ENS 57899
ENS Event | |
|---|---|
15:10 Sep 4, 2025 | |
| Title | |
| Event Description | The following information was provided by the licensee via phone email:
On September 4, 2025, at 1110 EDT, it was determined that the units are in an unanalyzed condition. A review of DC control circuit protection schemes identified circuits which are uncoordinated due to inadequate fuse sizing. This results in a concern that postulated fire damage in one area could cause a short circuit without adequate protection, leading to the unavailability of equipment credited for 10 CFR 50 Appendix R safe shutdown. This condition is not bounded by existing design and licensing documents; however, it poses no impact to the health and safety of the public or plant personnel. Therefore, this event is being reported as an eight-hour, non-emergency notification per 10 CFR 50.72(b)(3)(ii)(B). Compensatory actions for affected fire areas have been implemented. The NRC Senior Resident Inspector has been notified. |
| Where | |
|---|---|
| Peach Bottom Pennsylvania (NRC Region 1) | |
| Reporting | |
| 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition | |
| LER: | 05000277/LER-2025-002 Uncoordinated DC Circuits Cause Unanalyzed Condition |
| Time - Person (Reporting Time:+-2.47 h-0.103 days <br />-0.0147 weeks <br />-0.00338 months <br />) | |
| Opened: | Matthew Batdorf 12:42 Sep 4, 2025 |
| NRC Officer: | Ernest West |
| Last Updated: | Sep 4, 2025 |
| 57899 - NRC Website
Loading map... {"minzoom":false,"maxzoom":false,"mappingservice":"leaflet","width":"350px","height":"250px","centre":false,"title":"","label":"","icon":"","lines":[],"polygons":[],"circles":[],"rectangles":[],"copycoords":false,"static":false,"zoom":6,"defzoom":14,"layers":["OpenStreetMap"],"image layers":[],"overlays":[],"resizable":false,"fullscreen":false,"scrollwheelzoom":true,"cluster":false,"clustermaxzoom":20,"clusterzoomonclick":true,"clustermaxradius":80,"clusterspiderfy":true,"geojson":"","clicktarget":"","imageLayers":[],"locations":[{"text":"\u003Cb\u003E\u003Cdiv class=\"mw-parser-output\"\u003E\u003Cp\u003E\u003Ca class=\"mw-selflink selflink\"\u003EENS 57899\u003C/a\u003E - \u003Ca href=\"/Peach_Bottom\" title=\"Peach Bottom\"\u003EPeach Bottom\u003C/a\u003E\n\u003C/p\u003E\u003C/div\u003E\u003C/b\u003E\u003Cdiv class=\"mw-parser-output\"\u003E\u003Cp\u003E\u003Ca href=\"/Unanalyzed_Condition\" title=\"Unanalyzed Condition\"\u003EUnanalyzed Condition\u003C/a\u003E\n\u003C/p\u003E\u003C/div\u003E","title":"ENS 57899 - Peach Bottom\n","link":"","lat":39.75920833333333,"lon":-76.26879444444444,"icon":"/w/images/b/be/Constellation_icon.png"}],"imageoverlays":null} | |
WEEKMONTHYEARENS 578992025-09-04T15:10:0004 September 2025 15:10:00
[Table view]10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Unanalyzed Condition ENS 569572024-02-09T18:22:0009 February 2024 18:22:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Unanalyzed Condition - Inadequate Fuses for Fuel Pool Cooling ENS 532652018-03-15T19:24:00015 March 2018 19:24:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Failure to Meet Appendix R Requirements ENS 524782017-01-09T20:30:0009 January 2017 20:30:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident, 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Emergency Diesel Generators Non-Conforming with Licensing Basis for Tornado Generated Missiles ENS 501282014-05-21T15:00:00021 May 2014 15:00:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Unanalyzed Condition Involving Fire Safe Shutdown Capability ENS 474422011-11-16T00:52:00016 November 2011 00:52:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition High Pressure Coolant Injection Steam Supply Valve Cable Unprotected During Postulated Fire 2025-09-04T15:10:00 | |