05000341/FIN-2014004-01
From kanterella
Jump to navigation
Jump to search
Finding | |
|---|---|
| Title | Potential Missile Hazards from Unrestrained Equipment near the 345-Kilovolt and 120-Kilovolt Switchyards |
| Description | On September 10, with severe weather predicted for the vicinity of Fermi Unit 2, the inspectors walked down locations outside the plant, including areas near the 120-kilovolt and 345-kilovolt switchyards. Multiple examples of unrestrained and loosely restrained materials were identified that could have become missiles in the event of high winds and caused damage to components in the switchyards. In response to the inspectors identified concerns, the licensee initiated CARDs 14-27157 and 14-27160 to assign details to remove the hazards from the areas and evaluate their potential impact to the switchyards. This issue of concern is considered a URI pending the inspectors review of the licensees evaluation of the identified conditions and corrective actions to determine whether the issue is a performance deficiency of more than minor significance (URI 05000341/2014004-01, Potential Missile Hazards from Unrestrained Equipment near the 345-Kilovolt and 120-Kilovolt Switchyards. |
| Site: | Fermi |
|---|---|
| Report | IR 05000341/2014004 Section 1R01 |
| Date counted | Sep 30, 2014 (2014Q3) |
| Type: | URI: |
| cornerstone | Mitigating Systems |
| Identified by: | NRC identified |
| Inspection Procedure: | IP 71111.01 |
| Inspectors (proximate) | B Kemker D Kimble J Cassidy J Nance M Kunowski P Smagacz R Jickling R Morris S Bell T Brileya Dahbura Shaikh B Kemker J Bozga M Kunowski M Learn P Smagacz R Edwards S Bell |
| INPO aspect | |
| ' | |
Finding - Fermi - IR 05000341/2014004 | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Fermi) @ 2014Q3
| |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||