05000325/LER-1986-001, :on 860102,reactor Bldg Fire Hose Stations Rendered Inoperable.Caused by Downstream Isolation Valve of Hose Stations Supply Deluge Valve Being Shut to Isolate Gasket Leak.Mechanical Jumper Installed

From kanterella
(Redirected from 05000325/LER-1986-001)
Jump to navigation Jump to search
:on 860102,reactor Bldg Fire Hose Stations Rendered Inoperable.Caused by Downstream Isolation Valve of Hose Stations Supply Deluge Valve Being Shut to Isolate Gasket Leak.Mechanical Jumper Installed
ML20151S074
Person / Time
Site: Brunswick Duke Energy icon.png
Issue date: 01/31/1986
From: Dietz C, Pastva M
CAROLINA POWER & LIGHT CO.
To:
NRC OFFICE OF ADMINISTRATION (ADM)
References
BSEP-86-0076, BSEP-86-76, LER-86-001, LER-86-1, NUDOCS 8602060415
Download: ML20151S074 (2)


LER-1986-001, on 860102,reactor Bldg Fire Hose Stations Rendered Inoperable.Caused by Downstream Isolation Valve of Hose Stations Supply Deluge Valve Being Shut to Isolate Gasket Leak.Mechanical Jumper Installed
Event date:
Report date:
3251986001R00 - NRC Website

text

5 Fer e 380 as2>

U S. NUCLEAN EE [ULATOAV COMMISSION AreROVED Out NO Jtso_0toA LICENSEE EVENT REPORT (LER)

'*""" 8 m '

FACILITY NAME H)

DocutET NUMGER (21 PAGE+3h Brunswick Steam Electric Plant Unit 1 0 [S l 0 l0 l 0 l3 l 2l5 1 lOFl0 l l title tel Isolation of Reactor Building Fire Hose Stations EVENT DATE 153 LER NUMSER 161 R EPORT DATE (7)

OTHER F ACILITIES INVOLVED (se MONTH OAY YEAR YEAR "0UNa"a '

wen UONTH DAY YEAR F ACILITV Newts DOCKE T Ni.,veEmist 0 lSl0 l0l0l [ l 0l 1 0l2 8

6 8l6 0l 0 l1 0 l0 0l1 3l1 8l 6 0 ;5 to,0,0 i ; i OPE R ATING THIS REPORT IS SUOMITTED PURSUANT TO THE REQUIREMENTS OF 10 CPR $ IChece o.e er more er ene rolleer.fA (11)

"oot

  • I 2o ac2m to sosa.

so.73r.H2Hm 73.Fim I r 0,0 2a.oewn He so 3ei.im 2a.oewmm so.73iaH2H,i 73.Fim 20.4attaHTHdil sa a.H2 so.73taH2H it no, X

90.73(aH2H4 gMgs=g.g 4 60.73(aH2Hve66HA)

J66A1 20 406taH1Hivl 60.73(aH2Hal 90.73ieH2Hve66HS) 20.40sieH?Het 50.73taH2Heall 50.73(eH2Hal LICENSEE CONTACT FOR TMit LER H29 Nl.ME TELEPMONE NUwSER ARE A CODE M. J. Pastva, Jr., Regulatory Technician 9 1 Il9 4 5 l 7l 12 l 3l1 l 5 1

COMPLETE ONE LINE FOR E ACM COMPONENT F AILURE DESCRIBED IN THIS REPORT H39 CRT

^ C' Tg

CAUSE

SYSTEM COMPONENT wa ACr R

^

PRO

CAUSE

Sv3TEU COMPONENT 9

g O NPR X

K;P [I[S l V A i 6l0l6 Yes

, i

.g l ; i l

I I I l l I I

! ! I I I l SUPPLEMENTAL REPORT EXPECTED 1148 90NTM CAY YEAR SU SW1$$1QN YEs ;lf yes, come ete EXPLCTED SVDhrts$10N CA TE)

NO l

l l

A.ST R ACT w,,o r a --,...,e.

. u,

.,,..,Y on

, n.>

On 01/02/86, at 2100, the Unit 1 Reactor Building fire hose stations were rendered inoperable when 1-FP-V322, downstream isolation valve of the hose stations' supply deluge valve, 1-FP-DV-319, was shut to isolate a gasket leak of approximately five gpm at the latch arm trip mechanism of DV-319.

Technical Specifications (T/S) required action, to establish within one hour:

(1) an alternate means of fire suppression for the unprotected areas or (2) additional equivalent capacity fire hose to the unprotected areas from an operable fire hose station, was not met until 01/03/86, at 1430. The leakage of DV-319 was discovered and reported to the Unit 1 Control Operator by a Reactor Building fire watch person. Throughout the event Unit I was at 1007..

A mechanical jumper (a length of 23" diameter fire hose) was installed to provide an alternate source of fire suppression to the downstream piping of 1-FP-V322.

The T/S required action time frame was not met because procedures did not provide for timely installation of an alternate source of fire suppression supply to the fire hose stations.

DV-319, Automatic Sprinkler Corp. Model No. C, was appropriately repaired and returned to service on 01/04/86, at 1330. Procedures to minimize the time for installation of required alternate fire suppression capability will be developed and implemented.

g NRC Form 388 ges33 e UAGPO:thttt07W

O

.Cp&L ru m.,..

vn.

Carolina Power & Light Company

- mm_ -_

.-._,em m

Brunswick Steam Electric Plant P. O. Box 10429 Southport, NC 28461-0429 January 31, 1986 FILE: B09-13510C SERIAL: BSEP/86-0076 NRC Document Control Desk U.S. Nuclear Regulatory Commission Washington, DC 20555 BRUNSWICK STEAM ELECTRIC PLANT UNIT 1 DOCKET NO. 50-325 LICENSE NO. DPR-71 LICENSEE EVENT REPORT 1-86-001 Gentlemen:

In accordance with Title 10 to the Code of Federal Regulations, the enclosed Licensee Event Report is submitted. This report fulfills the requirement for a written report within thirty (30) days of a reportable occurrence and is in accordance with the format set forth in NUREG-1022, September 1983.

Very truly yours, iy C. R. Dietz, General Manager Brunswick Steam Electric Plant MJP/mbh Enclosure cc:

Dr. J. N. Grace 4

'l'