ENS 52478
From kanterella
Jump to navigation
Jump to search
ENS Event | |
|---|---|
20:30 Jan 9, 2017 | |
| Title | Emergency Diesel Generators Non-Conforming with Licensing Basis for Tornado Generated Missiles |
| Event Description | On January 9, 2017, during evaluation of protection for Technical Specification (TS) equipment from the damaging effects of tornado generated missiles, Peach Bottom Atomic Power Station identified a non-conforming condition in the plant design such that specific TS equipment is considered to not be adequately protected from tornado generated missiles. A tornado could generate multiple missiles that could strike one or more of the four emergency diesel generator (EDG) exhaust stacks. This could result in crimping of the stack, which could affect the ability of the EDG to perform its design function if such a tornado would occur.
This condition is reportable per 10 CFR 50.72(b)(3)(ii)(B) for any event or condition that results in the nuclear power plant being in an unanalyzed condition that significantly degrades plant safety, and per 10 CFR 50.72(b)(3)(v)(D) for any event or condition that at the time of discovery could have prevented the fulfillment of the safety function of structures or systems that are needed to mitigate the consequences of an accident. This condition is being addressed in accordance with NRC enforcement guidance provided in EGM 15-002 and DSS-ISG-2016-01. Compensatory measures have been implemented in accordance with these documents. The NRC Resident Inspector has been informed of this notification. |
| Where | |
|---|---|
| Peach Bottom Pennsylvania (NRC Region 1) | |
| Reporting | |
| 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident | |
| Time - Person (Reporting Time:+-3.57 h-0.149 days <br />-0.0212 weeks <br />-0.00489 months <br />) | |
| Opened: | Mike Schweigler 16:56 Jan 9, 2017 |
| NRC Officer: | Steven Vitto |
| Last Updated: | Jan 9, 2017 |
| 52478 - NRC Website
Loading map... | |
Unit 2 | |
|---|---|
| Reactor critical | Critical |
| Scram | No |
| Before | Power Operation (100 %) |
| After | Power Operation (100 %) |
Unit 3 | |
|---|---|
| Reactor critical | Critical |
| Scram | No |
| Before | Power Operation (100 %) |
| After | Power Operation (100 %) |
Peach Bottom | |
WEEKMONTHYEARENS 582282026-04-01T13:24:0001 April 2026 13:24:00
[Table view]10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Unanalyzed Condition ENS 578992025-09-04T15:10:0004 September 2025 15:10:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Unanalyzed Condition ENS 569572024-02-09T18:22:0009 February 2024 18:22:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Unanalyzed Condition - Inadequate Fuses for Fuel Pool Cooling ENS 552242021-04-30T03:54:00030 April 2021 03:54:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident High Pressure Coolant Injection (Hpci) Declared Inoperable ENS 543302019-10-15T16:10:00015 October 2019 16:10:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident High Pressure Coolant Injection (Hpci) System Inoperable ENS 536172018-09-21T04:00:00021 September 2018 04:00:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident, 10 CFR 50.72(b)(2)(i), Tech Spec Required Shutdown, 10 CFR 50.72(b)(3)(ii)(A), Seriously Degraded High Pressure Coolant Injection System Inoperable ENS 532652018-03-15T19:24:00015 March 2018 19:24:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Failure to Meet Appendix R Requirements ENS 524782017-01-09T20:30:0009 January 2017 20:30:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident, 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Emergency Diesel Generators Non-Conforming with Licensing Basis for Tornado Generated Missiles ENS 524192016-12-09T03:37:0009 December 2016 03:37:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident Hpci Surveillance Failure ENS 522642016-09-26T22:45:00026 September 2016 22:45:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident High Pressure Coolant Injection System Declared Inoperable ENS 516302015-12-31T11:30:00031 December 2015 11:30:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident High Pressure Coolant Injection Inoperable ENS 501282014-05-21T15:00:00021 May 2014 15:00:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Unanalyzed Condition Involving Fire Safe Shutdown Capability ENS 483762012-10-04T13:59:0004 October 2012 13:59:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident Both Trains of Control Room Emergency Ventilation System Out of Service ENS 474422011-11-16T00:52:00016 November 2011 00:52:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition High Pressure Coolant Injection Steam Supply Valve Cable Unprotected During Postulated Fire ENS 469872011-06-26T04:30:00026 June 2011 04:30:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident Piping Leak Isolated on High Pressure Coolant Injection ENS 466772011-03-16T20:47:00016 March 2011 20:47:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident High Pressure Coolant Injection Declared Inoperable ENS 452892009-08-24T18:15:00024 August 2009 18:15:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident, 10 CFR 50.72(b)(3)(v)(C), Loss of Safety Function - Release of Radioactive Material Station Safety Grade Pneumatic Supply Issue ENS 449262009-03-21T16:07:00021 March 2009 16:07:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident Hpci Declared Inoperable Following Failure of Valve to Fully Open During Surveillance Test ENS 449042009-03-12T20:20:00012 March 2009 20:20:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident Hpci Declared Inoperable ENS 442902008-06-12T04:40:00012 June 2008 04:40:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident High Pressure Coolant Injection (Hpci) System Identified Inoperable During Surveillance ENS 432382007-03-14T18:55:00014 March 2007 18:55:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident Hpci Declared Inoperable ENS 424782006-04-05T20:15:0005 April 2006 20:15:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident High Pressure Coolant Injection Declared Inoperable (Hpci) ENS 416762005-05-07T01:36:0007 May 2005 01:36:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident Degraded Pipe Restraint on Hpci Discharge Piping ENS 416382005-04-25T20:55:00025 April 2005 20:55:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident Hpci Declared Inoperable ENS 415102005-03-21T22:00:00021 March 2005 22:00:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident Hpci Declared Inoperable - Entering 14 Day Lco Action Statement ENS 414582005-03-03T23:25:0003 March 2005 23:25:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident High Pressure Coolant Injection System Inoperable ENS 411072004-10-09T05:15:0009 October 2004 05:15:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident High Pressure Coolant Injection System Condensate Storage Tank Suction Valve Failed to Auto-Close During Surveillance ENS 409732004-08-22T00:00:00022 August 2004 00:00:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident Accident Mitigation - High Pressure Coolant Injection System Flow Controller Malfunction ENS 405932004-03-17T17:35:00017 March 2004 17:35:00 10 CFR 50.72(b)(3)(v)(B), Loss of Safety Function - Remove Residual Heat, 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident High Pressure Coolant Injection System Inoperable ENS 405762004-03-08T16:30:0008 March 2004 16:30:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident Hpci System Inoperable Due to Failure of Torus Suction Valve to Fully Open ENS 403942003-12-16T20:40:00016 December 2003 20:40:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident High Pressure Coolant Injection System Inoperable ENS 403842003-12-10T23:00:00010 December 2003 23:00:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident Reduction in Accident Mitigation Due to Improper Hpci Suction Transfer 2026-04-01T13:24:00 | |