05000325/LER-2016-002
| Brunswick Steam Electric Plant (Bsep), Unit 1 | |
| Event date: | 03-04-2016 |
|---|---|
| Report date: | 08-08-2016 |
| Reporting criterion: | 10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications 10 CFR 50.73(a)(2)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident 10 CFR 50.73(a)(2)(iv)(A), System Actuation 10 CFR 50.73(a)(2)(v), Loss of Safety Function |
| Initial Reporting | |
| ENS 51769 | 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident |
| 3252016002R01 - NRC Website | |
comments regarding burden estimate to the FOIA, Privacy and Information Collections Branch (T-5 F53), U.S. Nuclear Regulatory Commission, Washington, DC 20555-0001, or by e-mail to used to impose an information collection does not display a currently valid OMB control number, the NRC may not conduct or sponsor, and a person is not required to respond to, the information collection.
Brunswick Steam Electric Plant (BSEP), 002 05000-325 2016 - 01 Energy Industry Identification System (EIIS) codes are identified in the text as [XX].
Background
Initial Conditions At the time of this event, Unit 1 was in Mode 5 (i.e., Refuel), in a refueling outage which began on February 26, 2016.
Unit 2 was in Mode 1 (i.e., Power Operation) with reactor power at approximately 100 percent of rated thermal power. Emergency Diesel Generator 1 (EDG 1) [EK] was inoperable in support of modifications, maintenance activities, and testing. Emergency bus El [EB] and balance of plant (BOP) bus 1D were deenergized in support of this work. No other Unit 2 safety-related equipment was inoperable.
Reportability Criteria 10 CFR 50.73(a)(2)(v)(D) Brunswick EDG capacity is such that any three of the four diesels can supply the required loads for the safe shutdown of one unit and a design basis accident on the other unit without offsite power. As such, simultaneous inoperability of EDGs 1 and 3 is reportable in accordance with 10 CFR 50.73(a)(2)(v)(D), as an event or condition that could have prevented the fulfillment of a safety function needed to mitigate the consequences of an accident. The NRC was initially notified of the event on March 4, 2016 (i.e., Event Number 51769).
As discussed below, it has been determined that EDG 3 was inoperable from February 7, 2016, until March 4, 2016. During this time, EDGs 1, 2, and 4 were also inoperable, at various times, for surveillance testing and associated activities. These occurrences are also reportable in accordance with 10 CFR 50.73(a)(2)(v)(D), as an event or condition that could have prevented the fulfillment of a safety function needed to mitigate the consequences of an accident.
Event Number 51769 also reported loss of safety function of the Conventional Service Water system [BI], the Control Room EmerOency Ventilation system [VI], and the Control Room Air Condition system [VI].
After additional review, it has been determined that a loss of safety fundtion of these systems did not occur. As such, this event is not reportable per 10 CFR 50.72(b)(3)(v) or 10 CFR 50.73(a)(2)(v) for those systems.
10 CFR 50.73(a)(2)(i)(B) This event is reportable in accordance with 10 CFR 50.73(a)(2)(i)(B) as operation prohibited by the plant's Technical Specifications (TSs) for both Unit 1 and Unit 2. The following conditions resulted in unintentional operation prohibited by the plant's TSs given the inoperability of EDG 3.
comments regarding burden estimate to the FOIA, Privacy and Information Collections Branch (T-5 F53), U.S. Nuclear Regulatory Commission, Washington, DC 20555-0001, or by e-mail to used to impose an information collection does not display a currently valid OMB control number, the NRC may not conduct or sponsor, and a person is not required to respond to, the information collection.
Brunswick Steam Electric Plant (BSEP), 002 05000-325 2016 - 01
- On February 8, 2016, at 2211 Eastern Standard Time (EST), Unit 2 would have been required to be in Mode 3 in accordance with TS 3.8.1, Required Action H.1, for one offsite circuit inoperable and one EDG inoperable (i.e., TS 3.8.1, Condition F).
- On February 12, 2016, at 2357 EST, Unit 1 entered Mode 2 from Mode 4. This constituted a violation of Limiting Condition for Operation (LCO) 3.0.4.
- On February 20, 2016, at 1157 EST, Unit 1 would have been required to be in Mode 3 in accordance with TS 3.8.1, Required Action H.1, for a single EDG inoperable (i.e., TS 3.8.1, Condition D).
- On February 21, 2016, at 0806 EST, Unit 1 and Unit 2 would have been required to be in Mode 3 in accordance with TS 3.8.1, Required Action H.1, for two EDGs inoperable (i.e., TS 3.8.1, Condition G).
- On March 3, 2016, at 2108 EST, Unit 2 would have been required to be in Mode 2 in accordance with LCO 3.0.3, per TS 3.8.1, Condition I, (i.e., one or more offsite circuits and two or more Diesel Generators (DGs) inoperable).
10, CFR 50.73(a)(2)(iv)(A) On March 3, work was ongoing to restore power to BOP bus 1D when an error in the restoration sequence resulted in an invalid auto-start of EDGs 2 and 4 at 1332 EST. EDGs 2 and 4 responded properly to the auto-start signal and ran unloaded. Since no actual bus under voltage condition existed which required the EDGs to start, and the start was not in response to actual plant conditions satisfying the requirements for initiation, this event has been classified as an invalid actuation. Because the invalid auto-starts of EDGs 2 and 4 are directly related to the events associated with this LER, the event is being reported via this LER rather than the optional 60-day telephone notification as allowed by 10 CFR 50.73(a)(1).
Event Description
On March 2, at 1458 EST, EDG 1 was declared inoperable in support of modifications, maintenance activities, and testing. Emergency bus El and balance of plant (BOP) bus 1D were deenergized in refueling outage. Due to the shared electrical distribution system at Brunswick, Unit 2 was in TS 3.8.1, Condition B (i.e., two Unit 1 offsite circuits inoperable due to one Unit 1 balance of plant circuit path to the downstrethm 4.16 kV emergency bus inoperable for planned maintenance and the EDG associated with the affected downstream 4.16 kV emergency bus inoperable for planned maintenance).
On March 3, work was ongoing to restore power to BOP bus 1D when an error in the restoration sequence resulted in an invalid auto-start of EDGs 2 and 4. The invalid signal mimicked undervoltage on the startup auxiliary transformer (SAT) [EA], which is not a TS required start and, per design, would have started EDGs 1, 2, 3, and 4. EDG .1 was under clearance and, as such, did not start. However, it was also expected that EDG 3 should have started. Troubleshooting activities and a thorough EDG 1 modification review were initiated. As a result, on March 4, 2016, at 1235 hours0.0143 days <br />0.343 hours <br />0.00204 weeks <br />4.699175e-4 months <br /> EST, it was determined that continuity was lost across a dummy fuse block in the auto-start circuitry for EDG 3. This failure prevented TS comments regarding burden estimate to the FOIA, Privacy and Information Collections Branch (T-5 F53), U.S. Nuclear Regulatory Commission, Washington, DC 20555-0001, or by e-mail to used to impose an information collection does not display a currently valid OMB control number, the NRC may not conduct or sponsor, and a person is not required to respond to, the information collection.
Brunswick Steam Electric Plant (BSEP), 002 05000-325 2016 - 01 entered TS 3.8.1, Condition I, (i.e., one or more offsite circuits and two or more Diesel Generators (DGs) inoperable). Required Action 1.1 directs immediate entry into LCO 3.0.3.
Duke Energy Progress, Inc., verbally requested a Notice of Enforcement Discretion (NOED) to extend the time required by LCO 3.0.3 for Unit 2 to be in Mode 2, Mode 3, and Mode 4 by 17 hours1.967593e-4 days <br />0.00472 hours <br />2.810847e-5 weeks <br />6.4685e-6 months <br />. The NRC verbally approved the NOED at 1535 EST on March 4, 2016. EDG 3 was restored to operable status and LCO 3.0.3 was exited at 1834 EST after replacement of the fuse holder. This was before the original Completion Time of LCO 3.0.3 (i.e., be in Mode 2 by March 4, 2016, at 1935 EST).
As a result of the root cause evaluation of this event, the direct cause of the EDG 3 failure to auto-start was identified as a loss of continuity in the 2-DG3-FU-1-ECR Dummy Fuse at EDG 3 Emergency Control Relay (ECR) Disconnect; specifically, loose fuse clamps in the dummy fuse block/holder. Further, there is firm evidence that this condition existed since February 7, 2016, when EDG 3 successfully auto-started in response to a Unit 1 SAT lock-out condition, the details of which are discussed in Brunswick for EDG 3 (i.e., annunciator UA-21 5-2, and lights) had cleared, without operator action. This provides indication that the loss of continuity in the dummy fuse holder occurred at that time. The unexpected clearing indicates a loss of power to the ECR relay, the same failure mechanism that prevented EDG 3 auto-start on March 3. Therefore, it is concluded that the equipment issue was present from February 7 until March 4, when the fuse holder was replaced. Inoperability of EDG 3 was determined to be from 2211 EST on February 7, when the EDG 3 was secured from the auto-start, until 1834 EST on March 4, 2016, following replacement of the faulty fuse holder.
A review was performed to determine instances when EDGs 1, 2, or 4 were inoperable during the period from February 7, 2016, until March 4, 2016. The following instances were identified. Note, the times provided are approximate, based on Operations Log entries.
EDG 1 February 20 at 1806 EST to March 2 at 1226 EST (i.e., 10 days, 18 hours2.083333e-4 days <br />0.005 hours <br />2.97619e-5 weeks <br />6.849e-6 months <br />, 20 minutes) for planned replacement of the automatic voltage regulator and margin improvement modifications.
March 2 at 1458 EST to March 9 at 0,151 EST (i.e., 6 days, 10 hours1.157407e-4 days <br />0.00278 hours <br />1.653439e-5 weeks <br />3.805e-6 months <br />, 53 minutes) for Division 1 electrical outage and DG 1 governor modification. Note that EDG 3 was restored to operable status at 1834 EST on March 4.
EDG 2 February 19 from 2025 EST to 2053 EST (i.e., 28 minutes) for barring.
February 19 from 2104 EST to February 20 at 0014 EST (i.e., 3 hours3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br />, 10 minutes) for surveillance testing.
comments regarding burden estimate to the FOIA, Privacy and Information Collections Branch (T-5 F53), U.S. Nuclear Regulatory Commission, Washington, DC 20555-0001, or by e-mail to infocollects.Resource@nrc.gov, and to the Desk Officer, Office of Information and Regulatory Affairs, used to impose an information collection does not display a currently valid OMB control number, the NRC may not conduct or sponsor, and a person is not required to respond to, the information collection.
Brunswick Steam Electric Plant (BSEP), 002 05000-325 2016 - 01 EDG 4 February 15 from 1235 EST to 1434 EST (i.e., 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br />, 59 minutes) for surveillance testing.
February 18 from 2106 EST to 2140 EST (i.e., 34 minutes) for barring.
February 18 from 2154 EST to February 19 at 0119 EST (i.e., 3 hours3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br />, 25 minutes) for surveillance testing.
During the above periods, Unit 2 was in Mode 1. Unit 1 was in Mode 1 until February 26 at 2129 when Mode 3 was entered to start the refueling outage.
Event Cause The root cause of this event is a design vulnerability associated with relaxation of the EDG 3 fuse holder fingers which was not properly mitigated. The existing design lacks circuit continuity indication that is not mitigated by design or testing.
The direct cause for the EDG 3 failure to start was determined to be a loss of continuity through a dummy fuse in the auto-start logic circuit for EDG 3, which prevented the ECR coil from being energized and thus starting the diesel. The loss of continuity through the ECR fuse block assembly was a result of loose fuse holder fingers. ECR fuse block assembly was installed as a result of a 2011/2012 modification performed on the auto-start circuitry of each EDG. This modification installed an intermediate clearance point between the Lock Out Control Relay (LOCR) and ECR. During the 2011 engineering change process where the fuse block design was identified, the risk was identified that fuse block/clip-to-fuse electrical contact may open/fail. The risk was identified but positive measures were not put into place to mitigate the risk beyond visual verification that the brass dummy fuse was installed.
Safety Assessment The safety significance of this event is minimal.
On March 3, 2016, BOP Bus,1D, E1, E5, and EDG 1 were inoperable due to,ongoing maintenance (i.e., Unit 1 Division 1 AC outage window). The planned Unit 1 maintenance activity had been properly risk assessed prior to the beginning of the outage. The unplanned inoperability of EDG 3 had minimal impact on Unit 1. EDG 3/E3 are primarily associated with Unit 2 loads. A loss of power to E3 could have impacted the lA Residual Heat Removal (RHR) pump [BO] and the 1A RHR Service Water (SW) pump [BO]. However, on March 3, Unit 1 was flooded up with the spent fuel pool gates removed. Time to boil was approximately 19 hours2.199074e-4 days <br />0.00528 hours <br />3.141534e-5 weeks <br />7.2295e-6 months <br />. Per TS 3.9.7, one RHR shutdown cooling subsystem is required to be operable and in operation in Mode 5 with irradiated fuel in the Reactor Pressure Vessel (RPV) and the water level greater than or equal to 21 feet 10 inches above the RPV flange. The primary means of shutdown cooling was B RHR with D RHR the backup. Additionally, EDG 3 could be manually started.
Based on these considerations, the event is of minimal safety significance for Unit 1.
comments regarding burden estimate to the FOIA, Privacy and Information Collections Branch (T-5 F53), U.S. Nuclear Regulatory Commission, Washington, DC 20555-0001, or by e-mail to used to impose an information collection does not display a currently valid OMB control number, the NRC may not conduct or sponsor, and a person is not required to respond to, the information collection.
Brunswick Steam Electric Plant (BSEP), 002 05000-325 2016 - 01 On March 3, 2016, Unit 2 remained in Mode 1. EDG 2, EDG 4, and offsite power sources (i.e., excluding offsite power to emergency bus El) were not affected by the EDG 1 maintenance and were operable.
Emergency buses E2, E3, and E4 continued to be powered from offsite power. As such, sufficient offsite power supplies remained available to complete their intended safety function. The Supplemental Diesel Generator (SUPP-DG), installed to support a 14-day completion time for an inoperable EDG, remained available, as well as the two permanently installed FLEX diesels. The SUPP-DG is rated at 4000 kW, 4160 VAC, and can provide power to the emergency busses in approximately 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br />. Each FLEX diesel is rated at 500 kW, 480 VAC, and can be connected to the emergency busses in less than one hour.
Except for the periods of time for repair activities and post-repair testing, EDG 3 was available via manual start.
A Probabilistic Risk Assessment (PRA) was performed to determine the impact of EDG 3 being inoperable from February 7 until March 4, 2016. This analysis concluded that this was of very low safety significance.
Corrective Actions
Any changes to the corrective actions and schedules noted below will be made in accordance with the site's corrective action program.
The following corrective action to prevent recurrence is planned.
- A design change, for each EDG ECR fuse block, to ensure continuity is maintained or a loss of circuit continuity is detected will be installed. Installation is currently scheduled to be completed by December 31, 2017.
In addition, the following corrective actions have been completed or are planned.
- EDG 3 was restored to operable status on March 4, 2016, after replacement of the degraded dummy fuse holder. The dummy fuse holders for EDGs 1, 2, and 4 will be replaced. This is currently scheduled to be completed by October 10, 2016.
Previous Similar Events
A review of LERs for the past five years identified the following previous similar occurrence.
- LER 1-2015-002, Revision 1, dated November 11, 2015, reported loss of safety function due to inoperability of EDGs 3 and 4. The root cause of the event was a procedural inadequacy in the commercial grade dedication process that allowed an unauthorized component modification to go unrecognized. To prevent recurrence of a similar event, procedure AD-EG-ALL-1103, "Procurement Engineering Products," was revised. Since the causes of the events were different, the actions from LER 1-2015-002 could not have reasonably been expected to prevent the condition reported in LER 1-2016-002.
comments regarding burden estimate to the FOIA, Privacy and Information Collections Branch (T-5 F53), U.S. Nuclear Regulatory Commission, Washington, DC 20555-0001, or by e-mail to used to impose an information collection does not display a currently valid OMB control number, the NRC may not conduct or sponsor, and a person is not required to respond to, the information collection.
Brunswick Steam Electric Plant (BSEP),
- 002 05000-325 2016 - 01 Commitments No regulatory commitments are contained in this report.