|
---|
Category:NPDES NONCOMPLIANCE NOTIFICATION
MONTHYEARML20206C9871999-04-27027 April 1999 NPDES Noncompliance Notification:On 990319,station Personnel Observed Foam Emanating from Manhole Vent Associated with Outfall 001,no Foam Was Observed on Any Waterway.Caused by Inappropriate Addition of Betz 3625 to Spray Pond ML20207D6171999-02-26026 February 1999 NPDES Noncompliance Notification:On 990111,discovered That Weelkly Analysis for non-oxidizing Biocide Betz 3625 Was Not Performed.Caused by Sample Being Inappropriately Delayed for Future Chemical Addition.Counseled Individuals Involved ML20202F0591999-01-19019 January 1999 NPDES Noncompliance Notification:On 990112,Auxiliary Boiler Source Number OAS502 Found to Have Malfunctioning Opacity Monitor.Caused by Stepdown Transformer within Power Supply. Power Supply Replaced ML20198J2811998-12-21021 December 1998 NPDES Noncompliance Notification:On 981102,release of 500 Gallons of 12% Sodium Hypochlorite to Environment Occurred. Caused by Failure of Tank Discharge Fittings.Integrity Testing Will Be Performed on All New Tanks.With ML20206R3491998-12-21021 December 1998 NPDES Noncompliance Notification:On 981102,500 Gallons of 12% Sodium Hypochlorite Released to Environ.Caused by Failure of Tank Discharge Fittings & Subsequent Leaks from Secondary Containment.Culvert Was Flushed Repeatedly ML20236V2001998-07-27027 July 1998 NPDES Noncompliance Notification:On 980619,geometric Mean Coliform Concentration Calculated to Be 223 Colonies Per 100 Ml.Sample Procedure Enhanced to Ensure Normal Operating Conditions ML20248C9461998-05-27027 May 1998 NPDES Noncompliance Notification:On 980414,total Iron Discharge Through Outfall 001 Exceeded Limits Set in Ltr Dtd 960508.Total Iron Discharge Limit Exceeded During Cleaning Evolution.Limit Revised ML20217N6921998-02-27027 February 1998 NPDES Noncompliance Notification:On 980107 Net Total Suspended Solids (TSS) for Units 1 & 2 Cooling Towers at Outfall 001 Exceeded NPDES Permit Daily Limit of 60 Ppm. Caused by Contaminated Sample Lines.Replaced Tygon Tubing ML20141G0271997-06-27027 June 1997 NPDES Noncompliance Notification:On 970512,sample for Kjeldahl Omitted Due to Personnel Error.Counseled Individual Responsible.On 970521,Net TSS Exceeded NPDES Daily Limit Due to Fouled Sample Tubing.Replaced Sample Tubing ML20137M5511997-03-27027 March 1997 NPDES Noncompliance Notification:On 970228,flow Integrator Used to Measure Spray Pond Effluent Flow Was Identified to Be Malfunctioning & Declared Inoperable Due to Lodged Debris.Revised Procedure for Spray Pond Effluent Flow ML20134G3241997-01-31031 January 1997 NPDES Noncompliance Notification:On 970108,util Informed NRC That PA Dept of Environ Protection Granted Approval for Temporary Discharge at Lgs,Per 961219 ML20138G9651996-12-24024 December 1996 NPDES Noncompliance Notification:On 960428,calibration of Flowmeter Used to Measure Spray Pond Flow Was Not Checked on Routine Basis Because Person Required to Develop Maint Was Unaware of Requirements.Installed New Meter ML20135A5851996-11-27027 November 1996 NPDES Noncompliance Notification:On July-Sept 1996 Re NPDES Limit for Fecal Coloform Concentration Not Met.Caused by Inadequate Gasket Installation.Ozonators Overhauled to Ensure Peak Performance ML20134E0641996-10-28028 October 1996 NPDES Noncompliance Notification:During Month of Sept 1996, NPDES Limit for Fecal Coliform Concentration at Discharge of Bradshaw Reservoir Pumps Was Not Met.Caused by Leaking Gaskets on Ozone Gas Diffusers.New Gaskets,Installed ML20129E5681996-09-27027 September 1996 NPDES Noncompliance Notification:On 960805,geometric Mean of Fecal Coliform Concentration Calculated to Be 641 Colonies Per 100 Ml.Cause Suspected to Be Due to Malfunctioning Ozone Disinfection Sys.Adjustments to Sys Have Been Made ML20129E5411996-09-26026 September 1996 NPDES Noncompliance Notification:On 960812,discharge Observed from Unit 2 Cooling Tower Overflow to Outfall 021. Caused by Personnel Error in Performing Required Analysis of Cooling Tower Overflow Sample.Individual Counseled ML20117G7071996-08-23023 August 1996 NPDES Noncompliance Notification:On 960715,geometric Mean of Fecal Coliform Concentration Exceeded NPDES Permit Limit. Caused by Leaking Seals on Ozone Diffusers.Temporary Adjustments Made to Ozone Gas Flow Balance ML20116B3851996-07-24024 July 1996 NPDES Noncompliance Notification:On 960602 Identified Ph Levels Exceeded NPDES Permit Limitations.Caused by Natural Biological activity.CO2 Injection Established,Maintained & Monitored Until 960612 ML20115G1151996-07-12012 July 1996 NPDES Noncompliance Notification:On 960619,resulting Net TSS Value 82.8 mg/1,exceeded Max Daily Limit of 60 Mg/L.Caused by Excessive Storm Water Runoff.Net TSS Revised ML20113C4451996-06-24024 June 1996 NPDES Noncompliance Notification:On 960318,flow Integrator Used to Measure Spray Pond Effluent Flow Declared Inoperable.Caused by Faulty Flow Integrator.Frequency of Use of Instrument Changed to Daily as Stated in Issue Number ML20108A3671996-04-28028 April 1996 NPDES Noncompliance Notification:On 960314,personnel Observed Sewage Overflowing from MH-07 & Into Storm Drain W-4.Caused by Blockage of Pipe Section Between MH-07 & MH-08.Sewer Contract Svc Pressure Cleaned ML20108A3801996-04-28028 April 1996 NPDES Noncompliance Notification:On 960223,identified Seven Issues of Administrative non-compliance/ambiguity W/Permits. Caused by Inadequate Administration.Individuals Gained Better Understanding W/Guidance ML20101K4661996-03-28028 March 1996 NPDES Noncompliance Notification:On 960218,discovered That No Records Existed for Bradshae Reservoir Discharge Water Temp for Listed Time Periods.Caused by Temporary Reassigment of Personnel.Review of Staffing in Progress ML20100P6311996-02-28028 February 1996 NPDES Noncompliance Notification:On 951108,discharge 001 Net TSS in Excess of Maximum Daily Limit.Caused by Flaw in Methodology to Calculate Net TSS concentration.Follow-up Composite Samples Taken ML20072R4601994-08-31031 August 1994 NPDES Noncompliance Notification:On 940708 & 0815,Discharge 001 Total Zinc Concentrations Exceeded Max Daily Limitations.Daily Zinc Trending Analysis Will Be Upgraded & Chemistry Technician Involved in 940815 Event Counselled ML20071L1761994-07-27027 July 1994 NPDES Noncompliance Notification:On 940609,zinc Analyses Indicated That Discharge 001 Total Zinc Levels in Excess of Max Daily Limitations in Both Cooling Towers.Daily Zinc Control Limits Will Be Administratively Maintained Lower ML20149E7291994-07-26026 July 1994 NPDES Discharge Monitoring Rept:On 940713,approx 18 Gallons of Betz Clamtrol CT-1 Inadvertently Released from Injection Sys Located South of LGS Spraypond Pumphouse.Caused by Break in Pump Discharge Line.Polyethylene Piping Replaced ML20065B9221994-03-25025 March 1994 NPDES Noncompliances Notification:On 940204,discharge 001 Maximum Daily Limit of 1.0 mg/1 Total Zinc Was Exceeded. Caused by Low Ph Transient in Unit 2 Cooling Tower Water Sys.Isolated Acid Injection Sys ML20064C7701994-02-25025 February 1994 NPDES Noncompliance Notification:On 940116 & 17 Manual Reactor Scram Occurred.Caused by Failure to Adequately Throttle Cooling Tower Bypass Valves.Procedure Revised ML20059C4941993-10-26026 October 1993 NPDES Noncompliance Notification:On 930907,cooling Tower Blowdown Water Discharged Into Possum Hollow Creek Due to Loss of Two of Four Operating Circulating Water Pumps. Procedures for Performing Excavations Revised ML20056G3921993-08-27027 August 1993 NPDES Noncompliance Notification:On 930710,13,14 & 25, Water Processing Facility (Wpf) Discharge Temp Exceeded Max Limitation of 74 Degrees F.Rev to NPDES Permit,Removing Temp Limits Approved & Wpf Chillers Removed from Svc ML20024H8441993-08-19019 August 1993 NPDES Noncompliance Notification Re Perkiomen Storage Tank Overflow to Possum Hollow Run.Application for Amend to Permit PA0051926 Submitted ML20046B8051993-07-29029 July 1993 NPDES Noncompliance Notification:On 930618,20 & 27,water Processing Facility Temp Exceeded Permitted Max Limitation of 74 Degrees F.Caused by Lack of Training & Written Instructions.Training Provided & Addl Instruction Issued ML20044G7641993-05-21021 May 1993 NPDES Noncompliance Notification:From 930417-18,equipment Problems Occurred Which Rendered Dissolved Oxygen & Ph Monitoring Instrumentation Inoperable.Caused by Debris in Sample Line.Methods for Filtering Flow Under Investigation ML20044C4051993-03-16016 March 1993 NPDES Noncompliance Notification:On 930222,discovered That Contractor Personnel Discharged Treated Water from Fire Hydrant Supplied by Unit 1 Cooling Tower Into Storm Water Drain E-3.2.Caused by Personnel Error.Label Applied ML20128N1251993-02-17017 February 1993 NPDES Noncompliance Notification:On 930103,cooling Tower Blowdown Water Overflowed from Discharge 001 Pipeline & Flowed Into Possum Hollow Creek.Caused by Failure to Throttle Unit 2 Bypass Valves.Procedure Changed ML20128A5071993-01-25025 January 1993 NPDES Noncompliance Notification:On 921117 & 25,analytical Results for inductively-coupled Plasma Analyzer at Discharge Point 001 Exceeded Zinc Concentration.Total Zinc Concentration Analysis Will Be Performed Onsite ML20126G9991992-12-24024 December 1992 NPDES Noncompliance Notification:On 921104,dissolved Oxygen Monitoring Equipment at Bradshaw Reservoir Discharge & Water Processing Facility Became Fouled by Organic Concentrations. Caused by Heavy Rainfall.Manual Samples Will Be Obtained ML20117A5761992-11-23023 November 1992 NPDES Noncompliance Notification:On 921013 & 14,four of Five Samples Collected from Discharge Point 001 Exceeded Daily Max Permit Limit of 1.0 Mg/L.Caused by Heavy Rains Across Southeastern PA on 921009.Injection Rates Decreased ML20101H5321992-06-26026 June 1992 NPDES Noncompliance Notification:On 920504,crack Discovered on Above Ground Cleanout for Sewage Line Leading from Plant Training Ctr to Plant Sewage Sys Holding Tanks.Caused by Expansion of Sewage Spill Line.Clamps Installed ML20095J1201992-04-23023 April 1992 NPDES Noncompliance Notification:On 920322,cooling Tower Blowdown Water Discharged Into Possum Hollow Creek.Caused by Procedure Deficiency.Sys Operating Procedure S09.4.A Expected to Be Revised by 920501 ML20141M0551992-03-25025 March 1992 NPDES Noncompliance Notification:On 920206,rain Water Pumped from Eletrical Manhole Into Storm Water Runoff Drain Due to Inadequate Procedural Guidance.Blue Drains to Be Labelled, Indicating Use for Storm Water Runoff Only by 920801 ML20091Q4301992-01-23023 January 1992 NPDES Noncompliance Notification:On 911218 Cooling Tower Blowdown Water Discharged to Possum Hollow Creek Resulting in Unpermitted Discharge Due to Failure to Identify & Revise All Appropriate Procedures.Procedure GP-3 to Be Revised ML20086E4981991-11-22022 November 1991 NPDES Noncompliance Notification:On 911016 Underground Fire Water Pipeline Inadvertently Punctured by Contractor Backhoe Ram During Excavation of Trench.Caused by Inadequate Review of Required Prints.Backhoe Ram Operator Terminated ML20082L9871991-08-28028 August 1991 NPDES Noncompliance Notification:On 910707 & 19,electrical Storm Caused Loss of Power to Bedminster Water Processing Facility & Tripped Chillers.On 910721,discharge Temp Exceeded Permitted Limits.Permit Limits Changed ML20217C2131991-07-0808 July 1991 NPDES Noncompliance Notification:On 910629,chillers at Bedminster Water Processing Facility for Bradshaw Reservoir Tripped Due to Unexpected Failure of Logic Control Unit. Chiller Control to Primary Computer Restored ML20077G5771991-06-20020 June 1991 NPDES Noncompliance Notification:On 910528,chiller C at Bedminster Water Processing Facility Tripped Due to High Vibration & Temp at Discharge 001 Exceeding Permitted Instantaneous Temp.Discharge Temp Setpoint Lowered ML20077D8701991-05-17017 May 1991 NPDES Noncompliance Notification:On 910512,cooling Tower Experienced Failure,Causing Large Vol of Cooling Tower Water to Bypass Normal Blowdown Discharge Pathway.Cooling Tower Will Be Inspected During mid-yr Outage ML20070S3071991-03-22022 March 1991 NPDES Noncompliance Notification:On 910204,discovered That Misalignment of Diverter Valve to Outfall 003 May Have Allowed Mixture of Storm Water & Steam Condensate to Be Released from Outfall.Valve Repositioned ML20065M6811990-11-29029 November 1990 NPDES Noncompliance Notification:On 901003,routine Weekly Discharge 001 Sample Exceeded Max Permit Limits for Grease & Oil.Sample Contained 43.7 Mg Per Liter of Oil & Grease. Abnormal Reading Believed to Be Caused by Oily Silt 1999-04-27
[Table view] Category:TEXT-ENVIRONMENTAL REPORTS
MONTHYEARML20206C9871999-04-27027 April 1999 NPDES Noncompliance Notification:On 990319,station Personnel Observed Foam Emanating from Manhole Vent Associated with Outfall 001,no Foam Was Observed on Any Waterway.Caused by Inappropriate Addition of Betz 3625 to Spray Pond ML20207D6171999-02-26026 February 1999 NPDES Noncompliance Notification:On 990111,discovered That Weelkly Analysis for non-oxidizing Biocide Betz 3625 Was Not Performed.Caused by Sample Being Inappropriately Delayed for Future Chemical Addition.Counseled Individuals Involved ML20202F0591999-01-19019 January 1999 NPDES Noncompliance Notification:On 990112,Auxiliary Boiler Source Number OAS502 Found to Have Malfunctioning Opacity Monitor.Caused by Stepdown Transformer within Power Supply. Power Supply Replaced ML20206E2161998-12-31031 December 1998 1998 Annual Environ Operating Rept (Non-Radiological) for Limerick Generating Station,Units 1 & 2 ML20205T0581998-12-31031 December 1998 Annual Radiological Environ Operating Rept 15 for 1998 ML20206R3491998-12-21021 December 1998 NPDES Noncompliance Notification:On 981102,500 Gallons of 12% Sodium Hypochlorite Released to Environ.Caused by Failure of Tank Discharge Fittings & Subsequent Leaks from Secondary Containment.Culvert Was Flushed Repeatedly ML20198J2811998-12-21021 December 1998 NPDES Noncompliance Notification:On 981102,release of 500 Gallons of 12% Sodium Hypochlorite to Environment Occurred. Caused by Failure of Tank Discharge Fittings.Integrity Testing Will Be Performed on All New Tanks.With ML20236V2001998-07-27027 July 1998 NPDES Noncompliance Notification:On 980619,geometric Mean Coliform Concentration Calculated to Be 223 Colonies Per 100 Ml.Sample Procedure Enhanced to Ensure Normal Operating Conditions ML20248C9461998-05-27027 May 1998 NPDES Noncompliance Notification:On 980414,total Iron Discharge Through Outfall 001 Exceeded Limits Set in Ltr Dtd 960508.Total Iron Discharge Limit Exceeded During Cleaning Evolution.Limit Revised ML20217N6921998-02-27027 February 1998 NPDES Noncompliance Notification:On 980107 Net Total Suspended Solids (TSS) for Units 1 & 2 Cooling Towers at Outfall 001 Exceeded NPDES Permit Daily Limit of 60 Ppm. Caused by Contaminated Sample Lines.Replaced Tygon Tubing ML20203H1911997-12-31031 December 1997 Annual Effluent Release Rept 23 for Jan-Dec 1997 ML20216F3371997-12-31031 December 1997 Annual Environmental Operating Rept (Non-Radiological) for 970101-1231 ML20203L5691997-12-31031 December 1997 Occupational Exposure Tabulation Rept for LGS Units 1 & 2 for 1997 ML20203H2201997-12-31031 December 1997 Tower 1 Joint Frequency Distributions of Wind Speed & Direction by Atmospheric Stability Class Rept 13 for 1997 ML20217P1941997-12-31031 December 1997 Annual Environ Operating Rept (Non-Radiological) for Jan-Dec 1997, for LGS Units 1 & 2 ML20217M6471997-12-31031 December 1997 Annual Radiological Environ Operating Rept 14,Jan-Dec 1997 for Limerick Generating Station,Units 1 & 2 ML20141G0271997-06-27027 June 1997 NPDES Noncompliance Notification:On 970512,sample for Kjeldahl Omitted Due to Personnel Error.Counseled Individual Responsible.On 970521,Net TSS Exceeded NPDES Daily Limit Due to Fouled Sample Tubing.Replaced Sample Tubing ML20137M5511997-03-27027 March 1997 NPDES Noncompliance Notification:On 970228,flow Integrator Used to Measure Spray Pond Effluent Flow Was Identified to Be Malfunctioning & Declared Inoperable Due to Lodged Debris.Revised Procedure for Spray Pond Effluent Flow ML20134G3241997-01-31031 January 1997 NPDES Noncompliance Notification:On 970108,util Informed NRC That PA Dept of Environ Protection Granted Approval for Temporary Discharge at Lgs,Per 961219 ML20135D0161996-12-31031 December 1996 Occupational Exposure Tabulation Rept for LGS Units 1 & 2 for 1996 ML20148B6671996-12-31031 December 1996 LGS Units 1 & 2 Annual Radiological Environ Operating Rept 13 for 960101-1231 ML20135C7691996-12-31031 December 1996 1996 Annual Effluent Release Rept No 22 ML20138J5291996-12-31031 December 1996 Annual Environ Operating Rept (Non-Radiological) for Jan- Dec 1996 ML20135C7731996-12-31031 December 1996 1996 Annual Tower No 1 Joint Frequency Distribution of Wind Speed & Direction by Atmospheric Stability Class Rept No 12 ML20138G9651996-12-24024 December 1996 NPDES Noncompliance Notification:On 960428,calibration of Flowmeter Used to Measure Spray Pond Flow Was Not Checked on Routine Basis Because Person Required to Develop Maint Was Unaware of Requirements.Installed New Meter ML20135A5851996-11-27027 November 1996 NPDES Noncompliance Notification:On July-Sept 1996 Re NPDES Limit for Fecal Coloform Concentration Not Met.Caused by Inadequate Gasket Installation.Ozonators Overhauled to Ensure Peak Performance ML20134E0641996-10-28028 October 1996 NPDES Noncompliance Notification:During Month of Sept 1996, NPDES Limit for Fecal Coliform Concentration at Discharge of Bradshaw Reservoir Pumps Was Not Met.Caused by Leaking Gaskets on Ozone Gas Diffusers.New Gaskets,Installed ML20129E5681996-09-27027 September 1996 NPDES Noncompliance Notification:On 960805,geometric Mean of Fecal Coliform Concentration Calculated to Be 641 Colonies Per 100 Ml.Cause Suspected to Be Due to Malfunctioning Ozone Disinfection Sys.Adjustments to Sys Have Been Made ML20129E5411996-09-26026 September 1996 NPDES Noncompliance Notification:On 960812,discharge Observed from Unit 2 Cooling Tower Overflow to Outfall 021. Caused by Personnel Error in Performing Required Analysis of Cooling Tower Overflow Sample.Individual Counseled ML20117G7071996-08-23023 August 1996 NPDES Noncompliance Notification:On 960715,geometric Mean of Fecal Coliform Concentration Exceeded NPDES Permit Limit. Caused by Leaking Seals on Ozone Diffusers.Temporary Adjustments Made to Ozone Gas Flow Balance ML20116B3851996-07-24024 July 1996 NPDES Noncompliance Notification:On 960602 Identified Ph Levels Exceeded NPDES Permit Limitations.Caused by Natural Biological activity.CO2 Injection Established,Maintained & Monitored Until 960612 ML20115G1151996-07-12012 July 1996 NPDES Noncompliance Notification:On 960619,resulting Net TSS Value 82.8 mg/1,exceeded Max Daily Limit of 60 Mg/L.Caused by Excessive Storm Water Runoff.Net TSS Revised ML20113C4451996-06-24024 June 1996 NPDES Noncompliance Notification:On 960318,flow Integrator Used to Measure Spray Pond Effluent Flow Declared Inoperable.Caused by Faulty Flow Integrator.Frequency of Use of Instrument Changed to Daily as Stated in Issue Number ML20108A3801996-04-28028 April 1996 NPDES Noncompliance Notification:On 960223,identified Seven Issues of Administrative non-compliance/ambiguity W/Permits. Caused by Inadequate Administration.Individuals Gained Better Understanding W/Guidance ML20108A3671996-04-28028 April 1996 NPDES Noncompliance Notification:On 960314,personnel Observed Sewage Overflowing from MH-07 & Into Storm Drain W-4.Caused by Blockage of Pipe Section Between MH-07 & MH-08.Sewer Contract Svc Pressure Cleaned ML20101K4661996-03-28028 March 1996 NPDES Noncompliance Notification:On 960218,discovered That No Records Existed for Bradshae Reservoir Discharge Water Temp for Listed Time Periods.Caused by Temporary Reassigment of Personnel.Review of Staffing in Progress ML20100P6311996-02-28028 February 1996 NPDES Noncompliance Notification:On 951108,discharge 001 Net TSS in Excess of Maximum Daily Limit.Caused by Flaw in Methodology to Calculate Net TSS concentration.Follow-up Composite Samples Taken ML20108C9281995-12-31031 December 1995 LGS Units 1 & 2 1995 Annual Environ Operating Rept (Non- Radiological) Jan-Dec 1995 ML20100L8861995-12-31031 December 1995 Annual Effluent Release Rept 21,Jan-Dec 1995 ML20108B7391995-12-31031 December 1995 Annual Radiological Environ Operating Rept 12 Jan-Dec 1995 ML20100L8961995-12-31031 December 1995 Tower 1 Joint Frequency Distributions of Wind Speed & Direction by Atmospheric Stability Class 1995 Rept 11 ML20080N1061994-12-31031 December 1994 Annual Effluent Release Rept 20 Jan-Dec 1994 PECO Energy LGS Units 1 & 2 ML20082N5061994-12-31031 December 1994 Annual Environ Operating Rept ML20087H7231994-12-31031 December 1994 Annual Radiological Environ Operating Rept 11 for Jan-Dec 1994 ML20080N1121994-12-31031 December 1994 Tower 1 Joint Frequency Distributions of Wind Speed & Direction by Atmospheric Stability Class 1994 Rept 10 ML20072R4601994-08-31031 August 1994 NPDES Noncompliance Notification:On 940708 & 0815,Discharge 001 Total Zinc Concentrations Exceeded Max Daily Limitations.Daily Zinc Trending Analysis Will Be Upgraded & Chemistry Technician Involved in 940815 Event Counselled ML20071L1761994-07-27027 July 1994 NPDES Noncompliance Notification:On 940609,zinc Analyses Indicated That Discharge 001 Total Zinc Levels in Excess of Max Daily Limitations in Both Cooling Towers.Daily Zinc Control Limits Will Be Administratively Maintained Lower ML20149E7291994-07-26026 July 1994 NPDES Discharge Monitoring Rept:On 940713,approx 18 Gallons of Betz Clamtrol CT-1 Inadvertently Released from Injection Sys Located South of LGS Spraypond Pumphouse.Caused by Break in Pump Discharge Line.Polyethylene Piping Replaced ML20065B9221994-03-25025 March 1994 NPDES Noncompliances Notification:On 940204,discharge 001 Maximum Daily Limit of 1.0 mg/1 Total Zinc Was Exceeded. Caused by Low Ph Transient in Unit 2 Cooling Tower Water Sys.Isolated Acid Injection Sys ML20064C7701994-02-25025 February 1994 NPDES Noncompliance Notification:On 940116 & 17 Manual Reactor Scram Occurred.Caused by Failure to Adequately Throttle Cooling Tower Bypass Valves.Procedure Revised 1999-04-27
[Table view] |
Text
.
PHILADELPHIA ELECTRIC COMPANY LIMERICK GENERATING STATION i P. O. BOX 2300 !
SANATOGA, PA 19464-2300 (215) 327-1200 EXT. 2000 ROBERT W. BOYCE tuNr u4u4aEs August 27 , 1993 UMERICK GENERATING STATION Mr. Peter G. Noll Department of Health Neshaminy Manor Center Doylestown, PA 18901
Subject:
Noncompliances with NPDES Permit Bradshaw Reservoir ,
NPDES Permit No. PA-0052221 j i
Dear Mr. Noll:
i During the month of July 1993, four noncompliances with NPDES Permit No. PA-0052221, Bradshaw Reservoir, occurred. All four ,
noncompliances resulted from the Water Processing Facility (WPP) 'I discharge temperature exceeding the permitted maximum limitaticn ,
of 74 degrees F. Each noncompliance is described below including i the causes and corrective actions.
t
- 1. DESCRIPTION OF NONCOMPLIANCE NO. 1 r
On July 10, 1993, between 1100 hours0.0127 days <br />0.306 hours <br />0.00182 weeks <br />4.1855e-4 months <br /> and 2000 hours0.0231 days <br />0.556 hours <br />0.00331 weeks <br />7.61e-4 months <br />, due to !
extreme ambient conditions (heat wave), the WPF discharge 4 temperature exceeded the permitted limit of 74 degrees F.
The maximum temperature recorded during this time period has 75.2 degrees F. Discharge flow had been reduced as low as -;
possible in an attempt to maintain discharge temperature !
below the permit limit. The minimum required East Branch '
Perkiomen Creek flow rate was maintained. !
- i CAUSE OF THE NONCOMPLIANCE -l The actual operating conditions on July 10, 1993,-were beyond the design basis conditions of the WPP. Prior to the i violation, the cooling equipment had been thoroughly checked -
and adjustments were made to ensure the full cooling capacity of the facility was being-achieved.
9309030075 930827
[
PDR ADOCK 05000352 h
- I
)
S PDR h
1 Page 2 PREVENTION OF-A' FUTURE OCCURRENCE On July 29, 1993, a revision to the NPDES permit which removed all temperature limits was approved by the DER. On July 29, 1993, the WPF chillers were removed from service.
- 2. DESCRIPTION OF NONCOMPLIANCE NO. 2 At 1341 hours0.0155 days <br />0.373 hours <br />0.00222 weeks <br />5.102505e-4 months <br /> on July 13, 1993, the WPF chillers automatically shutdown due to a false low facility flow signal. Bradshaw flow was immediately reduced to the summer minimum East Branch Perkiomen Creek flow rate. During the next 1 1/2 hours attempts were made to restart the chillers; however the chillers tripped twice again on low facility flow. At 1510 hours0.0175 days <br />0.419 hours <br />0.0025 weeks <br />5.74555e-4 months <br />, the low facility flow shutdown signal was bypassed, thereby allowing the chillers to continue to operate. As a result of this transient, the discharge temperature limit of 74 degrees F was exceeded for approximately two hours, with the maximum instantaleous temperature reaching about 83 degrees F.
CAUSE OF THE NONCOMPLIANCE The unexpected chiller shutdowns were caused by an erratic facility inlet flow signal. The cooling equipment automatically shuts down when measured inlet flow drops to 8000 gpm to prevent the evaporator pumps from emptying the facility reservoirs.
The erratic flow signal was believed to be due to debris on the paddlewheel of the inlet flow sensor. Several hours later the signal returned.to normal. Facility design did not adequately address this potential problem.
PREVENTION OF A FUTURE OCCURRENCE On July 14, 1993, a time delay was incorporated into the control system for low facility flow shutdown. This was done
.to prevent future shutdowns when the inlet flow signal drops below 8000 gpm momentarily. No additional unexpected shutdowns on low facility flow have occurred since the incorporation of this time delay. Since the NPDES permit was revised on July 29, 1993, the WPF chillers will no longer be operated and the erratic flow signal will no longer affect permit compliance.
- 3. DESCRIPTION OF NONCOMPLIANCE NO. 3 At 2231 hours0.0258 days <br />0.62 hours <br />0.00369 weeks <br />8.488955e-4 months <br /> on July 14, 1993, the Bradshaw Reservoir pumps tripped during an electrical storm and subsequently the WPF chillers shutdown by design on low facility flow. During the process of restarting the chillers after the Bradshaw Reservoir pumps automatically restarted, the discharge temperature exceeded the limit of 74 degrees F, with the maximum instan'taneous temperature reaching about 82 degrees
I Page 3
}
F'. Temperature was stabilized below 74 degrees F by 2305 l hours. Shortly thereafter, it was recognized that the 3 Bradshaw Reservoir pumps would have to be shutdown in order j to select a different lead pump such that the required number of pumps could be operated. ;
.i At 0030 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br /> on July 15, 1993, the Bradshaw Reservoir. pumps [
were shutdown, and the pumps were restarted at 0040 hours4.62963e-4 days <br />0.0111 hours <br />6.613757e-5 weeks <br />1.522e-5 months <br />. E While attempting to restart the WPP chillers as the Bradshaw .!
flow was gradually being increased, all three chillers
tripped immediately after starting. This caused a 30 minute restart lock-out for motor protection. As a result, :
discharge temperature exceeded the 74 degrees F limit with a j maximum temperature of 82 degrees P from 0110.to 0220 hours0.00255 days <br />0.0611 hours <br />3.637566e-4 weeks <br />8.371e-5 months <br />, '
while the required summer minimum East Branch Perkiomen Creek '
flow rate was being maintained. -
CAUSE OF THE NONCOMPLIANCE:
The temperature limit violation on July 14, 1993, was due to i written instructions for the WPF system not being fully i followed. Contrary to recently provided training and written !
instructions available in the Main Control Room, Bradshaw l flow was not gradually increased to match cooling capacity as l the chillers were being restarted. [
The causes of the chiller trips resulting in the July 15, 1993 temperature limit violation were spurious and are indeterminant. Each chiller subsequently restarted without j incident. '
PREVENTION OF A PUTURE OCCURRENCE: )
5 The individual involved in the July 14, 1993, violation was i counseled regarding the need for attention to detail when following instructions.
The cause of the chiller trips which resulted in the July 15, i 1993, violation is indeterminate. As stated previously, ,
operation of the WPP chillers is no longer required by the l NPDES permit as of July 24, 1993. Therefore, no long term - i corrective actions to prevent recurrence are planned. [
I t
- 4. DESCRIPTION OF NONCOMPLIANCE NO. 4: :
r on July 25, 1993, while attempting to repair a communication-failure with one 10 cal control unit (LCU) at the WPF, numerous unexpected control system anomolies occurred. Large ;
motors were unexpectedly shutting off and on, and valves were j cycling open and closed. In order to prevent serious i*
equipment damage and personnel injury, the entire facility had-to be temporarily shutdown at 1540 hours0.0178 days <br />0.428 hours <br />0.00255 weeks <br />5.8597e-4 months <br />. As a result, ,
discharge temperature exceeded the 74 degrees P limit with a !
maximum temperature of 76.5 degrees P for about two hours l (from 1540 to 1740 hours0.0201 days <br />0.483 hours <br />0.00288 weeks <br />6.6207e-4 months <br />) while the summer minimum East ;
Branch Perkiomen Creek flow rate was being maintained. By ;
i
. .- _., , _ . - - , _ .- l
Page 4 1740 hours0.0201 days <br />0.483 hours <br />0.00288 weeks <br />6.6207e-4 months <br />, the control system was returned to normal and the chillers were returned to service.
- This event is considered to be an allowable " bypass" (water ,
being diverted from cooling equipment) which met the criteria specified in Part B, Section 1.e(2) of the NPDES permit for ,
the following reasons:
i o The problems encountered requiring the facility shutdown could not have been reasonably anticipated.
o Serious equipment damage which would have jeopardized .
the ability of the cooling equipment to function f subsequently for permit compliance could have occurred. 'l o Operation of the WPF chillers on July 25, 1993,' required -
personnel to be physically in the vicinity of high ,
voltage and high speed rotating equipment. Therefore, -5 personnel were susceptible to injury.
CAUSE OF THE NONCOMPLIANCE:
i The cause of this noncompliance is believed to be a !
combination of an equipment failure (i.e., LCU) and either errors made by technical personnel during the repair process i or an additional failure of the computer system during the 1 repair process.
PREVENTION OF A FUTURE OCCURRENCE:
As previously indicated, operation of the WPF chillers is no 'j longer required. However, we recognize the generic ,
implications of the LCU failure. Therefore, an investigation .
of the LCU failure and repair process problems will continue j since the Ozone Disinfection System utilizes LCUs and is ,
required to remain in operation. When the investigation is I complete, appropriate corrective actions will_be implemented ,
as necessary. 1 If you have any questions please contact Jim Kantner at 327-1200 extencion 3400. .
i Sincerely, l
- i. -
i c'
'N ,
i DMS:cah I
cc: U.S. Nuclear Regulatory Commission !
Document Control Desk Docket-Nos. 50-352/50-353 ,
Washington, D.C. 20555 .
r
I k
Page.5 ]
. u I
'T. T. Martin i Administrator, Region I, USNRC [
Docket Nos. 50-352/50-353 i N. S. Perry l USNRC Senior Resident Inspector, LGS
Docket Nos. 50-352/50-353 l J. A. Feola -!
Pennsylvania Department of Environmental Resources '
Regional Water Quality Manager l Lee Park, Suite 6010 l 555 North Lane '
Conshocken, PA 19428 -
Program Management Section (3WM52) ;
Permits Enforcement Branch Environmental Protection Agency
Region III 841 Chestnut Building Philadelphia, PA 19107 h
f h
?
1
-l i
i l
)
o l
, . _ - .. . -