| | | Reporting criterion |
|---|
| 05000324/LER-1986-001-01, :on 860107,testing of Safety Relief Valves Revealed That 10 Valves Exhibited Symptoms of Setpoint Drift.Caused by High Friction in Labyrinth Seal Area.Valves Refurbished & Recertified.Discs Replaced |
- on 860107,testing of Safety Relief Valves Revealed That 10 Valves Exhibited Symptoms of Setpoint Drift.Caused by High Friction in Labyrinth Seal Area.Valves Refurbished & Recertified.Discs Replaced
| |
| 05000324/LER-1986-001, :on 860107,discovered That 10 of 11 Safety Relief Valves Tested Exhibited Symptoms of higher-than- Allowed Setpoint Drift.Caused by Pilot disc-to-seat Sticking & High Friction.Maint Program Revised |
- on 860107,discovered That 10 of 11 Safety Relief Valves Tested Exhibited Symptoms of higher-than- Allowed Setpoint Drift.Caused by Pilot disc-to-seat Sticking & High Friction.Maint Program Revised
| |
| 05000325/LER-1986-001, :on 860102,reactor Bldg Fire Hose Stations Rendered Inoperable.Caused by Downstream Isolation Valve of Hose Stations Supply Deluge Valve Being Shut to Isolate Gasket Leak.Mechanical Jumper Installed |
- on 860102,reactor Bldg Fire Hose Stations Rendered Inoperable.Caused by Downstream Isolation Valve of Hose Stations Supply Deluge Valve Being Shut to Isolate Gasket Leak.Mechanical Jumper Installed
| |
| 05000325/LER-1986-002-01, :on 860106,HVAC Periodic Test 46.4 Found Inadequate to Meet Tech Spec Surveillance Requirements. Caused by Electrical Contacts Not Being Tested.Periodic Test Will Be Revised |
- on 860106,HVAC Periodic Test 46.4 Found Inadequate to Meet Tech Spec Surveillance Requirements. Caused by Electrical Contacts Not Being Tested.Periodic Test Will Be Revised
| |
| 05000325/LER-1986-003, :on 860106,automatic Isolation of Unit 1 & 2 Common Control Bldg HVAC Sys Occured Due to Actuation of Sys Air Intake Plenum Chlorine Detector 2X-AT-2977.Caused by Spurious Actuation of Detector 2X |
- on 860106,automatic Isolation of Unit 1 & 2 Common Control Bldg HVAC Sys Occured Due to Actuation of Sys Air Intake Plenum Chlorine Detector 2X-AT-2977.Caused by Spurious Actuation of Detector 2X
| |
| 05000324/LER-1986-003-02, :on 860131,ultrasonic Exam of Reactor Shroud Head hold-down Bolts Revealed Existence of Crack Indications in 15 of Total 36 Bolts.Caused by Igscc.Addl Data Re Indication Phenomenon Will Be Acquired |
- on 860131,ultrasonic Exam of Reactor Shroud Head hold-down Bolts Revealed Existence of Crack Indications in 15 of Total 36 Bolts.Caused by Igscc.Addl Data Re Indication Phenomenon Will Be Acquired
| |
| 05000324/LER-1986-004-02, :on 860303,primary Containment Group 6 Isolation,Automatic Isolation of Reactor Bldg Vent Sys & Automatic Start of Standby Gas Treatment Sys Occurred. Caused by Blown Fuse F-5.Fuse Replaced |
- on 860303,primary Containment Group 6 Isolation,Automatic Isolation of Reactor Bldg Vent Sys & Automatic Start of Standby Gas Treatment Sys Occurred. Caused by Blown Fuse F-5.Fuse Replaced
| |
| 05000325/LER-1986-004, :on 860108 & 22,automatic Starting of Units 1 & 2 Common Control Bldg Emergency Air Filtration Sys Train 2A Occurred Due to Fire Alarms in Control Bldg.Caused by Actuation of Fire Detector |
- on 860108 & 22,automatic Starting of Units 1 & 2 Common Control Bldg Emergency Air Filtration Sys Train 2A Occurred Due to Fire Alarms in Control Bldg.Caused by Actuation of Fire Detector
| |
| 05000324/LER-1986-005-02, :on 860209,during Local Leak Rate Testing, Discovered Nonquantifiable Leakage Rate for Primary Containment Isolation Valve 2-RXS-PV-1222C.Caused by Leakage Past Valve Seat.Valves Being Replaced |
- on 860209,during Local Leak Rate Testing, Discovered Nonquantifiable Leakage Rate for Primary Containment Isolation Valve 2-RXS-PV-1222C.Caused by Leakage Past Valve Seat.Valves Being Replaced
| |
| 05000325/LER-1986-005, :on 860113,control Bldg HVAC Sys Auto Isolated & Train 2A of Control Bldg Emergency Air Filtration Sys Auto Started.Caused by Failure of Isolation Signal Relay K2. Relay & Trip Module Replaced |
- on 860113,control Bldg HVAC Sys Auto Isolated & Train 2A of Control Bldg Emergency Air Filtration Sys Auto Started.Caused by Failure of Isolation Signal Relay K2. Relay & Trip Module Replaced
| |
| 05000324/LER-1986-006-02, :on 860223,automatic Closure of Primary Containment Isolation Valves G16-F004 & F020 & Isolation of Reactor Bldg Ventilation Sys Occurred.Caused by Personnel Error.Plant Sys Returned to Svc |
- on 860223,automatic Closure of Primary Containment Isolation Valves G16-F004 & F020 & Isolation of Reactor Bldg Ventilation Sys Occurred.Caused by Personnel Error.Plant Sys Returned to Svc
| |
| 05000325/LER-1986-006-01, :on 860212 & 16,automatic Isolations of Common Control Bldg HVAC Occurred Due to Actuations of Chlorination Sys Storage Area Detector X-AT-2979.Caused by Chlorine Due to Maint Activity & Flange Leak |
- on 860212 & 16,automatic Isolations of Common Control Bldg HVAC Occurred Due to Actuations of Chlorination Sys Storage Area Detector X-AT-2979.Caused by Chlorine Due to Maint Activity & Flange Leak
| |
| 05000324/LER-1986-007-01, :on 860309,high Radiation Alarm Trip of Reactor Bldg Ventilation Exhaust Radiation Monitor D12-RM-N010B Occurred,Resulting in Automatic Isolation of Bldg Ventilation Sys.Caused by Grounding |
- on 860309,high Radiation Alarm Trip of Reactor Bldg Ventilation Exhaust Radiation Monitor D12-RM-N010B Occurred,Resulting in Automatic Isolation of Bldg Ventilation Sys.Caused by Grounding
| |
| 05000325/LER-1986-007, :on 860224,control Bldg Emergency Air Filtration Sys Train 2A Automatically Actuated Due to Control Bldg Fire Alarm.Caused by Actuation of Fire Detector in Control Room Kitchen Due to Cooking Fumes |
- on 860224,control Bldg Emergency Air Filtration Sys Train 2A Automatically Actuated Due to Control Bldg Fire Alarm.Caused by Actuation of Fire Detector in Control Room Kitchen Due to Cooking Fumes
| |
| 05000324/LER-1986-008, :on 860310,emergency Ac 4160-volt Bus E-4 Automatically Deenergized.Caused by Auxiliary Operator Inadvertently Deenergizing Potential Transformer in Compartment Ako.Bus E-4 Reenergized |
- on 860310,emergency Ac 4160-volt Bus E-4 Automatically Deenergized.Caused by Auxiliary Operator Inadvertently Deenergizing Potential Transformer in Compartment Ako.Bus E-4 Reenergized
| |
| 05000325/LER-1986-008-01, :on 860317,RWCU Sys Inlet Primary Containment Isolation Valve 1-G31-F004 Automatically Closed Due to Primary Containment Isolation Signal.Caused by False Indication of RWCU Area High Temp Condition |
- on 860317,RWCU Sys Inlet Primary Containment Isolation Valve 1-G31-F004 Automatically Closed Due to Primary Containment Isolation Signal.Caused by False Indication of RWCU Area High Temp Condition
| |
| 05000325/LER-1986-009-02, :on 860326,unit Automatically Scrammed as Result of Main Turbine Trip & Stop Valve Closure.Caused by Hydraulic Perturbation of Instruments Common Variable Serving Leg.Evaluation of Event Continuing |
- on 860326,unit Automatically Scrammed as Result of Main Turbine Trip & Stop Valve Closure.Caused by Hydraulic Perturbation of Instruments Common Variable Serving Leg.Evaluation of Event Continuing
| |
| 05000324/LER-1986-009, :on 860311,upscale Spike of Reactor Bldg Ventilation Exhaust Radiation Monitor Instrument Trip Unit Occurred.Cause Not Determined.Trip & Isolation Signals Reset & Sys Returned to Svc |
- on 860311,upscale Spike of Reactor Bldg Ventilation Exhaust Radiation Monitor Instrument Trip Unit Occurred.Cause Not Determined.Trip & Isolation Signals Reset & Sys Returned to Svc
| |
| 05000324/LER-1986-010, :on 860317,primary Containment Group 6 Isolation Signal Occurred,Resulting in Automatic Isolation of Reactor Bldg Ventilation Sys.Caused by Electrical Shorting.Fuse Replaced & Signal Reset |
- on 860317,primary Containment Group 6 Isolation Signal Occurred,Resulting in Automatic Isolation of Reactor Bldg Ventilation Sys.Caused by Electrical Shorting.Fuse Replaced & Signal Reset
| |
| 05000325/LER-1986-010-02, :on 860402 Feeder Breaker 1-AD7 from Auxiliary Transformer to 4,160-volt Ac Bus 1D Automatically Opened, Causing Automatic Reactor Scram.Possibly Caused by Malfunction Induced by Dc Ground |
- on 860402 Feeder Breaker 1-AD7 from Auxiliary Transformer to 4,160-volt Ac Bus 1D Automatically Opened, Causing Automatic Reactor Scram.Possibly Caused by Malfunction Induced by Dc Ground
| |
| 05000324/LER-1986-011, :on 860404,RWCU Sys Inlet Primary Containment Outboard Isolation Valve 2-G31-F004 Automatically Closed, Causing Isolation Trip Signal Initiation.Caused by Blown Fuse.Fuse Replaced |
- on 860404,RWCU Sys Inlet Primary Containment Outboard Isolation Valve 2-G31-F004 Automatically Closed, Causing Isolation Trip Signal Initiation.Caused by Blown Fuse.Fuse Replaced
| |
| 05000324/LER-1986-012, :on 860414,RWCU Sys Suction Valve G31-F001 Automatically Isolated While Performing Wiring Check.Caused by Ambient Temp Isolation Instrument Loose Negative Terminal.Proper Termination Verified |
- on 860414,RWCU Sys Suction Valve G31-F001 Automatically Isolated While Performing Wiring Check.Caused by Ambient Temp Isolation Instrument Loose Negative Terminal.Proper Termination Verified
| |
| 05000324/LER-1986-012-01, :on 860506,high Chlorine Alarm Condition Occurred.Caused by Failure to Close Chlorination Valve 2-CS-V34 Per Operating Procedures.Disciplinary Action Taken W/Personnel Involved |
- on 860506,high Chlorine Alarm Condition Occurred.Caused by Failure to Close Chlorination Valve 2-CS-V34 Per Operating Procedures.Disciplinary Action Taken W/Personnel Involved
| |
| 05000325/LER-1986-013-01, :on 860530,control Bldg Emergency Air Filtration Sys Train 2A Automatically Started Due to Actuation of Area Radiation Monitor/Indicator Trip Unit. Caused by Corroded Sensor.Parts Replaced |
- on 860530,control Bldg Emergency Air Filtration Sys Train 2A Automatically Started Due to Actuation of Area Radiation Monitor/Indicator Trip Unit. Caused by Corroded Sensor.Parts Replaced
| |
| 05000324/LER-1986-013, :on 860423,upscale Trip of Reactor Power source-range Monitor a Occurred While Reactor Protection Sys Shorting Links Removed.Caused by Personnel Error. Technicians Counseled |
- on 860423,upscale Trip of Reactor Power source-range Monitor a Occurred While Reactor Protection Sys Shorting Links Removed.Caused by Personnel Error. Technicians Counseled
| |
| 05000324/LER-1986-014, :on 860429,automatic Trip of Reactor Protection Sys Logic Channels a & B Occurred.Caused by Upscale Trip of Reactor Power intermediate-range Monitor D. Channels Reset |
- on 860429,automatic Trip of Reactor Protection Sys Logic Channels a & B Occurred.Caused by Upscale Trip of Reactor Power intermediate-range Monitor D. Channels Reset
| |
| 05000325/LER-1986-014-01, :on 860702,HPCI Turbine Steam Supply Primary Containment Inboard Isolation Valve E41-F002 Received Autoclose Signals.Caused by Failure of Resistor R1 of Temp Monitoring Module N603D.Module Replaced |
- on 860702,HPCI Turbine Steam Supply Primary Containment Inboard Isolation Valve E41-F002 Received Autoclose Signals.Caused by Failure of Resistor R1 of Temp Monitoring Module N603D.Module Replaced
| |
| 05000324/LER-1986-015, :on 860530,LPCI Subsystem Inoperable within 4 H of Initiating Maint on LPCI Sys Per Action Statements b.2 of Spec 3.5.3.1.Caused by Delay Due to Troubleshooting & Repair of Sensing Leg Isolation Valve |
- on 860530,LPCI Subsystem Inoperable within 4 H of Initiating Maint on LPCI Sys Per Action Statements b.2 of Spec 3.5.3.1.Caused by Delay Due to Troubleshooting & Repair of Sensing Leg Isolation Valve
| |
| 05000325/LER-1986-015-01, :on 860706,autostart of Trains 2A & 2B of Common Control Bldg Emergency Air Filtration Sys Occurred. Caused by Intermittent Failure of Radiation Monitor Sensor/Convertor.Monitor Reset |
- on 860706,autostart of Trains 2A & 2B of Common Control Bldg Emergency Air Filtration Sys Occurred. Caused by Intermittent Failure of Radiation Monitor Sensor/Convertor.Monitor Reset
| |
| 05000324/LER-1986-016-01, :on 860711,automatic Scram Signal Occurred Due to Reactor Low Level During Warmup Flush of Unit RHR Loop B. Caused by Failure to Terminate Warmup Flush Prior to Reactor Level Decreasing to lo-lo Setpoint |
- on 860711,automatic Scram Signal Occurred Due to Reactor Low Level During Warmup Flush of Unit RHR Loop B. Caused by Failure to Terminate Warmup Flush Prior to Reactor Level Decreasing to lo-lo Setpoint
| |
| 05000325/LER-1986-016, :on 860622,automatic Isolation of Control Bldg HVAC Sys Occurred Due to Warning of High Chlorine Alarm in Chlorine Storage Area.Procedures Will Be Revised to Ensure That Chlorination Sys Secured |
- on 860622,automatic Isolation of Control Bldg HVAC Sys Occurred Due to Warning of High Chlorine Alarm in Chlorine Storage Area.Procedures Will Be Revised to Ensure That Chlorination Sys Secured
| |
| 05000325/LER-1986-017-01, :on 860614,16 & 22,required Hourly Fire Watch of Common Bldg HVAC Sys,Cable Spread Rooms,Battery Rooms & Augmented Offgas Bldg Performed Late.Memo Issued to Ensure New Fire Watch Persons Cleared for Access |
- on 860614,16 & 22,required Hourly Fire Watch of Common Bldg HVAC Sys,Cable Spread Rooms,Battery Rooms & Augmented Offgas Bldg Performed Late.Memo Issued to Ensure New Fire Watch Persons Cleared for Access
| |
| 05000325/LER-1986-019, :on 850611,Tech Spec Limits Exceeded Re Performance of Functional Surveillance Testing of Fire Detection Instrumentation.Caused by Incorrect Notations. Personnel Counseled |
- on 850611,Tech Spec Limits Exceeded Re Performance of Functional Surveillance Testing of Fire Detection Instrumentation.Caused by Incorrect Notations. Personnel Counseled
| |
| 05000324/LER-1986-019-01, :on 860722,discovered That Reactor Transversing in-core Probe Sys Channel B,8 & 10 Tubing Pathways Interchanged at Channel Indexing Mechanism.Caused by Misidentification of Tubing |
- on 860722,discovered That Reactor Transversing in-core Probe Sys Channel B,8 & 10 Tubing Pathways Interchanged at Channel Indexing Mechanism.Caused by Misidentification of Tubing
| |
| 05000325/LER-1986-020, :on 860716 & 0806,hourly Fire Watches Performed Late.Caused by Inadequate Supervision & Detention in Control Bldg Elevator.Disciplinary Action Taken & Fire Watch Schedule Will Be Changed |
- on 860716 & 0806,hourly Fire Watches Performed Late.Caused by Inadequate Supervision & Detention in Control Bldg Elevator.Disciplinary Action Taken & Fire Watch Schedule Will Be Changed
| |
| 05000324/LER-1986-020-01, :on 860823,automatic Reactor Scram Occurred Due to Erroneous Reactor Low Level Signal.Caused by Personnel Error.Involved Technician Counseled.Appropriate Personnel Received Training |
- on 860823,automatic Reactor Scram Occurred Due to Erroneous Reactor Low Level Signal.Caused by Personnel Error.Involved Technician Counseled.Appropriate Personnel Received Training
| |
| 05000324/LER-1986-021-01, :on 860919,reactor Protection Sys Bus a Inadvertently Deenergized Due to Personnel Error.Bus Output Breakers Opened Instead of Respective Unit 1 Breakers. Personnel Disciplined |
- on 860919,reactor Protection Sys Bus a Inadvertently Deenergized Due to Personnel Error.Bus Output Breakers Opened Instead of Respective Unit 1 Breakers. Personnel Disciplined
| |
| 05000325/LER-1986-021, :on 860819,automatic Scram Occurred Due to Main Turbine Trip/Stop Valve Fast Closure from Main Turbine Master Trip Signal.Caused by Electrical Grounding of Dc Power Supply of Limit Switch |
- on 860819,automatic Scram Occurred Due to Main Turbine Trip/Stop Valve Fast Closure from Main Turbine Master Trip Signal.Caused by Electrical Grounding of Dc Power Supply of Limit Switch
| |
| 05000324/LER-1986-022-01, :on 861003,reactor Shut Down Due to Unsuccessful Restart of Motor Generator Set.Caused by Opened Fuses.Fuse 7 Transformer Replaced,Motor Generator Restarted & Loop Returned to Svc |
- on 861003,reactor Shut Down Due to Unsuccessful Restart of Motor Generator Set.Caused by Opened Fuses.Fuse 7 Transformer Replaced,Motor Generator Restarted & Loop Returned to Svc
| |
| 05000325/LER-1986-022, :on 860821,intermediate Range Monitors Tripped Upscale,Resulting in Reactor Scram.Cause Undetermined. Intermediate Range Monitors Grounding Straps Cleaned as Preventive Measure |
- on 860821,intermediate Range Monitors Tripped Upscale,Resulting in Reactor Scram.Cause Undetermined. Intermediate Range Monitors Grounding Straps Cleaned as Preventive Measure
| |
| 05000325/LER-1986-023, :on 860905,Tech Spec 3.0.3 Entered When Reactor Core Spray Subsys B & RHR LPCI Loop B Found Inoperable.Caused by Loss of 125-volt Dc Control Power. Control Power Returned |
- on 860905,Tech Spec 3.0.3 Entered When Reactor Core Spray Subsys B & RHR LPCI Loop B Found Inoperable.Caused by Loss of 125-volt Dc Control Power. Control Power Returned
| |
| 05000324/LER-1986-023-01, :on 861009,primary Containment Group 4 Isolation of HPCI Sys Occurred.Caused by Loss of Electrical Continuity at Terminal Connections of Thermocouple Leads. Thermocouple Lead Terminations Improved |
- on 861009,primary Containment Group 4 Isolation of HPCI Sys Occurred.Caused by Loss of Electrical Continuity at Terminal Connections of Thermocouple Leads. Thermocouple Lead Terminations Improved
| |
| 05000325/LER-1986-024, :on 860913,automatic Reactor Scram Occurred Due to 90% Full Open MSIV Position.Caused by Main Generator Output Voltage Oscillations.Manual Potentiometer Contact Wiper & Slide Assembly Replaced |
- on 860913,automatic Reactor Scram Occurred Due to 90% Full Open MSIV Position.Caused by Main Generator Output Voltage Oscillations.Manual Potentiometer Contact Wiper & Slide Assembly Replaced
| |
| 05000324/LER-1986-024-01, :on 861021,core Spray Subsys Pumps a & B Started & Injected 7,500-9,000 Gallons of Water from Torus Into Reactor.Caused by Personnel Error During Maint of Eccs. Personnel Disciplined & Inverters Relabeled |
- on 861021,core Spray Subsys Pumps a & B Started & Injected 7,500-9,000 Gallons of Water from Torus Into Reactor.Caused by Personnel Error During Maint of Eccs. Personnel Disciplined & Inverters Relabeled
| |
| 05000325/LER-1986-025, :on 860916,control of Bldg HVAC Sys & Control Bldg Emergency Air Filtration Autoisolated,Causing Train 2B to Start.Caused by Open Relay Coil.Relay Replaced & Sys Returned to Svc |
- on 860916,control of Bldg HVAC Sys & Control Bldg Emergency Air Filtration Autoisolated,Causing Train 2B to Start.Caused by Open Relay Coil.Relay Replaced & Sys Returned to Svc
| |
| 05000324/LER-1986-025-01, :on 861120,determined That 861119 Surveillance of Reactor Jet Pump Missed.Caused by Personnel Error. Surveillance Performed Satisfactorily.Personnel Disciplined & Training Initiated |
- on 861120,determined That 861119 Surveillance of Reactor Jet Pump Missed.Caused by Personnel Error. Surveillance Performed Satisfactorily.Personnel Disciplined & Training Initiated
| |
| 05000324/LER-1986-025, :on 861119,determined That Surveillance Testing for Reactor Jet Pump Not Performed.Caused by Personnel Error.Personnel Involved discplined.Real-time Training Completed |
- on 861119,determined That Surveillance Testing for Reactor Jet Pump Not Performed.Caused by Personnel Error.Personnel Involved discplined.Real-time Training Completed
| |
| 05000324/LER-1986-026-01, :on 861211,fire Watches Performed 15 Minutes Late.Caused by Restricted Access to Affected Fire Watch Areas Due to Radiological Spill Onto 50-ft Elevation Floor. Fire Watches Conducted & Personnel Disciplined |
- on 861211,fire Watches Performed 15 Minutes Late.Caused by Restricted Access to Affected Fire Watch Areas Due to Radiological Spill Onto 50-ft Elevation Floor. Fire Watches Conducted & Personnel Disciplined
| |
| 05000325/LER-1986-026, :on 860917,unit Manually Scrammed as Result of Leak in Main Condenser Online Tubing Cleaning Sys.Caused by Corrosion of Device Piping Matl.Amertap Corp Part 1AM-OB-1004 Replaced |
- on 860917,unit Manually Scrammed as Result of Leak in Main Condenser Online Tubing Cleaning Sys.Caused by Corrosion of Device Piping Matl.Amertap Corp Part 1AM-OB-1004 Replaced
| |
| 05000325/LER-1986-027, :on 861001,sampling & Isotopic Analysis of Steam Jet Air Ejector (SJAE) Discharge Not Performed within 4 H of 50% Increase in SJAE Discharge Radiation Reading. Caused by Operator Error.Operator Disciplined |
- on 861001,sampling & Isotopic Analysis of Steam Jet Air Ejector (SJAE) Discharge Not Performed within 4 H of 50% Increase in SJAE Discharge Radiation Reading. Caused by Operator Error.Operator Disciplined
| |