maintenance of Emergency Preparedness

a. Inspection Scope

The inspectors reviewed the corrective actions identified through the Emergency Preparedness program to determine the significance of the issues, the completeness and effectiveness of corrective actions, and to determine if issues were recurring. The licensees post-event action reports, self-assessments, and audits were reviewed to assess the licensees ability to be self-critical, thus avoiding complacency and degradation of their emergency preparedness program. Inspectors reviewed the licensees 10 CFR 50.54(q) change process, personnel training, and selected screenings and evaluations to assess adequacy. The inspectors toured facilities and reviewed equipment and facility maintenance records to assess licensees adequacy in maintaining them. The inspectors evaluated the capabilities of selected radiation monitoring instrumentation to adequately support Emergency Action Level (EAL)declarations.

The inspection was conducted in accordance with NRC Inspection Procedure 71114.05, Maintenance of Emergency Preparedness. The applicable planning standards, related 10 CFR 50, Appendix E requirements, and 10 CFR 50.54(q) and

(t) were used as reference criteria.

Documents reviewed are listed in the Attachment. This inspection activity satisfied one inspection sample for the maintenance of emergency preparedness on a biennial basis.

b. Findings

No findings were identified.

1EP6 Drill Evaluation

.1 April 23, 2014, EP Radiological Emergency Plan (REP) training drill

a. Inspection Scope

The inspectors observed an EP REP training drill that contributed to the licensees Drill/Exercise Performance (DEP) and Emergency Response Organization (ERO)performance indicator (PI) measures on April 23, 2014. This drill was intended to identify any licensee weaknesses and deficiencies in classification, notification, dose assessment and protective action recommendation (PAR) development activities. The inspectors observed emergency response operations in the simulated control room, Technical Support Center, and Operations Support Center to verify that event classification and notifications were done in accordance with EPIP-1, Emergency Classification Procedure, and licensee conformance with other applicable Emergency Plan Implementing Procedures. The inspectors attended the post-drill critiques to compare any inspector-observed weaknesses with those identified by the licensee in order to verify whether the licensee was properly identifying EP related issues and entering them in to the CAP, as appropriate. This activity constituted one EP training drill inspection sample.

b. Findings

No findings were identified.

.2 June 11, 2014, EP Radiological Emergency Plan (REP) simulator evaluation

a. Inspection Scope

The inspectors observed the simulator portion of an EP REP training drill that contributed to the licensees Drill/Exercise Performance (DEP) and Emergency Response Organization (ERO) performance indicator (PI) measures on June 11, 2014.

This drill was intended to identify any licensee weaknesses and deficiencies in classification, notification, dose assessment and protective action recommendation (PAR) development activities. The inspectors observed emergency response operations to verify that event classification and notifications were done in accordance with EPIP-1, Emergency Classification Procedure, and licensee conformance with other applicable Emergency Plan Implementing Procedures. The inspectors attended the post-drill critiques to compare any inspector-observed weaknesses with those identified by the licensee in order to verify whether the licensee was properly identifying EP related issues and entering them in to the CAP, as appropriate. This activity constituted one EP simulator evaluation inspection sample.

b. Findings

No findings were identified.

RADIATION SAFETY

2RS6 Radioactive Gaseous and Liquid Effluent Treatment

a. Inspection Scope

Radioactive Effluent Treatment Systems: The inspectors walked-down selected components of the gaseous and liquid radioactive waste (radwaste) processing and effluent discharge systems. To the extent practical, the inspectors observed and evaluated the material condition of in-place waste processing equipment for indications of degradation or leakage that could constitute a possible release pathway to the environment. Inspected components included drain tanks, standby gas treatment systems, liquid waste processing equipment, and associated piping and valves. The inspectors interviewed licensee staff regarding radwaste equipment configuration and effluent monitor operation. The inspectors also reviewed surveillance testing records for standby gas treatment systems.

Effluent Sampling and Release: The inspectors observed the collection and processing of airborne effluent samples from the refuel floor, turbine building, and main plant stack.

The inspectors reviewed recent liquid and gaseous release permits including pre-release sampling results, effluent monitor alarm setpoints, and public dose calculations. The inspectors reviewed the 2013 Annual Radioactive Effluent Report to evaluate reported doses to the public, to review any anomalous events, and to review Offsite Dose Calculation Manual (ODCM) changes. The inspectors also reviewed compensatory sampling data for time periods when selected radiation monitors were out of service.

The inspectors reviewed the results of the 2012 radiochemistry cross-check program.

The inspectors also reviewed effluent source term evaluation and changes to effluent release points. In addition, the inspectors evaluated recent land use census results and meteorological data used to calculate doses to the public.

Ground Water Protection: The inspectors reviewed the licensees continued implementation of the industrys Ground Water Protection Initiative (Nuclear Energy Institute (NEI) 07-07) as part of Inspection Procedure 71124.07.

Problem Identification and Resolution: The inspectors reviewed Corrective Action Program (CAP) documents in the area of gaseous and liquid effluent processing and release. The inspectors evaluated the licensees ability to identify and resolve the identified issues. The inspectors also reviewed recent self-assessment results.

Radwaste system operation and effluent processing activities were evaluated against requirements and guidance documented in the following: 10 CFR Part 20; 10 CFR Part 50 Appendix I; ODCM; Final Safety Analysis Report (FSAR) Section 9; Regulatory Guide (RG) 1.21, Measuring, Evaluating, and Reporting Radioactivity in Solid Wastes and Releases of Radioactive Materials in Liquid and Gaseous Effluents from Light-Water-Cooled Nuclear Power Plants; RG 1.109, Calculation of Annual Doses to Man from Routine Releases of Reactor Effluents for the Purpose of Evaluating Compliance with 10 CFR Part 50 Appendix I; and Technical Specifications (TS) Section 5. Procedures and records reviewed during the inspection are listed in the report Attachment.

This activity constituted one inspection sample for Radioactive Gaseous and Liquid Effluent Treatment.

b. Findings

No findings were identified.

2RS7 Radiological Environmental Monitoring Program (REMP)

a. Inspection Scope

REMP Implementation: The inspectors observed routine sample collection and surveillance activities as required by the licensees environmental monitoring program.

The inspectors noted the material condition and operability of airborne particulate filter and iodine cartridge sample stations and observed collection of weekly air samples at selected monitoring locations. The inspectors also checked environmental thermoluminescent dosimeters and water sampling stations for material condition at selected sites.

The inspectors reviewed calibration and maintenance surveillance records for the installed environmental air sampling stations. The inspectors also reviewed the 2012 and 2013 Radiological Environmental Operating Reports, the 2012 and 2013 Annual Radioactive Effluent Reports, recent results of the interlaboratory cross-check program for the environmental lab, and procedural guidance for environmental sample collection and processing. Selected environmental measurements were reviewed for consistency with licensee effluent data, evaluated for radionuclide concentration trends, and compared with detection level sensitivity requirements. In addition, the inspectors reviewed and evaluated land use census results, changes to the ODCM, and monitoring for hard-to-detect radionuclides.

Meteorological Monitoring Program: The inspectors walked-down the meteorological tower and observed local data collection equipment readouts. The physical condition of the tower and the instruments were observed and equipment operability and maintenance history were reviewed and discussed with responsible licensee staff. The transmission of locally generated meteorological data to the main control room operators was also evaluated. The inspectors reviewed applicable tower instrumentation calibration records for the meteorological measurements of wind speed, wind direction, and temperature, and evaluated measurement data recovery for 2012 and 2013.

Ground Water Protection: The inspectors discussed program guidance for spills, leaks, and unexpected discharges with licensee staff and reviewed recent entries into the 10 CFR 50.75(g) decommissioning file. The inspectors reviewed and discussed the licensees program for monitoring of structures, systems, and components with the potential to release radioactive material to the environment. Potential effluent release points due to onsite surface water bodies were also evaluated. In addition, the inspectors reviewed recent groundwater sampling results.

Problem Identification and Resolution: The inspectors reviewed CAP documents in the areas of radiological environmental monitoring, meteorological tower maintenance, and groundwater monitoring. The inspectors evaluated the licensees ability to identify and resolve the issues in accordance with licensee procedures. The inspectors also reviewed recent self-assessment results.

REMP implementation, meteorological monitoring activities, and groundwater monitoring were reviewed against the guidance and requirements of 10 CFR Part 20; Appendices E and I to 10 CFR Part 50; TS Section 5; FSAR Chapter 2; ODCM Rev. 21; RG 4.15, Quality Assurance for Radiological Monitoring Programs (Normal Operation) - Effluent Streams and the Environment; RG 1.23, Meteorological Monitoring Programs For Nuclear Power Plants; ANSI/ANS-2.5-1984, Standard for Determining Meteorological Information at Nuclear Power Sites; Branch Technical Position, An Acceptable Radiological Environmental Monitoring Program - 1979; NEI 07-07, Industry Groundwater Protection Initiative - Final Guidance Document; and approved licensee procedures. Documents reviewed are listed in the Attachment.

This activity constituted one inspection sample for Radiological Environmental Monitoring Program.

b. Findings

No findings were identified.

OTHER ACTIVITIES

4OA1 Performance Indicator (PI) Verification

.1 Cornerstone: Mitigating Systems

a. Inspection Scope

The inspectors reviewed the licensees procedures and methods for compiling and reporting the following Performance Indicators (PIs). The inspectors examined the licensees PI data for the specific PIs listed below for the second quarter 2013 through first quarter of 2014. The inspectors reviewed the licensees data and graphical representations as reported to the NRC to verify that the data was correctly reported.

The inspectors validated this data against relevant licensee records (e.g., PERs, Daily Operator Logs, Plan of the Day, Licensee Event Reports, etc.), and assessed any reported problems regarding implementation of the PI program. The inspectors verified that the PI data was appropriately captured, calculated correctly, and discrepancies resolved. The inspectors used the Nuclear Energy Institute (NEI) 99-02, Regulatory Assessment Performance Indicator Guideline, to ensure that industry reporting guidelines were appropriately applied. This activity constituted nine performance indicator inspection samples.

  • Unit 1,2, and 3 MSPI for Heat Removal System (RCIC)
  • Unit 1, 2, and 3 Safety System Functional Failures

b. Findings

No findings were identified.

.2 Emergency Preparedness Cornerstone

a. Inspection Scope

The inspectors sampled licensee submittals relative to the PIs listed below for the period April 1, 2013, through March 31, 2014. To verify the accuracy of the PI data reported during that period, PI definitions and guidance contained in NEI 99-02, Regulatory Assessment Performance Indicator Guideline, Revision 7, was used to confirm the reporting basis for each data element.

  • Emergency Response Organization (ERO) Drill/Exercise Performance
  • ERO Drill Participation
  • Alert and Notification System Reliability For the specified review period, the inspectors examined data reported to the NRC, procedural guidance for reporting PI information, and records used by the licensee to identify potential PI occurrences. The inspectors verified the accuracy of the PI for ERO drill and exercise performance through review of a sample of drill and event records.

The inspectors reviewed selected training records to verify the accuracy of the PI for ERO drill participation for personnel assigned to key positions in the ERO. The inspectors verified the accuracy of the PI for alert and notification system reliability through review of a sample of the licensees records of periodic system tests. The inspectors also interviewed the licensee personnel who were responsible for collecting and evaluating the PI data. Documents reviewed are listed in the Attachment. This inspection satisfied three inspection samples for PI verification on an annual basis.

b. Findings

No findings were identified.

4OA2 Problem Identification and Resolution of Problems

.1 Review of items entered into the Corrective Action Program:

a. Inspection Scope

As required by Inspection Procedure 71152, Identification and Resolution of Problems, and in order to help identify repetitive equipment failures or specific human performance issues for follow-up, the inspectors performed a daily screening of items entered into the licensees CAP. This review was accomplished by reviewing daily PER and Service Request (SR) reports, and periodically attending Corrective Action Review Board (CARB) and PER Screening Committee (PSC) meetings.

b. Findings

No findings were identified.

.2 Semi-annual Trend Review:

a. Inspection Scope

As required by Inspection Procedure 71152, the inspectors performed a review of the licensees CAP and other associated programs and documents to identify trends that could indicate the existence of a more significant safety issue. The inspectors review was focused on repetitive equipment issues, but also included licensee trending efforts and licensee human performance results. The inspectors review nominally considered the six-month period of January through June 2014, although some examples expanded beyond those dates when the scope of the trend warranted. Inspectors reviewed licensee trend reports for the period in order to determine the existence of any adverse trends that the licensee may not have previously identified. The inspectors review also included the licensees Integrated Trend Reports (ITR). The inspectors verified that adverse or negative trends identified in the licensees PERs, periodic reports and trending efforts were entered into the CAP. This inspection satisfied one inspection sample for Semi-annual Trend Review.

b. Observations and Findings

No findings were identified. In general, the licensee had identified trends and appropriately addressed them in their CAP. The inspectors observed that the licensee had performed a detailed review. The licensee routinely reviewed cause codes and utilized key words and system links to identify potential trends in their data. The inspectors compared the licensee process results with the results of the inspectors daily screening. Trends that have been identified by licensees trending program and the CAP included the following:

  • Adverse trend in tagging activities where the maintenance was not performed A trend that had not been identified by licensees trending program was one related to inadequate operator system operating instruction procedures resulting in configuration control events and inoperabilities that were considered minor issues.

.3 Focused Annual Sample Review:

a. Inspection Scope

The inspectors reviewed the Licensee corrective actions related their failure to submit the results of their Unit 2 reactor pressure vessel surveillance capsule results in the amount of time required by 10 CFR 50 Appendix H. There was a shift in the operating pressure and temperature curves as a result of the testing performed on the surveillance capsule. The operating curve shift has been included in the licensees shift operating orders and a change to the Unit 2 technical specification 3.4.9 is being prepared. This activity constituted one Focused Annual Corrective Action sample.

b. Findings

No findings were identified.

4OA3 Follow-up of Events and Notices of Enforcement Discretion

.1 (Closed) Licensee Event Report (LER) 05000259/2013-006-01 and, 05000259/2013-006-

02, 1B Standby Liquid Control Pump Inoperable for Longer than Allowed by Technical Specifications

a. Inspection Scope

The inspectors reviewed LERs 05000259/2013-006-01 and 05000259/2013-006-02 dated February 25, 2014, and April 16, 2014. Revision 00 to LER 05000259/2013-006 had been submitted December 3, 2013, by TVA. TVA had determined that 1B Standby Liquid Control pump had been inoperable from December 1, 2012, to February 14, 2013, due to a piece of the motor breakers arc chute that had become dislodged and relocated to between the breaker contacts. The original LER failed to recognize that the failure also resulted in a Safety System functional failure (SSFF) due to loss of the function of the Standby Liquid Control system to inject Boron 10 into the reactor coolant system or control suppression pool pH during a loss of coolant accident. Revision 01 documented the addition of the SSFF documentation. Following additional cause analysis, the licensee submitted revision 02 to the LER to document that the damaged arc chute was due to a human performance error caused during transport. The licensee had no requirement to inspect the arc chutes prior to installation to the breaker. The NRC inspectors reviewed the new information and confirmed the specified corrective actions were appropriate and were being implemented.

b. Findings

No additional findings or violations of NRC requirements were identified.

.2 (Closed) Licensee Event Report (LER) 05000296/2014-001-00, Automatic Reactor

Scram due to Turbine Trip on high Moisture Separator Controller Level

a. Inspection Scope

Inspectors reviewed LER 05000296/2014-001-00. The licensee identified that the failed moisture separator level controller caused a turbine trip and the reactor protection system appropriately initiated the subsequent reactor scram. The licensee initiated PER 860625 to enter this issue into the CAP. The root cause of the scram was attributed to introduction of foreign material (metallic shaving) into the control arm area of the level controller control relay during original manufacture of the controller. The licensee corrective actions were to remove similar control relays from the plant and provide instructions to add cleaning instruction for future similar controller rebuilds. The NRC inspectors reviewed previous work history of the failed controller, verified there were no performance deficiencies, and confirmed the specified corrective actions were appropriate and were being implemented.

b. Findings

No findings or violations or NRC requirements were identified.

4OA5 Other Activities

.1 Independent Spent Fuel Storage Installation (ISFSI) Change Evaluations

a. Inspection Scope

Under the guidance of IP 60855, the inspectors reviewed the licensees evaluations of the changes to the Independent Spent Fuel Storage Installation (ISFSI) in accordance with 10 CFR 72.48, Changes, Tests, and Experiments, as well as the licensees procedure for implementing 10 CFR 72.48 evaluations. The review focused on the changes that were implemented since the last inspection. The review determined that the evaluations were consistent with the requirements of 10 CFR 72.48 and the evaluations were documented in accordance with NPG-SPP-09.9, 10 CFR 72.48 Evaluations of Changes, Tests and Experiments for Independent Spent Fuel Storage Installation. The inspectors also reviewed any changes to 10 CFR 72.212, Report of Evaluations since the last inspection.

b. Findings

No findings were identified.

4OA6 Meetings, Including Exit

On July 11, 2014, the resident inspectors presented the quarterly inspection results to Mr. Keith Polson, Site Vice President, and other members of the licensees staff, who acknowledged the findings. The inspectors verified that all proprietary information was returned to the licensee.

4OA7 Licensee-Identified Violations

The following violations of very low safety significance (Green) were identified by the licensee and are violations of NRC requirements which meet the criteria of the NRC Enforcement Policy, for being dispositioned as a Non-Cited Violation.

  • 10 CFR 50, Appendix B, Criterion XI, Test Control, required in part that testing demonstrated that components perform satisfactorily in service and that test procedures incorporate the requirements and acceptance limits contained within applicable design documents. On May 4, 2012, modification DCN 69492, Stage 7 was implemented which replaced the 480V Shutdown Board 3A Normal Feeder Breaker (BFN-3-BKR-231-0003A/1C) with an updated model. Contrary to the above, breaker checkout and testing procedure, (ECI-0-000-BKR011), did not test all the required design functions of the newly installed breaker, specifically the secondary contact circuitry which provides control for the load shed function. Subsequent testing on February 17, 2014, of the Emergency Diesel Generator (EDG) in accordance with Surveillance 3-SR-3.8.1.9(3A), EDG Load Acceptance Test, identified that the 480V Shutdown Board 3A failed to load shed as designed. The licensee entered this issue into the CAP as problem evaluation report (PER) 847155.

Troubleshooting determined the failure of the load shed function was due to a lack of continuity or adequate engagement of the breakers secondary control contacts.

Using inspection manual chapter 0609, Appendix A, Exhibit 2 (Mitigating Systems);this finding was determined to be of very low safety significance (green) because the EDG remained capable of meeting its design function even with the additional load induced by the failure of the 480V load shed function.

SUPPLEMENTAL INFORMATION

KEY POINTS OF CONTACT

Licensee

M. Acker, Licensing Engineer
J. Addison, Manager of Drills and Exercises
T. Adkins, EP Systems Manager
E. Bates, Licensing Engineer
R. Beck, Manager of the Engineering Rapid Response Team
S. Bono, General Plant Manager
D. Campbell, Operations Superintendent
M. Clark, EP Specialist
T. Cole, Superintendent - Radiation Protection Support
R. Cox, System Engineer
D. Curtley, Maintenance Rule Coordinator (Sequoyah)
D. Green, Licensing Engineer
L. Grigsby, Chemist
K. Harvey, Raw Water Systems Engineer
L. Hughes, Manager Operations
E. Johnson, System Engineer
J. Kulisek, EP Manager
J. Lacasse, System Engineer
W. Lee, Corporate EP Manager
B. McNutt, Ops Shift Manager
M. Moebes, Unit Supervisor
S. Norris, Engineering Manager
M. Oliver, Licensing Engineer
J. Parshall, EP Program Planning and Implementation Manager
J. Paul, Nuclear Site Licensing Manager
K. Polson, Site Vice President
M. Rasmussen, Work Control Manager
M. Roy, Maintenance Rule Coordinator (Browns Ferry)
S. Samaras, Civil Design Engineer
T. Scott, Performance Improvement Manager
G. Smith, Unit Supervisor
S. Spears, Electrical Maintenance Supervisor
S. Taubuki, EP Specialist
B. Tidwell, EP Specialist
J. Wheat, System Engineer
J. Whitlock, Unit Supervisor
A. Yarborough, Assistant Director for Site Engineering
T. Young, Switchyard Systems Engineer
T. Young, Transmission Service Center Manager

LIST OF ITEMS

OPENED, CLOSED AND DISCUSSED

Opened

05000259/260/296/2014003-02 URI TRM Allowances Conflicting with Technical Specifications (Section 1R15)

Opened and Closed

05000259/260/296/2014003-01 FIN RHRSW Pump Power Cables Submerged in Water (Section 1R06.2)

Closed

05000259/2013-006-01 LER 1B Standby Liquid Control Pump Inoperable for Longer than Allowed by Technical Specifications (Section 4OA3.1)
05000259/2013-006-02 LER 1B Standby Liquid Control Pump Inoperable for Longer than Allowed by Technical Specifications (Section 4OA3.1)
05000296/2014-001-00 LER Automatic Reactor Scram due to Turbine Trip on High Moisture Separator Level (Section 4OA3.2)
05000259, 260, 296/2014-002-01 URI RHRSW pump power cables submerged in water in Handhole 26 contrary to TVA General Specification G-40. (Section 1R06.2)
05000259, 260, 296/2014-002-02 URI Inadequate Corrective Action for sump pump in Handhole 15 allowing RHRSW pump power cables to be submerged in water without the pump operating. (Section 1R06.2)

Discussed

None

LIST OF DOCUMENTS REVIEWED